Plan Review Details - Permit 05091456
Plan Review Stops For Permit 05091456
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By lursu Date 2006-03-28 Time 15:14 Rev Time 0.00
Received By jwitmer Date 2006-05-24 Time 11:21 Sent To  
Notes
2006-03-28 00:00:00NEW ADDRESS ASSIGNED TO BLDG 5:
 1580 SAMANTHA LN ( EXT #0001 OFF MAIN
 SITE ADDRESS 715 HANK AARON DR)

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By lursu Date 2006-03-01 Time 14:36 Rev Time 0.00
Received By lursu Date 2006-03-01 Time 14:32 Sent To  
Notes
2006-03-01 00:00:00NEED SITE PLAN AND PROPOSED STREET NAMES
 BEFORE ISSUING AN ADDRESS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-26 Cont ID  
Sent By jwitmer Date 2006-05-26 Time 16:05 Rev Time 20.00
Received By jwitmer Date 2006-05-24 Time 11:21 Sent To  
Notes
2006-05-24 00:00:00 
 .
 BUILDING PLAN REVIEW
 PERMIT: 05091456MIZNER LAKES
 ADD: 1580 SAMANTHA LN
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 ARCH:SLATTERY & ASSOC/PAUL J SLATTERY
 2060 NW BOCA RATON BLVD
 BOCO RATON, FL
 TEL: (561) 392-3848
 FAX: (561) 392-5402
  
 STRUC: CHM STRUCTURAL ENG, LLC
 9200 S DADELAND, SUITE 409
 MIAMI, FL
 TEL (305) 667-1621
 FAX (305) 662-9673
  
 ARCHITECTURAL SHEET A.002, BUILDING
 DATA DOES NOT IDENTIFY THE MINIMUM
 BUILDING DESIGN GOVERNED BYINTENDED
 OCCUPANCYSEE 503.1.2 AND TABLE 500.
 COMMENT# 10 ALSO REFERS BACK TO THIS
 SAME ISSUE. PLEASE PROVIDE THIS
 INFORMATION ON A-002 UNDER BUILDING# 5
 DATA.
  
 ARCHITECTURAL SHEET A-251 INDICATES THAT
 THIS PLAN WAS DEVELOPED UNDER THE 2001
 FBC, BUT HAS CODE REFRENCES FOR THE 2004
 FBC (TYPE II-B). S-0.00 ALSO INDICATES
 THE PLANS WERE DEVELOPED UNDER THE 2001
 FBC.
 NOTE A-253-A-256 STILL REFRENCE A R-3
 OCCUPANCY WHICH IS FOR SINGLE
 FAMILY THIS WILL BE AN R2 OCCUPANCY CLASSIFICATION.
  
 THIS BUILDING IS A MIXED OCCUPANCY
 BUILDING AND TO COMPLY WITH SECTION 303.
 PLANS ARE TO INDICATE WHERE AREA AND
 HEIGTH MODIFICATIONS ARE TAKEN, SECTION
 503.
  
 THIS REVIEW WILL BE COMPLETED UNDER THE:
 2001 FBC
 TYPE: II, SPRINKLERED NFPA 13
  
  
 ---NOTE---
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1)2ND REQUEST, PROVIDE NOC RECORDED WITH
 THE CLERK OF COURT BEFORE A PERMIT CAN
 BE ISSUED. NOTE: FL S S 713.13(2) IF THE
 NOC ISRECORDED AT THE CLERK OF THE
 COURT ANDWORK HAS NOT STATED WITH 90
 DAYS OF RECORDING IT IS NULL & VOID
 REQUIRING RE-RECORDING.
  
 2) 2ND REQUEST,FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING
 CAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF
 THE SOIL IS NOT DEFINITLY KNOWN OR IS IN
 QUESTION THE BUILDING OFFICIAL MAY
 REQUIRE EXPLORATIONS, TEST OR OTHER
 ADEQUATE PROOF AS TO THE PERMISSIBLE
 SAFE BEARING CAPACITY. REQUIRED TEST AND
 RECOMMENDATIONS SUBMITTED TO VERIFY
 BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICALREPORT FROM A DESIGN
 PROFESSIONAL PROPERLY LICENSED IN THE
 STATE OF FLORIDA.
  
 3)2ND REQUEST, FBC 13-103.1.2 BEFORE A
 BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4)COMPLIED.
  
 5)2ND REQUEST, BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 6)2ND REQUEST,WPB AMENDMENT 105.13.6.
 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 104.1.2*:
  
 10)SHEET A-002
  
 10A) 2ND REQUEST,AS NOTED ABOVE PLANS
 ARE TO INDICATE THE MINIMUM BUILDING
 TYPE, 503.1.2& TABLE 500.PROVIDE AREA
 AND HEIGTH MODIFICATIONS.
  
 10C)A) FLOOD ZONE
 10C)B) FLOOD ELEVATION (IF A ZONE)
 10C)C) LOMAR (IF A ZONE)
 10C)D) COMPLIED.
 10C)E) COMPLIED.
 10C)F) COMPLIED.
 10C)G) COMPLIED.
 10C)H) COMPLIED.
 10C)I) COMPLIED.
 10C)J) COMPLIED.
 10C)K) SQ FT UNDER ROOF (TOTAL)
  
 11) SHEET A-102;
  
 11A) COMPLIED.
  
 11B) COMPLIED.
  
 12) COMPLIED.
  
 13A)2ND REQUEST, PROVIDE A SECTION
 THROUGH STAIRWAYS INDICATING COMPLIANCE
 WITH GUARDRAILS FOR HEIGHT (HEAD PROTECTION).COMMON
 PROBLEM TO ALL STAIRWAYS,11-4.4.2 HEAD ROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AILES OR
 OTHER CIRCULATION SPACES SHALL HAVE 80
 INCHES MINIMUM CLEAR HEAD ROOM (SEE
 FIGURE 8(A)). IF VERTICAL CLEARENCE OF
 AN AREAADJOINING AN ACCESSIBLE ROUTE IS
 REDUCED TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR VISUALLY-IMPARED
 PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)).
  
 13B) 2ND REQUEST, STAIR TOWER# 4 WINDOWS
 WITHIN 10'-0" OF TOWER OPENINGS SEE
 1006.1.3.2 THE 2001 CODE DOES NOT
 PROVIDE A WATER CURTAIN AS AN EQUALENT.
  
 13C) COMPLIED.
  
 13D)THIS COMMENT TO BE RESTATED!!!SINCE
 THIS REVIEW THE CONFIGURATION OF LOFT
 UNITS VS PASSAGE TO THE PARKING GARAGE
 WITH NO EXIT ACCESS CORRIDOR WAS BROUGHT
 TO THE ATTENTION OF THE BUILDING
 OFFICIAL. WE ARE SEEING MORE OF THIS
 TYPE DESIGN AND THE BUILDING OFFICIAL
 HAS RULED THAT THIS IS AN UNSAFE
 PRACTICE. THE OCCUPANTS LEAVE THE R-2
 UNIT AND HAVE NO EXIT ACCESS CORRIDOR
 WHEN ENTERING THE PARKING GARAGE AREA.
 ALTHOUGH THE CODE DOESN'T QUOTE A
 SECTION, THAT AN EXIT ACCESS CORRIDOR IS
 REQUIRED THE BUILDING OFFICIAL IS USING
 THESE (2) CODE SECTIONS TO ENFORCE
 REQUIRING A EXIT ACCESS CORRIDOR TAKING
 THE OCCUPANT TO THE SAFETY OF AN EXIT.
 103.6** REQUIREMENTS NOT COVERED BY
 THE CODE. ANY REQUIREMENTS NECCESAARY
 FOR THE STRENGTH, STABILITY OR PROPER
 OPERATION OF EXITING OR PROPOSED
 BUILDING, STRUCTURE, ELECTRIC, GAS,
 MECANICAL OR PLUMBING SYSTEM, OR FOR
 PUBLIC SAFETY, HEALTH AND GENERAL
 WELFARE , NOT SPECIFICALLY COVERED BY
 THIS OR OTHER TECHNICAL CODES, SHALL BE
 DETERMINED BY THE BUILDING OFFICIAL. IN
 ADDITION, OTHER REQUIREMENTS TO
 IMPLEMENT, CLARIFY OR SET PROCEDURES TO
 IMPLEMENT THIS CODE MAY BE SET IN
 WRITING BY THE BUILDING OFFICIAL AND BE
 POSTED ELECTRONICALLY FOR BUBLIC ACCESS.
 1001.1.4 WHEN UNUSUALLY HAZARDOUS
 CONDITIONS EXIST, THE BUILDING
 OFFICIAL MAY REQUIRE ADDITIONAL MEANS
 OF EGRESS TO ASSURE THE SAFETY OF
 THE OCCUPANTS.
  
 NOTE: COMMENTS 13E-13H NOT FOUND IN
 COMMENT SHEET!!!!!!!!!!!!!!!!
 13E) ON THE RIGHT SIDE OF 201- 202 THE
 COMMERCIAL AREA, IT APPEARS THERE IS A
 HANDICAPPED RAMP AND STAIRS, BUT NO
 SECTIONS THROUGH FOR FURTHER DETAILS? NO ELEVATIONS
 PROVIDED? IT APPEARS THAT THE
 EXHAUST FROM THE PARKING GARAGE IS
 WITHIN 5'-0" OF THE HANDICAPPED RAMP, IS
 THERE FLARINGS TO DIRECT EXHAUST FROM
 THE RAMP?
  
 13F) HANDICAPPED SPACE WITHIN PARKING
 GARAGE NEEDS TO SHOW VAN ACCESSIBLE
 PARKING.11-4.1.2(5)(B) IN PARKING
 STRUCTURES, ONE IN EVERY EIGHT
 ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL
 BE DESIGNED AS REQUIRED BY 11-4.6.3.
 THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH ?11-4.6.5.ALL SUCH
 SPACES MAY BE GROUPED ON ONE LEVEL OF A
 PARKING STRUCTURE.WHEN SUCH SPACES ARE
 PROVIDED IN A PARKING STRUCTURE AND ONLY
 ONE IN EIGHT MEET THE HEIGHT REQUIREMENT
 OF 11-4.6.5, THEY SHALL BE DESIGNATED AS
 REQUIRED BY 11-4.6.4.
  
 13G) PROVIDE MORE INFORMATION, PLANS
 INDICATE A TRASH ROOM # 103 BUT THERE IS
 AN AREA # 124 TRAASH AREA? EXPLAIN?THIS
 AREA IS NOT AUTOMOBILE STORAGE BUT A S1
 STORAGE REQUIRING A 3HR SEPERATION. SEE
 TABLE 704.1.
  
 13H) THE 2 STORY LOFT UNITS DO NOT HAVE
 EXIT ACCESS CORRIDORS TO THESE UNITS.
 EXIT ACCESS CORRIDORS WILL BE REQUIRED
 BECAUSE THE GARAGE ENTRY DOOR IS THE
 PRIMARY ENTRY DOOR COVERED UNDER FAIR
 HOUSING. SEE FAIR HOUSING P. 1.22
 ELEVATORS MUST PROVDE ACCESS TO PRIMARY
 ENTRY FLOORS OF 2-STORY DWELLING IN
 ELEVATOR BUILDINGS. NOTED THE 2-STORY
 LOFT UNITS DO HAVE A FRONT DOOR WHERE
 STAIRS ARE PRESENT, THE ENTERIOR ENTRY
 DOOR IS CONSIDERED THE MAIN OR PRIMARY
 ENTRY DOOR.
 1001.1.3 MEANS OF EGRESS SHALL CONSIST
 OF CONTINUOUS AND UNOBSTRUCTED PATHS OF
 TRAVEL TO THE EXTERIOR OF A BUILDING.
 MEANS OF EGRESS SHALL NOT BE PERMITTED
 THROUGH KITCHENS, CLOSETS, RESTROOMS AND
 "SIMILAR AREAS" NOR THROUGH ADJACENT
 TENANT SPACES.
 THE BUILDING OFFICIAL HAS REVIEWED
 THE LAYOUT OF THIS PLAN AND INTERPRETS
 THROUGH THE GARGE AS SIMILAR AREAS.
 1001.1.4 WHEN UNUSUALLY HAZARDOUS
 CONDITIONS EXIST, THE BUILDING OFFICIAL
 MAY REQUIRE ADDITIONAL MEANS OF EGRESS
 TO ASSURE THE SAFETY OF THE OCCUPANTS
  
 14) A.203
 14A) COMPLIED
  
 14B) COMPLIED.
  
 14C) COMPLIED.
  
 14D) MAY BE REVISITED RESULTS OF 13D.
  
 15) A.204
 15A) COMPLIED.
  
 15B) COMPLIED.
  
 15C) COMPLIED.
  
 16) A.205
 16A) COMPLIED.
  
 16B) COMPLIED.
  
 16C) POOL PAVILION SINK DETAIL STILL
 DOESN'T INDICATE COUNTER HEIGTH.
  
 16D) COMPLIED.
  
 16E) COMPLIED.
  
 16F)2ND REQUEST RESPONCE BY MEP
 ENGINEER?
 POOL DECK DRAINS WILL BE INSTALLED
 IN A RATED FLOOR, PROVIDE THE TYPE OF
 PIPE TO BE USED AND THE RATED ASSEMBLY
 FOR THIS INSTALATION.
 705.6 PENETRATIONS OF HORIZONTAL
 ASSEMBLIES. ALL PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH 705.2 OR SHALL COMPLY
 WITH ?705.6.1 THROUGH 705.6.4.
 705.6.1 THROUGH-PENETRATIONS. THROUGH-PENETRATIONS
 OF FIRE RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY
 WITH 705.6.1.1 OR 705.6.1.2.
  
 16G) NOTED
  
 16H) NOTED.
  
 16I) COMPLIED.
  
 16J) COMPLIED.
  
 17) A.206
  
 17A) COMPLIED.
  
 17B) COMPLIED.
  
 17C) COMPLIED.
  
 17D) 2ND REQUEST, STAIRWELL# 2, IT
 APPEARS THAT A SHAFT IS DIRECTLY IN
 FRONT OF THE STAIRWELL. PROVIDE SECTION
 THROUGH GIVING WALL TYPE AND RATING?
 705.2.2 SHAAFT ENCLOSURES. A SECTION
 THROUGH THE STAIRWELL WALL IS PROVIDED
 BUT NOT THE SHAFT ENCLOSURE.
  
 18) A.208
 18A) COMPLIED.
  
 18B) COMPLIED.
  
 19) A.300
 19A) COMPLIED.
  
 19B) COMPLIED.
  
 20) A.403-A.406
 20A) COMPLIED.
  
 20B) 2ND REQUEST, 1404.1.1 ARCHITECTURAL
 TRIM ON BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE
 STORIES OR 40 FT (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION, THIS MEANS FOAM
 CAN NOT BE USED SINCE THIS BUILDING IS
 OVER 40'-0". FOAM IS CONSIDERED A
 CONBUSTIBLE.
  
 20C) COMPLIED.
  
 20D) 2ND REQUEST, PRODUCT APPROVALS
 SUBMITTED WITH PERMIT APPLICATION AFTER
 OCTOBER 1, 2003 ARE REQUIRED TO COMPLY
 WITH THE FLORIDA PRODUCT APPROVAL
 SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20E) COMPLIED.
  
 20F) PRODUCT APPROVALS:
 A)WINDOWS/STOREFRONT FL APPROVAL
 NEEDED, MEETS PRESSURES
 B) WINDOWS: LAWSON SH-7500- REQUIRES
 SHUTTERS NO LARGE OR SMALL NISSLE
 TESTING ARCHITECT ALL GLAZING SHALL
  
 BE IMPACT RESISTANT.
 C) MULLIONS- NO REPORT SUBMITTED SPANS
  
 OF 23'-0" SPANDRIAL GLASS
  
 D) SLIDING GLASS DOORS-NO LARGE OR
 SMALL MISSLE IMPACT RATING
  
 E) LOUVERED DOORS- NO REPORT SUBMITTED
  
 F) STEEL DOORS- FIREDOOR CORP MISSING
 FLORIDA APPROVAL, PRESSURES GOOD
 FOR:
 4080 FIREDOOR SINGLE OUTSWING
 8080 FIREDOOR OUTSWING
  
 G) EXTERIOR OVERHEAD DOORS- NO REPORT
 SUBMITTED
  
 H) EXTERIOR HANDRAILS- NO REPORT
 SUBMITTED.
  
 I)STORM SHUTTERS- ARCHITECT INDICATES
 NO STORM SHUUTERS IMPACT GLASS BUT
 CONTRACTOR IS SUBMITTING PRODUCT
 APPROVALS REQUIRING SHUTTERS.
  
 J) TRUSS ANCHORS- NO REPORT SUBMITTED
  
 K) ROOFING ASSEMBLIES:BOTH MISSING
 FLORIDA APPROVAL:
  
 GAF MODIFIED BITUMEN ROOF SYSTEMS
 CONTRACTOR FAILED TO IDENTIFY WHICH SUB-SYSTEM TO
 BE USED, NOTE IF
 LITATION 7 OR 9 ALLOWED. IF
 LIMITATION# 7, PROVIDE CALCULATIONS
  
 FOR ENHANCED FASTENING.
 NOTE, VARIOUS ROOF DETAILS DO
 INDICATE RIGID INSULATION ON ROOF.
  
 MONIER TILE: THE STRUCTURAL
 CONTRACTOR TO IDENTIFY WHICH
 FASTENING SYSTEMS WILL BE USED FOR
 ZONES 1,2 &3.
  
 20G)) AN INTERPRETATION FROM THE
 BUILDING OFFICIAL ON STORM SHUTTERS THAT
 ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2001
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 20H) PROVIDE STORM PANEL INFORMATION
 WITH INSTALLATION SCHEDULE AND KEY PLAN
 WITH SPECIFIC ANCHORS AND MOUNTING TO BE
 USED FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 20I) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 20J) COMPLIED.
  
 21) A550/ A.650
 21A) THE PLANS STILL DO NOT IDENTIFY
 WHAT TYPE OF ROOF SHEATHING TO BE USED?
 TABLE 600- TYPE II BUILDING.
  
 21B) COMPLIED.
  
 21C) COMPLIED.
  
 22) A.651
 22A) NOW SHEET A.650 DETAIL 21, PRODUCT
 APPROVALS ARE NOT REQUIRED FOR THIS
 SHUTTER, BUT THE ENGINEER WILL NEED TO
 PROVIDE CALCULATIONS FOR FIXED SHUTTER
 IN THE OPEN POSITION FOR 140 MPH WIND
 ZONE.
  
 22B) COMPLIED.
  
 22C) COMPLIED.
  
 22D) COMPLIED.
  
 23) A.701
 23A) COMPLIED.
  
 23B) COMPLIED.
  
 23C) COMPLIED.
  
 24) A.704
 24A) COMPLIED.
  
 24B) COMPLIED.
  
 24C) COMPLIED.
  
 25) A.801-A807,A.903
 25A) COMPLIED.
  
 25B) COMPLIED.
  
 26) A903/A.902/A.901
 26A) COMPLIED.
  
 26B) COMPLIED.
  
 27) A9.05
 27A) COMPLIED.
  
 27B) COMPLIED.
  
 27C) COMPLIED.
  
 28) S-0.00
 28A) COMPLIED.
  
 28B) COMPLIED.
  
 28C) COMPLIED.
  
 28D) COMPLIED.
  
 28E) COMPLIED.
  
 28F) COMPLIED.
  
 29) S3.2 COMPLIED.
  
 30) M0.2
  
 30A) 2ND REQUEST,
 ROOF TOP CONDENSING UNITS TO MEET
 THE CLEARENCE REQUIREMENTS:
 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
  
 30B) 2ND REQUEST,
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-09 Cont ID  
Sent By jwitmer Date 2006-02-09 Time 08:38 Rev Time 16.00
Received By jwitmer Date 2006-02-09 Time 07:12 Sent To  
Notes
2006-02-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091456MIZNER LAKES
 ADD: XXXN CONGRESS
  
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 ARCH:SLATTERY & ASSOC
 2060 NW BOCA RATON BLVD
 BOCO RATON, FL
 TEL: (561) 392-3848
 FAX: (561) 392-5402
  
 STRUC: CHM STRUCTURAL ENG, LLC
 9200 S DADELAND, SUITE 409
 MIAMI, FL
 TEL (305) 667-1621
 FAX (305) 662-9673
  
 ARCHITECTURAL SHEET A.002, BUILDING
 DATA DOES NOT IDENTIFY TO WHICH CODE
 THIS BUILDING WAS DESIGNED TO. THE
 BUILDING DATA SHEET ALSO DOES NOT
 PROVIDE THE MINIMUM BUILDING DESIGN
 GOVERNED BYINTENDED OCCUPANCYSEE
 503.1.2 AND TABLE 500.
  
 ARCHITECTURAL SHEET A-251 INDICATES THAT
 THIS PLAN WAS DEVELOPED UNDER THE 2001
 FBC, BUT HAS CODE REFRENCES FOR THE 2004
 FBC. S-0.00 ALSO INDICATES THE PLANS
 WERE DEVELOPED UNDER THE 2001 FBC.
 NOTE A-251 OCCUPANCY R-3 IS FOR SINGLE
 FAMILY THIS WILL BE AN R2 OCCUPANCY CLASSIFICATION.
  
 THIS REVIEW WILL BE COMPLETED UNDER THE:
 2001 FBC
 TYPE: II, SPRINKLERED NFPA 13
 ---NOTE---
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE: FL S S 713.13(2) IF THE NOC IS
 RECORDED AT THE CLERK OF THE COURT AND
 WORK HAS NOT STATED WITH 90 DAYS OF
 RECORDING IT IS NULL & VOID REQUIRING RE-RECORDING.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) ARCHITECTURAL SHEETS ARE COPIES OF
 SIGNATURE:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239.
  
 9) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 104.1.2*:
 10C)A) FLOOD ZONE
 10C)B) FLOOD ELEVATION (IF A ZONE)
 10C)C) LOMAR (IF A ZONE)
 10C)D) NUMBER OF UNITS
 10C)E) NUMBER OF FLOORS
 10C)F) NUMBER OF BEDROOMS
 10C)G) NUMBER OF ROOMS
 10C)H) NUMBER OF BATHROOM
 10C)I) SQ FT LIVING SPACE(TOTAL)
 10C)J) SQ FT FOOT PRINT
 10C)K) SQ FT UNDER ROOF (TOTAL)
  
 10)SHEET A-002
  
 10A) AS NOTED ABOVE PLANS ARE TO
 INDICATE THE MINIMUM BUILDING TYPE,
 503.1.2& TABLE 500.
  
 11) SHEET A-102;
  
 11A)DEFINITION, TERM TOWNHOUSE:A SINGLE
 FAMILY DWELLING CONSTRUCTED IN A SERIES
 OR GROUP OF ATTACHED UNITS WITH PROPERTY
 LINES SEPARATING EACH UNIT. IF TRUELY
 TOWNHOUSE CONSTRUCTION PROVIDE A REPLAT
 OF THE LAND SHOWING INDIVUAL LOT LINES.
 OTHERWISE RENAME THESE UNITS TO SOME
 OTHER TERMINOLOGY. PLANS ARE NOT BUILT
 TO THE TOWNHOUSE STANDARD FOUND UNDER
 SECTION704.4(1-5).
  
 11B) THERE APPEARS TO BE NUMBERS ON
 VARIOUS ITEMS OF THE PLANS AND TO THE
 RIGHT NOTES STATING WITH # 1 BUT NO
 OTHER INFORMATION? COMPLETE.
  
 12 ) SHEET A.300- A.304STAIR TOWER # 1
 ON EACH FLOOR MISSING CLEARENCE AT DOOR
 TO STAIRS.18"X60" LATCH SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 13) A201/ A202
 13A)2ND REQUEST, PLANS DO NOT PROVIDE A
 CUT SECTION
 THROUGH STAIRWAYS INDICATING COMPLIANCE
 WITH GUARDRAILS FOR HEIGHT (HEAD PROTECTION).COMMON
 PROBLEM TO ALL STAIRWAYS,11-4.4.2 HEAD ROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AILES OR
 OTHER CIRCULATION SPACES SHALL HAVE 80
 INCHES MINIMUM CLEAR HEAD ROOM (SEE
 FIGURE 8(A)). IF VERTICAL CLEARENCE OF
 AN AREAADJOINING AN ACCESSIBLE ROUTE IS
 REDUCED TO LESS THAN 80 IN. (NOMINAL
 DIMENSION), A BARRIER TO WARN BLIND OR VISUALLY-IMPARED
 PERSONS SHALL BE
 PROVIDED. (SEE FIGURE 8(C-1)).
  
 13B) 2ND REQUEST, STAIR TOWER# 4 WINDOWS
 WITHIN 10'-0" OF TOWER OPENINGS SEE
 1006.1.3.2 THE 2001 CODE DOES NOT
 PROVIDE A WATER CURTAIN AS AN EQUALENT.
  
 13C) COMPLIED.
  
 13D)THIS COMMENT TO BE RESTATED!!!SINCE
 THIS REVIEW THE CONFIGURATION OF
  
  
  
  
  
  
  
  
 13E) ON THE RIGHT SIDE OF 201- 202 THE
 COMMERCIAL AREA, IT APPEARS THERE IS A
 HANDICAPPED RAMP AND STAIRS, BUT NO
 SECTIONS THROUGH FOR FURTHER DETAILS? NO ELEVATIONS
 PROVIDED? IT APPEARS THAT THE
 EXHAUST FROM THE PARKING GARAGE IS
 WITHIN 5'-0" OF THE HANDICAPPED RAMP, IS
 THERE FLARINGS TO DIRECT EXHAUST FROM
 THE RAMP?
  
 13F) HANDICAPPED SPACE WITHIN PARKING
 GARAGE NEEDS TO SHOW VAN ACCESSIBLE
 PARKING.11-4.1.2(5)(B) IN PARKING
 STRUCTURES, ONE IN EVERY EIGHT
 ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL
 BE DESIGNED AS REQUIRED BY 11-4.6.3.
 THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH ?11-4.6.5.ALL SUCH
 SPACES MAY BE GROUPED ON ONE LEVEL OF A
 PARKING STRUCTURE.WHEN SUCH SPACES ARE
 PROVIDED IN A PARKING STRUCTURE AND ONLY
 ONE IN EIGHT MEET THE HEIGHT REQUIREMENT
 OF 11-4.6.5, THEY SHALL BE DESIGNATED AS
 REQUIRED BY 11-4.6.4.
  
 13G) PROVIDE MORE INFORMATION, PLANS
 INDICATE A TRASH ROOM # 103 BUT THERE IS
 AN AREA # 124 TRAASH AREA? EXPLAIN?THIS
 AREA IS NOT AUTOMOBILE STORAGE BUT A S1
 STORAGE REQUIRING A 3HR SEPERATION. SEE
 TABLE 704.1.
  
 13H) THE 2 STORY LOFT UNITS DO NOT HAVE
 EXIT ACCESS CORRIDORS TO THESE UNITS.
 EXIT ACCESS CORRIDORS WILL BE REQUIRED
 BECAUSE THE GARAGE ENTRY DOOR IS THE
 PRIMARY ENTRY DOOR COVERED UNDER FAIR
 HOUSING. SEE FAIR HOUSING P. 1.22
 ELEVATORS MUST PROVDE ACCESS TO PRIMARY
 ENTRY FLOORS OF 2-STORY DWELLING IN
 ELEVATOR BUILDINGS. NOTED THE 2-STORY
 LOFT UNITS DO HAVE A FRONT DOOR WHERE
 STAIRS ARE PRESENT, THE ENTERIOR ENTRY
 DOOR IS CONSIDERED THE MAIN OR PRIMARY
 ENTRY DOOR.
 1001.1.3 MEANS OF EGRESS SHALL CONSIST
 OF CONTINUOUS AND UNOBSTRUCTED PATHS OF
 TRAVEL TO THE EXTERIOR OF A BUILDING.
 MEANS OF EGRESS SHALL NOT BE PERMITTED
 THROUGH KITCHENS, CLOSETS, RESTROOMS AND
 "SIMILAR AREAS" NOR THROUGH ADJACENT
 TENANT SPACES.
 THE BUILDING OFFICIAL HAS REVIEWED
 THE LAYOUT OF THIS PLAN AND INTERPRETS
 THROUGH THE GARGE AS SIMILAR AREAS.
 1001.1.4 WHEN UNUSUALLY HAZARDOUS
 CONDITIONS EXIST, THE BUILDING OFFICIAL
 MAY REQUIRE ADDITIONAL MEANS OF EGRESS
 TO ASSURE THE SAFETY OF THE OCCUPANTS.
  
 14) A.203:
  
 14A) STAIRWELL# 3 THERE IS A WALL JUST
 TO THE LEFT OF THE STAIRWELL, PROVIDE A
 SECTION THROUGH IS THIS A HANDRAIL OR A
 WALL ?
  
 14B) BOTTOM LEFT OF PAGE WHERE THE
 MATCHLINE STARTS THERE IS A AREA NO ROOM
 REFRENCE, IT APPEARS POSSIBLY A FENCE
 BLOCKS THIS AREA OFF?
  
 14C) FANS UPPER RIGHT INTAKE OR EXHAUST?
  
 14D) COLUMN LINE RIGHT SIDE OF PAGE NEXT
 TO THE COMMERCIAL AREA, CUTS INTO THE
 ACCESSIBLE ISLE, MEANS OF EGRESS,
 44"MINIMUM.
  
 15) A204:
  
 15A) DOOR 204 SWINGS AGAINST THE TRAFFIC
 FLOW TO THE STAIR TOWER# 1.
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS.
  
 15B) AREA JUST RIGHT OF STAIR TOWER# 1,
 IS THIS A WINDOW, OPEN, OR HANDRAIL?
  
 15C) LEFT SIDE OF PAGE COMMENT# 14 B),
 THERE IS A PAIR OF DOORS THAT SWING INTO
 THE REQUIRED EGRESS PATH AND A COLUMN
 THAT BLOCKS THE CLEAR AREA TO THE
 COLUMN, ONLY 1'-0" CLEAR. SEE 1012.1.4.
  
 16)A.205;
  
 16A) CONDO UNIT C-4 IT APPEARS THERE MAY
 BE A SHAFT, NO INFO NO CUT SECTION?
  
 16B) POOL EQUIPMEENT ROOM JUST ABOVE
 LEFT & RIGHT IT APEARS TO HAVE MASONARY
 WALLS(M3) WWITH SOME TYPE OF OPENING ,
 RAIL? NO SSECTION?
  
 16C) POOL PAVILION INDICATES A SECTION
 A304 BUT WRONG REFRENCE?PROVIDE SECTION
 OF SINK CABINET.
  
 16D) PROVIDE ADDITIONAL INFORMATION JUST
 TO THE LEFT OF THE POOL PAVILION THERE
 APPEARS TO BE A GRILL? IF GAS:
 SECTION 2808
 BARBECUES - FACTORY-BUILT
 FACTORY-BUILT BARBECUES SHALL BE OF AN
 APPROVED TYPE AND SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS.
  
 16E)POOL DECK PLAN DOES N'T INDICATE
 WHAT TYPE OF FINISH OTHER THAN THE PAVER
 DECK, WHAT ARE THE OTHER AREAS COVERED
 WITH? PLANS DO NOT PROVIDE SLOPE TO DECK
 DRAINS OR DECK DRAINS?
  
 16F) POOL DECK DRAINS WILL BE INSTALLED
 IN A RATED FLOOR, PROVIDE THE TYPE OF
 PIPE TO BE USED AND THE RATED ASSEMBLY
 FOR THIS INSTALATION.
 705.6 PENETRATIONS OF HORIZONTAL
 ASSEMBLIES. ALL PENETRATIONS OF A FLOOR, FLOOR/CEILING
 ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH 705.2 OR SHALL COMPLY
 WITH ?705.6.1 THROUGH 705.6.4.
 705.6.1 THROUGH-PENETRATIONS. THROUGH-PENETRATIONS
 OF FIRE RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY
 WITH 705.6.1.1 OR 705.6.1.2.
  
 16G)NOTE: SEE DEPARTMENT OF HEALTH
 [DOH] RULE 64E-9, FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 514, FLORIDA STATUTES
 FOR SECURITY & REQUIRED FENCING. TO BE
 IN PLACE AT TIME OF BUILDING C.O.
  
 16H) NOTE:13-412.1.ABCD.2.4.2 COVERS
 REQUIRED. SPAS AND HEATED SWIMMING POOLS
 SHALL BE EQUIPPED WITH A COVER DESIGNED
 TO MINIMIZE HEAT LOSS.TO BE IN PLACE AT
 TIME OF BUILDING C.O.
  
 16I) PROVIDE EXITING SIGNAGE FOR POOL DECK.1016.1.1
 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE
 WITH THIS SECTION FOR EVERY BUILDING AND STRUCTURE.
 FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE
 ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND
 PASSAGEWAYS LEADING TO AN EXIT.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 16J) STAIR TOWER# 4, THE DOOR SWINGS THE
 WRONG WAY:1012.1.2EGRESS DOORS SHALL BE
 SIDE SWINGING TYPE.DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS
  
 17)A.206
  
 17A)PAIR OF DOORS # 351 SWING THE WRONG
 WAY AGAINST EXITING PATTERNS.1012.1.2.
  
 17B) RESIDENT STORAGE ROOM 313, TO BE
 CONSIDERED AN S1 REQUIRING 3 HR
 SEPERATION.TABLE 704.1.
  
 17C) SEE A-253 LIFE SAFETY PLAN STAIR
 TOWER# 1 AND DOOR 302 CAN'T ACCOMADATE
 THE OCCUPANT LOAD FOR THE UNITS AND THE
 POOL DECK, 1/2 THE LOAD OR 175 HAVE TO
 GO THROUGH DOOR 302. 175X.2=35" OF CLEAR
 OPENING, A 3'-0" DOOR CLEAR IS 34". THE
 STAIR IS 4'-4"/.3=173.3. DOOR 103 AT THE
 BOTTOM OF THE STAIR ALSO WILL BE TO
 SMALL TO ACCOMADATE THE OCCUPANT LOAD
 FROM THIS FLOOR.
  
 17D) STAIRWELL# 2 IT APPEARS THAT A
 SHAFT IS DIRECTLY IN FRONT OF THE
 STAIRWELL PROVIDE SECTION THROUGH GIVING
 WAAL TYPE AND RATING?705.2.2 SHAFT
 ENCLOSURES. ALL OPENINGS THROUGH A FLOOR
 AND PENETRATIONS THROUGH A FLOOR SHALL
 BE PROTECTED BY A SHAFT ENCLOSURE IN
 ACCORDANCE WITH 705.2.3.
  
 18) A.208:
  
 18A) STORAGE UNITS IN ROOM# 411 WILL
 REQUIRE A 3 HR WALL AROUND THE PERIMETER
 OF THE ROOM.
  
 18B) PROVIDE A CUT SECTION FOR JUST
 OUTSIDE THE FITNESS ROOM AND STORAGE
 ROOM IT APPEARS TO BE A ROOF, NO
 DETAILS.
  
 19) A.300:
  
 19A) STAIR TOWER# 1, DOOR# 103,
 1012.1.3 THE ELEVATION OF THE FLOOR
 SURFACES ON BOTH SIDES OF A DOOR SHALL
 NOT VARY BY MORE THAN 1/2 IN. (13 MM).
 THE ELEVATION SHALL BE MAINTAINED ON
 BOTH SIDES OF THE DOORWAY FOR A DISTANCE
 AT LEAST EQUAL TO THE WIDTH OF THE
 WIDEST LEAF.THRESHOLDS AT DOORWAYS
 SHALL NOT BE MORE THAN 1/2 IN. (13 MM)
 IN HEIGHT.RAISED THRESHOLDS AND FLOOR
 LEVEL CHANGES MORE THAN 1/4 IN. (6.4 MM)
 AT DOORWAYS SHALL BE BEVELED WITH A
 SLOPE NOT STEEPER THAN 1:2.
  
 19B) THE RAMP JUST TO THE LEFT OF THE
 TRASH COMPACTOR ROOM ONLY HAS A 4'-0"
 BOTTOM RAMP.11-4.8.4.(2) LANDINGS. ALL
 LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60" CLEAR, & THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72" OF STRAIGHT
 & LEVEL CLEARENCE.
  
 20)A.403- A.406 ELEVATIONS:
  
 20A) ELEVATIONS, PLEASE PROVIDE THE
 POSITIVE AND NEGATIVE PRESSURES FOR ALL
 OPENINGS, INTERIOR AND END ZONES FOR ALL
 OPENINGS. DESIGN TO ASCE 7-98
  
 20B) PLANS INDICATE THE USE OF FOAM
 BANDS, SEE 1404.1.1 ARCHITECTURAL TRIM
 ON BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES
 OR 40 FT (12.2 M) HIGH MAY BE OF TYPE VI CONSTRUCTION,
 AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS OF TYPE
 III, V AND VI CONSTRUCTION.TRIM SHALL
 BE SECURED TO THE WALL WITH METAL OR
 OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL TRIM IS LOCATED ALONG
 THE TOP OF EXTERIOR WALLS, IT SHALL BE
 COMPLETELY BACKED BY THE EXTERIOR WALL
 AND SHALL NOT EXTEND OVER THE TOP OF
 EXTERIOR WALLS.
  
 20C) EXTERIOR ALUMINIUM RAILINGS TO
 COMPLY WITH1608.2.2.1 GUARDRAIL SYSTEMS
 SHALL BE DESIGNED AND CONSTRUCTED FOR A CONCENTRATED
 LOAD OF 200 LB (890 N)
 APPLIED AT ANY POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
 1608.2.2.4 LOADING CONDITIONS IN
 1608.2.2.1, ?1608.2.2.2 AND 1608.2.2.3
 SHALL NOT BE APPLIED SIMULTANEOUSLY, BUT
 EACH SHALL BE APPLIED TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE RESPECTIVE
 COMPONENTS OR ANY OF THE SUPPORTING
 COMPONENTS.
  
 20D)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20E)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 20F) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED/ STOREFRONT
 B) WINDOWS OPERATABLE
 C) MULLIONS
 D) EXTERIOR DOORS GLAZED, SLIDERS
 E) EXTERIOR LOUVERED DOORS
 F) DOORS STEEL
 G)EXTERIOR OVERHEAD DOORS
 H)HANDRAILS
 I) STORM SHUTTERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) PREMANUFACTURED A/C STANDS
 M) STORM SHUTTERS
  
 20G)) AN INTERPRETATION FROM THE
 BUILDING OFFICIAL ON STORM SHUTTERS THAT
 ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 20H) PROVIDE STORM PANEL INFORMATION
 WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 20I) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 20J) PROVIDE ROOF PRESSURE ZONES FOR
 ZONES 1,2& 3. SEE 1606.6/ ASCE 7-98.
  
 21) A.550/ A.650:
  
 21A) THERE ARE VARIOUS
 DETAILS SHOWING ROOF SECTIONS WITH METAL
 STUD FRAMING. THERE IS NO NOTES AS TO
 THE TYPE OF FRAMING MEMBER TO BE USED,
 IF STRUCTURAL, SIZE, GAUGE, DESCRIPTION
 OF TYPE FRAMING , FLANGE WIDTH OR
 MATERIAL THICKNESS. C/C.
 PLANS DO NOT PROVIDE WHAT TYPE OF
 DECKING IS TO BE USED ON THIS PROJECT.
  
 21B)SECTION 06 IS FOR A SUN SHADE, A
 SEPERATE PERMIT IS REQUIRED. PROVIDE
 ENGINEERING FOR FRAME & CANVAS FOR 140
 MPH WIND.
  
 21C) SECTION 07 IS A DESIGN THAT WILL BE INCORPORATED
 INTO THE GUARDRAIL DESIGN.
 1015.3 OPENINGS. OPEN GUARDRAILS SHALL
 HAVE INTERMEDIATE RAILS OR ORNAMENTAL
 PATTERN SUCH THAT A 4-INCH (102 MM)
 DIAMETER SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES.A
 BOTTOM RAIL OR CURB SHALL BE PROVIDED
 THAT WILL REJECT THE PASSAGE OF 2-INCH
 (51 MM) DIAMETER SPHERE.
  
  
 22) A.651:
  
 22A) DETAIL# 05 PROVIDE PRODUCT TESTING
 REPORT FOR EXHAUAST FAN FOR PRESURES+/-
 ZONES 1,2 & 3.
  
 22B) DETAIL# 09 IS A BOXED IN RAIN
 LETTER, PLEASE PROVIDE LOCATON ON FLOOR
 PLAN, MORE COMMENTS MAY APPEAR.
  
 22C) DETAIL# 14 RAILING TO MECHANICAL
 PENTHOUSE PROVIDE THE HEIGHT OF
 GUARDRAIL?1015.2 HEIGHT. GUARDRAILS
 SHALL FORM A VERTICAL PROTECTIVE BARRIER
 NOT LESS THAN 42 INCHES (1067 MM) HIGH.
  
 22D) DETAIL# 22 REMOVE THE WORD
 TOWNHOUSE,
  
 23) A.701 ELEVATOR MACHINE ROOMS;
  
 23A) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 23B)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 23C)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 24)SHEET A.704:
  
 24A) TRASH CHUTE PLANS DO NOT INDICATE A
 TWO HR WALL FOR SHAFT.705.2.4.2 REFUSE
 AND LAUNDRY CHUTE ENCLOSURES. A SHAFT
 CONTAINING AREFUSE OR LAUNDRY CHUTE
 SHALL BE USED FOR NO OTHER PURPOSE AND
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH ?705.2.3.
  
 24B)705.2.4.6 AUTOMATIC SPRINKLERS. AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP AND AT
 ALTERNATE FLOOR LEVELS IN REFUSE AND
 LAUNDRY CHUTES AND IN THE TERMINATION
 AND INCINERATOR ROOMS.
  
  
 24E) 705.2.4.2 REFUSE AND LAUNDRY CHUTE ENCLOSURES.ALL
 OPENINGS INTO THE SHAFT
 ENCLOSURE, INCLUDING THOSE FROM ACCESS
 ROOMS AND TERMINATION ROOMS, SHALL BE
 PROTECTED IN ACCORDANCE WITH TABLE
 705.1.2.SUCH OPENING PROTECTIVES SHALL
 BE SELF-CLOSING OR AUTOMATIC-CLOSING
 UPON DETECTION OF SMOKE, EXCEPT THAT
 THE OPENING PROTECTIVE BETWEEN THE SHAFT
 AND THE TERMINATION ROOM MAY BE CLOSED
 BY A HEAT-ACTIVATED DEVICE.
  
 25) SHEET A.801-A807A/ A.903
  
 25A) SEE FAIR HOUSING PRIMARY ENTRY
 DOORS AS WELL AS USABLE DOORS .SEE PAGES
 3.1-3.5
 ACCESSIBLE DOORS- DWELLING UNIT ENTRY
 DOORS ARE TO MEET ANSI 4.13 WITH A 32"
 CLEAR MEAASUREMENT, A 2'-10" DOOR
 REQUIRED.
 USABLE DOORS- 32" NOMINAL CLEAR WIDTH
 IS REQUIRED FOR USABLE DOORS.
  
 25B) A901-A902 DOOR SCHEDULE FOR ALL
 FIRE RATED DOORS THE HARDWARE SCHEDULE
 IS MISSING REQUIRED SILLS. 705.1.3.1
 SILLS, IN ACCORDANCE WITH THE
 REQUIREMENTS OF NFPA 80.
  
 26) A903 :
  
 26A)DOOR NOTES,HURRICANE MISSLE IMPACT
 NOTES , FRENCH DOORS TO COMPLY WITH
 STATEMENT 20G.
  
 26B) BURGLAR INTRUSION NOTES
 3) INDICATE USE OF BOLTS OR PINS FOR
 EXTRA SECURITY DEVICES, SEE FAIR HOUSING
 SECONARY EXTERIOR DOORS, SLIDING GLASS
 DOORS PAGE 3.10-3.12 FOR CLEAR WIDTH AND HARDWARE.
  
 (7) INACTIVE LEAF OF A PAIR OF DOORS
 SHALL BE PROVIDED WITH MULTIPLE POINT
 LOCKS AS REQUIRED BY PRODUCT APPROVALS.
 AGAIN THESE LOCKS HAVE TO BE ABLE FOR
 THE HANDICAPPED TO BE ABLE TO OPERATE
 FROM A WHEELCHAIR!!!!!
  
 27) A9.05
  
 27A) DETAILS FOR RATED WALL U-419/ U-423
 WITH A RATED CEILING RAE NOT SHOWN IN
 THE UL DIRECTORY, IN BOTH CASES UL
 STATES THE DRYWALL IS TO GO TO THE FLOOR
 OR ROOF DECK ABOVE.
 704.2.1.3 ALL OTHER PARTITIONS REQUIRED
 TO HAVE A FIRE RESISTANCE RATING SHALL
 EXTEND FROM THE TOP OF THE FLOOR BELOW
 TO THE CEILING ABOVE AND SHALL BE
 SECURELY ATTACHED THERETO.WHERE SAID
 CEILING IS NOT A PART OF AN ASSEMBLY
 HAVING A FIRE RESISTANCE RATING AT LEAST
 EQUAL TO THAT REQUIRED FOR THE
 PARTITION, THE PARTITION SHALL BE
 CONSTRUCTED TIGHT AGAINST THE FLOOR OR
 ROOF DECK ABOVE.
  
 27B) MASONARY WALLS DO NOT GIVE THERE
 MINIMUM EQUAVALENT THICKNESS FOR HOUR
 RATING.
  
 27C) WALL TYPE NOTES:
 ALL PLYWOOD SHEATHING TO BE FIRE
 RETARDANT TREATED PLYWOOD. SEE SECTION
 604 ALL STRUCTURAL MEMBERS ARE TO BE NONCOMBUSTIBLE
 WITH VARYING HR RATINGS
 TABLE 600 PROVIDES THE HR RATINGS
 REQUIRED FOR EACH TYPE OF STRUCTURAL
 COMPONENT. FIRE RETARDANT TREATED
 PLYWOOD WHEN EXPOSED TO FLAME WILL BURN
 AS LONG AS FIRE IS AVAILABLE.
  
 28) S-0.00
  
 28A) CODES INDICATE FBC 2001 BUT ALL
 REFRENCES 02 ACI 318-02 CORRECT
  
 28B)
 WIND LOADS ARE FIGURED 130MPH SHOULD
 READ 140 MPH 3 SECOND GUST,
 AND ASCE 7-98
  
 28C) IMPORTANCE FACTOR 1 IS BUILDINGS
 SUCH AS FARM BUILDINGS RECLASSIFY
  
 28D) EXPOSURE CATEGORY "C" THE CITY IS
 LOCATED IN A "B" ZONE, IF DESIGNING TO
 THE MORE RIGID "C" ZONE THE PRESSURES
 REQUESTED ITEM (20A) WILL HAVE TO
 REFLECT THE HIGHER VALUES FOR WALLS
 OPENINGS AND ROOF PRESSURES.
  
 28E) THRESHOLD BUILDING INSPECTION PLAN:
 WRONG ADDITION TO ASCE7-98 CORRECT
 EDITION FOR FBC 2001.
 28F) BALCONY MOISTURE PROTECTION THIS
 SECTION OF THE CODE IS FOR THE HIGH WIND
 VELOCITY ZONES DADE & BROWARD ONLY!
  
 29) S3.2 FOTTER, COLUMN & BEAM SCHEDULES
 NOT FILED IN MUST COMPLETE FOR REVIEW.
  
 30) M0.2
  
 30A) ROOF TOP CONDENSING UNITS TO MEET
 THE CLEARENCE REQUIREMENTS:
 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
  
 30B) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 PLANS ARE NOT COMPLETE ENOUGH TO DO A
 THOROUGH PLAN REVIEW, ADDITIONAL
 COMMENTS MAY OCCUR ON THE NEXT REVIEW
 WITH THE NEW INFORMATION BEING
 SUBMITTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-11 Cont ID  
Sent By dpalmer Date 2006-06-11 Time 14:07 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 20:38 Sent To  
Notes
2006-06-11 00:00:00REVIEW CONTINUED
 ******** UNSAT 2ND REVIEW ***********
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH ARE NEEDED TO BE
 ADDRESSED. PLEASE ALSO SEE SOME NEW
 COMMENTS.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT DESIGN/LAYOUT WHICH
 WILL HAVE A DIRECT AFFECT ON ELECTRICAL PLANS.(BUILDING
 NOTES).
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW ANS NEW
 NOTES ARE ADDED TO THE BOTTOM.
  
 *********IMPORTANT***********
  
 PLEASE BE SURE THREE COMPLETE SETS ARE
 SUBMITTEDAS THIS IS A THRESHOLD JOB
 AND PLEASE BE SURE ALL SHEETS ARE BOUND
 TOGETHER IN A MEANS THAT SETS AND SHEETS
 DO NOT READILY FALL APART.
 THE SETS SUBMITTED DO NOT CONTAIN
 STAPLES THAT ADEQUATELY HOLD SETS/SHEETS
 IN PLACE. THANK YOU FOR ANTICIPATED
 ATTENTION TO THIS.
 **************************************
  
  
 MIZNER LAKES BLDG #5.
  
 1)NOTE: NO, PLEASE SEE APPLICATION STILL
 INDICATES 117 UNITS.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE BLDG PLANS AND
 PERMIT APPLICATION WITH ELECTRICAL
 PLANS. PLEASE SEE BLDG SHEETS INDICATE
 114 UNITS, ALTHOUGH PERMIT APPLICATION
 INDICATE 117.
 PLEASE ALSO CORRELATE SQ FT FROM BLDG
 SHEET (A) WITH ELECTRICAL PLANS AS THE
 A/C SQ FT FOR SOME DO NOT SEEM TO MATCH
 UP.
  
 2)NOTE: OK.
  
 3)NOTE: NOTE #3 OK FOR MOST, HOWEVER
 PLEASE SEE FIRE PROTECTION SHEETS STILL
 REFERENCE THE 1999 NFPA-20. PLEASE SEE
 FIRE REVIEW COMMENTS.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE ALL ARCHITECTUAL
 AND ELECTRICAL SHEETS CONTAIN REFERENCE
 TO THE 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72, NFPA-20 2002 WITH ANY
 OTHER CODES CURRENTLY IN EFFECT NEEDED.
  
 4)NOTE:NOTE #4, NO, PLEASE STILL SEE
 THERE IS SOME DIFFERENCES IN PLANS.
 PLEASE SEE FP SHEETS IDENIFY THE FIRE
 PUMP CONTROLLER AND ATS. IF THIS PUMP IS
 DIESEL AS INDICATED IN RESPONSE, THNE
 THE ATS MUST BE A MISPRINT. PLEASE SEE
 FIRE SHEET FS0.2
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE FIRE PUMP CONTROLLER
 (DIESEL) AND PUMP. THESE MUST BE IN SETS
 EVEN IF THE FIRE PUMP IS GOING TO BE
 SUBMITTED SEPARATELY.
  
 ** PREVIOUS NOTE **PLEASE SEE FP
 SHEETS AND A SHEETS INDICATE A FIRE PUMP
 AND FIRE HOUSE, HOWEVER THERE IS NOT
 INDICATION OF THIS ON ELECTRICAL RISER
 ETC.
 PLEASE KNOW, AS PER DISCUSSION WITH
 CHIEF ELECTRICAL INSPECTOR AND FIRE
 MARSHAL'S OFFICE, GENERATOR BACK UP MAY
 BE REQUIRED IF ELECTRIC FIRE PUMP AND
 NOT DIESEL.
 IT WAS ALSO MENTIONED THERE MAY BE ONE
 FOR EACH BLDGOR ONE FOR BOTH?
 PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS
 AND 695 OF NEC.(2002).
 695.3, 9.2, 9.6.2.2
 PLEASE SEE THIS BLDG SET OF PLANS
 CONTAINS MORE INFORMATION THAT THERE
 WILL BE AN ELECTRICAL FIRE PUMP. PLEASE
 SEE ALL OTHER COMMENTS FROM ELECTRIC AND
 FIRE REVIEWER(S).
 PLEASE KNOW THERE IS NOT ENOUGH
 INFORMATION FOR THE REVIEW.
 PLEASE ALSO KNOW, SINCE THE REVIEW OF
 BLDG #4, IT IS BEING DISCUSSED WITHIN
 THE AHJ IF A GENERATOR SIZED FOR THE MIN
 BACK UP OF FIRE PUMP WILL BE REQUIRED.
 IF INDEED THIS IS THE CASE IT WILL ALSO
 REQUIRE A MIN OF ON SITE FUEL FOR A MIN
 OF 8HRS RUNNING TIME.
  
  
 5)NOTE: NOTE #5 NO, PLEASE SEE IT IS NOW
 INDICATED THAT THE FIRE PUMP IS OF FUEL
 TYPE HOWEVER NO SPECS FOR TANK/FUEL
 STORAGE AND MIN FUEL FOR STORAGE ON
 SITE. PLEASE SEE A MIN OF 8HRS RUNNING
 IS REQUIRED.
 1999 NFPA-20 8-4.3, 2003 NFPA-20 11-4.3
 PLEASE SEE MORE INFORMAION IS STILL
 NEEDED FOR REVIEW OF FIRE PUMP/FP HOUSE/
 ETC THIS WILL ALSO BE IN FIRE MARSHAL'S
 REVIEW.
  
 **PREVIOUS REVIEW **
 IF AN ELECTRICAL FIRE PUMP IS
 INSTALLED, PLEASE SUBMIT ALL
 SPECS/MANUFACTURES CUT SHEETS FOR PUMP,
 FIRE PUMP CONTROLLER, GENERATOR AND ANY
 SUB-BASE FUEL TANKS.
 PLEASE BE SURE ALL SPECS/CUT SHEETS
 CONTAIN A LISTING FROM A NRTL.
  
 6)NOTE: OK.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE NEW NOTES
 AND FLOORS WHICH EM FIXTURES ARE NOT
 SHOWN.2.41-2.72
 THIS IS MORE DETAILED IN NEW NOTES.
 PLEASE SEE MOST WERE DONE.
  
 ** PREVIOUS NOTE ** PLEASE KNOW, A MIN
 BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN MAIN ELECTRICAL RM,
 ELECTRICAL RMS, FIRE PUMP RM/HOUSE,
 ELEVATOR EQUIPMENT RMS.
 700.16,7.8,7.9 ETC.
  
 8)NOTE: OK.
  
 9)NOTE: NOTE #9, NO, PLEASE SEE NEW
 NOTES WITH RESPECT TO FIXTURES ON UPER
 FLRS. 2.41-2.72
  
 ** PREVIOUS NOTE**
 PLEASEIDENTIFY THE FIXTURE
 TYPES IN STAIR TOWERS. PLEASE LABEL.
  
 10)NOTE:NOTE #10 NO, THIS COULD NOT BE
 LCOATED. PLEASE SEE REPSONSE MENTIONS
 THIS DETAIL IS ON E0.9, HOWEVER THIS
 SHEET E0.9 IS NOT IN ANY OF THE TWO SETS SUBMITTED?
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE DETAIL FOR
 DISCONNECT(S) FOR ROOF TOP UNITS.
 440.11, MAY BE A "TYPICAL" DETAIL FOR
 CU'S.
  
