Plan Review Details - Permit 05091636
Plan Review Stops For Permit 05091636
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-24 Cont ID  
Sent By kstevens Date 2006-01-24 Time 13:05 Rev Time 0.00
Received By lmartine Date 2006-01-24 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By dpalmer Date 2005-11-17 Time 21:11 Rev Time 0.50
Received By dpalmer Date 2005-11-17 Time 21:04 Sent To  
Notes
2005-11-17 00:00:00************* UNSAT *****************
  
 **************************************
  
 PLEASE KNOW, PLANS WERE ONLY SUBMITTED
 FOR "PLAN REVIEW" BEFORE THE OCTOBER
 1ST, 2005. THEDEADLINE FOR THE CODE
 CHANGE TO THE 2004 FBC.
 PLEASE KNOW, PLANS WILL BE REQUIRED TO
 BE SUBMITTED FOR PERMIT UNDER THE 2004
 FBC AND MUST GENERATE A NEW PERMIT
 NUMBER.
 THE EXISTING "PROJECT" NUMBER WILL NO
 LONGER BE IN EFFECT.
 *************************************
  
 1)NOTE: PLEASE SEE NOTE ABOVE AND PLEASE
 ADJUST ALL CODES REFERENCED IN PLANS FOR
 THE 2001 FBC.
 PLEASE ALSO KNOW, AS OF JAN 1ST, 2005 ,
 THE STATE ADOPTED THE 2003 LS CODE
 NFPA-101, NFPA-72, IS NOW THE 2002
 EDITION.
 PLEASE SEE ALL OTHER LOCATIONS ON PLANS
 FOR ALL TRADES.
 PLEASE SEE THAT ELECTRICAL PLANS
 REFERENCE THE CURRENT NEC UNDER ADOPTION
 BY THE STATE. (2002).
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. PLEASE SEE FLORIDA ADMINISTRATIVE
 CODE, FAC 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUES FOR
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER REQUIRED.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS CONTAINING THE
 TITLE BLOCKS OF SAID FIRM INCLUSIVE OF
 MEP'S.
 THIS COMMENT IS NOT FOR KAMM CONSULTING
 ENGINEERS.
  
 3)NOTE: PLEASE SEE 2002 NECWHICH
 REQUIRES THE GFI PROTECTION FOR ALL
 15A,20A 120V RECEPTS IN KITCHENS.
 PLEASE SEE CC-18
  
 4)NOTE: PLEASE SEE PANEL "CC2" WHICH
 DOES NOT SEEM TO MEET 110.26 FOR MIN
 CLEARNECE TO THE LEFT AND RIGHT OF PANEL
 WITH WH SHOWN AT LOCATION ON PLANS.
  
 5)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 215.3,230.42 ETC.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 10:58 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 10:37 Sent To  
Notes
2005-11-10 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED DAILY.
  
 3. WRONG CODE INFORMATION. SHOULD
 READ NFPA 101, 2003 EDITION INSTEAD
 OF NFPA 101, 2000 EDITION.
  
 4. ALL EXITS TO REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 5. FIRST AID ROOM BEING TURNED INTO
 PREP ROOM. CONTACT FIRE RESCUE TO
 DISCUSS.
  
 6. WHAT FIRE RATING EXISTS FOR DOOR E
 ON PAGE A2.00.
  
 7. EXISTING FIRE SPRINKLER HEADS ARE
 NOT BE PAINTED. IF THEY ARE PAINTED THEY
 ARE TO BE REPLACED.
  
 8. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 9. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODEL.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By lmartine Date 2006-01-24 Time 13:05 Rev Time 0.00
Received By lmartine Date 2005-09-30 Time 16:54 Sent To  
Notes
2005-10-04 00:00:00TO "COMM" BD#4
2005-09-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By hmoser Date 2005-11-08 Time 16:13 Rev Time 0.00
Received By hmoser Date 2005-11-08 Time 15:25 Sent To  
Notes
2005-11-08 00:00:00PLAN DENIED
 1) PLEASE PROVIDE ROUND OR FLEX DUCT
 SIZE ON THE PLANS.
 IF THEY ARE INSTALLING HOODS OR WALK IN
 COOLERS IN THE CAFE ADDITIONAL PERMITS
 ARE REQUIRED.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-08 Cont ID  
Sent By kstevens Date 2005-12-08 Time 07:38 Rev Time 2.00
Received By kstevens Date 2005-12-07 Time 19:06 Sent To  
Notes
2005-12-08 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A0.01 CODE INFORMATION: CODE
 REFERENCE SHALL BE FBC-2004 AS PLANS
 WERE NOT SUBMITTED FOR APPLICATION PRIOR
 TO 10-1-05.
 2. ALL ARCHITECTURAL SHEETS SHALL SHOW
 THE FIRM LICENSE NUMBER IN THE TITLE
 BLOCK AND THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT. ALSO THE SEAL
 SHALL HAVE THE SIGNATURE AND THE DATE
 SEAL WAS AFFIXED TO THE DOCUMENT. NO
 DATE ON SEAL. FAC 61G1-16.004(2)(5)(6)
 AND FS 481.219 - 481.2055
 3. SHT P0.1 DOMESTIC WATER ISOMETRIC,
 THE WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF. INSTALL.
 INSTRUCTIONS. (SEE PLUMBING NOTE #13). -
 THERMAL EXPANSION CONTROL MAY BE
 REQUIRED ON THE WATER HEATER.
 4. SHT P0.1 PLUMBING NOTES #1 SHALL READ
 FBC-2004 NOT 2001 AS SHOWN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]