Plan Review Details - Permit 05091455
Plan Review Stops For Permit 05091455
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-20 Cont ID  
Sent By jwitmer Date 2006-07-20 Time 09:34 Rev Time 2.22
Received By jwitmer Date 2006-07-20 Time 09:34 Sent To  
Notes
2006-07-20 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091455
 ADD: 2995 45TH ST
 CONT: B& M CONSTRUCTION
 TEL: (954)427-4886
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NEW COMMENT, GLAZED STOREFRONT FROM
 THE FIRST REVIEW I ASSUMED JUST THE
 GLASS BEING REPLACED WAS NEW. IT APPEARS
  
 THAT A WHOLE NEW STOREFRONT WILL BE
 REPLACED AS OF THE NOTES ON SHEET D-1 &
 A-1.
 ONE ISSUE IS THAT THE COLUMN LINE ON
 THE LEFT SIDE OF THE OPENING KEEPS
 SHIFTING. THE DEMO SHEET AND A-1 SHOULD
 CORALATE OR SHOW NEW COLUMN AND BEAM TIE
 IN.ADDITIONAL INFO REQUIRED.
 THE SECOND ISSUE IS WHEN NEW
 GLAZINGIS INSTALLED IT WILL NEED TO MEET
  
 WIND REQUIREMENTS AS WELL AS LARGE
 MISSLE IMPACT TESTING. THIS CAN BE MET
 BY IMPACT GLAZING AND FRAME OR STORM
 SHUTTERS. THE TESTING REPORT SUBMITTED
 FOR THE WINDOWS IS FOR WIND ONLY WILL
 REQUIRE IMPACT TESTED STORM SHUTTERS AS
 WELL. 1609.1.4 PROTECTION OF OPENINGS.
  
 3) NEW COMMENT DEALS WITH THE EXISTING
 RESTROOMS. NOTE# 3 ON SHEET A-1
 INDICATES NEW VANITY, THIS VANITY STILL
 MUST MEET THE REQUIREMENTS OF :
 *** 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 *** 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 4) PLUMBING AND ELECTRICAL SHEETS HAVE
 THE WRONG SITE ADDRESS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By jwitmer Date 2005-12-01 Time 13:12 Rev Time 0.77
Received By jwitmer Date 2005-12-01 Time 13:12 Sent To  
Notes
2005-12-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091455
 ADD: 2995 45TH ST
 CONT: B& M CONSTRUCTION
 TEL: (954)427-4886
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 2) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
 3 ) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 08:03 Sent To  
Notes
2006-07-23 00:00:00********* UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE ALL NOTES FROM PREVIOUS
 REVIEW.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH
 FUTHER DETAIL ADDED TO EACH NOTE TO HELP
 PROJECT ALONG.
 ** PLEASE ALSO SEE NEW NOTE ADDED.
  
 **IMPORTANT**
 NOTES FROM MULTIPLE REVIEWERS IN
 PREVIOUS REVIEW INCLUDING ELECTRICAL
 REQUESTED FOR ALL OLD/VOIDED SHEETS TO
 BE COMPLETELY "REMOVED" FROM SETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ALSO MENTIONS ONLY TO SUBMIT "ONE" COPY
 OF THE OLD /VOIDED SHEETS SEPARATELY FOR
 REFERENCE.NONE OF THIS WAS DONE.
 PLEASE DO SO BEFORE RESUBMITTING PLANS
 FOR THE NEXT REVIEW.
  
 ***********************************
  
 1)NOTE: NO, PLEASE SEE NUMEROUS PAGES
 ARE STILL CONTAIN A RAISED SEAL OF
 PHOTO-COPIED SIGNATURES. PLEASE SEE THAT
 SOME SHEETS WERE DONE NEW , HOWEVER THE
 MECHANICAL WERE NOT DONE AT ALL AND MANY
 OF THE ELECTRICAL SHEETS ARE STILL THE
 SAME FROM PREVIOUS REVIEW.
 THE PREVIOUS REVIEW NOTE MENTIONED THIS
 WAS REQUIRED FOR ALL M>E>P SHEETS
 WHETHER OR NOT COMMENT WAS MADE BY OTHER
 REVIEWER(S). PLEASE KNOW, ONE SET OF MEP
 PLANS FROM BOTH HAVE NOW BEEN RETAINED.
 PLEASE SEENEW COMMENT AT THE END OF
 REVIEW.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE ALL M
 SEALED PHOTCOPIES OF ENGINEER'S ORIGINAL
 SIGNATURE. PLEASE SEE FS 471.025 AND FAC
 61G15-23 WHICH REQUIRES THE ENGINEER TO
 SIGN, DATE WITH AN "ORIGINAL" SIGNATURE.
 THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT THE COMMENT IS
 MADE BY OTHER REVIEWER(S),
 PLEASE KNOW, ONE COPY MAY BE RETAINED
 FOR POSSIBLE REVIEW BY FBPE'S, PLEASE
 MAKE CORRECTIONS.
  
 2)NOTE: NO, PLEASE SEE MANY SHEETS ARE
 THE SAME FROM THE PREVIOUS REVIEW AND
 NEW SHEETS ARE STILL MISSING THE
 REQUIRED INFORMATION ON SAID TITLE
 BLOCKS.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE NUMBER FOR THE ENGINEER OF
 RECORD.
 PLEASE SEE THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED.
 PLEASE SEEMISSING THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT ON THE SHEETS
 DONE BY THE ARCHITECTURAL SHEETS.
 PLEASE SEE FLORIDA ADMINISTRATIVE
 CODES;61G1-16.004, 61G15-23.002 AND
 FLORIDA STATUES 471.023
 ** PLANS ARE BEING RETAINED**
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING TITLE
 BLOCK/TITLE BLOCK INFORMATION WHICH IS
 REQUIRED UNDER FLORIDA ADMINISTRATIVE
 CODE (FAC) 61G15-23.002.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE # OF PE.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE OTHER INFORMATION ETC AS
 LISTED.
 PLEASE KNOW, THIS INFORMATION IS ALSO
 REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES.
  
 3)NOTE:NO, PLEASE SEE SHEET E-3 WHICH
 REPLACED OLD SHEET 3 IS COMPLETELY
 DIFFERENT AND NO LIGHTING IS SHOWN??
 WHERE IS THE LIGHTING ?
 PLEASE SEE PREVIOUS NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: NO, NOT DONE. SMAE SHEET.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
 (LIGHTING ETC)
  
 5)NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2002 NEC 210.8B3,
 WHICH REQUIRES ALL 15 AND 20A 120V
 CIRCUITS/DEVICES LOCATED IN KITCHEN
 AREAS TO BE GFI/GFI PROTECTED.
  
  
 ********* NEW NOTES ************
  
 6) NOTE: PLEASE SEE NEW SHEETS DO NOT
 CONTAIN ANY REVISION NOTED IN TITLE
 BLOCKS FOR LOCATIONS OF ANY POSSIBLE
 CHANGES. PLEASE KNOW, ALL REV'S SHOULD
 BE IDENTIFIED BY CLOUDS/TRIANGLES AND
 REVISED SHEET DATES ETC SHOUDL CORRELATE
 IN TITLE BLOCKS.
 IT IS UNCLEAR WHAT CHANGES WERE MADE AS
 SOME OF THE NEW SHEETS ARE NOW
 COMPLETELY DIFFERENT FROM THE SAME
 SHEETS PERVIOUSLY SUBMITTED.
 PLEASE KNOW, A REPONSE LETTER FROM THE
 DESIGN TEAM ON HOW EACH COMMENT WAS
 ADDRESSED OR COMMENTS WITH REPSECT TO
 REVIEW COMMENTS WOULD GREATLY HELP
 EXPEDITE THE REVIEW PROCESS. PLEASE SEE
 THAT NO RESPONSE LETTER WAS IN PACKAGE
 SUBMITTED.
  
 7) NOTE: PLEASE SEE ADDRESS IN TITLE
 BLOCKS FOR LOCATION OF SAID PROJECT IS
 NOT CORRECT ON SHEETS. PLEASE SEE MORE
 THAN ONE ADDRESS IS BEING SHOWN, HOWEVER
 THE ADDRESS OF RECORD AS APPLIED FOR IS
 2995 45TH ST. THIS ADDRESS MUST BE
 CORRECT ON "ALL" SHEETS AND FOR "ALL"
 TRADES. THIS WAS NOTED BY THE BUIDLIGN
 REVIEWER ALSO.
  
 8) NOTE: PLEASE SEE THE BRIGHT COLORED
 SHEET NOW ATTACHED TO REVIEW NOTES WHICH
 REFERENCES FS 553.80(2)(B) WITH RESPECT
 TO THE DESIGN PROFESSIONALS AND REPEAT
 CODE COMPLIANT COMMENTS. PLEASE KNOW,
 ONE SET OF PLANS ARE NOW RETAINED BY
 THIS OFFICE FOR POSSIBLE REVIEW BY THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 AND STATE'S LEGAL COUNSEL TO THE BOARD
 FOR SAID COMMENTS ABOVE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAYAFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE BE SURE ONE SET OF OLD/VOIDED
 SHEETS IS SUBMITTED FOR REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 17:54 Rev Time 1.00
Received By dpalmer Date 2005-11-16 Time 17:45 Sent To  
Notes
2005-11-16 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE ALL M
 SEALED PHOTCOPIES OF ENGINEER'S ORIGINAL
 SIGNATURE. PLEASE SEE FS 471.025 AND FAC
 61G15-23 WHICH REQUIRES THE ENGINEER TO
 SIGN, DATE WITH AN "ORIGINAL" SIGNATURE.
 THIS IS REQUIRED OF ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT THE COMMENT IS
 MADE BY OTHER REVIEWER(S),
 PLEASE KNOW, ONE COPY MAY BE RETAINED
 FOR POSSIBLE REVIEW BY FBPE'S, PLEASE
 MAKE CORRECTIONS.
  
 2)NOTE: PLEASE SEE MISSING TITLE
 BLOCK/TITLE BLOCK INFORMATION WHICH IS
 REQUIRED UNDER FLORIDA ADMINISTRATIVE
 CODE (FAC) 61G15-23.002.
 PLEASE SEE MISSING PRINTED NAME AND
 LICENSE # OF PE.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE OTHER INFORMATION ETC AS
 LISTED.
 PLEASE KNOW, THIS INFORMATION IS ALSO
 REQUIRED FOR ALL SHEETS AND FOR ALL
 TRADES.
  
 3)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF
 EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42 ETC.
 (LIGHTING ETC)
  
 5)NOTE: PLEASE SEE 2002 NEC 210.8B3,
 WHICH REQUIRES ALL 15 AND 20A 120V
 CIRCUITS/DEVICES LOCATED IN KITCHEN
 AREAS TO BE GFI/GFI PROTECTED.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAYAFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ANY
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE BE SURE ONE SET OF OLD/VOIDED
 SHEETS IS SUBMITTED FOR REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-10 Cont ID  
Sent By mwennerg Date 2006-08-10 Time 13:22 Rev Time 0.00
Received By mwennerg Date 2006-08-10 Time 13:22 Sent To  
Notes
2006-08-10 00:00:00***DENIED***
  
 PLEASE NOTE THAT IT DOES NOT APPEAR THAT
 COMMENTS FROM THE FIRST FIRE REVIEW HAVE
 BEEN ADDRESSED. PLEASE SEE THE FOLLOWING
 THAT HAS BEEN TAKEN FROM THE FIRST FIRE
 REVIEW:
  
 1) DEMOLITION, RENOVATION AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) DEBRIS SHALL BE REMOVED DAILY FROM
 THE SITE.
  
 3) ALL EXIT DOORS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 4) PLEASE PROVIDE DETAILL ON THE TYPES
 OF FOOD THAT WILL VBE PREPARED ON THE
 ROLLER GRILLS AND PLEASE EXPLAIN "HOT
 SANDWICHES".
  
 5) WHAT DEVICE DIRECTS PERSONS TO THE
 REAR EXIT? THE EMERGENCY/EXIT SIGN WITH
 LIGHT MAY NOT BE VISIBLE.
  
 6) PLEASE INDICATE MINIMUM INTERIOR
 FINSH CLASSIFICATIONS FOR THE NEW
 CEILING TILES IN TERMS OF CLASSA,B ORC.
  
 7) PROPER VENTILATION IS REQUIRED FOR
 THE USE OF GASOLINE POWERED DEMOLITION
 EQUIPMENT. CARBON MONOXIDE FUMES CAN
 DEVELOP IF EQUIPMENT IS NOT PROPERLY
 VENTILATED.
  
 PLEASE RESPOND TO THESE COMMENTS AND
 ILLUSTRATE ON DRAWINGS AND PROVIDE
 RESPONSES TO HELP EXPEDITE THIS PROCESS.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 10:10 Rev Time  
Received By mcarsill Date   Time   Sent To  
Notes
2005-11-10 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED DAILY FROM
 THE SITE.
  
 3. ALL EXIT DOORS SHALL REMAIN CLEAR
 AND UNOBSTRUCTED.
  
 4. PLEASE PROVIDE DETAIL ON THE TYPES
 OF FOOD THAT WILL BE PREPARED ON THE
 ROLLER GRILLS AND PLEASE EXPLAIN "HOT
 SANDWICHES".
  
 5. WHAT DEVICE DIRECTS PERSONS TO THE
 REAR EXIT. THE EMERENCY EXIT SIGN
 WITH LIGHT MAY NOT BE VISIBLE.
  
 6. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR THE NEW CEILING
 TILES.
  
 7. PROPER VENTILATION IS REQUIRED FOR
 THE USE ONY GASOLINE POWERED DEMOLITION
 EQUIPMENT. CARBON MONOXIDE FUMES CAN
 DEVELOP IF EQUIPMENT IS NOT PROPERLY
 VENTILATED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 11:22 Sent To  
Notes
2006-07-18 00:00:00TO "COMM" BD#52
2006-07-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-07 Cont ID  
Sent By kstevens Date 2005-12-07 Time 18:35 Rev Time 0.00
Received By kstevens Date 2005-09-29 Time 18:58 Sent To  
Notes
2005-09-29 00:00:00TO "COMM" BD#11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By pkrauss Date 2006-08-11 Time 09:06 Rev Time 0.00
Received By pkrauss Date 2006-08-11 Time 07:22 Sent To  
Notes
2006-08-11 00:00:00DENIED:
 ORIGINAL REVIEW BY HAROLD MOSER DATED
 11-14-06.
  
 COMMENT 1:OKAY
 COMMENT 2:PLEASE INDICATE THE RETURN
 AIR SIZES TO P/U 1 & 2.PLAN INDICATES
 A R/A PLENUM BOX AS 26" X 18".PLEASE
 CLARIFY DUCT SIZE FROM PLENUM BOX TO R/A
 GRILLE.WILL THE DUCTS BE THE SAME SIZE
 AS THE "NECK SIZE" AS SHOWN ON THE AIR
 DISTRIBUTION SCHEDULE?
  
 COMMENT 3:SEE COMMENT 2.
  
 ***************NEW COMMENT**************
 COMMENT 4:ENGINEER'S SIGNATURE ON
 PLAN SHEET M-1 IS A PHOTOCOPY WHICH IS
 NOT ACCEPTABLE PER FS 471.025 & FAC
 61G15-23.
  
 COMMENT 5:ADDTIONAL PERMIT IS REQUIRED
 FOR ANY NEW WALK-IN COOLERS OR HOODS.
 PLEASE PROVIDE PLANS & MANUFACTURER'S
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By hmoser Date 2005-11-14 Time 14:00 Rev Time 0.00
Received By hmoser Date 2005-11-14 Time 14:00 Sent To  
Notes
2005-11-14 00:00:00PLAN DENIED
 1) MAIN TRUNKLINES ON MECHANICAL PLANS
 DO NOT MATCH GENERAL NOTES #39
 2) PLEASE INDICATE RETURN AIR SIZES FOR
 P/U 1&2 ON MECHANICAL PLANS.
 3) PLEASE INDICATE DUCT SIZES IN
 BATHROOMS ON PLANS
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-09 Cont ID  
Sent By kstevens Date 2006-08-09 Time 11:06 Rev Time 0.00
Received By kstevens Date 2006-08-09 Time 11:06 Sent To  
Notes
2006-08-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. SHT P-0 SPECIFIC DEMO NOTES:
 #1 IN THE INSTALLATION OR REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. ALL
 CAPPED SECTIONS SHALL BE APPROVED BY THE
 PLUMBING INSPECTOR PRIOR TO COVERING.
 ****NO RESPONSE, NOT ADDRESSED,
  
