| 2006-02-07 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE PROPOSED PROJECT APPEARS TO |
| | COMPRISE MORE THAN ONE PARCEL. PLEASE |
| | SUBMIT A COPY OF THE REPLAT. |
| | |
| | 3) IN ORDER TO DETERMINE THE PERCENTAGE |
| | OF WALL AREA ALLOWED AS OPENINGS BY FBC |
| | TABLE 600, SUBMIT A SURVEY INDICATING |
| | THE LOCATIONS OF THE ASSUMED PROPERTY |
| | LINES BETWEEN THE BUILDINGS. |
| | |
| | 4) PROVIDE AN AREA CALCULATION TABLE |
| | LISTING THE FLOOR AREA BREAKDOWNS BY |
| | FLOOR FOR EACH UNIT AND THE TOTALS FOR |
| | ALL FOUR UNITS. |
| | |
| | 5) THE FBC DOES NOT ALLOW HEIGHT AND |
| | AREA INCREASES FOR NFPA 13R SPRINKLER |
| | SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D). |
| | SPECIFY THE TYPE OF SPRINKLER SYSTEM ON |
| | THE PLANS. MUST BE A FULL NFPA 13 SYSTEM |
| | FOR HEIGHT INCREASE. SUBMIT FIRE |
| | SPRINKLER PLANS PER FBC 104.3.1.1. |
| | |
| | 6) FBC 2504.4.1 AND GA 216 REQUIRE WOOD |
| | FURRING TO BE NOT LESS THAN 3/4" X |
| | 1-1/2" ACTUAL SIZE. ALSO, THE SURFACE |
| | CAN NOT VARY MORE THAN 1/8" FROM THE |
| | PLANE OF ADJACENT FURRING MEMBERS. |
| | DETAIL 1 ON A10.0.0 SHOWS THE FURRING |
| | ATTACHED OVER 3/4" POLYSTYRENE. PLEASE |
| | REVISE DETAIL TO COMPLY WITH CODE. |
| | |
| | 7) SPECIFY THE INSULATION THAT WILL BE |
| | USED IN THE FLOOR/CEILING ASSEMBLY ABOVE |
| | THE GARAGE. |
| | |
| | 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO |
| | DISCHARGE ONE FOOT AWAY FROM THE |
| | STRUCTURE PER FBC 1503.4.4. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC MECH. TABLE |
| | 403.3 FOR REQUIRED OUTDOOR AIR |
| | VENTILATION AT GARAGES OF 100 CFM PER |
| | CAR. |
| | |
| | 10) ON SHEET A-4.8.1 TWO BEDROOMS ARE |
| | LABELED BEDROOM #2. |
| | |
| | 11) SPECIFY THE EXTERIOR FINISH AT THE |
| | UNDERSIDE OF THE BAY WINDOW SHOWN ON |
| | A-7.1.2. SPECIFY THE EXTERIOR SHEATHING, |
| | LATH AND STUCCO. NOTE: SEE ASTM C 926 |
| | FOR REQUIRED STUCCO THICKNESS. |
| | |
| | 12) ASTM C 926 REQUIRES 7/8" OF STUCCO |
| | WHEN APPLIED VERTICALLY ON METAL PLASTER |
| | BASE OVER SOLID BASE. PLEASE REVISE NOTE |
| | #46 FOR SECTION 4 ON A-7.0.2. |
| | |
| | 13) SPECIFY THE MEAN ROOF HEIGHT OF THE |
| | STRUCTURE. THIS IS THE VERTICAL DISTANCE |
| | FROM FINISHED GRADE TO THE A POINT AT |
| | THE AVERAGE HEIGHT OF THE ROOF. |
| | |
| | 14) SUBMIT SHOP DRAWINGS FOR THE BALCONY |
| | GUARDRAILS. SPECIFY ATTACHMENTS, SPACING |
| | OF INTERMEDIATE RAILS, ETC. |
| | |
| | 15) SPECIFY THE METHOD OF ATTACHMENT FOR |
| | THE ROOF TILES. THE PRODUCT APPROVAL |
| | THAT WAS SUBMITTED HAS AN ATTACHMENT |
| | RESISTANCE MOMENT OF 24.5 FT-LBF FOR |
| | MORTAR SET TILE. FOR 140 MPH EXPOSURE B |
| | WITH 40FT MRH, THE REQUIRED MOMENT IS |
| | 28.3 FT-LBF. PLEASE REVISE ROOF TILE |
| | DETAILS TO COMPLY WITH CODE. |
| | |
| | 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE |
| | RATING NOT ONE HOUR AS SPECIFIED ON THE |
| | PLANS FOR WALL TYPES IN DETAILS 2 AND 6 |
| | ON A-10.00. |
| | |
| | 17) SPECIFY DRAFTSTOPPING IN THE ROOF |
| | OVERHANGS IN LINE WITH THE TENANT |
| | SEPARATION WALLS AS REQUIRED BY FBC |