 11)NOTE: NOTE #11 NO, ALTHOUGH MOST ALL
 WAS DONE PLEASE SEE SHEET 2.32 WHICH IS
 MISSING CIRCUITING FOR CORRIDIOR.
 PLEASE SEE NEW NOTES FOR THIS SAME
 SHEET.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL CIRCUITING
 ON PLANS, INCLUDING ALL COMMON AREAS ,
 PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING.
 MOST ARE ON PLANS SOME ARE
 MISSING. SEE SOME REDLINED.
  
 12)NOTE: OK THIS WAS DONE, HOWEVER
 PLEASE SEE NEW NOTES.
  
 13)NOTE:NOTE #13 NO, PLEASE SEE THE
 CIRCUIUTS HAVE NOW BEEN DIVIDED, HOWEVER
 LOADS FOR THESE STILL ARE NOT REFLECTED
 ON PANEL SCHEDULES. PLEASE SEE
 210.52B1,210.11C1 AND 220.16A WHICH
 REQUIRES 1.5VA FOR EACH OF THE TWO OR
 MORE CIRCUITS. PLEASE SEE DINING, AND
 NOOK AREAS ARE CONSIDERED AS AREAS OF
 THE LIKE AS STATED IN 210.52B
 PLEASE SEE THESE ONES HAVE BEEN REDLINED
 ON ONE SET OF PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.52B1 WHICH
 REQUIRES RECEPTS IN DINING AREAS/ROOMS T
 BE ON THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE LIGHTING ETC MAY
 NOT BE ON THESE CIRCUITS. THIS WOULD
 ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS.
  
 14)NOTE: OK.
  
 15)NOTE:OK, HOWEVER PLEASE SEE NEW
 NOTES FOR MORE DETAIL OF MANY FIXTURES.
 PLEASE ALSO SEE THE RESPONSE LETTER
 MENTIONS TO SEE SHEET E0.9, HOWEVER NO
 SHEET E0.9 WAS SUBMITTED.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE FIXTURE SCHEDULE
 CORRELATE WITH PLANS AND "LABELING" OF
 SOME SORT ALSO CORRELATES.
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
 18)NOTE: OK.
  
 19)NOTE: NOTE#15 NO, PLEASE SEE LAUNDRY
 CIRCUIT STILL SHOWN AS 1.2.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.11C, 220.16B
 WHICH REQUIRES A MIN OF 1.5KW FOR
 LAUNDRY/WASHER CIRCUITS.
 PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME
 SHOWN WITHOUT LOADS.
  
 20)NOTE: N/A
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: NOTE#24 NO, PLEASE SEE SOME
 LOCATIONS WHICH RECEPTS ARE MISSING.
 PLEASE SEE ONE SET OF ELECTRICLA PLANS
 HAVE BEEN REDLINED. C-4, TH2
 PLEASE NOTE: AREAS CONTAINING RAILS ARE
 CONSIDERED WALL SPACE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE LOCATIONS ON PLANS
 FOR MISSING RECEPTS PER 210.52, DINING
 RM WALL C-2, BEDRM IN C-5, C-4 VERIFY
 ANY OTHER POSSIBLE LOCATIONS.
  
 25)NOTE: OK.
  
 26)NOTE: OK.
  
 27)NOTE: OK, HOWEVER SEE NEW NOTES NOW
 THAT CIRCUITS WERE ADDED.
  
 ** PREVIOUS NNOTE **
 PLEASE SEE SOME CIRCUITING
 MISSING ON PLANS FOR BATH ETC C-5
  
 28)NOTE: NOTE #28 NO, IT WAS NOTED THAT
 SOME OF THE CLOSETS MAY NOT BE LARGE
 ENOUGH, HOWEVER SEE UNIT TH2 WHICH
 APPEARS THIS WOULD NOT BE THE CASE. THIS
 WAS CONFIRMED WITH THE MECH REVIEWER AND
 A LT WOULD BE REQUIRED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 210.70 FOR MIN LT
 REQUIRED FOR A/C CLOSETS.
  
 29)NOTE: OK, MOST APPEAR TO BE OK.
  
 30)NOTE: NOTE #30 NO, PLEASE SEE THE
 SAME COUNTER SPACE IS REDLINED.
  
 ** PREVIOUS NOTE **
 PLEASE SEE POSSIBLE MISSING
 RECEPT FOR KITCHEN COUNTERSPACE PER
 210.52C1, C-4
  
 31)NOTE: OK.
  
 32)NOTE: OK, HOWEVER SEE NEW NOTES FOR CIRCUITING.
  
 33)NOTE: OK.
  
 34)NOTE: NOTE #34 NO, PLEASE SEE
 RESPONSE MENTIONS TO SEE 7.1.1 FOR
 DETAIL, HOWEVER NO DETAIL WAS SHOWN FOR
 "BUS-DUCT" PENETRATIONS.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE MIN CURB DETAIL
 FOR THROUGH FLOOR PENETRATIONS.368.6
 FOR BUS-DUCT RISER.
  
 35)NOTE: NOTE # 35 NO, PLEASE SEE KW
 RATINGS WERE REVISED, HOWEVER PLEASE SEE
 LOADS AND OCP DO NOT CORRELATE WITH THE
 MECHANICAL PLANS.
 PLEASE SEE MAX OCP ETC.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MANY A/C HEAT LOADS
 ARE SHOWN AS "0"??
 PLEASE ALSO SEE OTHERS WHICH INDICATE
 65% OF 4KW AS 20KW? PLEASE RE-FIGURE
 LOADS FOR A/C'S AND PLEASE ADJUST PANELS
 AND LOAD CALCULATIONS.
  
 36)NOTE: NOTE #36 NO, PLEASE SEE A NOTE
 WAS ADDED, HOWEVER THIS NOTE NOW
 MENTIONS TO "PROVIDE A BUILDING
 LIGHTNING PROTECTION SYSTEM".
 PLEASE SEE PREVIOUS NOTE WAS NOT TO
 REQUIRE A LIGHTNING PROTECTION AS THE
 STRUCTURE DOES NOT FALL UNDER CODES
 WHICH DO REQUIRE LIGHTNIGN PROTECTION.
 THE NOTE WHICH WAS REQUESTED WAS FOR ANY
 SYSTEM WHICH MAY BE INSTALLED UNDER A
 SEPARATE PERMIT SHALL MEET NFPA-780, UL
 96.
 PLEASE KNOW MANY SYSTEMS ARE ON THE
 MARKET WHICH DO NOT MEET CODE.
  
 ** PREVIOUS NOTE **
 PLEASE PLACE NOTE ON "ROOF TOP"
 PLANS WHICH WILL BE WORDED TO MENTION:
 ANY PROPOSED LIGHTNING PROTECTION
 SYSTEM, SHALL BE INSTALLEDPER
 NFPA-780" OR WORDS TO THAT AFFECT.
  
 37)NOTE: OK.
  
 38)NOTE: OK, HOWEVER SEE NEW NOTES.
  
 39)NOTE: OK.
  
 40)NOTE: OK.
  
 41)NOTE:NOTE #41 NO, PLEASE SEE IT IS
 NOTED THAT THE "STREET" LIGHTING IS DONE
 BY THE CITY OF WEST PALM BEACH AS THE
 PLANS MENITONS PALM BEACH COUNTY. PLEASE
 KNOW, THIS COMMENT WAS FOR ANY POLE
 LIGHTING ON POOL DECK AREA.
  
 ** PREVIOUS NOTE **
 PLEASE SEE SITE PLANS INCLUDE
 SITE LIGHTING.
 PLEASE SUBMIT ALL WIND LOAD CALCULATIONS
 AT THIS TIME FOR REVIEW IF ALL SITE
 LIGHTING POLES AND FIXTURES ARE GOING TO
 BE INCLUDED UNDER BLDG #5 SCOPE OF WORK
 AND PERMIT.
 IF DESIRED, THIS MAY BE PULLED FROM SETS
 AND SUBMITTED FOR SEPARATE PERMIT, PLANS
 AND FEES AT A LATER DATE.
 PLEASE BE SURE CALCULATIONS INLCUDE LT
 FIXTURES ON POLES.
 PLEASE ALSO COMPLETE DETAIL FOR POLE
 BASE WITH ALL DIMENSIONS, ONCE
 CALCULATIONS ARE DONE.
  
 42)NOTE: OK.
  
 *********** NEW NOTES ****************
  
 43) NOTE: PLEASE SEE SEC'S TO "L1FP" ARE
 SHOWN AS 1/0'S WHERE THE MCB OCP IS
 400A'S?? PLEASE ADJUST 240.4,310.16
  
 44) NOTE: PLEASE SEE THE ADDRESS OF
 PROJECT IS NOW ASSESSED, PLEASE REVISE
 TITLE BLOCKS ACCORDINGLY.
  
 ** PLEASE SEE ALL SHEETS SHALL
 CONTAIN THE PRINTED LICENSE NUMBER FOR
 THE ARCHITECTUARAL FIRM AS REQUIRED
 UNDER FAC 61G1-16.004.
 PLEASE ALSO SEE ALL SHEETS SIGNED AND
 SEALED BY THE ARCHITECT SHALL ALSO
 CONTAIN THE PRINTED ANME AND THE PRINTED
 LICENSE NUMBER OF SAID ARCHITECT.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER ORNOT COMMENT IS
 MADE BY OTHER TRADES. THIS COMMENT IS
 NOT FOR KAMM CONSULTING , HOWEVER ALL
 MEP,FS, FA SHEETS CONTAINING THE
 ARCHITECTURAL FIRM SHALL CONTAIN THE
 FIRM LICENSE NUMBER.
 ** PLEASE KNOW, FOR SHEET WHICH DO NOT
 NEED TO BE REVSIED MAY HAVE THIS NUMBER
 STAMPED/PRINTED/ ON SHEETS.
 PLEASE SEE ALL SHEETS MAY END UP BEING
 CHANGED.
 THIS WAS MISSED ON PREVIOUS REVIEW.
  
 45) NOTE: PLEASE SEE UNLESS THE RETAIL
 SERVICE SHALL CONTAIN A MAIN IN THE MAIN ELECTRICAL RM
 WHICH THEN WOULD FEED THE
 GUTTER IN THE RETAIL ELECTRICAL RM. ONLY
 IF THERE IS A "FIRE WALL" SEPARATION.
 230.2E
  
 46) NOTE: PLEASE SEE AREA OF POOL DECK
 SHALL CONTAIN EM BATTERY BACK UP
 FIXTURES OF SOME SORT TO PROVIDE THE MIN
 LIGHTING LEVELS UNDER EMERGENCY
 CONDITIONS (1FT CANDLE) TO THE PUBLIC
 RIGHT OF WAY.
 NFPA-101 7.8.1.3, 7.8.1.1
  
 47) NOTE: PLEASE SEE MININUM SIZES FOR
 SEC'S SHALL BE SIZED PER 310.16, 240.4C
 PLEASE SEE ALL SEC'S SHALL BE EQUAL OR
 ABOVE THE OCP FOR DEVICES OVER 800A'S.
 PLEASE SEE SEC'S FOR SBA AND MSB.
  
 48) NOTE: PLEASE SEE SHEET 5.14 WHICH
 MENTIONS MSB SECTION 1 WITH A "MAIN 1 OF
 2", WHICH DOES NOT CORRELATE WITH THE
 OTHER SECTION OF MSB , AS THIS IS SHOWN
 AS "MAIN 1 OF 3".
 PLEASE SEE REDLINED PLANS.
  
 49) NOTE: PLEASE SEE ROOF TOP PLANS
 WHICH MENTIONS AND NOTES STAIR LTS
 FEEDING FLOOR ABOVE.??
  
 50) NOTE: PLEASE SEE SHEETS 2.41-2.72 AS PERVIOUSLY
 MENITONED IN ABOVE NOTES,
 THESE SHEETS SEEM TO BE MISSING THE
 EMERGENCY LIGHTING FIXTURE
 DESIGNATION(S) FOR STAIRS AND ROOMS.
 PLEASE SEE REDLINED PLANS.
 LS 101 7.8,7.9
  
 51) NOTE: PLEASE SEE FPL VAULT IS
 SHOWING LT FIXTURES "G". PLEASE CONFIRM
 WITH FPL AS THESE SHOUDL NOT BE IN THE
 FPL VAULT.
  
 52) NOTE: PLEASE SEE SHEET 2.32 WHICH
 SEEMS TO CONTAIN A MISPRINT AS IT IS
 LABLED FOR 2ND FLR AND 3RD FLR.
 REDLINED.
 215.5
  
 53) NOTE: PLEASE SEE PANEL IN UNIT C-3
 WILL NOT BE PERMITTED IN CLOSET.
 408.7,240.24 ETC
  
 54) NOTE: PLEASE SEE BATH RMS WHEN
 CIRCUITED AS REQUIRED FOR LIGHTING AND
 GFI RECEPT ON ONE CIRCUIT, THIS CIRCUIT
 MAY FEED ANY OTHER RMS, LTS, DEVICES
 ETC. PER 210.11C3
 PLEASE SEE UNITS C-4 AND C-1 AS THESE
 WERE REDLINED AS THE DEDIACTED BATH
 CIRCUITS AS SHOWN FEED OTHER
 LIGHTING.:CLOSET AND HALL.
  
 55) NOTE: PLEASE SEE SBA AND MSB CONTAIN
 NUMERICAL NOTES NEXT TO SOME BRANCH
 DEVICES "NOTE #1" YET, NOTE #1 ON PANEL
 SCHEDULE FOR EACH OF THESE ARE BLANK??
 PLEASE CLARIFY.215.5
  
 56) NOTE: PLEASE PLACE NOTE ON PLANS FOR
 ALL REQUIREMENTS OF THE FHAR 24CFR
 100.205 SHALL BE MET.
  
 57) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED AT LOCATIONS OF
 COMMENTS ON ONE SET OF THE PLANS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTSFROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
 PLEASE BE SURE TO SEE FIRE REVIEW
 COMMENTS AS THERE ARE MANY THAT WILL
 AHVE A DIRECT EFFECT ON ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS COMPLETELY AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 ** PLEASE SEE ONE COPY OF THE OLD SETS
 COULD NOT BE LOCATED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-06-09 00:00:00REVIEW STARTED.
2006-05-17 00:00:00ONE ROLL IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 17:33 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 15:58 Sent To  
Notes
2005-12-24 00:00:00REVIEW IN PROGRESS
 ********* UNSAT ************
  
  
 MIZNER LAKES BLDG #5.
 PLEASE KNOW, MANY ITEMS FROM THIS REVIEW
 CORRESPONSE TO REVIEW OF BLDG #4.
 PLEASE ALSO SEE ADDED NOTES FOR SITE,
 SITE LIGHTING ETC.
  
 1)NOTE: PLEASE CORRELATE BLDG PLANS AND
 PERMIT APPLICATION WITH ELECTRICAL
 PLANS. PLEASE SEE BLDG SHEETS INDICATE
 114 UNITS, ALTHOUGH PERMIT APPLICATION
 INDICATE 117.
 PLEASE ALSO CORRELATE SQ FT FROM BLDG
 SHEET (A) WITH ELECTRICAL PLANS AS THE
 A/C SQ FT FOR SOME DO NOT SEEM TO MATCH
 UP.
  
 2)NOTE: PLEASE SEE ALL ARCHITECTUAL
 SHEETS CONTAIN A "RUBBER STAMP" IN LEIU
 OF THE REQUIRED ORIGINAL SIGNATURE FROM
 THE ARCHITECT OF RECORD. FS 481.221
 PLEASE ALSO SEE BLDG REVIEW COMMENTS.
 THIS IS REQUIRED FOR A-SHEETS WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEWER(S)
 THIS IS NOT A KAMM CONSULTING COMMENT.
  
 3)NOTE: PLEASE BE SURE ALL ARCHITECTUAL
 AND ELECTRICAL SHEETS CONTAIN REFERENCE
 TO THE 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72, NFPA-20 2002 WITH ANY
 OTHER CODES CURRENTLY IN EFFECT NEEDED.
  
 4)NOTE: PLEASE SEE FP SHEETS AND A
 SHEETS INDICATE A FIRE PUMP AND FIRE
 HOUSE, HOWEVER THERE IS NOT INDICATION
 OF THIS ON ELECTRICAL RISER ETC.
 PLEASE KNOW, AS PER DISCUSSION WITH
 CHIEF ELECTRICAL INSPECTOR AND FIRE
 MARSHAL'S OFFICE, GENERATOR BACK UP MAY
 BE REQUIRED IF ELECTRIC FIRE PUMP AND
 NOT DIESEL.
 IT WAS ALSO MENTIONED THERE MAY BE ONE
 FOR EACH BLDGOR ONE FOR BOTH?
 PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS
 AND 695 OF NEC.(2002).
 695.3, 9.2, 9.6.2.2
 PLEASE SEE THIS BLDG SET OF PLANS
 CONTAINS MORE INFORMATION THAT THERE
 WILL BE AN ELECTRICAL FIRE PUMP. PLEASE
 SEE ALL OTHER COMMENTS FROM ELECTRIC AND
 FIRE REVIEWER(S).
 PLEASE KNOW THERE IS NOT ENOUGH
 INFORMATION FOR THE REVIEW.
 PLEASE ALSO KNOW, SINCE THE REVIEW OF
 BLDG #4, IT IS BEING DISCUSSED WITHIN
 THE AHJ IF A GENERATOR SIZED FOR THE MIN
 BACK UP OF FIRE PUMP WILL BE REQUIRED.
 IF INDEED THIS IS THE CASE IT WILL ALSO
 REQUIRE A MIN OF ON SITE FUEL FOR A MIN
 OF 8HRS RUNNING TIME.
  
  
 5)NOTE: IF AN ELECTRICAL FIRE PUMP IS
 INSTALLED, PLEASE SUBMIT ALL
 SPECS/MANUFACTURES CUT SHEETS FOR PUMP,
 FIRE PUMP CONTROLLER, GENERATOR AND ANY
 SUB-BASE FUEL TANKS.
 PLEASE BE SURE ALL SPECS/CUT SHEETS
 CONTAIN A LISTING FROM A NRTL.
  
 6)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL EGRESS PATHS,
 CORRIDORS, GARAGES, STAIRS TOWERS.
 PLEASE SEE 101, 7.8 WHICH REQUIRES A MIN
 OF 10 FT CANDLES UNDER NORMAL POWER AND
 1 FT CANDLE MIN UNDER EMERGENCY POWER OR
 BATTERY BACK UP.
  
 7)NOTE: PLEASE KNOW, A MIN BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN MAIN ELECTRICAL RM,
 ELECTRICAL RMS, FIRE PUMP RM/HOUSE,
 ELEVATOR EQUIPMENT RMS.
 700.16,7.8,7.9 ETC.
  
 8)NOTE:PLEASE SEE 620.23 WHICH ALSO
 REQUIRESDEDICATED BRANCH CIRCUIT(S)
 FOR RECEPT IN ELEVATOR MACHINE ROOM.
  
 9)NOTE: PLEASEIDENTIFY THE FIXTURE
 TYPES IN STAIR TOWERS. PLEASE LABEL.
  
 10)NOTE: PLEASE PROVIDE DETAIL FOR
 DISCONNECT(S) FOR ROOF TOP UNITS.
 440.11, MAY BE A "TYPICAL" DETAIL FOR
 CU'S.
  
 11)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS, INCLUDING ALL COMMON AREAS ,
 PLEASE ALSO SEE UNITS WHICH ARE MISSING
 CIRCUITING. MOST ARE ON PLANS SOME ARE
 MISSING. SEE SOME REDLINED.
  
 12)NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS. NEED TO
 VERIFY FOR CIRCUITING OF DINING AREAS
 ETC.
  
 13)NOTE: PLEASE SEE 210.52B1 WHICH
 REQUIRES RECEPTS IN DINING AREAS/ROOMS T
 BE ON THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE LIGHTING ETC MAY
 NOT BE ON THESE CIRCUITS. THIS WOULD
 ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS.
  
 14)NOTE: PLEASE SEE SOME UNITS WHICH
 INDICATE "J-BOX" FOR HABITABLE
 RMS/EGRESS PATHS WILL BE REQUIRED TO
 CONTAIN SOME SORT OF LIGHT FIXTURE TO
 MEET 210.70, LS101 7.8
 PLEASE SEE REDLINED PLANS.
  
 15)NOTE: PLEASE BE SURE FIXTURE SCHEDULE
 CORRELATE WITH PLANS AND "LABELING" OF
 SOME SORT ALSO CORRELATES.
  
 16)NOTE: PLEASE SEE NFPA-72 11.5.1.1
 WHICH REQUIRES ALL SMOKE DETECTORS TO BE
 WIRED "INLINE", HOWVER PLEASE SEE
 REDLINED PLANS WHERE SD'S IN THE SAME
 UNITS ARE ON MORE THAN ONE CIRCUIT.
  
 17)NOTE: PLEASE CORRELATE ALL CIRCUITING
 OF SD'S ON PLANS WITH PANEL SCHEDULES.
 PLEASE SEE THERE ARE MANY SD'S SHOWN ON
 DIFFERENT CIRCUITS OTHE THAN WHAT IS
 LISTED ON PANEL SCHEDULE.
  
 18)NOTE: PLEASE SEE MANY SD'S WHICH DO
 NOT INDICATE THE REQUIRED ARC FAULT
 PROTECTION AS MANY OTHERS ARE SHOWN.
 MAY ALSO INDICATE LISTING OF REQUIRED
 ARC FAULT CIRCUITS IN PANEL SCHEDULES.
 210.12, 2002 NEC.
  
 19)NOTE: PLEASE SEE 210.11C, 220.16B
 WHICH REQUIRES A MIN OF 1.5KW FOR
 LAUNDRY/WASHER CIRCUITS.
 PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME
 SHOWN WITHOUT LOADS.
  
 20)NOTE:
  
 21)NOTE: PLEASE CORRELATE ALL SQ FT
 CALCULATIONS ON ELECTRICAL PLANS WITH
 "A" SHEETS WHICHSOME DO NOT SEEM
 CORRELATE WITH ELECTRICAL SQ FT.
  
 22)NOTE: PLEASE MOVE MANY SD'S INTO
 BEDRM AREAS. PLEASE SEE MANY UNITS SEEM
 TO INDICATE SOME SORT OF CEILING HEIGHT
 CHANGE LINE.
 PLEASE SEE NFPA-72 11.8.3.5 WHICH
 REQUIRES ALL SD;S TO BE LOCATED WITHIN
 12" OF A FLAT CEILING, AND WITHIN 3' OF
 THE PEAK OF A SLOPED CEILING.
 PLEASE ADJUST LOCATIONS.
 PLEASE SEE REDLINED PLANS. C3,C4 ETC
  
 23)NOTE: PLEASE SEE PANEL SCHEDULES NOTE
 SD'S AND KITCHEN LTS, HOWEVER MANY UNITS
 SHOWS SD'S TO OTHER BEDRM CIRCUITS.
 PLEASE ALSO SEE PREVIOUS NOTE LISTED
 ABOVE WITH RESPECT TOARC FAULT AND
 CIRCUIITNG.
  
 24)NOTE: PLEASE SEE LOCATIONS ON PLANS
 FOR MISSING RECEPTS PER 210.52, DINING
 RM WALL C-2, BEDRM IN C-5, C-4 VERIFY
 ANY OTHER POSSIBLE LOCATIONS.
  
 25)NOTE: PLEASE INDICATE THE REQUIRED
 GFI PROTECTION FOR JACUZZI TUB,
 RECEPT/BRKR.680.71
  
 26)NOTE: PLEASE IDENTIFY THE PANELS IF
 THEY ARE "TYPICAL" FOR MULTIPLE UNIT
 TYPES, (A,B, C ETC).
  
 27)NOTE: PLEASE SEE SOME CIRCUITING
 MISSING ON PLANS FOR BATH ETC C-5
  
 28)NOTE: PLEASE SEE 210.70 FOR MIN LT
 REQUIRED FOR A/C CLOSETS.
  
 29)NOTE: PLEASE SEE CLOTHES CLOSET FOR
 MIN CLEARENCE REQUIRED FOR LT
 FIXTURE(S).
 410.8, SEE REDLINED.
  
 30)NOTE: PLEASE SEE POSSIBLE MISSING
 RECEPT FOR KITCHEN COUNTERSPACE PER
 210.52C1, C-4
  
 31)NOTE: PLEASE VERIFY TYOE OF CONTROLS
 LABLED AS FUTURE FOR J-BOX RIGHT ON THE
 EDGE OF THE JACUZZI???
 PLEASE SEE 680 FOR MIN CLEARENCES FOR
 ANY PROPOSED DEVICES.
  
 32)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH GFI RECEPT(S) REQUIRED. TH3 ETC
  
 33)NOTE:PLEASE VERIFY THE LAUNDRY
 CIRCUIT ON KITCHEN WALL? TH1
 SHOWN IN WHAT APPEARS TO BE LIVING RM IN
 TH2? PLEASE SEE OTHER LOCATIONS AND
 CORRELATE WITH ACTUAL LOCATIONS OF ANY
 SUCH WASHER/LAUNDRY UNITS.
  
 34)NOTE: PLEASE PROVIDE MIN CURB DETAIL
 FOR THROUGH FLOOR PENETRATIONS.368.6
 FOR BUS-DUCT RISER.
  
 35)NOTE: PLEASE SEE MANY A/C HEAT LOADS
 ARE SHOWN AS "0"??
 PLEASE ALSO SEE OTHERS WHICH INDICATE
 65% OF 4KW AS 20KW? PLEASE RE-FIGURE
 LOADS FOR A/C'S AND PLEASE ADJUST PANELS
 AND LOAD CALCULATIONS.
  
 36)NOTE: PLEASE PLACE NOTE ON "ROOF TOP"
 PLANS WHICH WILL BE WORDED TO MENTION:
 ANY PROPOSED LIGHTNING PROTECTION
 SYSTEM, SHALL BE INSTALLEDPER
 NFPA-780" OR WORDS TO THAT AFFECT.
  
 37)NOTE: PLEASE VERIFY FEEDER CONDUCTOR
 TYPES FOR UNITS. COPPER, ALUMINUM.
  
 38)NOTE: PLEASE VERIFY WHY MSB AND SBA
 BOTH INDICATE GFP PROTECTION, WHEN
 240.13, 230.95 ETC DOES NOT SEEM TO
 TRIGGER THE REQUIREMENT. THIS IS NOT A
 CODE COMPLIANCE VIOLATION AND MAY BE
 DONE, IT IS ONLY NOTED, AS IF THIS IS
 SHOWN ON PLANS, THEN THIS WILL BE
 REQUIRED.
  
 39)NOTE: PLEASE SEE 200A OPC FROM MSB TO
 PANEL L1HB WHICH IS SHOWN AS A 125A
 PANEL.
  
 40)NOTE: PLEASE VERIFY MSB SCHEDULE
 INDICATES A "HOUSE PUMP" ON MSB-11,
 HOWEVER RISER DIAGRAM DOES NOT CORRELATE
 WITH THIS?
  
 41)NOTE: PLEASE SEE SITE PLANS INCLUDE
 SITE LIGHTING.
 PLEASE SUBMIT ALL WIND LOAD CALCULATIONS
 AT THIS TIME FOR REVIEW IF ALL SITE
 LIGHTING POLES AND FIXTURES ARE GOING TO
 BE INCLUDED UNDER BLDG #5 SCOPE OF WORK
 AND PERMIT.
 IF DESIRED, THIS MAY BE PULLED FROM SETS
 AND SUBMITTED FOR SEPARATE PERMIT, PLANS
 AND FEES AT A LATER DATE.
 PLEASE BE SURE CALCULATIONS INLCUDE LT
 FIXTURES ON POLES.
 PLEASE ALSO COMPLETE DETAIL FOR POLE
 BASE WITH ALL DIMENSIONS, ONCE
 CALCULATIONS ARE DONE.
  
 42)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 @125%.
 215.3,230.42
  
  
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED AT LOCATIONS OF
 COMMENTS ON ONE SET OF THE PLANS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTSFROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS/DESIGN.
 PLEASE BE SURE TO SEE FIRE REVIEW
 COMMENTS AS THERE ARE MANY THAT WILL
 AHVE A DIRECT EFFECT ON ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS COMPLETELY AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-15 00:00:00IN ELEC FOR REVIEW

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-07-31 Cont ID  
Sent By rchokshi Date 2006-07-31 Time 10:58 Rev Time 0.00
Received By rchokshi Date 2006-07-31 Time 10:55 Sent To R
Notes
2006-07-31 00:00:00ALL COMMENTS MADE BY M. AMINI ON
 2005-10-19 HAVE NOT BEEN TAKEN CARE OF
 YET.
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-19 Cont ID  
Sent By mamini Date 2005-10-19 Time 10:49 Rev Time 1.00
Received By mamini Date 2005-10-19 Time 10:49 Sent To  
Notes
2005-10-19 00:00:00FAILED:
  
 1. PLEASE SUBMIT CALCULATION FOR THE
 PROPOSED STORM WATER SYS.
 2.PLEASE SUBMIT A COPY OF THE SFWMD
 PERMIT FOR OUR RECORD.
 3. PLEASE NOTE THAT A POLLUTION
 PREVENTION PLAN MUST BE INCLUDED IN
 CIVIL, SILT FENCE, TURBIDITY BARRIER,
 ETC. IT MUST BE IN PLACED PRIOR TO ANY
 CONSTRUCTION ACTIVITIES.
 4. A SEPARATE PERMIT AT NO COST FOR ALL
 THE WORK WITHIN PUBLIC R.O.W FROM PUBLIC
 UTILITIES AND ENG. IS REQUIRED, CONTACT
 WINDEL PALMER AT 494-1086, MOT MUST BE
 PROVIDED AT THE TIME OF APPLICATION.
 5. SHEET C-8 SHOWSADDITIONAL WATER
 CONNECTION FROM EXISTING 10" WM IN HANK
 ARRON TO THE BUILDING 5, PLEASE VRIFY.
 6. SHEET C-8, COULD NOT FIND ANY WATER
 SUPPLY CONNECTION FOR BUILDING 4, PLEASE
 VERIFY.
 7. A CLEAN OUT FOR EACH SEWER LATERAL
 MUST BE PROVIDED.
 8. PLEASE NOT THAT CIVIL PLAN MUST BE
 APPROVED FOR ALL THE CONNECTIONS TO THE
 CITY SERVICES BY THE PUBLIC UTILITIES &
 ENG.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 14:46 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 14:46 Sent To  
Notes
2006-07-03 00:00:00***DENIED***
  
 1) OK
  
 2) NO RESPONSE FOUND.
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) OK
  
 8) OK
  
 9) OK
  
 10) OK
  
 11) NO RESPONSE FOUND ON SHT A-206
  
 12) OK
  
 13) NO RESPONSE FOUND BY MEP ENGINEER
  
 14) PLEASE NOTE THAT 2A-10B,C RATED FIRE
 EXTINGUISHERS ARE REQUIRED.
  
 15) NO SUBMITTAL FOUND
  
 16) PLEASE REFERENCE NFPA 101, 2003
 EDITION SEC. 30.3.3.2.
  
 17) PLEASE ILLUSTRATE ON ELEVATIONS.
  
 18) OK, HOWEVER WHAT ABOUT LOSS OF
 POWER?
  
 19) OK
  
 20) OK
  
 21) NO RESPONSE BY MEP ENGINEER
  
 22) NO RESPONSE BY MEP ENGINEER
  
 23) NO RESPONSE FOUND
  
 24) NO RESPONSE FOUND
  
 25) NO RESPONSE FOUND
  
 26) RESPONSE DOESN'T ADDRESS COMMENT
 REGARDING UL.
  
 27) OK
  
 28) PLEASE SEE NFPA 101, 2003 EDITION
 SEC. 9.6.2.8.
  
 29) OK
  
 30) NO RESPONSE FOUND
  
 31) PLEASE SEE SHT FS0.1 REDLINED REF:
 EDITION.
  
 32) PLANS SHALL BE SUBMITTED SEPARATELY
 UNDER SEPARATE PERMIT.
  
 33) PLEASE NOTE THAT THE ATTACHED LETTER
 DOES NOT INDICATE APPROVAL FROM THIS
 OFFICE.
  
 34) OK
  
 35) NO NOTE FOUND
  
 36) OK
  
 37) NO RESPONSE FOUND
  
 38) NO RESPONSE FOUND
  
 39) NO RESPONSE FOUND
  
 40) OK
  
 PLEASE NOTE THAT PROVIDING RESPONSES
 INDICATING SHT FOR REVIEW WILL HELP
 EXPEDITE THIS PROCESS.
  
 PLEASE NOTE THAT CORRECT EDITIONS SHALL
 BE ILLUSTRATED ON PLANS IE. NFPA 20,
 2003 EDITION.
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By mwennerg Date 2005-12-21 Time 15:15 Rev Time 0.00
Received By mwennerg Date 2005-12-21 Time 15:15 Sent To  
Notes
2005-12-21 00:00:00******DENIED******
  
 BUILDING #5
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED AFTER JAN. 1, 2005.
  
 2) PERMIT APPLICATION INDICATES 117
 UNITS AND SHT A-002 SHOWS 114. PLEASE
 CORRULATE.
  
 3) DO TURN AROUNDS MEET THE THE 50'
 RADIUS REQUIREMENTS OF NFPA 1 ?
  
 4) PARKING GARAGE TO MEET SEPARATION AND
 ALL OTHER REQUIREMENTS IN ACCORDANCE
 WITH FBC AND NFPA 88A.
  
 5) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 6) PLEASE ILLUSTRATE THE HEIGHT OF THE
 BUILDING. HIGHRISE?
  
 7) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 8) PLEASE REVIEW ALL DOOR SWINGS THAT
 SERVE AREA WITH OCCUPANT LOADS > 50.
  
 9) THE DOORS LEADING FROM THE POOL AREA
 TO THE CORRIDORS SWING AGAINST THE
 DIRECTION OF TRAVEL BASED ON OCCUPANT
 LOADS GREATER THAN 50.
  
 10) THE LOBBY ENTRANCE DOORS SWING
 AGAINST THE DIRECTION OF TRAVEL.
  
 11) PLEASE INDICATE THE TYPE AND
 QUANTITY OF STORAGE PLANNED FOR POOL
 EQUIPMENT AREA.
  
 12) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 13) PLEASE PROVIDE ADDITIONAL
 INFORMATION ON TYPE OF BOILERS PLANNED.
  
 14) 2A-10B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED.
  
 15) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FABRIC AWNINGS.
  
 16) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILINGS IN
 TERMS OF CLASS A,B, OR C.
  
 17) AN ADDRESS IS REQUIRED FOR BUILDING,
 AND SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 18) WILL CARD READING DEVICES IMPACT
 REQUIRED EXITING?
  
 19) ELEVATORS TO COMPLY WITH ASME A
 17.1.
  
 20) WARNING SIGNS REQUIRED IN ELEVATOR
 LOBBIES.
  
 21) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 CAUSE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 22) EXITS SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'.
  
 23) HOW WILL OCCUPANT NOTIFICATION OCCUR
 IN REGARDS TO CO SENSORS?
  
 24) PLEASE REVIEW ALL ELECTRICAL SHTS
 AND ARRANGE EXIT LIGHT LOCATIONS TO MEET
 THE MINIMUM 100' DISTANCE REQUIREMENT.
  
 25) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 26) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
 DOCUMENTATION SHALL BE AVAILABLE AT THE
 TIME OF FIRE ALARM FINAL.
  
 27) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 28) PLANS DON'T SHOW SMOKE DETECTORS IN
 COMMON AREA CORRIDORS. PLEASE MAKE
 CORRECTION.
  
 29) ARE AUDIBLE DEVICES PLANNED FOR
 LIVING UNITS?
  
 30) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 31) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION.
  
 32) SEPARATE SHOP DRAWING, PERMIT AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP.
  
 33) A 1000 GPM FIRE PUMP IS PROPOSED.
 PLEASE PROVIDE DETAILS FROM MEETING HELD
 WITH CITY FIRE MARSHAL AND WHAT
 ARRANGEMENT HAS BEEN ACCEPTED BY THIS
 OFFICE. PLEASE INDICATE WHAT BUILDINGS
 WILL BE SUPPLIED BY FIRE PUMP.
  
 34) FIRE DEPARTMENT VALVES ON STANDPIPES
 ARE REQUIRED TO BE 2 1/2" TO 1 1/2"
 REDUCER WITH CHAIN.
  
 35) IN ADDITION TO ELECTRONIC
 SUPERVISION, DOUBLE CHECK DETECTOR
 ASSEMBLY SHALL BE SECURED WITH LOCKAND
 CHAIN.
  
 36) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA 51B.
  
 37) LOCKING KNOX BOX CAP REQUIRED ON
 FIRE DEPARTMENT CONNECTION.
  
 38) FA SHEETS ILLUSTRATE FIRE PUMP ROOM
 AND A SHEETS SHOW ANOTHER LOCATION.
 PLEASE EXPLAIN.
  
 39) FIRE ALARM SHAEETS DON'T SHOW SMOKE
 DETECTORS IN ELECTRICAL ROOMS, FIRE PUMP
 ROOM, CATV ROOM, MAIL ROOM ETC.
  
 40) FS SHT 0.1 REFERENCES NFPA 13R. NFPA
 13 SHALL BE USED FOR BUILDINGS GREATER
 THAN 4 STORIES IN HEIGHT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-10 Cont ID  
Sent By adarroug Date 2006-04-06 Time 10:34 Rev Time 0.00
Received By adarroug Date 2006-04-06 Time 10:34 Sent To  
Notes
2006-05-10 00:00:00TO "COMM" BD#46/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-03 Time   Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 13:39 Sent To  
Notes
2005-10-04 00:00:00TO "COMM" BD#48/PLANS ON RACK/4 ROLLS
2005-09-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-06-27 Cont ID  
Sent By pkrauss Date 2006-06-27 Time 07:20 Rev Time 0.00
Received By pkrauss Date 2006-06-26 Time 14:05 Sent To  
Notes
2006-06-27 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 COMMENTS BY HAROLD MOSER ON 1/10/2006
  
 COMMENT 1.RESPONSE REFERS TO FBC(M)
 404.1 & 404.2.SECTION 404 IN THE 2001
 CODE IS VENTILATION OF UNINHABITED
 SPACES WHEREAS THE 2004 FMC 404 IS
 ENCLOSED PARKING GARAGES.THIS BUILDING
 WAS SUBMITTED UNDER THE 2001 FLORIDA
 BUILDING CODE.PLEASE SHOW COMPLIANCE
 WITH 2001 FMC 502.10, 403.4 AND FBC
 411.4.
  
 COMMENT 2.OK
 COMMENT 3.OK
 COMMENT 4.RESPONSE INDICATES
 MECHANICAL CLOSETS WILL COMPLY WITH
 CHAPTER 4 OF THE ENERGY CODE.PLEASE
 NOTE THE SPECIFIC CODE SECTION IS
 410.1.ABCD.3.7 OF THE 2001 FBC.PER THE
 2001 FBC CO SENSORS MAY BE UTILIZED IN
 "PUBLIC" GARAGE.PLEASE CLARIFY IF THE
 PUBLIC NOT JUST THE RESIDENCE WILL HAVE
 ACCESS TO THE GARAGE.
  
 COMMENT 5. RESPONSE INDICATES THE
 ENGINEER OF RECORD IS TO SUBMIT THE
 MANUFACTURE SUBMITTAL DATA.THIS IS
 ACKNOWLEDGED BUT PERMIT CAN NOT BE
 ISSUED WITHOUT REVIEW OF THE EQUIPMENT.
  
 COMMENT 6.OK
 COMMENT 7.OK
 COMMENT 8.OK
 COMMENT 9.OK - RTU-2 IS SHOWN ON PLAN
 SHEET M2.7.2 NOT M2.7.1.
  
 COMMENT 10. OK
 **************NEW COMMENTS*************
  
 1.PLAN SHEET M2.1.1, SHOW THE GARAGE
 FANS DICHARGING ON TO A HANDICAP RAMP
 THAT IS LOCATED WITH IN 10 FT OF THE
 DISCHARGE ACCORDING TO PLAN SHEET A-201
 WHICH DOES NOT COMPLY WITH 2001 FMC
 401.5.2 & 401.5.PLEASE NOTE, IT IS
 RECOMMENDED THE GARAGE EXHAUST SYSTEMS
 ARE DESIGNED TO MINIMIZE NOISE LEVELS
 USING LINE FAN SILENCERS OR OTHER
 APPROVED METHODS.
  
 2.PLAN SHEET M2.3.2, 2.4.2, 2.5.2,
 2.6.2, INDICATES A 6" X 6" FLEX DUCT
 PENETRATING A RATED WALL AT THE
 FOLLOWING ROOM NUMBERS; 339, 434, 534,
 633 & 733.THE EXCEPTION FOR NOT
 INSTALLING A FIRE DAMPER ARE SPECIFIED
 IN 2001 FMC 607.1.3. #3.
  
 3.PLEASE CLARIFY DUCT FROM CORRIDOR
 INTO FOR THE RESIDENCE IS FOR OUTSIDE
 AIR.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 4.PLAN SHEET A-801 TH-1 1ST FLOOR
 DETAIL DESIGNATES THE DOOR TO THE AHU
 CLOSET AS D2.THIS IS ALSO WHAT IS
 DESIGNATED FOR THE CLOSET AREA THAT
 ENCLOSES THE DRYER AND THE AHU.THE
 DOOR SCHEDULE ON PLAN SHEET A-903 FOR
 THE 2 STORY CONDO UNITS (TH) SHOWS THESE
 DOORS AS BI-FOLD WOOD DOORS.RETURN AIR
 CAN NOT BE TRANSFERED THROUGH THE
 LAUNDRY CLOSET AREA TO THE AHU CLOSET.
 2001 FBC 610.1.ABC.3.7 & FMC 603.9.
  
 5.PLEASE NOTE, WOOD DOORS TO SHALL
 HAVE A FLAME SPREAD INDEX LESS THAN 25
 AND A SMOKE INDEX LESS THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84 PER
 2001 FMC 602.2.1.
  
 6.PLAN SHEETS M4.1, M4.2, & 4.3, SHOW
 ONLY CERTAIN UNITS THE ARCHITECTURAL
 PLANS INDICATE 25 UNITS WITH DIFFERENT
 SQUARE FOOTAGE.ARE THE MECHANICAL
 PLANS TO BE TYPICAL? EXAMPLE ARE ALL THE
 C2 UNIT GOING TO HAVE THE SAME AIR
 DISTRIBUTION AS A C2A, B, C, D, E, F, G,
 & H?
  
 7.PLAN SHEET M4.1 UNIT C2 DOES NOT
 INDICATE SUPPLY AIR INTO THE BATHROOM
 AREA, ONLY EXHAUST.PLEASE CLARIFY.
  
 8.PLAN SHEET M4.4 IN BOTH THE LOWER
 LOBBY AND THE UPPER LOBBY PLEASE CLARIFY
 THE MAKE-UP AIR THROUGH THE TRASH ROOM
 IN A TWO HOUR ENCLOSURE BUT THEN
 TERMINATES IN THE RATED WALLS. IF FIRE
 DAMPER'S ARE INSTALLED THIS WOULD
 NULLIFY THE MAKE-UP AIR REQUIREMENT FOR
 THE GARAGE SHOULD DAMPERS CLOSE.
  
 9.PLAN SHEET M5.1 THE DRYER EXHAUST
 SHAFT SHALL COMPLY WITH 2001 FBC
 705.2.3.3, ENCLOSURE AT BOTTOM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-10 Cont ID  
Sent By hmoser Date 2006-01-10 Time 07:24 Rev Time 0.00
Received By hmoser Date 2006-01-10 Time 07:24 Sent To  
Notes
2006-01-10 00:00:00PLAN DENIED
 1) PLEASE REFER TO TABLE 403.3 2001
 FBC(M).PRIVIT GARAGE.
 2) PLEASE PROVIDE TYPE OF METRIALS USED
 FOR CONDENSER WATER PIPING ON PLANS.
 3) PLEASE REFER TO SECTION 610.1.ABC.3.7
 FLORIDA ENERGY CODE 2001 MECHANICAL
 CLOSET.
 4) ALL DOORS FOR MECHANICAL CLOSETS
 SHALL BE NOMCOMBUSTIBLE SECTION
 602.2.1 METERIALS EXPOSED WITHIN
 PLENUMS.
 5) PLEASE SUBMIT A COPEY OF
 MANUFACTURERS INSTRUCTIONS FOR AHU,
 RTU,CCC TOWERS,AND CW.PUMPS.
 6) PLEASE REFER TO SECTION 306.1 FBC(M)
 CLEARANCES FOR MAINTENANCE AND
 REPLACEMENT. ON AHU.
 7) PLEASE REFER TO SECTION 307.2.3
 FBC(M) 2001 AUXILIARY DRAIN PANS.
 8) PLEASE PROVIDE FIRE STOP DETAILS
 FOR CONDENSER WATER PIPING ON
 MECHANICAL PLANS.
 9) PLEASE INDECATE ON PLANS WITCH RTU.
 IS NUMBER TWO.
 10) PLEASE SUBMIT DETAIL ON AHU ON PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-15 Cont ID  
Sent By kstevens Date 2006-06-15 Time 17:46 Rev Time 0.00
Received By kstevens Date 2006-06-12 Time 18:39 Sent To  
Notes
2006-06-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 1. ALL ARCHITECTURAL SHEETS: THE
 PERSONAL SEAL, SIGNATURE, AND THE DATE
 THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 THE SIGNATURE IS A "STAMP OF THE
 SIGNATURE" AND AS SUCH IS NOT APPROVED.
 THERE IS NOT DATE ON THE SEAL WHEN IT
 WAS AFFIXED TO THE PLANS. FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055
 ***RESPONSE NOTED, BUT THE DATE THE SEAL
 AND SIGNATURE ARE AFFIXED TO THE PLANS
 SHALL BE ON THE SEAL.
  
 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS
 PER REQUIREMENTS #6 & 7B FHA DESIGN
 MANUAL. THE CLEAR FLOOR SPACE FOR THE
 SHOWERS SHALL BE PARALLEL WITH THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 SEE PAGE 7.56 FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT NO OTHER FIXTURE
 MAY OVERLAP THE CLEAR FLOOR SPACE AT THE
 SHOWERS. THIS INCLUDES THE W/C'S, LAV
 VANITIES, OR SHOWER DOORS.
  
 9. SHTS A-801 THRU A-802C & A-808 ALL
 "TH" UNITS: PRIMARY LEVEL TO BE COVERED
 PER FHA DESIGN MANUAL. SHOW THE FLOOR
 PLAN FOR EACH TYPE OF "TH" UNIT WITH
 CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43
 & 7.47. ALSO SHOW MAX HEIGHT FOR LAV AT
 34" REQUIRED ON PAGE 7.52 FHA DESIGN
 MANUAL.
 ***RESPONSE NOTED, BUT THE W/C CAN NOT
 BE IN THE CLEAR FLOOR SPACE FOR THE
 SHOWER. PAGE 7.57
  
 10. SHTS A-803 THRU A-807A INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT -
 BATHROOM AS REQUIRED ON PAGES 7.34 &
 7.44 OF THE FHA DESIGN MANUAL.
 ***RESPONSE NOTED, BUT THE SPECIFICATION
 FOR EACH UNIT HAS NOT BEEN FOUND.
  
 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS
 P1.1, P5.1.4, P5.1.5, & P6.1.4 ARE NOT
 SHOWN ON THE INDEX.- SHTS P2.5.1 &
 P2.5.2 DO NOT REFLECT THE SHEETS
 SUBMITTED. - SHTS P2.6.1, P2.6.2,
 P2.7.1, P2.7.2, P2.8.1, P2.8.2, P3.6.1
 WERE NOT SUBMITTED. - SHT P5.1.3 DOES
 NOT REFLECT THE INDEX, AND P5.1.5 &
 P5.1.6 SHOWN AS STORM, BUT SHEETS
 INDICATE SANT. SYSTEM. PLEASE CLARIFY.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT SHTS
 P2.5.1 & P2.5.2 DO NOT REFLECT THE
 PLUMBING SHEET INDEX FOR SHEET
 IDENTIFICATION, AND SHT P3.6.1 IS NOT
 NUMBERED CORRECTLY.
  
 15. P2.1.2 FLOOR DRAINS IN THE TRASH
 ROOM/AREA AND IN THE CORRIDOR SHALL BE
 VENTED. SECTION 901.2.1.
 ***NO COMMENT RESPONSE NOTED, FLOOR
 DRAINS ARE NOT VENTED.
  
 22. SHT FOR 7TH FLOOR WEST SECTION
 DRAINAGE PLAN (P2.6.2). CONDENSATE FOR
 RESIDENT STORAGE & CONDO UNIT C-1(730)
 SHOWS PLAN NOTE #2. PLEASE CLARIFY.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, CONDENSATE
 NOTE FOR RESIDENT STORAGE UNCHANGED.
  
 23. SHT P2.7.1 SHOW THE LOCATION FOR ALL
 VENTS THRU ROOF AND INDICATE RISER
 NUMBER FOR EACH.
 ***NO COMMENT RESPONSE NOTED. NO VENTS
 THRU ROOF LOCATED.
  
  
 29. SHT INDICATING WATER SUPPLY PLAN 5TH
 FLOOR "NORTH" SECTION, PREVIOUS SHEETS
 WERE DESIGNATED AS "EAST" OR "WEST".
 THIS IS ALSO THE SECOND SHEET NUMBERED
 P3.5.1. - INDICATE WHAT DESIGNATION WSC2
 IS FOR. - NOTE STATES "SEE UNIT LAYOUTS
 ON SHEET P4.1". SHT P4.1 NOT SUBMITTED.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT NOW
 THERE ARE TWO SHEETS WITH THE NUMBER
 P3.5.2. THE FIRST SHOULD BE P3.5.1.
 PLEASE CLARIFY.
  
 30. FIRST SHT P3.6.2 INDICATES WATER
 SUPPLY PLAN 6TH FLOOR "SOUTH" SECTION.
 EAST AND WEST WERE INDICATED PRIOR TO
 THIS. 2ND SHT WITH THE SAME NUMBER
 INDICATES "WEST" SECTION. PLEASE
 CLARIFY.SECTION 104.2.1.
 ***NO COMMENT RESPONSE, PLANS STILL HAVE
 TWO SHEETS NUMBERED P3.6.2.
  
 35. SHT P5.1.1 STATES "SANT DRAINAGE
 ISOMETRIC "WEST" SECTION". THIS DOES NOT
 REFLECT THE PLUMBING SHEET INDEX. -
 VENTS ARE REQUIRED ON THE FLOOR DRAINS
 IN THE TRASH ROOM/AREA & CORRIDOR.
 SECTION 901.2.1. - CLEANOUTS REQUIRED IN
 BUILDING MAX. 100'. SECTION 708.3.2. -
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN UPSTREAM OF SANT. RISER #22. -
 RISER DIAGRAMS AS INDICATED TO "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 104.2.1.
 ***NO COMMENT RESPONSE NOTED, BUT VENTS
 FOR THE FLOOR DRAINS ARE NOT SHOWN.
  
 37. SHTS P5.1.3 THRU P5.1.5, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. ALL RISERS WITH VENT
 STACKS SHALL COMPLY. SECTION 903.4.
 ***NO COMMENT RESPONSE NOTED, BUT RISERS
 1, 2, 14, 18, 21, 23, 25 & 26 VENTSS
 STILL DO NOT CONNECT TO THE STACK.
  
 38. SHT P5.1.3 SANT RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN. AN EXTRA LAV IS
 SHOWN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, NOT ADDRESSED.
  
 41. SHT P5.1.3 SANT. RISER #8 DOES NOT
 REFLECT THE FLOOR PLAN FOR 2 BATHROOM
 GROUPS ALL FLOORS, AND THE FIRST
 BATHROOM GROUP 3RD FLOOR. SECTION
 104.2.1.
 ***NO COMMENT RESPONSE, RISER STILL DOES
 NOT REFLECT THE FLOOR PLAN FOR THE
 BRANCH & STACK CONNECTIONS TO THE
 BUILDING DRAIN. - SHOW LAV ARM FOR THE
 THIRD FLOOR LAST BATHROOM ON RISER.
  
 42. SHT P5.1.4 SANT. RISER #9 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, RISER D0ES NOT
 REFLECT THE FLOOR PLAN AT THE POWDER
 ROOM. THE W/C IS NOT VENTED. W/M TO
 DISCHARGE DOWNSTREAM OF THE BATHROOM
 FIXTURES. SECTIONS 901.2.1, & 909.1.
  
 44. SHT P5.1.4 SANT. RISER #12 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2, NOR WHERE THE RISERS & BRANCH
 LINES CONNECT TTO THE BUILDING DRAIN.
 SECTION 104.2.1.
 ***NO COMMENT RESPONSE, BUT THE BRANCH
 LINES AND RISER CONNECTIONS TO THE
 BUILDING DRAIN DO NOT REFLECT THE FLOOR
 PLAN.
  
 50. SHT P5.1.5 SANT. RISER #21 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 ***NO COMMENT RESPONSE, BUT THE RISER
 FOR THE W/M STILL DOES NOT REFLECT THE
 FLOOR PLAN.
  
 61. SUBMIT WATER ISOMETRICS FOR THE
 FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B,
 C-2C, C-2D, C-2E, C-2F, C-2G, C-2H,
 C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2,
 TH-2A, TH-2B, TH-2C.
 ***NO COMMENT RESPONSE, ALSO SUBMIT
 WATER RISERS FOR UNITS C1, C2, C3, C3A,
 C4, C5, TH1, AND TH1E.
  
 62.SHT P6.1.4 GAS PIPING ISOMETRIC:
 SUBMIT APPROVED TABLES FOR SIZING PIPE
 PER FBC-2001 FUEL GAS CODE.
 ***GAS TABLE INDICATED, BUT NOT
 SUBMITTED.
  
 63. SHT P6.1.4 PROVIDE MANUF.
 SPECIFICATION SHEETS FOR ALL PRV'S. -
 SHOW ALL VENT PIPING FOR PRV'S AND
 INDICATE THE MATERIAL REQUIRED FOR
 VENTS. SECTIONS 410.2 & 410.3. - A
 LISTED SHUTOFF VALVE SHAL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 SECTION 410.2(5) - POOL HEATER LINE
 DOWNSTREAM OF SHUTOFF VALVE INDICATES
 "MAXIMUM LENTH = 20'". MAXIMUM DISTANCE
 FROM APPLIANCES TO SHUTOFF VALVE IT 6'.
 SECTION 409.7. - PIPE DOWNSTREAM OF
 METER TO 1ST BRANCH LINE STARTS OFF
 1-1/4", THEN REDUCES TO 1", THEN
 INCREASES TO 1-1/4". PLEASE CLARIFY.
 ***NO COMMENT RESPONSE, NOT ADDRESSED.
  
 PROVIDE THE FOLLOWING FOR APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS.
 ***NO COMMENT RESPONSE, NOT ADDRESSED
  
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 ***NO COMMENT RESPONSE.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
 ***NO COMMENT RESPONSE, MANUF. SHEETS
 NOT FOUND.
  
 64. INFORMATIONAL: PLANS DO NOT APPEAR
 TO BE COMPLETE AT THIS TIME. MORE
 COMMENTS MAY BE FORTHCOMING UPON NEXT
 SUBMITTAL OF PLAN AND DEPENDING UPON
 COMMENT RESPONSES.
 ***IT APPEARS THAT MAJOR PLAN
 DEVELOPMENT WAS DONE BETWEEN SUBMITTALS
 FOR REVIEW. THAT PLUS THE LACK OF
 COMMENT RESPONSES ATTRIBUTE TO THE
 ADDITIONAL TIME TO REVIEW PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO COMMENT RESPONSES FROM THE
 ENGINEER.
  
 **************NEW COMMENTS**************
  
 1B. SUBMIT A CONDENSATE ISOMETRIC FOR
 THE BUILDING DRAIN SHOWING ALL PIPE
 SIZES, RISERS, AND POINT OF TERMINATION.
 ALSO SUBMIT CONDENSATE RISER DIAGRAMS
 SHOWING ALL PIPE SIZES AND VENTS.
 SECTION 104.3.1.1.
  
 2B. SUBMIT WATER RISER DIAGRAM
 ISOMETRICS FOR EACH UNIT TYPE. SHOW ALL
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTVE RANGE"
 NOT IN THE CEILING. SECTION 104.3.1.1.
  
 3B. SHT P0.1 SHEET INDEX, SHEET NUMBERS
 ARE OUT OF SEQUENCE AND INDICATES "NORTH
 & SOUTH" WHERE AS "EAST" & "WEST" ARE
 USED ON MOST SHEETS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 4B. SHTS P2.1.1, P2.1.2, P5.1.1 & P5.1.2
 INDICATE DFU'S FOR RETAIL SPACES. TABLE
 709.1(2).
  
 5B. SHTS P2.1.2 & P5.1.1 FLOOR DRAINS
 NOT VENTED. RELEIF VENT REQUIRED FOR THE
 AAV FOR THE TOILET ROOM NEAR THE BASE OF
 STACK S/13. SECTION 917.3.2.
  
 6B. SHT P2.1.3 ORD SDR 1/2 INDICATES 4"
 PIPE. SDR # 1/2 RISER DIAGRAM AND TABLE
 1106.3 INDICATE 6" PIPE REQUIRED. PLEASE
 CORRELATE RISER AND FLOOR PLAN LAYOUT.
 SECTION 104.2.1.
  
 7B. SHT P2.2.1 ORD SDR # 1/2 INDICATES
 3600SF. SRD # 1/2 ARE 900SF EACH. PLEASE
 CORRELATE SDR & ORD. SECTION 104.2.1.
  
 8B. SHT P2.3.2 INDICATES 3RD FLOOR
 "SOUTH". PREVIOUS SHEETS INDICATE "EAST"
 OR "WEST". PLEASE CLARIFY. SECTION
 104.2.1.
  
 9B. SHT P2.4.2 INDICATES 4TH - 6TH
 FLOORS "SOUTH" PLEASE CLARIFY.
  
 10B. SHTS P2.7.1, P2.7.2 & PT.2.1 ODR'S
 SHALL DRAIN THE SAME AREA AS THE SDR
 DRAINS. PLEASE INDICATE THE AREA TO BE
 DRAINED, AND NOT THE MAXIMUM AREA
 ALLOWED. TABLE 1106.3.
  
 11B. TWO P3.4.2 SHEETS SUBMITTED.
 MISSING SHT P3.4.1. PLEASE CORRELATE
 SHEET NUMBERS WITH SHEET INDEX. SECTION
 104.2.1.
  
 12B. TWO P3.5.2 SHEETS SUBMITTED.
 MISSING SHT P3.5.1. PLEASE CORRELATE
 SHEET NUMBERS WITH SHEET INDEX. SECTION
 104.2.1.
  
 13B. SHTS P4.16 & P4.17 SHOWS 2 "TH2B"
 UNITS, AND NO "TH2A" UNITS. PLEASE
 CLARIFY.
  
 14B. SHT P5.1.4 RISER 27 A RELIEF VENT
 IS REQUIRED FOR THE AAV. SECTION
 917.3.2.
  
 15B. SHT P5.1.4 RISER #13 30DFU'S, RISER
 15 33DFU'S, RISER 16/20 110DFU'S.
 RECHECK ALL RISER DFU'S PER TABLES 709.1
 & 709.2.
  
 16B. SHT P5.2.1 SDR'S 2, 8, 10, & 15.
 THE FLOOR DRAINS AT THE 2ND FLOOR ARE
 MISSING FROM THE RISERS. SECTION
 104.2.1.
  
 17B. SHT P5.2.1 SHOWS 2 SDR & ODR #9'S
 AND TWO 3 10"S. PLEASE CLARIFY. SECTION
 104.2.1.
  
 18B. SHT P5.2.1 SDR #2 INDICATES 1800SF
 BUT ROOF PLAN SHOWS 900SF. PLEASE
 CORRELATE RISER & ROOF PLAN. SECTION
 104.2.1.
  
 19B. SHT P5.2.2 15" 56,755SF THRU 15"
 69,655SF TO BE RUN A MINIMUM 1/4"/FT
 SLOPE. PLEASE INDICATE ON PLANS AT THE
 FLOOR PLAN AND THE BLDG DRAIN ISOMETRIC.
 TABLE 1106.3.
  
 20B. SHT P5.2.2 ODR/DDR'S #1 & #18 10"
 PIPE REQUIRED. TABLE 1106.3
  
 21B. SHT P5.2.2 DDR'S #4 & #8 2ND FLOOR
 FLOOR DRAINS NOT SHOWN ON RISER DIAGRAM.
 SECTION 104.2.1.
  
 22B. SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 55.80(2)(B).
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 PLEASE SUBMIT ONE SET OF OLD PLANS FOR
 COMPAIRSON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-13 Cont ID  
Sent By kstevens Date 2006-01-13 Time 20:40 Rev Time 0.00
Received By kstevens Date 2006-01-11 Time 18:29 Sent To  
Notes
2006-01-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: THE
 PERSONAL SEAL, SIGNATURE, AND THE DATE
 THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 THE SIGNATURE IS A "STAMP OF THE
 SIGNATURE" AND AS SUCH IS NOT APPROVED.
 THERE IS NOT DATE ON THE SEAL WHEN IT
 WAS AFFIXED TO THE PLANS. FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055
 2. SHT A.003 DETAILS 1(A)(B)(C)(D),
 2(A)(B), & 4(A)(B(C)(D), WATER CLOSETS
 ADJACENT TO WALLS SHALL BE 1'6", NOT
 1'6" MINIMUM. THIS IS AN ABSOLUTE
 MEASUREMENT. SEE PAGES 6.3 & 6.5 FHA
 DESIGN MANUAL.
 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS
 PER REQUIREMENTS #6 & 7B FHA DESIGN
 MANUAL. THE CLEAR FLOOR SPACE FOR THE
 SHOWERS SHALL BE PARALLEL WITH THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 SEE PAGE 7.56 FHA DESIGN MANUAL.
 4. SHT A.003 UNIT DETAILS INDICATE
 "APPLICABLE TO UNITS A, B, C, D ETC. BUT
 FLOOR PLANS INDICATE UNITS C1, C2, C3,
 C4 ETC. PLEASE CORRELATE FLOOR PLANS
 WITH TYPICAL DETAILS. SECTION 104.2.1.
 5. SHT A.003 INDICATE WHICH POWDER ROOM
 DETAILS APPLY TO WHICH "TH" UNITS.
 SECTION 104.2.1.
 6. SHT A.003 DETAIL 1(C) PER HUD, THE
 BIDET HAS NO REQUIREMENTS, BUT THE BIDET
 SHALL NOT ENCROACH INTO THE CLEAR FLOOR
 SPACE OF THE WATER CLOSET.
 7. SHT A-106 BUSINESS OFFICE (553)
 ACCESS TO TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR
 BELOW THE EMPLOYEES REGULAR WORK AREA.
 SECTION 403.4.
 8. SHT A-108 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SF FOR EACH AREA DRAINED, ALONG WITH
 1/2 AREA OF ALL VERTICAL WALLS AND ANY
 AREA OF ROOF THAT DRAINS ONTO THE ROOF
 FROM ABOVE. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 9. SHTS A-801 THRU A-802C & A-808 ALL
 "TH" UNITS: PRIMARY LEVEL TO BE COVERED
 PER FHA DESIGN MANUAL. SHOW THE FLOOR
 PLAN FOR EACH TYPE OF "TH" UNIT WITH
 CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43
 & 7.47. ALSO SHOW MAX HIEGHT FOR LAV AT
 34" REQUIRED ON PAGE 7.52 FHA DESIGN
 MANUAL.
 10. SHTS A-803 THRU A-807A INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT -
 BATHROOM AS REQUIRED ON PAGES 7.34 &
 7.44 OF THE FHA DESIGN MANUAL.
 11. SUBMIT A FINISH SCHEDULE FOR PUBLIC
 - COMMON USE TOILET FACILITIES ON THE
 THIRD FLOOR. SECTIONS 1204.2 & 104.2.1.
 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS
 P1.1, P5.1.4, P5.1.5, & P6.1.4 ARE NOT
 SHOWN ON THE INDEX.- SHTS P2.5.1 &
 P2.5.2 DO NOT REFLECT THE SHEETS
 SUBMITTED. - SHTS P2.6.1, P2.6.2,
 P2.7.1, P2.7.2, P2.8.1, P2.8.2, P3.6.1
 WERE NOT SUBMITTED. - SHT P5.1.3 DOES
 NOT REFLECT THE INDEX, AND P5.1.5 &
 P5.1.6 SHOWN AS STORM, BUT SHEETS
 INDICATE SANT. SYSTEM. PLEASE CLARIFY.
 SECTION 104.2.1.
 13. ALL PLUMBING SHEETS: INDICATE RISER
 NUMBER FOR EACH SYSTEM THROUGH ALL
 FLOORS IN ORDER TO TRACE RISERS THROUGH
 BUILDING. - MATCH LINES ARE EITHER NOT
 SHOWN AT ALL OR THE INFORMATION OVERLAPS
 FROM ONE SHEET TO THE OTHER. PLEASE SHOW
 INFORMATION FOR THE EAST SECTION ON THE
 EAST SECTIONS AND THE INFORMATION FOR
 THE WEST SECTION ON THE WEST SECTIONS.
 SECTION 104.2.1.
 14. SHT P2.1.1 SD UP RISER NEXT TO 4"
 SAN DOWN (70DFU) SHOWS NO PIPING TO
 BUILDING DRAIN. SECTION 104.2.1.
 15. P2.1.2 FLOOR DRAINS IN THE TRASH
 ROOM/AREA AND IN THE CORRIDOR SHALL BE
 VENTED. SECTION 901.2.1. - CLEANOUTS IN
 THE BUILDING DRAIN ARE REQUIRED A
 MAXIMUM OF EVERY 100'. SECTION 708.3.2.
 - 3/4" CONDENSATE UP NOT SHOWN ON THE
 FLOOR ABOVE. - SANT. UP NOT SHOWN ON THE
 FLOOR ABOVE. (S.W. CORNER). SECTION
 104.2.1.
 16. SHT P2.2.2 INDICATES 2ND FLOOR -
 "SOUTH" SECTION. PLUMBING SHEET INDEX
 AND PREVIOUS FLOOR LEVELS INDICATE "WEST
 SECTION" PLEASE CORRELATE FLOOR PLANS
 AND INDEX. - TWO SETS OF STORM RISERS
 SHOWN ON THE FLOOR PLAN WERE NOT SHOWN
 ON PREVIOUS LEVEL FLOOR PLAN. - ONE SET
 OF STORM RISERS SHOWN ON THE FLOOR PLAN
 WERE NOT SHOWN ON THE FOLLOWING LEVEL
 FLOOR PLAN - ONE SANT. RISER SHOWN ON
 PREVIOUS & FOLLOWING FLOOR PLANS ARE NOT
 SHOWN ON FLOOR PLAN. - 1 FD4 SHOWN
 CONNECTING TO TWO SD RISERS. PLEASE
 CLARIFY. SECTION 104.2.1.
 17. SHT P2.3.1 SHOW THE LOCATION OF ALL
 SECONDARY DRAINS REQUIRED BY SECTION
 1107. SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY DRAINS PER 1106 & 1107. SEE
 COMMENT NUMBER 8.
 18. SHT P2.3.2 UNIT C-1B(313) PIPING
 DOES NOT REFLECT THE FLOOR PLAN
 FIXTURES. - UNIT C-2B(331) MASTER BATH
 WATER CLOSET, LAV, & SHOWER PIPING DOES
 NOT CONNECT TO A BRANCH LINE. - SANT.
 RISER #24 NOT SHOWN ON THE FLOOR BELOW.
 PLEASE CLARIFY. SECTION 104.2.1.
 19. SHT P2.4.1 INDICATES 4TH-6TH FLOORS
 EAST SECTION. PLUMBING SHEET INDEX AND
 SHEET I.D. BY TITLE BLOCK INDICATE 4TH
 FLOOR ONLY. PLEASE CORRELATE SHEETS AND
 INDEX. SECTION 104.2.1.
 20. SHT P2.5.1 INDICATE CONDENSATE PLAN
 NOTE NUMBER FOR AHU IN UNIT C-5A(520) -
 CONDO UNIT C-2(515) INDICATES PLAN NOTE
 #3. PLEASE CLARIFY. SECTION 104.2.1.
 21. SHT P2.5.2 CONDENSATE RISERS IN
 UNITS C-2G(529) & C-1A(523) INDICATES
 PLAN NOTE #5. PLEASE CLARIFY. SECTION
 104.2.1.
 22. SHT FOR 7TH FLOOR EAST SECTION
 DRAINAGE PLAN IS MIS-NUMBERED. - SHT FOR
 7TH FLOOR WEST SECTION DRAINAGE PLAN IS
 MIS-NUMBERED. ALSO CONDENSATE FOR
 RESIDENT STORAGE & CONDO UNIT C-1(730)
 SHOWS PLAN NOTE #2. PLEASE CLARIFY AND
 CORRELATE WITH SHT P0.1 PLUMBING SHEET
 INDEX. SECTION 104.2.1.
 23. SHT P2.7.1 SHOW THE LOCATION FOR ALL
 VENTS THRU ROOF AND INDICATE RISER
 NUMBER FOR EACH. -SUBMIT CALCULATION
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SEE COMMENT #8. SECTIONS 1106 & 1107 AND
 ALL SUBSECTONS.
 24. SHT P2.7.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SEE
 COMMENT #8. SECTIONS 1106 & 1107. -
 DRAINS FOR CCC UNITS SHALL BE LOCATED
 UNDER THE UNITS TO PREVENT TRIPPING
 HAZARDS AND TO KEEP STORM WATER FROM
 DRAINING INTO THE SANT. SYSTEM. ONE
 DRAIN FOR EACH UNIT REQUIRED. CITY CODE
 90-125(5).
 25. SHT P3.1.2 COLD WATER UP TO CHUTE
 WASHDOWN REQUIRES BACKFLOW PROTECTION.
 INDICATE METHOD OF PROTECTION. SECTION
 608.
 26. SHT P3.2.1 GAS LINE APPEARS TO EXIT
 & ENTER THE BLDG. PRIOR TO RISER UP TO
 POOL ROOM . PLEASE CLARIFY SEC 104.2.1.
 27. SHT P3.3.1 SEPARATE BACKFLOW
 PROTECTION REQUIRED FOR POOL FILL LINE.
 AN RPZV BACKFLOW IS REQUIRED. SECTION
 608.13.2.
 28. SHEET INDICATING WATER SUPPLY PLAN
 5TH FLOOR-WEST SECTION MIS-NUMBERED.
 PLEASE CLARIFY/CORRELATE WITH PLUMBING
 SHEET INDEX. SECTION 104.2.1.
 29. SHT INDICATING WATER SUPPLY PLAN 5TH
 FLOOR "NORTH" SECTION, PREVIOUS SHEETS
 WERE DESIGNATED AS "EAST" OR "WEST".
 THIS IS ALSO THE SECOND SHEET NUMBERED
 P3.5.1. - INDICATE WHAT DESIGNATION WSC2
 IS FOR. - NOTE STATES "SEE UNIT LAYOUTS
 ON SHEET P4.1". SHT P4.1 NOT SUBMITTED.
 SECTION 104.2.1.
 30. FIRST SHT P3.6.2 INDICATES WATER
 SUPPLY PLAN 6TH FLOOR "SOUTH" SECTION.
 EAST AND WEST WERE INDICATED PRIOR TO
 THIS. 2ND SHT WITH THE SAME NUMBER
 INDICATES "WEST" SECTION. PLEASE
 CLARIFY.SECTION 104.2.1.
 31. SHTS P3.6.1 & 2ND SHT P3.6.2
 INDICATE WHAT DESIGNATION WSC2 MEANS.
 SHT P4.1 REFERENCED HAS NOT BEEN
 SUBMITTED. PLEASE CLARIFY. SEC 104.2.1.
 32. SHTS P3.7.1 & P3.7.2 SHT P4.1
 REFERENCED HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY. SECTION 104.2.1.
 33. SHT P4.1.1INDICATES TWO "TYPICAL
 UNIT "C2" FOR THE WATER SUPPLY. ONLY ONE
 C2 FLOOR PLAN FOUND. PLEASE CLARIFY.
 SECTION 104.2.1.
 34. PLEASE SUBMIT WATER SUPPLY PLANS AND
 FLOOR PLANS FOR THE FOLLOWING UNITS:
 C-1A, C-2A, C-2B, C-2C, C-2D, C-2E,
 C-2F, C-2G, C-2H, C-5A, TH-1A, TH-1B,
 TH-1C, TH-1D, TH-2A, TH-2B, TH-2C.
 35. SHT P5.1.1 STATES "SANT DRAINAGE
 ISOMETRIC "WEST" SECTION". THIS DOES NOT
 REFLECT THE PLUMBING SHEET INDEX. -
 VENTS ARE REQUIRED ON THE FLOOR DRAINS
 IN THE TRASH ROOM/AREA & CORRIDOR.
 SECTION 901.2.1. - CLEANOUTS REQUIRED IN
 BUILDING MAX. 100'. SECTION 708.3.2. -
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN UPSTREAM OF SANT. RISER #22. -
 RISER DIAGRAMS AS INDICATED TO "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CLARIFY. SECTION 104.2.1.
 36. SHT P5.1.2 STATES "SANITARY DRAINAGE
 ISOMETRICS - "EAST" SECTION. THIS DOES
 NOT REFLECT THE PLUMBING SHEET INDEX. -
 RISER DIAGRAMS AS INDICATED TO THE "TH"
 UNITS DO NOT REFLECT THE FLOOR PLAN.
 CLEANOUTS FOR BUILDING DRAIN SHALL BE
 INSTALLED A MAXIMUM OF 100'. SECTION
 708.3.2. - CLEANOUT AT END OF RUN BY
 SANT. RISER #8 NOT SHOWN. - BLDG DRAIN
 DOES NOT REFLECT THE FLOOR PLAN WHERE
 THE DRAIN SPLITS TOWARD RISERS #1 &
 RISERS 4 THRU 8. SECTION 104.2.1.
 37. SHTS P5.1.3 THRU P5.1.5, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. ALL RISERS WITH VENT
 STACKS SHALL COMPLY. SECTION 903.4.
 38. SHT P5.1.3 SANT RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN. AN EXTRA LAV IS
 SHOWN. SECTION 104.2.1.
 39. SHT P5.1.3 SANT RISER #4 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWS A SHOWER,
 BUT A TUB IS ON FLOOR PLAN.- A VENT IS
 REQUIRED ON LAV IN THE MASTER BATH.
 SECTIONS 104.2.1 & 901.2.1.
 40. SHT P5.1.3 SANT RISER #6 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 & BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 41. SHT P5.1.3 SANT. RISER #8 DOES NOT
 REFLECT THE FLOOR PLAN FOR 2 BATHROOM
 GROUPS ALL FLOORS, AND THE FIRST
 BATHROOM GROUP 3RD FLOOR. SECTION
 104.2.1.
 42. SHT P5.1.4 SANT. RISER #9 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 43. SHT P5.1.4 SANT. RISER #10 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2. SECTION 104.2.1.
 44. SHT P5.1.4 SANT. RISER #12 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2, NOR WHERE THE RISERS & BRANCH
 LINES CONNECT TTO THE BUILDING DRAIN.
 SECTION 104.2.1.
 45. SHT P5.1.4 SANT. RISER #13 DOES NOT
 REFLECT THE FLOOR PLAN. 1ST & 2ND FLOORS
 ARE NOT SHOWN ON RISER. SECTION 104.2.1.
 46. SHT P5.1.4 SANT. RISER #14 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARM NEXT
 TO JAC2. SECTION 104.2.1.
 47. SHT P5.1.4 SANT. RISERS #'S 16 & 20
 DRAIN REQUIRED FOR EACH CCC UNIT ON THE
 ROOF LOCATED UNDERNEATH THE UNITS TO
 PREVENT A TRIPPING HAZARD AND TO PREVENT
 STORM WATER FROM ENTERING THE SANT.
 SYSTEM.
 48. SHT P5.1.4 SANT RISER #17 BATHROOM
 GROUPS DO NOT REFLECT THE FLOOR PLAN 3RD
 THRU 7TH FLOORS. SECTION 104.2.1.
 49. SHT P5.1.5 SANT. RISER #18 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 50. SHT P5.1.5 SANT. RISER #21 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 51. SHT P5.15 SANT. RISER #22 DOES NOT
 REFLECT THE FLOOR PLAN ON THE 1ST FLOOR
 AT TH W/C AND LAV. SECTION 104.2.1.
 52. SHT P5.1.5 SANT. RISER #23 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 53. SHTS P5.2.1, P5.2.2 & P5.2.3SHOWS
 CONDENSATE LINES CONNECTING TO NEAREST
 SANT. VENT. THIS IS NOT APPROVED.
 SECTION 901.2. - SECONDARY DRAINS ARE
 NOT SHOWN FOR THE POOL DECK LEVEL AS
 REQUIRED BY SECTION 1107. DISCHARGE
 SHALL BE ABOVE GRADE IN A LOCATION WHICH
 WOULD NORMALLY BE OBSERVED BY THE
 BUILDING OCCUPANTS OR MAINTENANCE
 PERSONAL, AND SEPARATE SYSTEMS ARE
 REQUIRED FOR PRIMARY AND SECONDARY
 DRAINS. SECTION 1107.2- SIZING OF
 STORM SYSTEM TO BE CHECKED AFTER
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS ARE SUBMITTED. SECTION 1106
 & 1107.
 54. SHT P6.1.1 SEPARATE RPZV BACKFLOW IS
 REQUIRED FOR THE IRRIGATION SYSTEM.
 SECTION 608.13.2.
 55. SHT P6.1.3 TYPICAL UNIT "C1" WATER
 HAMMER ARRESTOR REQUIRED ON ICE MAKER
 LINE, AND ON BOTH HOT & COLD LINES FOR
 THE W/M. SECTION 604.9
 56. SHT P6.1.3 TYPICAL UNIT "C2" WATER
 HAMMER ARRESTOR REQUIRED ON COLD WATER
 AT KITCHEN SINK FOR ICE MAKER. SECTION
 604.9.
 57. SHT P6.1.3 TYPICAL UNIT "C3" WATER
 HAMMER ARRESTOR REQUIRED ON COLD WATER
 AT KITCHEN SINK FOR ICE MAKER. - RISER
 DOES NOT REFLECT THE FLOOR PLAN.
 SECTIONS 104.2.1 & 604.9.
 58. SHT P6.1.3 TYPICAL UNIT "C5" DOES
 NOT REFLECT THE FLOOR PLAN. SECTION
 104.2.1.
 59. SHT P6.1.3 TYPICAL UNIT "TH-1" WATER
 HAMMER REQUIRED ON ICE MAKER LINE.
 SECTION 604.9.
 60. SHT P6.1.3 SHOWS 2 OTHER "TYPICAL
 UNITS C1". THESE DO NOT REFLECT ANY
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 61. SUBMIT WATER ISOMETRICS FOR THE
 FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B,
 C-2C, C-2D, C-2E, C-2F, C-2G, C-2H,
 C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2,
 TH-2A, TH-2B, TH-2C.
 62.SHT P6.1.4 GAS PIPING ISOMETRIC:
 SUBMIT APPROVED TABLES FOR SIZING PIPE
 PER FBC-2001 FUEL GAS CODE.
 63. SHT P6.1.4 PROVIDE MANUF.
 SPECIFICATION SHEETS FOR ALL PRV'S. -
 SHOW ALL VENT PIPING FOR PRV'S AND
 INDICATE THE MATERIAL REQUIRED FOR
 VENTS. SECTIONS 410.2 & 410.3. - A
 LISTED SHUTOFF VALVE SHAL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
 SECTION 410.2(5) - POOL HEATER LINE
 DOWNSTREAM OF SHUTOFF VALVE INDICATES
 "MAXIMUM LENTH = 20'". MAXIMUM DISTANCE
 FROM APPLIANCES TO SHUTOFF VALVE IT 6'.
 SECTION 409.7. - PIPE DOWNSTREAM OF
 METER TO 1ST BRANCH LINE STARTS OFF
 1-1/4", THEN REDUCES TO 1", THEN
 INCREASES TO 1-1/4". PLEASE CLARIFY.
 PROVIDE THE FOLLOWING FOR APPROVAL:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS.
 B. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 C. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 64. INFORMATIONAL: PLANS DO NOT APPEAR
 TO BE COMPLETE AT THIS TIME. MORE
 COMMENTS MAY BE FORTHCOMING UPON NEXT
 SUBMITTAL OF PLAN AND DEPENDING UPON
 COMMENT RESPONSES.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By eschneid Date 2006-05-23 Time 09:28 Rev Time 0.00
Received By eschneid Date 2006-05-22 Time 18:37 Sent To  
Notes
2006-05-22 00:00:001) PER ORDINANCE NO. 3914-05, PRIOR TO
 THE ISSUANCE OF THE FIRST BUILDING
 PERMIT, THE APPLICANT/OWNER SHALL:
  
