Plan Review Details - Permit 05091467
Plan Review Stops For Permit 05091467
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By shill Date 2006-03-09 Time 15:24 Rev Time 40.00
Received By shill Date 2006-01-24 Time 09:08 Sent To  
Notes
2006-03-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
 FHA 98 DESIGN MANUAL
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 4.)FBC* 105.13.1SPECIAL INSPECTOR.
 A STRUCTURAL INSPECTION PLAN MUST BE
 SUBMITTED PRIOR TO THE ISSUANCE OF A
 BUILDING PERMIT FOR THE CONSTRUCTION OF
 A THRESHOLD BUILDING.A THRESHOLD
 BUILDING IS ANY BUILDING WHICH IS
 GREATER THAN THREE STORIES OR 50 FEET IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY
 OCCUPANCY WITH 5,000 SQ FT AREA AND
 GREATER THAN 500 OCCUPANTS.THREE
 COPIES OF THE PLANS AND OTHER DOCUMENTS
 WILL BE REQUIRED FOR PERMITTING
 PURPOSES.ALSO, PLEASE ARRANGE WITH
 HAROLD PISKURA (INSPECTION SERVICES
 MANAGER, 561-805-6711) A MEETING
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR,
 AND ENGINEER.
  
 5.)IF THE DWELLING UNITS ARE TO BE
 SOLD AS CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 6.)DOCUMENTS PREPARED BY AN ENGINEER
 ARE TO HAVE ALL INFORMATION REQUIRED BY
 FAC61G15-23.002.THE CIVIL SHEETS ARE
 LACKING A CA NUMBER AND PRINTED LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT.ALSO, THE SIGNATURE APPEARS
 TO BE A STAMP.ORIGINAL "WET" SIGNATURE
 REQUIRED AS PER FBPE.THE STRUCTURAL
 CALCS DO NOT HAVE THE COFA NUMBER FOR
 THE ENGINEER.CHECK ALL SHEETS,
 CALCULATIONS AND SPECIFICATIONS FOR
 TITLE BLOCK COMPLIANCE PRIOR TO
 RESUBMITTAL.
  
 7.)THE STRUCTURAL ENGINEER'S AND FIRE
 PROTECTION ENGINEER'S SEALS ARE OLD
 SEALS.PLEASE NOTE THAT THE SEAL SHOULD
 STATE "LICENSE" RATHER THAN
 "CERTIFICATE" IF SEALED AFTER DECEMBER
 31, 2005.THIS COMMENT APPLIES TO
 ANYTHING SEALED AFTER THIS DATE ONLY
 (FUTURE SUBMITTALS).
  
 8.)ARCHITECT BUSINESS NUMBER FOR
 COLLADO AND PARTNERS, INC. IS REQUIRED
 ON ALL SHEETS, FAC61G1-16.002, 003.
  
 9.)PROVIDE WIND DESIGN INFORMATION
 FBC1606.1.7.
  
 10.)PROVIDE A SCHEDULE OF OPENINGS
 WITH DESIGN PRESSURES, OR INDICATE
 DESIGN PRESSURES ON THE ELEVATIONS.
  
 11.)THE STRUCTURAL CALCS PROVIDE A
 BUILDING HEIGHT OF 70 ON SHEET ED4,
 SECTION 2.
  
 12.)THE STRUCTURAL CALCS, SECTION 5,
 CD74, REFERS TO ACI 318-95 FOR CODE.
 THIS REFERENCE IS NOT THE CURRENT
 STANDARD, FBC35.
  
 13.) FBC 13-103.0ENERGY CODE
 COMPLIANCE SHALL BE DEMONSTRATED BY
 SUBMITTAL OF APPROPRIATE CODE COMPLIANCE
 FORMS.
  
 14.) FBC 13-103.1.2BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 15.)PROVIDE A SURVEY FOR THIS
 PROPERTY.
  
 16.)SOME OF THE SHEETS SUBMITTED WERE
 NOT SEALED.ALL SHEETS ARE TO BE
 SIGNED, SEALED, AND DATED ORIGINALS.
 ALL SEALS ARE TO BE LEGIBLE.
  
 17.)PLEASE REVISE A-1.0 TO INCLUDE THE
 GOVERNING CODE WHICH IS APPARENTLY
 FBC2001 (HANDWRITTEN AND NOT INITIALED
 BY ARCHITECT).NEITHER THE ARCHITECT
 NOR ENGINEER DECLARED GOVERNING CODE.
 THIS REVIEW HAS BEEN DONE UNDER THE
 FBC2001 CODE.
  
 18.)SHEET S1 STATES IN VARIOUS PLACES
 THAT THIS HAS BEEN DESIGNED TO HVHZ AND
 ACI318 99.CITY OF WEST PALM BEACH IS
 NOT IN THE HIGH VELOCITY HURRICANE ZONE
 AND THE CORRECT ACI STANDARD IS 318 02,
 FBC35.ALSO THERE ARE INCORRECT
 REFERENCES ON A-G.1.CHECK ALL
 REFERENCES AND REVISE AS NECESSARY.
  
 19.)SHEETS REFERRED TO ON THE INDEX
 SHEET, A-G.0, ARE NOT IN THE PLAN.FOR
 INSTANCE, S7.5, 7.6, 7.7 ARE NOT IN THE
 PLAN.S8.1, WIND PRESSURES, IS REFERRED
 TO FOUR TIMES ON THE INDEX BUT IS NOT IN
 THE PLAN.THIS SHEET IS NECESSARY TO
 DETERMINE CODE COMPLIANCE.PLEASE
 CONFIRM THAT ALL SHEETS NECESSARY ARE IN
 THE PLAN AND REVISE THE INDEX SHEET TO
 CORRELATE.THE LIST REFERRED TO ABOVE
 ARE NOT A COMPLETE LIST; OTHER SHEETS
 ARE MISSING.
  
 20.)ELEVATORS ARE TO CONFORM TO ASME
 A17.1, FBC3001.1.PLEASE ADD TO THE
 NOTE, A-G.2, ITEM 14, CONVEYING SYSTEMS,
 OR ANOTHER APPROPRIATE SHEET.
  
 21.) FBC 3003.4.1STRETCHER ACCESSIBLE
 ELEVATOR.AT LEAST ONE PASSENGER
 ELEVATOR SHALL ACCOMMODATE AN AMBULANCE
 STRETCHER 76IN LONG AND 24IN WIDE IN THE
 HORIZONTAL POSITION.THIS ELEVATOR
 SHALL BE IDENTIFIED BY SIGNAGE.AMEND
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 22.)A1.0 DECLARES THE OCCUPANCY AS R2
 WITH AREA CALCULATIONS FOR THE
 RESIDENTIAL UNITS.INCLUDE AREA
 CALCULATIONS AND OCCUPANCY (IF
 APPLICABLE) FOR THE OTHER AREAS OF THE
 BUILDING SUCH AS THE PARKING GARAGE,
 COMMON AREAS, MECHANICAL ROOMS, ETC.
 BUILDING VALUATION CANNOT BE DETERMINED.
  
 23.)DECLARE BUILDING HEIGHT ON SHEET
 A1.0, FBC412.BASED ON ELEVATIONS
 PROVIDED, BUILDING HEIGHT EXCEEDS 75FT.
  
 24.)SHOW REQUIRED OCCUPANCY SEPARATION
 FBC TABLE 704.1.
  
 25.)THE MEZZANINE LEVEL WITH PARKING
 AND AN ELEVATOR LOBBY DOES NOT COMPLY
 WITH THE DEFINITION OF MEZZANINE, FBC
 CHAPTER2, FBC 503.2.3.REVISE THE
 DESIGNATION OF THIS AREA AND FLOOR.
  
 26.)ALL ELEVATORS ON ALL FLOORS SHALL
 OPEN INTO ELEVATOR LOBBIES WHICH ARE
 SEPARATED FROM THE REMAINDER OF THE
 BUILDING BY 1 HR FIRE RESISTANT
 CONSTRUCTION WITH 20MINUTE OPENING
 PROTECTIVES, FBC412.6.1.THE LOBBY
 SHOWN ON THE MEZZANINE LEVEL DOES NOT
 COMPLY, ROOF LEVELS DO NOT HAVE A LOBBY.
  
 27.)PROVIDE AREA CALCULATIONS FOR THE
 UNIT MEZZANINES TO SHOW COMPLIANCE WITH
 FBC503.2.3.2.
  
 28.)PROVIDE A LIFE SAFETY PLAN.
  
 29.)A2.1, EMERGENCY STAIRS 1
 DISCHARGES INTO THE PARKING GARAGE.SEE
 FBC1001.1.3, 1001.1.4.DISCHARGING INTO
 THE PATH OF VEHICULAR TRAFFIC WOULD BE
 CONSIDERED HAZARDOUS CONDITIONS.
  
 30.)A2.2, A6 SHOW VENTILATION DUCTS
 THROUGH THE EXIT STAIR 1.SEE
 FBC1006.1.3.1.OTHER SHEETS MAY BE
 AFFECTED.PLEASE REVISE.
  
 31.)A1.0, % OF OPENINGS, STATES THAT
 THE ALLEY SIDE HAS A 1FT SETBACK.THE
 SITE PLAN SHOWS 6IN.PLEASE MAKE THE
 TWO CONSISTENT.
  
 32.)A1.0, % OF OPENINGS, STATES THAT
 THE WEST SIDE HAS A 4IN SETBACK, 6IN IS
 SHOWN.PLEASE MAKE THE TWO CONSISTENT.
  
 33.)SHOW THE DISTANCE OF THE BUILDING
 TO THE PROPERTY LINE, DATURA SIDE, A1.0.
  
 34.)SHEET A2.10, A4.2, AND OTHER
 SHEETS REFER TO ALUMINUM RAILING
 DETAILS, SHEET AX.X.PLEASE PROVIDE
 DETAILS FOR ALL GUARDRAILS AS WELL AS
 DESIGN CRITERIA.CHECK ALL DETAILS.
  
 35.) FBC 1608.2, PROVIDE DESIGN CRITERIA
 FOR BOTH THE HANDRAILS AND GUARDRAILS.
  
 36.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISHES, FBC TABLE 803.3.
  
 37.)PROVIDE A DETAIL FOR THE
 MECHANICAL STANDS, FBC1511.7.
  
 38.)FBC1007.5.5, 11-4.94(2), THE
 HANDRAIL WILL EXTEND AT LEAST 12IN
 HORIZONTALLY BEYOND THE TOP RISER OF A
 FLIGHT.ENDS OF HANDRAILS SHALL BE
 EITHER ROUNDED OR RETURNED SMOOTHLY TO
 FLOOR, WALL OR POST, FBC11-4.94(6),
 FIGURE 11-19.A6.0, A6.1, ALSO OTHER
 DETAILS MAY BE AFFECTED; PLEASE CHECK
 ALL DETAILS.
  
 39.)LOFT UNIT STAIRS, A4.1, AT THE
 BOTTOM, THE HANDRAIL SHALL CONTINUE TO
 SLOPE FOR A DISTANCE OF THE DEPTH OF ONE
 TREAD FROM THE BOTTOM RISER,
 FBC1007.5.5.
  
 40.)A3.5 SHOWS A DESIGNATION AS LEVEL
 3 TO 7, A3.6 IS LEVEL 7 PH.SHOULDN'T
 THIS BE LEVEL 8PH?
  
 41.)A3.6.5 IS LEVEL 7PH, A DUPLICATE
 OF A3.6.ACCORDING TO THE INDEX, THIS
 SHEET SHOULD BE LEVEL 8PH2.
  
 42.)SHEETS A2.5, A2.6, A2.65 DO NOT
 PROVIDE DOOR DESIGNATIONS TO CORRELATE
 WITH THE DOOR SCHEDULE.
  
 43.)WHAT WILL BE STORED IN THE STORAGE
 ROOMS?INDICATE THAT IT IS NONHAZARDOUS
 OR DECLARE AN OCCUPANCY AND SHOW
 REQUIRED PROTECTION IF APPLICABLE,
 FBC704.1.1.2(4).
  
 44.)THE TRASH CHUTE IS TO COMPLY WITH
 NFPA82.SHOW THE 6IN REQUIREMENT OF
 3-2.4.3.1 ON THE TRASH CHUTE SECTION.
  
 45.)COMBUSTIBLES NOT ALLOWED IN
 CONCEALED SPACES, FBC707.1.A7.7
 SPECIFIES PT WOOD BACKING FOR CABINETS.
 A6.7 REFERS TO PT FURRING; NOTE THE
 REQUIREMENT OF FBC803.9.1 FOR FURRING.
 CHECK ALL DETAILS AND SPECIFICATIONS.
  
 46.)A8.0, DOOR FIRE RATING SHOULD BE
 IN HOURS RATHER THAN A LETTER RATING,
 FBC705.1.3.2.1.
  
 47.)A8.0 REFERS TO SFBC.GOVERNING
 CODE IS FBC2001.REVISE THE CODE
 REQUIREMENT FROM SFBC3706 TO
 FBC705.1.3.4.PLEASE CHECK ALL
 REFERENCES TO COMPLY WITH GOVERNING
 CODE.
  
 48.)PROVIDE CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS, FBC1503.
 PLEASE ALSO SEE PLUMBING REVIEW NOTES
 REGARDING INCONSISTENCIES IN SCUPPER
 DETAILS.
  
 49.)THE DETAILS ON A7.0 ARE MARKED
 A7.4.
  
 50.)THERE ARE TWO DIFFERENT SHEETS
 LABELED A7.7.
  
 51.)WL2185, A7.1, REFERS TO 3A
 OPTIONAL PACKING MATERIAL.THE UL
 ASSEMBLY DOES NOT INDICATE THIS AS
 OPTIONAL.3B SPECIFIES A MINIMUM OF
 1/2IN THICKNESS, UL ASSEMBLY SPECIFIES A
 MINIMUM OF 5/8IN.WL 2159 ALSO
 SPECIFIES A THICKNESS WHICH DOES NOT
 COMPLY WITH THE CURRENT UL LISTING.
 CHECK ALL UL ASSEMBLY AND SYSTEM
 DETAILS.ALL SPECIFICATIONS SHOULD BE
 CLEAR AND ALL INCLUSIVE FOR
 CONSTRUCTION.
  
 52.)A7.3 PARKING DETAILS DO NOT COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS.
 PLEASE SEE ATTACHED.
  
 53.)DETAIL 10 A7.4 ON SHEET A7.0
 REFERS TO SFBC.
  
 54.)DOOR G05 IS TO BE FIRE RATED, FBC
 TABLE 704.1.
  
 55.)SPECIFY A DOOR TYPE AT RESIDENT?S
 STORAGE, A2.3.
  
 56.)M2.4 SHOWS EXHAUST AIR DUCTS ON
 THE EAST WALL.EVERY EXTERIOR WALL
 WITHIN 15FT OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH APPROVED OPENING
 PROTECTIVES, FBC705.1.1.2.
  
 57.)M2.4, A2.13 OPENINGS FOR
 VENTILATION ARE ALSO SHOWN ON THE SOUTH
 PROPERTY LINE.CLEARLY INDICATE FIRE
 RESISTANCE RATING REQUIREMENTS OF FBC
 TABLE 600 ON THE PLANS AND SHOW
 COMPLIANCE.EVERY EXTERIOR WALL WITHIN
 15FT OF A PROPERTY LINE SHALL BE
 EQUIPPED WITH APPROVED OPENING
 PROTECTIVES, FBC705.1.1.2.
  
 58.)A2.25, ACTIVITY ROOM HAS WINDOWS
 WHICH ARE REQUIRED TO BE PROTECTED,
 FBC705.1.1.2.CLEARLY NOTE FIRE RATING
 REQUIREMENTS ON THE PLAN TO AVOID
 CONFUSION IN THE FIELD.
  
 59.)M2.2 AND M2.3 SHOW FRESH AIR
 INTAKES WHICH ARE REQUIRED TO BE
 PROTECTED, FBC705.1.1.2.ALSO SEE
 FBC705.1.1.4, PROTECT AGAINST EXTERIOR
 FIRE EXPOSURE.PLEASE ADDRESS.
  
 60.)PROVIDE PRODUCT APPROVALS FOR ALL
 COMPONENTS AND CLADDING.ANY PRODUCT
 APPROVALS NOT REVIEWED FOR CODE
 COMPLIANCE PRIOR TO PERMIT ISSUANCE WILL
 REQUIRE SEPARATE PERMITS FOR THOSE ITEMS
 WITH SEPARATE FEES BASED ON VALUE.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED IN ADDITION TO THE EVALUATION
 REPORT, FAC9B72.SEE
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 61.)FHA SECTION 5, ACCESSIBLE ENTRANCE
 REQUIRED FOR THE GROUND FLOOR UNITS.
 SEE ALSO SECTION 3, 100.205(D) EXAMPLE
 (1).FOR THE POWDER ROOM ALSO SEE
 REQUIREMENT 7, USABLE KITCHENS AND
 BATHROOMS.
  
 62.)DOORS T10, T12 DO NOT MEET THE
 MIMIMUM CLEARANCE OF 32 IN, FHA
 GUIDELINES SECTION 5 REQUIREMENT 3,
 USABLE DOORS.SEE PAGE 7.17, DESIGN
 MANUAL.
  
 63.)THE SLIDING GLASS DOORS TO THE
 BALCONIES ARE TO BE USABLE, FHA
 GUIDELINES SECTION 5 REQUIREMENT 3.
 CONFIRM THAT THE PRODUCT YOU SELECT
 COMPLIES WITH THE 32IN NOMINAL WIDTH.
  
 64.)PROVIDE A DETAIL FOR GRAB BAR
 BACKING, CHAPTER 6 OF DESIGN MANUAL.
  
 65.)WHEN RESUBMITTING, PLEASE CHANGE
 ONLY SHEETS WHICH HAVE CHANGED AND
 SUBMIT OLD SHEETS SEPARATELY.TO
 EXPEDITE PLAN REVIEW, CLEARLY CLOUD ALL
 CHANGES AND PROVIDE A RESPONSE LETTER
 EXPLAINING HOW EACH ITEM HAS BEEN
 ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-25 Cont ID  
Sent By dpalmer Date 2005-12-25 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 13:15 Sent To  
Notes
2005-12-25 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.
 ********** UNSAT ************
  
 SKYLINE LOFTS.
  
 1)NOTE: PLEASE BE SURE PLANS MAKE
 REFERENCE TO CURRENT ELECTRICAL CODE IN
 EFFECT. NFPA-70 2002, 2002 NFPA-72
  
 2)NOTE: PLEASE BE SURE ALL SHEETS ARE
 SIGNED , DATED A ND SEALED AS REQUIRED
 UNDER FS 481.221, 471.025, AND 472.025
 PLEASE SEE PD-1, -2 AND WS SHEETS WHICH
 SOME ARE SEALED PHOTO-COPIES AND SOME
 ARE ONLY PHOTOCOPIES AND NOT SEALED OR
 DATED.
 THIS SIS REQUIRED FOR ALL SHEETS AND FRO
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE SEE MISSING LICENSING
 INFORMATION FOR M AND P SHEETS. PLEASE
 SEE FLORIDA ADMINISTRATIVE CODE WHICH
 REQUIRES THE CERTIFICATE OF
 AUTHORIZATION NUMBER ON SAID TITLE BLOCK
 AS REQUIRED UNDER FS 471.023
 THIS IS NOT A COMMENT FOR THE ELECTRICAL
 ENGINEERING FIRM.
  
 4)NOTE: PLEASE CORRELATE THE NUMBER OF
 UNITS. PLEASE SEE STRUCTUAL CALCULATION
 BOOK SUBMITTED INDICATE 103 UNITS, AND
 ELECTRICAL PLANS INDICATE 99?
  
 5)NOTE: PLEASE OBTAIN A LETTER FROM MR.
 BILL HARTIGAN(FPL) WITH RESPECT TO THE
 APPROVAL OF THE FPL VAULT AS SHOWN.
 PLEASE SEE LOCATION AND SIZE IS TO BE
 DETERMINED BY FPL.
 IT IS NOT COMMON FOR THE VAULT TO BE
 LOCATED INSIDE BUILDING WITHOUT DIRECT
 ACCESS FROM OUTSIDE.
  
 6)NOTE: PLEASE ALSO KNOW, IT WILL BE
 REQUIRED TO BE IN FURTHER DISCUSSION
 WITH THE FIRE MARSHAL'S OFFICE WITH
 RESPECT TO THE LOCATION AND ACCESS TO
 THE MAIN ELECTRICAL ROOM. IT APPEARS
 FIRE DEPT PERSONNEL WOULD HAVE TO ENTER
 THROUGH THE BLDG AND POSSIBLY THE
 PARKING GARAGE FOR SOME DISTANCE IN
 ORDER TO SHUT DOWN MAINS ELECTRICAL
 SYSTEMS? THIS WOULD NOT BE PERMITTED. A
 DIRECT ACCESS (4HR RATED) WOULD BE
 REQUIRED. THIS WILL REQUIRED FURTHER
 REVIEW.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 ROOMS NOTED FOR ACCESS.(FIRE PUMP)
  
 7)NOTE: PLEASE SEEMAIN ELECTRICAL
 ROOM, GENERATOR RM, FIRE PUMP RM, WILL
 REQUIRE DOORS TO OPEN OUTWARD.
 THESE ROOMS WILL ALSO BE REQUIRED TO
 HAVE PANIC HARDWARE ON DOORS.
 PLEASE PROVIDE NOTE ON PLANS FOR DOOR
 HARDWARE.
 110.26, 90.4
  
 8)NOTE: PLEASE PROVIDE THE BUS-DUCT
 DETAIL AS SPECIFIED IN 368.6 FOR FLOOR
 PENETRATIONS. (4" CURBING ALL THE WAY
 AROUND).
  
 9)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL CORIDORS AND EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9
 WHICH REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A MIN
 OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURES OF SOME SORT WILL BE REQUIRED
 IN STAIR TOWERE AND CORRIDORS TO MEET
 THE MIN 1 FT CANDLE UNDER EM POWER.
 PLEASE SEE 7.9 WHICH REQUIRES THIS IN
 ALLEAVIATING IN AREA BEING IN TOTAL
 DARKNESS UPON THE TRIPPING OF A SINGLE
 DEVICE, SWITCH, BRKR ETC.
  
 10)NOTE: PLEASE PROVIDE A BATTERY BACK
 UP FIXTURE IN ELECTRICAL ROOMS, GEN RMS,
 FIRE PUMP RM, AND FIRE COMMAND ROOM.
 IT IS KNOWN SOME OF THESE ROOMS CONTAIN
 SOME ALREADY.
 700.16,LS 101 7.8, 7.9.700.12E
  
 11)NOTE: PLEASE SEE FIRE REVIEW NOTES
 WITH RESPECT TO FIRE COMMAND ROOM AND
 MISSING EQUIPMENT AS REQUIRED UNDER
 HIGH-RISEREQUIREMENTS IN 11.9 LS 101
 PLEASE ALSO VERIFY WITH FIRE MARSHAL'S
 OFFICE THE MIN SIZING OF ROOM WHICH MAY
 BE REQUIRED. PLEASE SEE SPACE ABOUT
 THESE CONTROL PANELS SEEM TO BE LIMITTED
 ON ANGLES OF ROOMS AND WITH OTHER ITEMS
 TO BE INSTALLED THIS MAY BE AN ISSUE.
  
 12)NOTE: PLEASE SEE FIRE REVIEW NOTES
 PERTAINING TO ALLEY WAY IN REAR OF BLDG.
 PLEASE SEE 14' ALLEY SHOWN, IS THIS
 PUBLIC? PRIVATE ?
 IF PRIVATE PLEASE SEE 7.8,7.9 LS 101,
 WHICH REQUIRES ILLUMINATION TO THE
 PUBLIC RIGHT OF WAY.
 PLEASE ALSO SEE ORIG FIRE NOTE WITH
 RESPECT TO VEHICULAR TRAFFIC.
  
 13)NOTE: PLEASE SEE 620.23 REQUIRE STHE
 LTS AND RECEPTS IN THE ELEVATOR MACHINE
 ROOM TO BE ON A DEDICATED CIRCUIT. THIS
 NOTED ON PANEL SCHEDULE, HOWEVER THE
 CIRCUITING ON PLANS SEEMS TO BE MISSING?
  
 14)NOTE: PLEASE SEE 110.26 FOR ALL
 ELECTRICAL ROOMS SHOWN.
 PLEASE SEE ALL MIN CLEARENCES WILL BE
 REQUIRED , EVEN FOR BUS-DUCT. PLEASE SEE
 REDLINED PLANS FOR LOCATIONS OF CONCERN.
  
 15)NOTE: PLEASE PROVIDE A DETAIL FOR THE
 MIN DISCONNECTING MEANS FOR ROOF TOP
 CU'S. THIS DETAIL MAY BE "TYPICAL".
 440.11
  
 16)NOTE: PLEASE SEE THAT THE
 PHOTOMETRICS SHOWN FOR THE POOL AREA
 MUST BE SUBMITTED FOR REVIEW AND
 STAMPING BY THE PALM BEACH COUNTY HEALTH
 DEPT.
 PLEASE KNOW, THE POOL IS REQUIRED TO BE
 UNDER A SEPARATE PERMIT.
  
 17)NOTE: PLEASE PROVIDE A NOTE ON
 ROOFTOP PLANS WITH RESPECT TO ANY
 LIGHTNING PROTECTION SYSTEM WHICH MAY BE
 PROPOSED.
 PLEASE MAKE NOTE TO ANY SYETM SHALL
 COMPLY COMPLETELY WITH NFPA-780 WITH
 WORDS TO THAT AFFECT.
  
 18)NOTE:PLEASE SEE UNITS WHICH ARE
 MISSING COUNTERSPACE GFI RECEPTS AS
 REQUIRED PER 210.52C1.
 SOME UNITS ARE SHOWING GFI'S WHERE
 COUNTERS AMY BE LESS THAN 12" AND SOME
 ARE SHOWN, YET OTHERS WHICH ARE MORE
 THAN 12" DO NOT CONTATIN ANY.
 PLEASE SEE MANY UNITS SEEM TO HAVE THESE
 RECEPTS LOCATED BEHIND THE FRIG??
 PLEASE MANY OF THESE HAVE BEEN REDLINED
 ON PLANS.
 ** PLEASE ALSO SEE RELDINED UNIT WHERE
 MICRO/HOOD CIRCUIT IS MISPLACED WITH
 SMALL APPL.(L101)
  
 19)NOTE: PLEASE SEE SOME CIRCUITING
 MISSING IN UNITS FOR DEVICES.
 215.5 PLEASE COMPLETE.
  
 20)NOTE: PLEASE SEE RECEPTS MISSNG FOR
 WALL SPACE PER 210.52. MANY OF THESE
 HAVE BEEN REDLINED.
 PLEASE SEE MOST ALL UNITS ARE MISSING
 DOORS, SO SOME MAY BE REQUIRED FURTHER
 ONCE DOOR OVERLAY HAS BEEN CORRECTED.
 PLEASE ALSO SEE AREAS WHICH APPEAR TO
 SHOW FIXED GLASS PANELS/WALLS WHICH ARE
 CONSIDERED WALL SPACE AND WOULD REQUIRE
 A RECEPT WITHIN 6' OF DOORWAY.
 SEE REDLINES.
  
 21)NOTE: PLEASE SEE LOFT UNITS NEED TO
 INDICATE THE MEANS OF EGRESS CONTROLL
 FOR LIGHTING LEADING TO FLOOR ABOVE.
 SOME SHOW "S" BUT NO S/3". 210.70 ETC.
  
 22)NOTE: PLEASE SEE MISSING FIRST LEVEL
 OF LOFT 6/7? 2.12
 NO REVIEW.
  
 23)NOTE: PLEASE SEE 410.8 FOR MIN
 CLEARENCE REQUIRED FOR CLOSETLTS.
 REDLINED.
  
 24)NOTE: PLEASE SEE MISSING SD'S OUTSIDE
 ALL SLEEPING RMS AS REQUIRED PER NFPA-72
 11.5.1.1
 PLEASE ALSO SEE FBC 905
 PLEASE ALSO PROVIDE A NOTE ON ALL UNIT
 SHEETS WHICH REFERENCES NFPA-72 11.8.3.5
 PLEASE SEE ALL SD'S ARE REQUIRED TO BE A
 MIN OF 3' FROM BATH AND KITCHEN DOOR'S,
 3' FROM SUPPLYAND 5' FROM RETURN AIR
 GRILLES.
 PLEASE ALSO SEE SD'S ARE ALSO REQUIRED
 TOBE A MIN OF 20' FROM COOKING
 APPLIANCES, WITH EXCEPTIONS.
  
 25)NOTE: PLEASE SEE UNIT 203, MASTER
 BATH GFI WHICH IS SHOWN ON SMALL
 APPLIANCE CIRCUIT. PLEASE SEE 210.52B1 ,
 NO OTHERS PERMITTED.
 THIS APPEARS TO BE A MISPRINT AS, THE
 BATH GFI CIRCUIT IS #2.
  
 26)NOTE: PLEASE SEE 210.52B1 WHICH DOES
 NOT PERMIT ANY OTHER OUTLETS/DEVICES ON
 THE ONE OR MORE SMALL APPL CIRCUITS.
 PLEASE SEE SOME DINING AREAS APPEAR TO
 CONTAIN OTHER GEN LT CIRCUIT.
 PLEASE DEFINE DINING AREA.
  
 27)NOTE: PLEASE SEE NOTE #29 ON RISER
 INDICATES SD'S TO BE WIRED TO THE
 BATH/KITCHEN LIGHTING CIRCUIT??
 PLEASE VERIFY THIS AS THE #'S DO NOT
 MATCH UP.
 THIS IS PERMITTED, HOWEVER THEN THE
 KITCHEN/BATH LTS WOULD ALSO BE ARC
 FAULT.210.12
  
 28)NOTE: PLEASE SEE REDLINED METER
 CENTER CALCULATIONS, PLEASE CORRLEATE
 ALL . 532/538 ETC
  
 29)NOTE: PLEASE SEE THE FEEDER FOR THE
 FIRE PUMP FROM THE GENERATOR SHALL ALSO
 BE ENCASED IN CONCRETE UNLESS "OUTSIDE"
 THE BLDG.695.6, LS 101 9.3
  
 30)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHETS FOR GENERATOR, ATS, FIRE
 PUMP, FIRE PUMP CONTROLLER AND SUB-BASE
 FUEL TANK. PLEASE KNOW, REVIEW FOR MANY
 ITEMS FOR CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME AS NONE WERE
 SUBMITTED.
 PLEASE ALSO VERIFY AND NOTE SETTING FOR
 LOCKED ROTOR PER 695.4B1
 PLEASE SEE NFPA-20 CHAPTERS 9 AND 10.
 PLEASE KNOW, THE SUB-BASE FUEL TANK WILL
 BE REVIEWED BY OTHERS.
  
  
 31)NOTE: PLEASE SEE NFPA-20 WHICH
 REQUIRES A MIN OF 8HRS RUNNING TIME AT
 100% LOAD FOR THE FIRE PUMP.
 9.6.2.2
 PLEASE ALSO BARE IN MIND THE MIN RUNNINF
 TIME AT 100% FOR ALL OTHER EMERGENCY
 LOADS.
  
 32)NOTE: PLEASE SEE 450.13 FOR MIN.
 SIZING OF CONDCUTORS FROM GENERATOR TO
 THE FIRST MEANS OF OCP.
 PLEASE VERIFY IF THE GENERATOR COMES
 WITH THE BUILT IN OCP IN LEIU OF
 ADDITIONAL DISCONNECTS.
  
 33)NOTE: PLEASE SEE "WHITE-OUT" ON E4.0
 FOR EDR, EDP AND MDP.
 PLEASE SEE FS 471. THIS IS TO BE
 CORRECTED WHEN RE-PRINTING PLANS.
  
 34)NOTE: PLEASE SEE L4E IS SBEING SHOWN
 AS BEING FED WITH 3/0'S FROM A 225A CB.
 PLEASE SEE 310.16, 3/0'S ONLY RATED AT
 200A'S. PLEASE ADJUST FEEDERS.
 PLEASE ALSO CORRECT RISER DIAGRAM.
  
 35)NOTE: PLEASE SEE RISER APPEARS TO
 SHOWS ALL SEC'S'A ND CONDUITS BEING
 ROUTED OVERHEAD FROM FPL VAULT INTO MAIN
 EQUIPMENT. PLEASE KNOW, THAT NO MORE
 THAN 8' OF UNPROTECTED CONDUCTORS ARE
 PERMITTED "INSIDE" THE BLDG. THIS
 INCLUDES THE MAIN ELECTRICAL ROOM.
 230.70
 IF MORE THAN 8' OF CONDUCTORS, THEN
 THESE WILL ALSO BE REQUIRED TO BE
 "ENCASED" IN CONCRETE.
  
 36)NOTE: PLEASE SEE MDP WHICH LISTS OCP
 AND FEED TO PANEL L-4, HOWEVER NOTE FOR
 THIS FEEDER MENTIONS "NOT USED" ON
 LEGEND?
 PLEASE ADJUST AND CORRELATE.
  
 37)NOTE: PLEASE SEE POOL PANEL IS BEING
 SHOWN ON PANEL SCHEDULE L-4, HOWEVER
 THIS IS NOT ON RIER DIAGRAM.
  
 38)NOTE: PLEASE SEE A PANEL L2E IS BEING
 SHOWN ON RISER DIAGRAM COMING FROM PANEL
 EDR, HOWEVER EDR DOES NOT INDICATE THIS
 PANEL, OCP ETC.
 PLEASE ADJUST.
  
 39)NOTE: PLEASE SEE EDP, WILL BE
 REQUIRED TO CONTAIN A MCB FOR GROUPING
 OF MAINS. IF THE EM MAIN IS SHUT DOWN,
 THE GENERATOR WOULD THEN TURN ON, AND
 SEND POWER TOEDP.
 PLEASE KNOW, A SHUNT TRIP WILL NOT BE
 PERMITTED.
 230.76,230.79, 230.72
  
 40)NOTE: PLEASE SHOW ALL CONTINUOUS
 LOADS @125%.
 LIGHTING/POOL MOTOR, LARGEST MOTORS ETC.
 215.3, 230.42
 THIS WILL AFFECT ALL LOADS ON ALL
 PANELS.
  
 41)NOTE: PLEASE VERIFY LOAD ON PANEL FOR
 UNITS OF 1150 SQ FT.
 LOAD SHOWN AFTER ALL DERATING, IS 124A'S
 WHICH IS VERLY CLOSE TO THE MAX LOAD OF
 125A BRKR WHICH SUPPLIES UNIT.
 PLEASE KNOW, SOME ROOM FOR FUTURE LOADS
 SHOWN BE ALLOTTED FOR UNITS AND SHOULD
 NOT BE DESIGNED THIS CLOSE.
 PLEASE VERIFY THE LOADS FOR APPLICANCES,
 DISH, DISP ETC.
 215.5
  
 42)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATER UNITS SHALL BE SIZED AT
 125%.422.13
 PLEASE ADJSUT OCP IN PANELS AND AWG
 WHERE NEEDED.
  
 43)NOTE: PLEASE SEE ANY COMMENTS FROM
 OTHER REVIEWERS WHICH MAY HAVE AN AFFECT
 ON THE ELECTRICAL PLANS.
  
 44)NOTE: PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 ** PLEASE KNOW, FURTHER INFORMATION MAY
 BE NEEDED FOR THE LOCATION MAIN
 ELECTRICAL ROOM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-13 Cont ID  
Sent By mamini Date 2005-10-13 Time 14:36 Rev Time 1.00
Received By mamini Date 2005-10-13 Time 14:36 Sent To  
Notes
2005-10-13 00:00:00FAILED:
  
 1. PLEASE NOTE THAT CIVIL PLANS MUST BE
 REVIEWD AND APPROVED FOR ALL THE
 CONNECTIONS TO THE CITY'S SERVICES BY
 THE PUBLIC UTILITIES AND ENGINEERING
 SERVICES, 494-1085, MANNY GONZALEZ.
 2. BACKFLOWS, DDCV MUST BE LOCATED ON
 THE PROPERTY CLOSEST TO THE SUPPLY
 SOURCE. VRIFY THE PROPOSED LOCATIONS
 WITH THE PUBLIC UTILITIES.
 3. CROSS OVER CLEARANCES FOR THE
 UNDERGROUND UTILITIES (WATER,SEWER,ETC.)
 MUST BE SHOWN.
 4. ALL HANDICAP RAMP MUST BE CONSTRUCTED
 PER LATEST FDOT INDEX 304, SEE DETAIL ON
 SHEET PD2.
 5. WE RECOMMEND THE REPLACING OF ALL
 EXISTING D CURB IN DATURA ST. AND S.
 SAPODILLA AVE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-11-18 Cont ID  
Sent By mcarsill Date 2005-11-18 Time 16:30 Rev Time 0.00
Received By mcarsill Date 2005-11-18 Time 15:54 Sent To  
Notes
2005-11-18 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 3. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 4. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 5. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 6. TAMPER SWITCHES, CHAIN AND
 LOCKS ARE REQUIRED ON FIRE LINE
 BACKFLOW DEVICE.
  
 7. BUILDING ADDRESS NOT SHOWN
 ON ELEVATION. A MINIMUM OF AT LEAST
 6" HIGH NUMBERS ARE REQUIRED.
  
 8. KNOX-BOX WILL BE REQUIRED.
  
 9. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED FOR FIRE DEPARTMENT
 CONNECTIONS.
  
 10. ELEVATOR WARNING SIGNS ARE
 REQUIRED.
  
 11. STAIRWELL SIGNS ARE REQUIRED.
  
 12. TACTILE SIGNAGE REQUIRED.
  
 13. PLEASE INDICATE STRETCHER
 ACCESSIBLE ELEVATORS. APPROPRIATE
 SIGNAGE IS REQUIRED.
  
 14. PLEASE EXPLAIN EXIT DISCHARGE.
  
 15. PLEASE EXPLAIN GATES TO OPEN
 AUTOMATICALLY IN FIRE EMERGENCY. A-2.1.
  
 16. PLEASE EXPLAIN VENTILATION DUCTS
 RUNNING THRU STAIR STAIR # 1 NOTE ON
 PAGE A-2.2.
  
 17. EAST EXIT DISCHARGE SHOWN THRU
 LOADING DOCK. PLEASE EXPLAIN.
  
 18. WHO OWNS THE 14" ALLEY WHERE STAIR
 # 2 DISCHARGES. WHAT PREVENTS PEOPLE
 FROM GETTING HIT BY VEHICLES.
  
 19. HOW IS ACCESS OBTAINED TO STAIR # 1
 ON THE MEZZANINE LEVEL WITH ALL THE
 PARKING SPACES ON PAGE A-2.3.
  
 20. A TWO HOUR FIRE SEPERATION IS
 REQUIRED BETWEEN THE PARKING GARAGE
 AND OTHER AREAS OF THE BUILDING.
  
 21. TRASH CHUTE TO COMPLY WITH
 NFPA 82.
  
 22. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR HANDRAILS
 AND GUARDRAILS.
  
 23. PLEASE INDICATE OCCUPANT LOAD FOR
 ROOF TERRACE AREA.
  
 24. PLEASE INDICATE OCCUPANT LOAD FOR
 POOL LEVEL AND EXPLAIN EXITING.
  
 25. PLEASE EXPLAIN EXIT DISCHARGE INTO
 GARAGE AREA?
  
 26. HANDRAILS ARE REQUIRED ON BOTH
 SIDES OF STAIRS.
  
 27. VOID AREA UNDER POOL STRUCTURE NOT
 TO BE USED FOR STORAGE UNLESS FIRE
 SPRINKLER PROTECTED.
  
 28. "NO EXIT" SIGNS WILL BE NEEDED ON
 DOORS LOCATED NEAR EXITS.
  
 29. PLEASE PROVIDE A LIFE SAFETY PLAN
 FOR THE BUILDING.
  
 30. SURFACES USED FOR EXITING SHALL BE
 SLIP RESISTANT.
  
 31. BUILDING WILL BE REQUIRED TO MEET
 HIGH-RISE REQUIREMENT IF GREATER THAN
 75 FEET IN HEIGHT.
  
 32. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 33. GARAGE VENTILATION DUCTS IN STAIR
 #1. PLEASE XPLAIN WHAT CODE ALLOWS THIS
 TO OCCUR.
  
 34. PLEASE PROVIDE FLAME SPREAD FOR
 TRASH CHUTE INSULTATION.
  
 35. EXIT SIGNS SHALL NOT EXCEED 100
 FEET.
  
 36. AN EMERGENCY COMMNAD CENTER SHALL
 COMPLY WITH NFPA 1, 2003 EDITION,
 SECTION 11-9. PLEASE ILLUSTRATE
 COMPLIANCE.
  
 37. ITEMS APPEAR TO BE MISSING FROM
 COMMAND CENTER.
  
 38. EMERGENCY LIGHTING AND STANDBY
 POWER SHALL COMPLY WITH APPLICABLE
 CODE SECTIONS.
  
 39. NO EXIT SIGNS AT THE POOL LEVEL.
  
 40. THE SMOKE CONTROL PANEL SHALL
 PROVIDE A GRAPHIC REPRESENTATION OF THE
 BUILDING. HOA SWITHCES ONLY WILL
 NOT BE ACCEPTED.
  
 41. FIRE ALARM SYSTEM SHALL BE UL LISTED
 FOR CENTRAL STATION SERVICE. FIRE
 ALARM SYSTEM SHALL BE CLASS A OR BE
 FULLY ADDRESSABLE.
  
 42. DUCT DETECTORS SHALL BE CORRECTED
 TO THE ALARM.
  
 43. HOW ARE REPAIRS HANDLED FOR THE
 PUMP ROOM SINCE IT IS LOCATED ON THE
 MEZZANINE.
  
 44. THE FIRE ALARM SYSTEM SHALL MEET
 THE SURVIVABILITY REQUIREMENT.
  
 45. HOSE VALVES SHALL BE INSTALLED AT
 FLOORS IN THE STAIRWELLS NOT
 INTERMEDIATE FLOORS.
  
 46. PLEASE EXPLAIN TEST HEADER ON
 MEZZANINE LEVEL.
  
 47. SEVERAL INCORRECT NOTES IN FIRE
 SPRINKLER BOX ON PAGE FP-1.0.
  
 48. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER PLANS.
  
 49. NOTES REGARDING FIRE PUMP SIZES
 DIFFERS IN SEVERAL LOCATIONS.
  
 50. WHERE ARE THE PORTABLE FIRE
 EXTINGUISHER LOCATIONS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-09 Cont ID  
Sent By shill Date 2006-03-09 Time 15:36 Rev Time 0.00
Received By shill Date 2005-10-04 Time 14:23 Sent To  
Notes
2005-10-04 00:00:00TO "COMM" BD#16/PLANS ON RACK/3 ROLLS
 AND BINDERS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By hmoser Date 2005-12-28 Time 07:19 Rev Time 0.00
Received By hmoser Date 2005-12-28 Time 07:19 Sent To  
Notes
2005-12-28 00:00:00PLAN DENIED
 1) PLEASE HAVE SEER OF A/C EQUIPMENT ON
 ENERGY CALCULATIONS.
 2) PLEASE REFER TO TABLE 403.3 PRIVATE
 GARAGES.2001 FBC(M)
 3) PLEASE PROVIDE A COPEY OF
 INSTALLATION INSTRUCTIONS FOR A/C
 EQUIPMENT
 4) PAGE M-2.1 CFM ON VEF-5 DOES NOT
 MATCH
 VENTILATION FAN SCHEDULE ON PAGE M-4.4.
 5) PAGE M-2.2 GENRATOR.PLEASE REFER TO
 SECTION 1305.7VENT PIPING.2001 FBC (M)
 6) PAGE M-2.3 BATHROOM EXHAUST MUST
 TERMINATE OUT DOORS.SECTION 501.3 2001
 FBC (M).
 7) PAGE M-2.3 CAN NOT BRING FRESH AIR
 FROM GARAGE INTO MECH/ELEC ROOMS.
 8) PAGE M-2.8 PLEASE REFER TO SECTION
 1511.7 AND TABLE 1511.7 2001
 FBC.CLEARANCE BELOW RAISED ROOF MOUNTED
 MECHANICAL UNITS.
 9) PAGE M-3.0 PLEASE REFER TO SECTION
 504.6 DRYER EXHAUST.
 10) PAGE M-3.2 PLEASE REFER TO SECTION
 602.2.1 MATERIALS EXPOSED IN PLENUMS
 (A/C CLOSIT DOORS ARE PART OF PLENUM)
 11) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.
 12) PLEASE SHOW CALCULATIONS ON PLANS
 FROM TABLE 1103.1 2001 FBC(M)ON
 REFRIGERANT LINES AND 2HR SHAFTS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By kstevens Date 2005-12-28 Time 17:18 Rev Time 0.00
Received By kstevens Date 2005-12-27 Time 18:57 Sent To  
Notes
2005-12-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1. SHT A-G.0 NOT SIGNED, SEALED AND
 DATED AS REQUIRED BY FAC 61G1-16.003 AND
 FS 481.2055.
 2. ALL ARCHITECTURAL SHEETS REQUIRE THE
 PERSONAL SIGNATURE OF THE ARCHITECT.
 PLEASE SUBMIT DRIVERS LICENSE, VOTERS
 REGISTRATION, OR OTHER PROOF OF LEGAL
 SIGNATURE. INITIALS ARE NOT APPROVED. IF
 THAT IS INDEED YOUR LEGAL SIGNATURE,
 SUBMIT A SIGNED, SEALED, DATED, PROPERLY
 NOTERIZED LETTER INDICATING LEGAL
 SIGNATURE FOR OUR FILES.
 3. SHTS PD1, PD2, WS1, WS2, WS3, & WS4 -
 SEAL INFORMATION REQUIRED BY FAC
 61G1-16.001 & .002 AND FS 481.321 IS NOT
 IMPRESSED ON THE PLANS. PLEASE RESEAL
 ALL SHEETS IMPRESSING REQUIRED
 INFORMATION. SIGNATURE IS A PHOTOCOPY
 AND SHALL BE A WET SIGNATURE. THE
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED BY FS 481.319(C) AND FAC
 61G1-16.004(2) SHALL BE ON EACH SHEET.
 4. SHT WS1 INDICATE TYPE OF DRAINAGE FOR
 THE TRENCH DRAIN. IF STORM DRAINAGE, IT
 WILL DRAIN TO STORM SEWER. CITY WPB CODE
 90-125(5).
 5. SHTS A-2.4, A-2.7, A-2.8, A-2.9 AND
 A-2.23. SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW THE SF
 OF EACH AREA WITH 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS, AND
 THE AREA OF ROOFS THAT DRAIN FROM ABOVE
 ON TO THE ROOF AREA IN THE CALCULATIONS.
 SECTIONS 1106, & 1107 AND ALL
 SUBSECTIONS.
 6. INFORMATIONAL - SEPARATE POOL PERMIT
 REQUIRED. PLANS SHALL BE ROUTED TO THE
 PALM BEACH COUNTY HEALTH DEPT. PRIOR TO
 BEING SUBMITTED TO THE CITY FOR REVIEW.
 PLANS SHALL BE STAMPED BY HEALTH DEPT.
 (MINIMUM TWO COPIES).
 7. SHTS A-2.10 THRU A-2.12 & A-2.15 THRU
 A-2.20.5. THE CLEAR FLOOR SPACE
 DIMENSIONS ARE TO BE APPLIED OR
 SUPERIMPOSED OVER A PLAN DURING THE
 DESIGN PROCESS TO DETERMINE IF SPACE
 REQUIREMENTS AT THE TOILETS ARE BEING
 MET. SEE PAGE 7.43.
 8. SHTS A-2.15 THRU A-2.20.5. THE 30" X
 48" CLEAR FLOOR SPACE FOR THE SHOWERS
 MUST BE PARALLEL TO THE FIXTURE & FLUSH
 WITH THE CONTROL WALL. SEE PAGE 7.56.
 9. ALL UNITS - SPECIFICATION "A" OR "B"
 SHALL BE INDICATED FOR THE BATHROOMS OF
 EACH UNIT. SEE PAGE 7.35.
 10. SHTS A-2.3 & A-2.25 TOILET ROOMS
 SHALL BE ACCESSIBLE. PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 11. SHT A-2.25 SUBMIT A DETAIL FOR THE
 ACCESSIBLE DRINKING FOUNTAIN. SHOW
 COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS.
 12. SHT A-4.0 CALLS OUT SHT A-X.X FOR
 DETAILS AND TYPICAL SPECS FOR ALUMINUM
 RAININGS. SHT A-X.X WAS NOT FOUND OR
 INDICATED ON THE INDEX SHEET. PLEASE
 CLARIFY. MORE INFORMATION IS REQUIRED.
 SECTION 104.2.1.
 13. SHT A-7.0 DETAIL #9 INDICATES A 4" X
 10" SCUPPER, BUT SHTS A-2.21 & A-2.22
 SHOW 14" X 6" SCUPPERS. PLEASE CLARIFY
 AND CORRELATE DETAILS AND ROOF PLANS.
 SECTION 104.2.1.
 14. SHT A-8.3 INTERIOR FININSH #032
 INDICATES PAINT ON GREEN BOARD DRYWALL.
 PLEASE INDICATE HOW THIS WILL MEET THE
 REQUIREMENTS OF SECTION 1204.2
 (NONABSORBENT MATERIAL TO A HEIGHT OF
 4FT ABOVE THE FLOORL.
 15. ALL PLUMBING & MECHANICAL SHEETS.
 THE CERTIFICATE OF AUTHROIZATION NUMBER
 IS REQUIRED ON EACH SHEET PER FAC
 61G15-23.002(2) AND FS 471.025.
 16. SHT P-1 THE SAND/OIL INTERCEPTOR
 SHALL BE SIZED BY LYNN MASSON
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT
 HER AT (561) 822-2271, OR FAX (561)
 822-2279, OR E-MAIL [email protected].
 WASTE ORD. 3434.
 17. P-1 MORE INFORMATION IS REQUIRED FOR
 THE WET-WELL PRECAST CONCRETE BASIN.
 SUBMIT MANUF. SPECIFICATION SHEETS.
 SECTION 104.2.1.2.
 18. THE SAND/OIL INTERCEPTOR SHALL BE
 LOCATED UPSTREAM OF THE PUMP SYSTEM.
 19. SHT P-1 SHOW SF OF ALL RISERS, ALL
 SF AS IT ACCUMULATES IN THE SYSTEM, AND
 ALL PIPE SIZES.
 20. SHT P-1 RISER AT COL. LINE C/3 IS
 NOT SHOWN ON SHT P-2. PLEASE CLARIFY.
 SECTION 104.2.1.
 21. SHT P-2 G.D. AT COL. LINE C/2 NOT
 SHOWN ON SHT P-1. PLEASE CLARIFY.
 SECTION 104.2.1.
 22. SHT P-2 RISER AT COL. LINE E/4 IS
 SHOWN AS 6" 1860SF, BUT ON SHTS P-1 &
 P-3 IT IS SHOWN AS 4" 930SF. PLEASE
 CLARIFY. SECTION 104.2.1.
 23. SHT P-2 4" DOWNSTREAM OF S/2, S/6,
 S/4D SHOWS 4" DN, BUT ENDS AT THAT
 POINT. PLEASE CLARIFY. SECTION 104.2.1.
 24. SHT P-2 12" SD AS IT EXITS THE
 BUILDING STATES "CONNECT CW LINE".
 PLEASE INDICATE WHAT CW MEANS.
 25. SHT P-3 F.D.'S IN TRASH ROOM ARE NOT
 SHOWN ON THE SANT. RISER DIAGRAM.
 SECTION 104.3.1.1.
 26. SHT P-3 RWL #3 SHOWN ON P-3 NOT
 SHOWN ON SHT P-2. PLEASE CLARIFY.
 SECTION 104.2.1.
 27. SHT P-3 AAV SHOWN ON THE COL. LINE C
 BETWEEN COLS. 4 & 5 REQUIRES A RELIEF
 VENT PER SECTION 617.3.2.
 28. SHT P-3 RPZV BACKFLOW SHALL BE
 LOCATED AS CLOSE TO THE METER AS
 POSSIBLE ON PRIVATE PROPERTY. PLEASE
 CONTACT ORVILLE POLK AT THE BACKFLOW
 DEPARTMENT (561) 822-2240 FOR PROPER
 LOCATION OF BACKFLOW PREVENTER.
 29. SHT P-4 MEN'S & WOMEN'S TOILET ROOMS
 AND FLOOR DRAINS IN THE PUMP ROOM ARE
 NOT SHOWN ON THE SANT. RISER DIAGRAMS.
 SECTION 104.3.1.1.
 30. SHT P-4 AAV SHOWN ON COL LINE C
 BETWEEN COLS. 4 & 5 REQUIRE A RELIEF
 VENT PER SECTION 617.3.2.
 31 SHT P-4 SUBMIT MANUF. SPECIFICATIONS
 FOR DOMESTIC WATER BOOSTER PUMPS. PUMPS
 SHALL BE LISTED. SECTION 303.4.
 32. SHT P-5 RWL #1 IS NOT SHOWN ON THE
 FLOOR PLAN BELOW. PLEASE CLARIFY.
 SECTION 104.2.1.
 33. SHT P-5 RISER S/4 AT COL. LINE 3
 WEST OF COL. E.4 IN INDICATED AS RISER
 S/4A ON SHT P-4. PLEASE CLARIFY. SECTION
 104.2.1.
 34. SHT P-5. INDICATE ALL RISER NUMBERS
 AT KITCHEN SINKS. RISERS NOT SHOWN ON
 PREVIOUS FLOOR PLAN SHEET. PLEASE
 CLARIFY. SECTION 104.2.1.
 35. SHT P-6 RISERS FOR KITCHEN SINKS ARE
 NOT SHOWN. PLEASE CLARIFY. SECTION
 104.2.1.
 36. SHT P-7 RISER S/4 SHOWN OFFSETTING
 IN CEILING. SHT P-7 INDICATES 3-6
 LEVELS. IS THIS OFFSET ON EACH FLOOR?
 PLEASE CLARIFY. SECTION 104.2.1.
 37. SHTS P-7 THRU P-11 KITCHEN SINKS
 RISERS ARE NOT SHOWN. PLEASE INDICATE
 THE RISER NUMBER FOR KITCHEN SINKS.
 SECTION 104.2.1.
 38. SHT P-8 OFFSET FOR S/4A AT COL. LINE
 D BETWEEN COLS. 5 & 6 IS NOT SHOWN.
 PLEASE CLARIFY. SECTION 104.2.1.
 39. SHT P-8 RISER S/6 NOT SHOWN ON
 PREVIOUS FLOOR PLAN. (P-6) PLEASE
 CLARIFY. SECTION 104.2.1.
 40. ALL PIPES 3" AND LARGER ARE NOT
 APPROVED IN BLOCK WALLS. SECTION
 1907.3.6.
 41. SHTS P-12 & P-13 SHOW THE LOCATION
 OF ALL VENTS THRU THE ROOF. SECTION
 104.2.1.
 42. SHT P-15 TOILET ROOMS AND SERVICE
 SINK ARE NOT SHOWN ON THE RISER DIAGRAM.
 SECTION 104.3.1.1.
 43. SUBMIT STORM RISER DIAGRAMS IN
 ISOMETRIC FORM. SHOW ALL PIPE SIZES,
 OFFSETS, & INDICATE SF AS IT ACCUMULATES
 IN RISER. SECTION 104.3.1.1.
 44. SUBMIT CONDENSATE RISER DIAGRAMS
 SHOWING ALL PIPE SIZES, OFFSETS ECT.
 45 SUBMIT A CONDENSATE BLDG DRAIN
 ISOMETRIC SHOWING THE LOCATION OF ALL
 CONDENSATE RISERS AND THE TERMINATION
 POINT OF THE CONDENSATE SYSTEM. SECTION
 104.3.1.1.
 46.SHTS P-16 & P-17 IF THERE ARE VENT
 THRU THESE ROOFS, PLEASE SHOW THE
 LOCATION OF EACH. SECTION 104.2.1.
 47. SHT P-18 INDICATES LEVEL 9 & LEVEL
 10. THE BUILDING IS ONLY 8 STORIES HIGH.
 PLEASE CLARIFY. SECTION 104.2.1.
 48. SHT P-18 RISER S/1 DOES NOT REFLECT
 THE FLOOR PLAN. NO TUBS SHOWN. SECTION
 104.2.1. PLEASE CORRELATE RISER & FLOOR
 PLAN.
 49. SHT P-18 RISER S/2 DOES NOT REFLECT
 THE FLOOR PLAN. RISER SHOWS KITCHEN
 SINKS AND FLOOR PLAN SHOWS W/M'S. PLEASE
 CORRELATE RISERS & FLOOR PLANS. SECTION
 104.2.1.
 50. SHT P-18 RISER S/2A NOT FOUND ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 51. SHT P-18 RISER S/2B NOT LOCATED ON
 THE FLOOR PLAN. UNABLE TO LOCATE UNIT H
 ON THE FLOOR PLAN. INDICATE UNIT
 DESIGNATION FOR EACH UNIT. A RELIEF VENT
 IS REQUIRED FOR THE AAV AT KITCHEN SINK
 ON THE 4TH (?) LEVEL. SECTION 917.3.2.
 AND SECTION 104.2.1.
 52. SHT P-18 RISER S/3 DOES NOT REFLECT
 THE FLOOR PLAN. W/C, SHR & LAV ON FLOOR
 PLAN, W/M ON RISER DIAGRAM. CORRELATE
 RISER & FLOOR PLAN. SECTION 104.2.1.
 53. SHT P-18 RISER S/3A UNABLE TO LOCATE
 ON THE FLOOR PLAN. INDICATE FLOOR
 ELEVATION, UNIT DESIGNATION ETC.
 INDICATE RISER VENT WILL CONNECT TO AND