| | 2305.2.3. |
| | |
| | 18)705.7.1 JOINTS INSTALLED IN OR |
| | BE- TWEEN FIRE RESISTANT WALLS, FIRE |
| | RESIS- TANT FLOORS OR FLOOR/ CEILING |
| | ASSEMBLIES AND FIRE RESISTANT ROOFS OR |
| | ROOF/ CEILING ASSEMBLIES SHALL BE |
| | PROTECTED BY AN APPROVED FIRE RESISTANT |
| | JOINT SYSTEM DESIGNED TO RESIST THE |
| | PASSAGE OF FIRE FOR A PERIOD NOT LESS |
| | THAN THE REQUIRED FIRE RESISTANCE RATING |
| | OF THE WALL, FLOOR OR FLOOR IN OR |
| | BETWEEN WHICH IT IS INSTALLED. SPECIFY |
| | THE JOINT SYSTEM AT THE TOP OF THE |
| | TENANT SEPARATION WALLS. |
| | |
| | 19) DETAIL 17 ON A-10 DOES NOT |
| | CORRESPOND TO GA ASSEMBLY FC 5517 |
| | SPECIFIED ON SHEET A 10.2.0. |
| | |
| | 20) SUBMIT SIGNED AND SEALED TRUSS |
| | LAYOUTS AND DRAWINGS THAT HAVE BEEN |
| | REVIEWED AND APPROVED BY THE DESIGNER OF |
| | RECORD FOR THE STRUCTURE. |
| | |
| | 21) THE UPLIFT LOAD VALUES LISTED IN THE |
| | TRUSS ANCHOR SCHEDULE ON S-3 FOR THE |
| | SIMPSON HETAL 16 & 20 ARE INCORRECT.THE |
| | ONE THIRD STRESS INCREASE FOR STEEL |
| | CALCULATIONS IS NO LONGER ALLOWED. SEE |
| | THE 2005 SIMPSON CATALOG. |
| | |
| | 22) THE HUGHES "USC" CONNECTORS ALSO |
| | HAVE INCORRECT UPLIFT VALUES. HUGHES WAS |
| | PURCHASED BY USP SEVERAL YEARS AGO AND |
| | IS LONGER IN BUSINESS. SEE THE 2005 USP |
| | CATALOG FOR VALUES. UPDATE THE TRUSS |
| | ANCHOR SCHEDULE. |
| | |
| | 23) UNDER KEY NOTES/ LEGEND ON A-4.0 AND |
| | OTHER SHEETS REFERENCE IS MADE TO SHEET |
| | A-13 FOR THE WALL TYPES. HOWEVER, THERE |
| | IS NO SHEET A-13. |
| | |
| | 24) THE ENERGY CALCULATIONS CONTAIN |
| | SEVERAL ERRORS. THESE ARE CONSIDERED |
| | MULTIFAMILY NOT SINLE FAMILY. THE |
| | ADJACENT WALL AT THE GARAGE IS METAL |
| | FRAME AND THE CEILING INSULATION IS |
| | SPECIFIED AS R-20 ICYENE. |
| | |
| | 25)PROVIDE MANUFACTURER'S SPECIFICATIONS |
| | FOR THE ICYENE INSULATION. |
| | |
| | 26) PRODUCT APPROVALS SUBMITTED |
| | WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| | 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE |
| | AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| | WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| | BE SUBMITTED WITH A COVER SHEET THAT |
| | LISTS THE PRODUCT IDENTITY NUMBER FROM |
| | THE STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| | FLORIDA COVER SHEETS FOR ALL PRODUCT |
| | APPROVALS. IN ADDITION TO THE COVERSHEET |
| | THE INSTALLATION INSTRUCTIONS OR PRODUCT |
| | EVALUATION AS LISTED ON THE STATE |
| | WEBSITE IS ALSO REQUIRED. TWO (2) COPIES |
| | ARE REQUIRED. |
| | |
| | 27) SUBMIT STATE PRODUCT APPROVALS FOR |
| | THE TRUSS CONNECTORS. |
| | |
| | 28) THE MIAMI-DADE NOA FOR THE SINGLE |
| | HUNG WINDOWS HAS THE INFO FROM THE FIXED |
| | GLASS WINDOWS ATTACHED TO THE NOA |
| | COVERSHEET. |
| | |
| | 29) THE DESIGN PRESSURES LISTED IN THE |
| | GARAGE DOOR PRODUCT APPROVALS DO NOT |
| | MEET THE PRESSURES SPECIFIED ON THE |
| | PLANS. SEE S-6. |
| | |
| | 30) SUBMIT MANUFACTURER'S SPECS. FOR THE |
| | DOOR CLOSERS. |
| | |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |