| 2005-10-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | MYRON JACOBS(561) 805 6726 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) THE SYSTEM CHOSEN FORM THIS PACKAGE |
| | DOES NOT MEET THE REQUIRED PRESSURES FOR |
| | A FLAT ROOF IN THE CITY OF WEST PALM |
| | BEACH. SEE SECOND COMMENT FOR MORE |
| | INFORMATION. |
| | |
| | 2) FBC 1606.2.5THE SYSTEM SELECTED |
| | FROM THE SUBMITTED FLAT ROOF PRODUCT |
| | APPROVAL NOA HAS A MAXIMUM DESIGN |
| | PRESSURE OF LESS THAN -89 PSF AND CITES |
| | GENERAL LIMITATION #9. GENERAL |
| | LIMITATION #9 PROHIBITS RATIONAL |
| | ANALYSIS OR EXTRAPOLATION TO ENHANCE THE |
| | UPLIFT PRESSURE AT PERIMETER AND CORNER |
| | AREAS BY REDUCING THE FASTENER SPACING |
| | IN THESE AREAS.EITHER SELECT AN |
| | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| | THAT DOES NOT CITE GENERAL LIMITATION |
| | #9.ALTERNATIVELY IF THE SELECTED |
| | SYSTEM DOES CITE GENERAL LIMITATION #9, |
| | IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| | OF 30 FEET OR LESS). |
| | |
| | BUILDING PLAN REVIEW |
| | MYRON JACOBS |
| | TEL: (561)805-6726 |
| | FAX: (561)659-8026 |
| | |