 A) RECORD PUBLIC ACCESS EASEMENTS FOR
 ROADWAYS AND ADJACENT SIDEWALKS
 THROUGHOUT THE SITE.THIS MAY BE DONE
 ON A PLAT OR SEPARATE INSTRUMENT.
  
 B) RECORD A RESTRICTIVE DEED OR COVENANT
 PREVENTING THE GATING OF ANY OF THE
 ROADWAYS IN THE MIZNER PARK RPD.
  
 C) RECORD A MAINTENANCE AGREEMENT FOR
 THE PAVERS AND LANDSCAPING IN THE HANK
 AARON DRIVE TRAFFIC OVAL.
  
 D) RECORD A MAINTENANCE AGREEMENT FOR
 THE LAKE PATH AND LANDSCAPING ADJACENT
 TO THE MIZNER LAKES RPD.
  
 2) THE MONUMENT SIGN HAS CHANGED
 LOCATION AND CONFIGURATION FROM THE
 PLANS APPROVED BY ORDINANCE NO. 3914-05.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.
  
 3) THE DETENTION AREAS HAVE CHANGED
 CONFIGURATION FROM THE PLANS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 4) THE EASTERNMOST OF THE 2 ADA SPACES
 ON THE SOUTH SIDE OF THE BUILDING SHALL
 HAVE ITS SHORTEST DEPTH AT 18 FEET (WEST
 LENGTH).THE SPACE SCALES AT APPROX. 16
 FEET, WHICH WOULD RESULT IN CARS
 OVERHANGING INTO THE STREET.
  
 5) THE PARKING SPACE DETAILS SHALL
 STATE AND SHOW THAT WHEEL STOPS BE
 LOCATED TWO (2) FEET FROM THE FRONT OF
 THE SPACE AND SHOW THE DOUBLE STRIPING
 AS REQUIRED BY THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
 6) THE LAYOUT OF THE PARKING STRUCTURE
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 7) THE PARKING CALCULATION TABLE ON
 SHEET A-002 IS INCORRECT.IT SHOWS THE
 WRONG NUMBER OF UNITS COMPARED TO THE
 UNIT BREAKDOWN TABLE.IT SHOULD ONLY
 LIST THE PARKING PROVIDED WITH THE
 PERMIT FOR BUILDING NO. 5 LIMITS OF
 WORK.THE SPACES PROVIDED SHALL EQUAL
 OR EXCEED THE SPACES REQUIRED.
 ENUMERATE THE LOADING SPACES THAT ARE
 PROVIDED. THE PARKING DATA TABLE -
 SPACES PROVICED - DOES NOT EQUAL THE
 SPACES PROVIDED.
  
 8) PROVIDE VERIFICATION FROM THE CITY?S
 ENGINEERING AND PARKING DEPARTMENTS THAT
 THE CITY RECOGNIZES THE SAME NUMBER OF
 PARALLEL PARKING SPACES ON HANK AARON
 DRIVE AS SHOWN ON THE SUBMITTED PLANS.
 SOME OF THE SPACES ON THE PLAN SCALE OUT
 AS TOO SHORT AND THUS MAY NOT COUNT
 TOWARD THE PROVIDED PARKING. APPLICANT'S
 RESPONSE STATED THAT HANK AARON DRIVE
 PARKING IS NOT COUNTED TOWARD THE
 PROVIDED SPACES, YET THE PLANS COUNT THE
 HANK AARON DRIVE PARKING AS PROVIDED
 PARKING.
  
 9) THE FOOTPRINT OF THE BUILDING, TO
 INCLUDE ENTRYWAYS AND SIDEWALKS, HAS
 CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 10) THE LAYOUT OF THE POOL/AMENITY DECK
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 11) THE LAYOUT OF THE PERIMETER AND POOL
 AMENITY DECK LANDSCAPING HAS CHANGED
 FROM WHAT WAS APPROVED BY ORDINANCE NO.
 3914-05.APPROVAL OF A MINOR AMENDMENT
 IS REQUIRED FOR THE NEW LAYOUT.
  
 12) SHOW THE THE SETBACK OF THE
 BALCONIES AND ROOF FROM THEHANK AARON
 DRIVE PROPERTY LINE.
  
 13) THE AMOUNT OF RETAIL SQUARE FOOTAGE
 IN BUILDING NO. 5 HAS CHANGED FROM WHAT
 WAS APPROVED BY ORDINANCE NO. 3914-05.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.PLEASE
 NOTE THAT THE PROJECT IS APPROVED FOR A
 TOTAL OF 20,900 SQUARE FEET OF RETAIL.
  
 14) REMEMBER THAT THE DEVELOPER IS
 RESPONSIBLE FOR CONSTRUCTING THAT
 PORTION OF THE LAKE PATH ADJACENT TO THE
 SUBJECT SITE TO CITY STANDARDS AT THE
 OWNER?S EXPENSE AND WILL CONTINUE THE
 THEME THAT HAS BEEN ESTABLISHED ADJACENT
 TO THE HOME DEPOT DEVELOPMENT PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE FIRST RESIDENTIAL UNIT
 IN THE MIZNER LAKES RPD. THE DEVELOPER
 OR PROPERTY OWNER?S ASSOCIATION IS
 RESPONSIBLE FOR THE MAINTENANCE OF SAID
 PORTION OF THE LAKE PATH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By eschneid Date 2006-03-03 Time 13:44 Rev Time 0.00
Received By eschneid Date 2006-03-03 Time 13:44 Sent To  
Notes
2006-03-03 00:00:001) PER ORDINANCE NO. 3914-05, PRIOR TO
 THE ISSUANCE OF THE FIRST BUILDING
 PERMIT, THE APPLICANT/OWNER SHALL:
  
 A) RECORD PUBLIC ACCESS EASEMENTS FOR
 ROADWAYS AND ADJACENT SIDEWALKS
 THROUGHOUT THE SITE.THIS MAY BE DONE
 ON A PLAT OR SEPARATE INSTRUMENT.
  
 B) RECORD A RESTRICTIVE DEED OR COVENANT
 PREVENTING THE GATING OF ANY OF THE
 ROADWAYS IN THE MIZNER PARK RPD.
  
 C) RECORD A MAINTENANCE AGREEMENT FOR
 THE PAVERS AND LANDSCAPING IN THE HANK
 AARON DRIVE TRAFFIC OVAL.
  
 D) RECORD A MAINTENANCE AGREEMENT FOR
 THE LAKE PATH AND LANDSCAPING ADJACENT
 TO THE MIZNER LAKES RPD.
  
 2) THE MONUMENT SIGN HAS CHANGED
 LOCATION AND CONFIGURATION FROM THE
 PLANS APPROVED BY ORDINANCE NO. 3914-05.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.
  
 3) THE DETENTION AREAS HAVE CHANGED
 CONFIGURATION FROM THE PLANS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 4) THE DISABLED PARKING SPACE DETAIL
 DOES NOT APPEAR TO PROVIDE ADEQUATE
 DEPTH TO PREVENT A CAR TO INTRUDE INTO
 THE DROVE AISLE.VERIFY GRAPHICALLY
 THAT THE DEPTH IS ADEQUATE.
  
 5) THE PARKING SPACE DETAILS SHALL STATE
 THAT WHEEL STOPS BE LOCATED TWO (2) FEET
 FROM THE FRONT OF THE SPACE.
  
 6) THE LAYOUT OF THE PARKING STRUCTURE
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 7) IS THE SPACE IN THE NORTHWEST CORNER
 OF THE GARAGE A LOADING ZONE OR A
 PARKING SPACE?IT IS LABELED
 DIFFERENTLY ON THE SITE, LANDSCAPE AND
 ENGINEERING PLANS AND SHEETS WITHIN THE
 PLANS.
  
 8) THE PARKING CALCULATION TABLE ON
 SHEET A-002 IS INCORRECT.IT SHOWS THE
 WRONG NUMBER OF UNITS COMPARED TO THE
 UNIT BREAKDOWN TABLE.IT SHOULD ONLY
 LIST THE PARKING PROVIDED WITH THE
 PERMIT FOR BUILDING NO. 5 LIMITS OF
 WORK.THE SPACES PROVIDED SHALL EQUAL
 OR EXCEED THE SPACES REQUIRED.
 ENUMERATE THE LOADING SPACES THAT ARE
 PROVIDED.
  
 9) PROVIDE VERIFICATION FROM THE CITY?S
 ENGINEERING AND PARKING DEPARTMENTS THAT
 THE CITY RECOGNIZES THE SAME NUMBER OF
 PARALLEL PARKING SPACES ON HANK AARON
 DRIVE AS SHOWN ON THE SUBMITTED PLANS.
 SOME OF THE SPACES ON THE PLAN SCALE OUT
 AS TOO SHORT AND THUS MAY NOT COUNT
 TOWARD THE PROVIDED PARKING.
  
 10) THE FOOTPRINT OF THE BUILDING, TO
 INCLUDE ENTRYWAYS AND SIDEWALKS, HAS
 CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
 11) THE LAYOUT OF THE POOL/AMENITY DECK
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 12) THE LAYOUT OF THE PERIMETER AND POOL
 AMENITY DECK LANDSCAPING HAS CHANGED
 FROM WHAT WAS APPROVED BY ORDINANCE NO.
 3914-05.APPROVAL OF A MINOR AMENDMENT
 IS REQUIRED FOR THE NEW LAYOUT.
  
 13) SHOW THE HANK AARON DRIVE PROPERTY
 LINE ON THE SHEETS WITH THE FLOOR AND
 ROOF PLANS INCLUDING A DIMENSION LINE TO
 SHOW THE SETBACK OF THE BUILDING,
 BALCONIES AND ROOF FROM THE PROPERTY
 LINE.
  
 14) THE AMOUNT OF RETAIL SQUARE FOOTAGE
 IN BUILDING NO. 5 HAS CHANGED FROM WHAT
 WAS APPROVED BY ORDINANCE NO. 3914-05.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.PLEASE
 NOTE THAT THE PROJECT IS APPROVED FOR A
 TOTAL OF 20,900 SQUARE FEET OF RETAIL.
  
 15) REMEMBER THAT THE DEVELOPER IS
 RESPONSIBLE FOR CONSTRUCTING THAT
 PORTION OF THE LAKE PATH ADJACENT TO THE
 SUBJECT SITE TO CITY STANDARDS AT THE
 OWNER?S EXPENSE AND WILL CONTINUE THE
 THEME THAT HAS BEEN ESTABLISHED ADJACENT
 TO THE HOME DEPOT DEVELOPMENT PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE FIRST RESIDENTIAL UNIT