 SHOW CONNECTION AT RISER CONNECTING TO.
 SECTION 104.2.1.
 54. SHT P-18 RISER S/4 DOES NOT REFLECT
 THE FLOOR PLAN. NO TUBS SHOWN ON THE
 FLOOR PLAN. SECTION 104.2.1. PLEASE
 CORRELATE RISER & FLOOR PLAN.
 55. SHT P-18 RISER S/5 DOES NOT REFLECT
 THE FLOOR PLAN. W/C, SHR, & LAV ONLY ON
 FLOOR PLAN. CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 56. SHT P-18 THE FOLLOWING RISER
 DIAGRAM SHOWN ON THE FLOOR PLAN WERE
 NOT SUBMITTED. S/1R, S/2R, S/4A, S/4B,
 S/4C, S/4D, S/6, S/6A, S/7 & S/9. PLEASE
 SUBMIT RISER DIAGRAMS FOR ALL RISERS
 INDICATED ON THE FLOOR PLAN. SECTION
 104.2.1.
 57. ALL SANITARY RISER DIAGRAMS: PLEASE
 SHOW ALL PIPE SIZES, OFFSETS, OFFSET
 VENTS, FIXTURE UNITS, (RECHECK FU ON ALL
 RISER DIAGRAMS), VENTS, RELIEF VENTS,
 (WHERE REQUIRED), ETC. SECTIONS 104.2.1
 & 104.3.1.1.
 58. SHT P-19 ALL WATER RISER DIAGRAMS:
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 ALL AIR CHAMBERS FROM ALL RISER
 DIAGRAMS. WATER HAMMER ARRESTORS ARE
 REQUIRED AT EACH DISH WASHER, WASH
 MACHINE, AND REFRIGERATOR. PDI-WH 201.
 SECTION 604.9 INDICATE UNIT TYPE FOR
 EACH WATER RISER DIAGRAM. SECTION
 104.2.1.
 59. SHT P-20 OVERALL SANITARY ISOMETRIC:
 SHOW ALL PIPE SIZES, ALL DFU'S FOR EACH
 RISER AND AS THEY ACCUMULATE IN THE
 SYSTEM, AND ALL FIXTURES THAT CONNECT TO
 THE BUILDING DRAIN NOT SHOWN ON THE
 RISERS. SECTIONS 104.2.1 & 104.3.1.1.
 60. SHT P-21 OVERALL WATER ISOMETRIC:
 SHOW ALL PIPE SIZES, RISER DESIGNATIONS,
 VALVES, (SEE SECTION 606.1(1)(2)(3)(4)).
 SUBMIT MANUF. SPECIFICATIONS FOR THE
 DOMESTIC WATER BOOSTER PUMP. SECTION
 303.4. BACKFLOW TO BE LOCATED PER
 BACKFLOW DEPT. CITY WPB.
 61. SHT P-22 PARTIAL GARAGE DRAINAGE
 ISOMETRIC: SHOW SF AS IT ACCUMULATES IN
 THE SYSTEM. DOES NOT REFLECT THE FLOOR
 PLAN. SAND/OIL INTERCEPTOR SHALL BE
 UPSTREAM OF THE PUMP/EJECTOR. 4" SD UP
 IS SHOWN AS 6" ON THE FLOOR PLAN. PLEASE
 CORRELATE RISERS AND FLOOR PLANS.
 SECTION 104.2.1.
 63. SHT P-23 RECHECK ALL ADDITION FOR
 SQUARE FOOTAGE. - INDICATE WHAT CW
 STANDS FOR WHERE STORM EXITS BUILDING.
 SECTION 104.2.1.
 64. SHT P-23 PUMPS CONNECTED TO THE
 DRAINAGE SYSTEM SHALL CONNECT TO THE
 BUILDING SEWER OR SHALL CONNECT TO A WYE
 FITTING IN THE BUILDING DRAIN A MINIMUM
 OF 10 FEET FROM THE BASE OF ANY SOIL
 STACK, WASTE STACK OR FIXTURE DRAIN.
 WHERE THE DISCHARGE LINE CONNECTS INTO
 THE HORIZONTAL DRAINAGE PIPING, THE
 CONNECTOR SHALL BE MADE THROUGH A WYE
 FITTING INTO THE TOP OF THE DRAINAGE
 PIPING. SECTION 712.3.5.
 65. SHT P-24 SAND/OIL INTERCEPTOR DETAIL
 TWO WAY CLEANOUTS ARE REQUIRED AS THE
 WATER ENTERS THE INTERCEPTOR AND AS THE
 WATER EXITS THE INTERCEPTOR. A VENT
 CONNECTION IS SHOWN, THE INTERCEPTOR
 SHALL BE INSTALLED IN ACCORDANCE WITH
 MANUF. INSTRUCTIONS. SECTION 1003.2 AND
 UTILITY STANDARDS.
 66. SHT P-24 PLUMBING GENERAL NOTES: 1B
 REFERENCES THE SOUTH FLORIDA BUILDING
 CODE AS WELL AS THE PLUMBING FIXTURE
 SCHEDULE #1). THESE SHALL REFERENCE THE
 FLORIDA BUILDING CODE-2001 AS WE HAVE
 BEEN IN THIS CODE STATEWIDE SINCE MARCH
 1, 2002.
 67. SHT P-24 PLUMBING GENERAL NOTES: 4.
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM REFERENCE. SECTION 604.9.
 68. SHT P-24 GARAGE AREA DRAIN SUMP PUMP
 DETAIL: SHOWS THE SUMP PIT TO BE
 18"X18"X18". SECTION 712.3.2 STATES THE
 SUMP PIT SHALL NOT BE LESS THAN 24"
 DEEP. PLEASE INDICATE ON DETAIL.
 69. ALL SANT., WATER, STORM, CONDENSATE
 RISER DIAGRAMS SHALL BE SHOWN ON EACH
 FLOOR AND SHALL REFLECT THE RISER
 DIAGRAMS FOR EACH SYSTEM. SOME RISERS
 ARE NOT SHOWN ON ONE FLOOR BUT APPEAR ON
 ANOTHER FLOOR. PLEASE CORRELATE ALL
 RISERS WITH THE FLOOR PLANS.
 70. PLANS DO NOT APPEAR TO BE COMPLETE
 AT THIS TIME AND MORE COMMENTS MAY BE
 GENERATED ACCORDING TO THE COMMENT
 RESPONSES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-19 Cont ID  
Sent By aaponte Date 2006-01-19 Time 09:30 Rev Time 0.00
Received By aaponte Date 2006-01-19 Time 09:30 Sent To  
Notes
2006-01-19 00:00:001. THE BUILDING IS SET BACK MORE THAN 5
 FEET FROM THE PREPERTY LINE ALONG
 SAPODILLA AVENUE. A VARIANCE FROM DAC IS
 REQUIRED.
 2. PARKING GARAGE EXHAUST VENTILATION
 CAN NOT BE LOCATED ON THE PLAZA. PLEASE
 RELOCATE.
 3.FIRST FLOOR UNITS ARE EXCEEDING THE
 MAXIMUM FINISHED FLOOR TO FINISHED FLOOR
 HEIGHT ALLOWED. A VARIANCE FROM DAC IS
 REQUIRED.
 4. MANAGER'S ROOM AND BATHROOMS ARE NOT
 ALLOWED AT THE MEZZANNINE LEVEL. ONLY
 MEZZANNINES INSIDE THE UNITS AND NOT
 LIVING SPACES IN THE PARKING AREA ARE
 ALLOWED.
 5. VEHICULAR ENTRIES ARE NOT PERMITTED
 ON PRIMARY STREETS
 6. PLEASE PROVIDE A DIAGRAM SHOWING THE
 AREA COUNTED AS OPEN SPACE. THE 10 FEET
 SIDEWALK REQUIREMENT CANNOT BE COUNTED
 AS PART OF THE OPEN SPACE.
 7. DEAD-END PARKING SHALL HAVE A MINIMUM
 OF 5 FEET BACK UP SPACE.
 8. PLEASE SUBMITT INFORMATION TO CONFIRM
 UNITY OF TITLE.
 9. EXPOSED TIE JOINTS PATTERN FOR THE
 EXPOSED ARCHITECTURAL CONCRETE EYEBROW
 MUST BE ALLIGNED.
 10. PLEASE REVIEW THE PLAZA DESIGN TO
 MAKE IT MOR INVITING FOR THE GENERAL
 PUBLIC AND LESS AS AN ENTRY FOR YOUR
 BUILDING. OPEN SPACE SHALL INCLUDE A
 DRINKING FOUNTAIN.