 2. SHT P-1 KEY NOTES:
 #4 OK
 #7 OK
 #12 OK
 #18 OK
  
 #20 GREASE TRAP SHALL BE SIZED BY LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MANAGER
 AND THE GREASE INTERCEPTOR SHALL BE
 LOCATED OUTSIDE THE BUILDING. PLEASE
 CONTACT LYNN MASSON AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****NO RESPONSE, NOT ADDRESSED.
  
 #26 NOT APPROVED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. OK
 4. SHT P-2 PLUMBING SPECIFICATIONS AND
 NOTES:
 #4 OK
 #10 OK
 4. ALL PME SHEETS:
  
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025.
 ****RESPONSE NOTED, BUT PRINTED NAME AND
 CA# STILL REQUIRED ON EACH SHEET.
  
 **************NEW COMMENTS**************
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL VOIDED/SUPERCEDED SHEETS AND
 SUBMIT ONE SET FOR COMPARISON SEPARATE
 FROM SETS OF PLANS SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-07 Cont ID  
Sent By kstevens Date 2005-12-07 Time 18:10 Rev Time 2.33
Received By kstevens Date 2005-12-07 Time 18:10 Sent To  
Notes
2005-12-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. SHT P-0 SPECIFIC DEMO NOTES:
 #1 IN THE INSTALLATION OR REMOVAL OF
 ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. SECTION 704.5. ALL
 CAPPED SECTIONS SHALL BE APPROVED BY THE
 PLUMBING INSPECTOR PRIOR TO COVERING.
 2. SHT P-1 KEY NOTES:
 #4 BACKFLOW PREVENTER IF INSTALLED
 INSIDE SHALL BE LOCATED A MAXIMUM 4'
 ABOVE THE FLOOR FOR SERVICE AND
 CERTIFICATION.
 #7 FLOOR SINK OR HUB DRAIN REQUIRED.
 SECTIONS 802.3 & 802.3.2. FLOOR SINKS
 ARE NOT APPROVED INDIRECT WASTE
 RECEPTORS.
 #12 WATER FILTERS SHALL MEET THE
 REQUIREMENTS OF NSF-42. SUBMIT MANUF.
 SPECIFICATIONS FOR FILTER. SECTION 611.1
 #16. NOT SHOWN AT THE 3-COMP SINK, BUT
 BY THE TEA/COFFEE MACHINES. PLEASE
 CLARIFY. SECTION 104.2.1.
 #18 ALSO SHOWN AT 3-COMP SINK. PLEASE
 CLARIFY. SECTION 104.2.1.
 #20 GREASE TRAP SHALL BE SIZED BY LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MANAGER
 AND THE GREASE INTERCEPTOR SHALL BE
 LOCATED OUTSIDE THE BUILDING. PLEASE
 CONTACT LYNN MASSON AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected].
 #26 NOT APPROVED.
 3. SHT P-2 SEE COMMENTS #1 & #2 KEY NOTE
 #20.
 4. SHT P-2 PLUMBING SPECIFICATIONS AND
 NOTES:
 #4 AIR CHAMBERS ARE NOT APPROVED.
 PLEASE DELETE FROM REFERENCE. SECTION
 604.9.
 #10 1/4"FT SLOPE REQUIRED FOR 2-1/2"
 PIPE AND SMALLER. TABLE 704.1.
 4. ALL PME SHEETS:
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025 - THE
 SIGNATURE FOR THESE SHEETS ARE SEALED
 PHOTOCOPIES AND ARE NOT APPROVED. A
 "WET" SEAL IS REQUIRED. NO TITLE BLOCK
 OR REQUIRED INFORMATION IS ON EACH SHEET
 AS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]