| 2005-11-17 00:00:00 | ************* UNSAT ***************** |
| | |
| | ************************************** |
| | |
| | PLEASE KNOW, PLANS WERE ONLY SUBMITTED |
| | FOR "PLAN REVIEW" BEFORE THE OCTOBER |
| | 1ST, 2005. THEDEADLINE FOR THE CODE |
| | CHANGE TO THE 2004 FBC. |
| | PLEASE KNOW, PLANS WILL BE REQUIRED TO |
| | BE SUBMITTED FOR PERMIT UNDER THE 2004 |
| | FBC AND MUST GENERATE A NEW PERMIT |
| | NUMBER. |
| | THE EXISTING "PROJECT" NUMBER WILL NO |
| | LONGER BE IN EFFECT. |
| | ************************************* |
| | |
| | 1)NOTE: PLEASE SEE NOTE ABOVE AND PLEASE |
| | ADJUST ALL CODES REFERENCED IN PLANS FOR |
| | THE 2001 FBC. |
| | PLEASE ALSO KNOW, AS OF JAN 1ST, 2005 , |
| | THE STATE ADOPTED THE 2003 LS CODE |
| | NFPA-101, NFPA-72, IS NOW THE 2002 |
| | EDITION. |
| | PLEASE SEE ALL OTHER LOCATIONS ON PLANS |
| | FOR ALL TRADES. |
| | PLEASE SEE THAT ELECTRICAL PLANS |
| | REFERENCE THE CURRENT NEC UNDER ADOPTION |
| | BY THE STATE. (2002). |
| | |
| | 2)NOTE: PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCK FOR ARCHITECTUAL |
| | FIRM. PLEASE SEE FLORIDA ADMINISTRATIVE |
| | CODE, FAC 61G1-16.004. |
| | PLEASE ALSO SEE FLORIDA STATUES FOR |
| | MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER REQUIRED. |
| | PLEASE KNOW, THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS CONTAINING THE |
| | TITLE BLOCKS OF SAID FIRM INCLUSIVE OF |
| | MEP'S. |
| | THIS COMMENT IS NOT FOR KAMM CONSULTING |
| | ENGINEERS. |
| | |
| | 3)NOTE: PLEASE SEE 2002 NECWHICH |
| | REQUIRES THE GFI PROTECTION FOR ALL |
| | 15A,20A 120V RECEPTS IN KITCHENS. |
| | PLEASE SEE CC-18 |
| | |
| | 4)NOTE: PLEASE SEE PANEL "CC2" WHICH |
| | DOES NOT SEEM TO MEET 110.26 FOR MIN |
| | CLEARNECE TO THE LEFT AND RIGHT OF PANEL |
| | WITH WH SHOWN AT LOCATION ON PLANS. |
| | |
| | 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| | AT 125%. |
| | 215.3,230.42 ETC. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABVOE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |