Plan Review Details - Permit 05091395
Plan Review Stops For Permit 05091395
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-02 Cont ID  
Sent By shill Date 2008-04-02 Time 15:40 Rev Time 0.00
Received By shill Date 2008-04-02 Time 15:40 Sent To  
Notes
2008-04-02 15:41:49REVISION, CHANGE FROM MONIER TILE TO HANSON

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-04-01 Cont ID  
Sent By shill Date 2008-04-01 Time 13:59 Rev Time 0.00
Received By shill Date 2008-04-01 Time 13:59 Sent To  
Notes
2008-04-01 14:01:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER
 BARRIER REQUIRED FS553.844(5)(A). PROVIDE
 INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO
 SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT.
 INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE
 MITIGATION.
  
 ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY;
 MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF
 EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 ____4.)FOR THE FLAT ROOF, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 ____5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO
 BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED
 ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB
 SHEET).
  
 _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM
 ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72.
  
 ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-30 Cont ID  
Sent By lmartine Date 2007-05-30 Time 16:49 Rev Time 0.00
Received By lmartine Date 2007-05-30 Time 16:49 Sent To  
Notes
2007-05-30 16:50:02PARTITION WALL REVISION OK#3

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-12 Cont ID  
Sent By tgordon Date 2006-04-12 Time 16:12 Rev Time 1.75
Received By alange Date 2006-03-27 Time 12:21 Sent To  
Notes
2006-03-27 00:00:00DENIED
  
 7.ALL OF THE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 A.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH THE STATE APPROVALS.
 (SEE ATTACHED NOTES ON PRODUCT
 APPROVALS)
  
 B.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-17 Cont ID  
Sent By alange Date 2006-02-17 Time 09:12 Rev Time 2.00
Received By alange Date 2006-02-17 Time 09:06 Sent To  
Notes
2006-02-17 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
  
 7.ALL OF THE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT:
 A.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH THE STATE APPROVALS.
  
 B.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By alange Date 2005-10-12 Time 07:20 Rev Time 3.25
Received By alange Date 2005-10-12 Time 07:06 Sent To  
Notes
2005-10-12 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PLEASE SUBMIT SPECS FOR GAS
 FIREPLACE.
  
 4.SUBMIT BBQ AND HOOD SPECIFICATIONS.
  
 5.SUBMIT TWO COPIES OF ORIGONAL SIGNED
 AND SEALED SURVEYS.FS 472.075
  
 6.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.
  
 7.ALL OF THE PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8.FBC 2305.2 DRAFTSTOPPING SHALL BE
 PROVIDED IN WOOD FRAME CONSTRUCTION IN
 THE LOCATIONS LISTED IN FBC 2305.2.2
 THROUGH FBC 2305.2.4.
 FBC 2305.2.2 FLOOR/CEILING ASSEMBLIES
 SINGLE FAMILY DWELLINGS.IN
 FLOOR/CEILING ASSEMBLIES SEPARATING
 USEABLE SPACES INTO TWO OR MORE
 APPROXIMATE AREAS WITH NO AREA
 GREATER THAN 500 SQ FT.DRAFTSTOPPING
 SHALL BE PROVIDED PARALLEL TO THE MAIN
 FRAMING MEMBERS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-06-24 Cont ID  
Sent By dpalmer Date 2008-06-24 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2008-06-24 Time 16:53 Sent To PC
Notes
2008-06-24 16:53:38REVISED PLANS OK.

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 16:56 Sent To PC
Notes
2008-06-16 16:57:06** DENIEDREVISIONS**
  
 1) NOTE: PLEASE SEE ELECTRICAL RISE IS STILL SHOWING AN
 EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.THIS SAME COMMENT
 HAS BEEN MADE NUMEROUS TIMES.
 THIS CREATES OBJECTIONABLE CURRENTS. 250.6, 250.24
 PLEASE ADJUST PLANS.
  
 2) NOTE: PLEASE COORDINATE RISER AND PANELS. PANEL *B*
 NOW SHOWS A NEW SUB-POOL PANEL YET THE RISER DOES NOT
 INCLUDE THIS. PLEASE INCLUDE.
 215, 230, 240.4, 310.16, ETC
 FBC 106.3.5.4
  
 3) NOTE: PLEASE SEE THE PANELS INDICATE PANELS AS MLO
 (MAIN LUG ONLY) YET THE RISER SHOWS THESE AS CONTAINING
 2-POLE MAIN BREAKERS.
 230.70, 230.71, 230.72.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 4) NOTE: PLEASE CLARIFY WHERE THE DINING ROOM
 RECEPTACLES ARE CIRCUITED. PLEASE SEE 210.52B1, 408.4,
 210.11C1 AND 220.52.
 DINING AREA RECEPTACLES NEED TO BE SPECIFIED MEETING
 THE SECTIONS GIVEN ABOVE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-07-18 Cont ID  
Sent By dpalmer Date 2007-07-18 Time 14:06 Rev Time 0.00
Received By dpalmer Date 2007-07-18 Time 12:45 Sent To P
Notes
2007-07-18 14:09:22*** REDLINED PLANS****
  
  
 1) NOTE: THE ELECTRICAL RISER DIAGRAM IS STILL SHOWING
 AN "EQUIPMENT GROUNDING CONDUCTOR" AHEAD OF THE FIRST
 MEANS OF DISCONNECT/MAINS. THIS NOT PERMITTED AND THIS
 COMMENT HAS BEEN REPEATED ON SEVERAL REVIEWS. PLEASE
 SEE 250.6 AND 250.24. IF THIS WAS INSTALLED, THIS WOULD
 CREATE OBJECTIONABLE CURRENTS BETWEEN THE NEUTRAL AND
 GROUDING.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 15:55 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 15:26 Sent To P
Notes
2007-07-03 15:55:39** UNSAT **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES AS THE SMOKE DEVICES
 ARE STILL BEING SHOWN AS SD ON PLANS AND SYMBOL LEGEND
 INDICATES SMOKE DETECTORS, HOWEVER THE NOTES ARE
 SOUNDING LIKE THESE ARE SMOKE ALARMS WHICH ARE NOT THE
 SAME AS SMOKE DETECTORS.
 PLEASE SEE NFPA-72 DEFINITIONS. PLEASE CALL IF THERE
 ARE ANY QUESTIONS ON THIS AS PREVIOUSLY NOTED.
  
 2) NOTE: PLEASE SEE PLANS NOW HAVE A REVISED RISER
 DIAGRAM WHICH DOES NOT MATCH WITH PLANS. PLEASE SEE
 PLANS INDICATE TWO MAINS OUTSIDE, HOWEVER THE RISER
 DOES NOT SHOW ANY MAINS AND THE PANELS ARE NOTED AS
 200A MLO PANELS?
 230.70,230.71,230.72, ETC
 DEPENDING ON WHETHER OR NOT THE MAINS ARE OUTSIDE AN
 *EQUIPMENT GROUNDING CONDUCTOR* IS STILL BEING SHOWN ON
 RISER FROM METER TO PANEL??
 250.6, 250.24
 ** PLEASE CALL TO GO OVER THIS IF THERE IS ANY
 QUESTIONS AS PREVIOUSLY NOTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-26 Cont ID  
Sent By dpalmer Date 2007-04-26 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2007-04-26 Time 08:28 Sent To B
Notes
2007-04-26 08:54:06** UNSAT **
  
 1) NOTE: PLEASE SEE THAT THE REVISED PLANS APPEAR TO BE
 FOR FINALS, PLEASE SEE MECHANICAL COMMENTS.
 PLEASE SUBMIT REVISED PANEL SCHEDULES PER 408.4. PLEASE
 SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE
 NEC.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 2) NOTE: PLEASE NFPA-72 DEFINITIONS. IF THE SMOKE
 DEVICES ARE 120V WIRED INLINE WITH BATTERY BACK-UP
 WHICH DETECT AND SOUND AN ALARM, THEN THESE NEED TO BE
 SHOWN AS SA FOR SMOKE ALARMS.
 ONLY IF THESE ARE DEVICES WHICH ONLY DETECT AND SEND A
 SIGNAL OUT O AN ALARM SYSTEM WITH SOUNDING DEVICES
 WOULD THESE BE SHOWN AS SD. PLEASE KNOW IF THESE ARE
 INDEED LV SMOKE DETECTORS, PLEASE SHOW SOUNDING
 DEVICES.
 IF THERE ARE ANY QUESTIONS ON THIS, PLEASE CALL.
  
 3) NOTE: PLEASE REVISE THE LOAD CALCULATIONS IF NEED
 FOR THE TOTAL SQ FT AND LOADS AS CHANGED.
 220
  
 4) NOTE: PLEASE SEE PREVIOUS REVISED PLANS FROM 4/06
 FOR EQUIPMENT GROUNDIGN CONDUCTOR WHICH IS SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 17:16 Sent To M
Notes
2006-03-18 00:00:00*** NOTE **
  
 PLEASE SEE PLANS WERE REVISED FROM
 "PROVISO" ON PREVIOUS REVIEW.
  
 1)PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS WERE ADDED TO RISER, HOWEVER
 THESE WERE ADDED TO CONDUITS FROM GUTTER
 TO MAINS(FIRST MEANS OF DISCONNECT)
 ALSO. PLEASE KNOW, "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. 250.6,250.24
 THIS DOES NOT NEED REVISING, ONLY IF
 REVISIONS ARE DONE AT A LATER DATE.
  
 *PLANS STAMPED, ALL OTHER NOTES FROM
 "PROVISO" WERE ADDRESSED 100%.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-14 Cont ID  
Sent By dpalmer Date 2006-02-14 Time 19:17 Rev Time 0.00
Received By dpalmer Date 2006-02-14 Time 18:05 Sent To M
Notes
2006-02-14 00:00:00********* PROVISO ***********
  
 ** IF PLANS COME BACK AS FAILED FOR ANY
 COMMENTS FROM OTHER TRADES, BE SURE TO
 MAKE THESE CORRECTIONS AT THIS TIME.****
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 IN PLANS.
  
 1)NOTE: PLEASE SEE PLANS INDICATE THE
 FAULT CURRENT CALCULATIONS , HOWEVER DO
 NOT INDICAT THE AIC RATINGS FOR THE
 MAINS. PLEASE SEE THE AFC AT SERVICE
 MAINS IS SHOWN @ 10,942, THEREFORE
 22,000 AIC RATED MAINS (MIN) ARE
 REQUIRED. PLEASE INDICATE.
 110.9,215.5
  
 2)NOTE: PLEASE SEE RISER SHOWS
 CONDUCTORS TO FPL TRANSFORMER AS 300MCM?
 PLEASE KNOW, IF THESE SEC'S ARE
 INSTALLED BY FPL, PLEASE DO NOT INDICATE
 SIZE. IF THE SEC'S ARE INSTALLED HOWEVER
 BY THE ELECTRICAL CONTRACTOR TO FPL,
 THESE CONDUCTORS SHALL BE SIZED AT A MIN
 PER 310.15B6. (400MCM MIN).
 400MCM IS SHOWN FROM METER TO GUTTER.
  
 3)NOTE: PLEASE SEE LOAD CALCUALTIONS
 SHALL INCLUDE LOADS FOR RECESSED LTS PER
 220.3B4, THESE LOADS ARE ABOVE THE MIN
 GENLT LIGHTING LOADS.
 PLEASE ADJUST AND REVISE LOAD
 CALCUALTIONS.
 PLEASE ALSO SEE THE RECESED LTS ARE NOW
 SHOWN ON FIXTURE LEGEND AS 100WATT,
 HOWEVER PLEASE VERIFY FIXTURE AS THE
 MAJORITY OF "AIR-TITE" RECESSED LTS DO
 NOT PERMIT IN EXCESS OF 75W'S.
 ADJUST LEGEND AS REQUIRED.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS FROM MAINS TO
 PANELS. 250.110,250.122 ETC.
  
 5)NOTE: PLEASE SEE NFPA-72 11.8.3.5 FOR
 LOCATIONS OF SMOKE DETECTORS, PLEASE SEE
 ROOMS AND AREAS WITH VAULTED/TRAY
 CEILINGS. PLEASE SEE SD'S SHALL BE
 WITHIN 12" OF THE HIGHEST POINT OF THESE
 CEILINGS.
  
 6)NOTE: PLEASE SEE CODE REFERENCED FOR
 MIN CLEARENCES FOR DISCONNECTS AT CU'S
 STATES THE 2001 NEC. PLEASE SEE THIS
 SHOULD BE 2002 NEC.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2'OR MORE OF WALL IN FOYER.210.52
  
 ****************************************
 PLEASE SUBMIT THE ABOVE CORRECTIONS
 BEFORE ANY ROUGH SLAB INSPECTION IS
 CALLED IN.
 ***************************************
 IF PLANS FAIL OR GO OUT FOR COMMENTS
 FROM OTHER REVIEWER(S), PLEASE MAKE
 THESE CORRECTIONS AT THIS TIME.
 ***************************************
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-07 Cont ID  
Sent By dpalmer Date 2005-10-07 Time 17:59 Rev Time 1.50
Received By dpalmer Date 2005-10-07 Time 17:12 Sent To M
Notes
2005-10-07 00:00:00******** UNSAT ********
  
  
 1)PLEASE SEE ADDRESSING WILL STILL NEED
 TO BE ASSIGNED. PLEASE ALSO SEE FAC
 61G1-16.004 WHICH REQUIRES THE ADDRESS
 OF NEW HOME.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE SEE IT IS NOTED FOR AIC RATINGS
 FOR NEW PANELS, HOWEVER NOT SUBMITTED
 FOR MAINS.
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1
 PLEASE SEE MISSING SD LEADING TO FLOOR
 ABOVE IN THE VICINITY OF STAIRS LEADING
 TO FLR ABOVE. (IF OPEN CEILING, WALL
 MOUNT).
 PLEASE ALSO SEE NFPA-72 11.8.3.5, WHICH
 REQUIRES SD'S TO BE LOCATED 3' FROM BATH
 DOORS,KITCHEN DOORS AND 20' FROM COOKING
 APPLICANCES UNLESS MEETING THE
 EXCEPTIONS LISTED.
  
 4)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
 PLEASE SEE ISLAND.
  
 5)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING COUNTERSPACE GFI.
 REDLINED ON PLANS.
  
 6)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE REDLINED AREAS ON PLANS.
  
 7)NOTE: PLEASE CORRELATE RISER DIGRAM(S
 WITH PANEL SCHEDULE(S).
 PLEASE SEE RISER SHOWS PANELS AS 200A
 AND PANELS ARE SHOWN AS 150A.
 PLEASE SEE LOAD ON PANEL WHICH EXCEEDS
 150A RATING OF PANEL.
 240.4
  
 8)NOTE: PLEASE SEE 240.4,310.15B6,310.16
 FOR SIZING OF SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS FOR PANELS.
 PLEASE SEE PANELS ARE SHOWN HAVING
 1/0'S(RATED AT 150A'S) WITH 200A
 OVERCURRENT PROTECTION.
 PLEASE SEE FEEDERS FROM MAINS TO PANELS.
 PLEASE ALSO SEE SEC'S ARE SHOWN AS
 300MCM WHICH ARE ONLY RATED FOR 285A'S.
 PLEASE SEE 310.15B6, WHICH REQUIRES
 400MCM MIN.
 PLEASE SEE CONDUCTORS FROM METER SHOULD
 BE RUN INDIVIDUALLY TO EACH MAIN
 DISCONNECTBY MEANS OF DOUBLE LUGS ON
 METER. PLEASE SEE MAIN DISCONNECT SHOULD
 NOT BE USED AS A RACEWAY.
 PLEASE SEE 300 MCM IS BEING SHOWN TO ONE
 MAIN AND 1/0'S ARE BEING SHOWN TO OTHER.
 PLEASE ADJUST
 PLEASE SEE 408.35
  
 9)NOTE: PLEASE SEE A/C CU'S ARE BEING
 NOTED AS HAVING DISCONNECTS, HOWEVER
 DISC'S SHOULD BE SHOWN IN ORDER TO
 VERIFY MIN CLEARENCE PER 110.26
 440.11.
  
 10)NOTE: PLEASE INDICATE THE REQUIRED
 GFI PROTECTION FOR JACUZZI TUB. 680.71
 (VERIFY 4KW AT 240V)
  
 11)NOTE: PLEASE SEE CONTTROL SW AT
 BOTTOM OF STAIRS DOES NOT INDICATE 3-WAY
 ,
 (MISPRINT). 210.70
 PLEASE SEE "MECH RM" WHICH CONTAINS
 WATER HEATER AND CENTRAL VAC, SHOWS A SW
 INSIDE FOR OUTSIDE LT, HOWEVER DOES NOT
 SHOW A LT INSIDE RM??
  
 12)NOTE: PLEASE SEE DIMMERS ARE SHOWN ON
 RECEPTS??
 PLEASE SEE HALF SWICHED RECEPTS ARE
 PERMITTED, HOWEVER JUST NOT ON A DIMMER.
  
 13)NOTE:PLEASE SEE NUMEROUS BRANCH
 CIRCUITS ON PANEL SCHEDULES WHICH
 CONTAIN 20A BRKRS(OCP) ON #14 AWG.
 PLEASE SEE 240.4, 310.16, WHICH REQUIRES
 #12 MIN FOR 20A OCP.
  
 14)NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR SHALL BE SIZED PER
 310.15B6/310.16/ 250.66
 (1/0 MIN).
  
 15)NOTE: PLEASE SEE NOTES 9 AND 10 OF
 ELECTRICAL NOTES. BOTH LANDSACPE
 LIGHTING AND LV WILL BE REQUIRED TO
 UNDER SEPARATE PERMIT IS NOT SHOWN ON
 PLANS.
  
 16)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 17)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE THE 2ND DISCONNECT AS INDICATED
 ON RISER.
 215.5
  
 18)NOTE: PLEASE INCLUDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
  
 PLEASE BE SURE TO SEE ANY OTHER COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE ONE COPY OF ALL OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESTITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-06-09 Cont ID  
Sent By adarroug Date 2008-06-09 Time 10:05 Rev Time 0.00
Received By adarroug Date 2008-06-09 Time 10:05 Sent To E
Notes
2008-06-09 10:06:17TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 11:46 Sent To B
Notes
2008-03-27 11:48:34TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 08:15 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 08:15 Sent To E
Notes
2007-07-16 08:15:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-07-03 Cont ID  
Sent By adarroug Date 2007-07-03 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-07-03 Time 09:56 Sent To E
Notes
2007-07-03 09:56:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 11:26 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 11:26 Sent To M
Notes
2007-06-19 11:26:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 15:03 Sent To M
Notes
2007-04-23 15:03:36TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 11:53 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 11:53 Sent To G
Notes
2006-09-12 00:00:00TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 17:04 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 17:04 Sent To B
Notes
2006-04-10 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 15:56 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 15:56 Sent To E
Notes
2006-03-16 00:00:00TO "DPALMER" DESK/RESUB-NEW ELECTRICAL
 SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 09:36 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 09:36 Sent To E
Notes
2006-02-13 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-08 Cont ID  
Sent By adarroug Date 2006-02-08 Time 10:38 Rev Time 0.00
Received By adarroug Date 2006-02-08 Time 10:38 Sent To Z
Notes
2006-02-08 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 11:11 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 11:11 Sent To E
Notes
2005-10-07 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-12 Cont ID  
Sent By alange Date 2005-10-12 Time 07:21 Rev Time 0.00
Received By alange Date 2005-09-29 Time 11:36 Sent To  
Notes
2005-09-29 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 12:28 Rev Time 0.30
Received By tgordon Date 2007-06-19 Time 12:28 Sent To  
Notes
2007-06-19 12:29:33REVISION TO MECH. PLANS BOTH PAGES

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2007-04-24 Cont ID  
Sent By tgordon Date 2007-04-24 Time 16:26 Rev Time 0.25
Received By tgordon Date 2007-04-24 Time 16:26 Sent To E
Notes
2007-04-24 16:35:44REVISION TO PLANS PAGE A-1
 *** DENIED ***
 1) BY CHANGING THE TOTAL UNDER AIR AREA FROM 4985 S.F.
 TO 5345 S.F. THE ENERGY CALCULATIONS, COOLING LOAD
 CALCULATIONS, AND MECHANICAL PLANS NEED TO BE REVISED
 TO SHOW CHANGES, PLEASE COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-11 Cont ID  
Sent By tgordon Date 2006-04-11 Time 14:27 Rev Time 0.00
Received By tgordon Date 2006-04-11 Time 16:12 Sent To B
Notes
2006-04-11 00:00:00 

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 10:40 Rev Time 1.30
Received By tgordon Date 2006-03-20 Time 10:40 Sent To B
Notes
2006-03-20 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR
 104,200 TOTAL BTU'S. PLANS ARE CALLING
 FOR 108,000 TOTAL BTU'S.. THE PLANS CAN
 NOT CALL FOR MORE THAN THE ENERGY CAL'S.
 PLEASE CORRECT.
  
 2) THE JOB ADDRESS MUST APPEAR ON THE
 MCCHANICAL PLANS.
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE SHOW THE TOTAL BTU'S. FOR EACH
 UNIT ON THE MECHANICAL PLANS.
  
 5) SUPPLY AIR DUCT (FLEX) FROM AHU #1 TO
 THE MIXING BOX NEEDS TO SHOW THE SIZE.
  
 6) OPEN DUCTS MAY NOT BE IN THE STORAGE
 AREA AS IT IS OPEN TO THE GARAGE.
  
 7) PLANS ARE SHOWING A GAS FIRE PLACE
 THE MANUFACTURE'S SPECIFICATION'S
 SUBMITTED ARE FOR A WOODBURNING FIRE
 PLACE PLEASE CORRECT.
  
 8) SUPPLY AIR DUCTS (FLEX) TO BEDROOMS 2
 & 3 ALL NEED TO BE SIZED.
  
 9) RETURN AIR TRANSFER DUCT (FLEX) TO
 MINI MASTER/OFFICE (GUEST) IS TO SMALL,
 SEE NOTE #11.
  
 10) RETURN AIR TRANSFER DUCT (FLEX) TO
 DEN IS NOT SIZED, SEE NOTE #11.
  
 11) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-02-15 Cont ID  
Sent By tgordon Date 2006-02-15 Time 10:06 Rev Time 0.35
Received By tgordon Date 2006-02-15 Time 10:06 Sent To P
Notes
2006-02-15 00:00:00*** DENIED ***
 1) MECHANICAL PLANS WERE NOT RESUBMITTED
 WITH REVISED PLANS.
  
 2) PLEASE SUBMIT MECHANICAL PLANS WITH
 A/C EQUIPMENT LISTING ON THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By tgordon Date 2005-10-11 Time 08:36 Rev Time 0.20
Received By tgordon Date 2005-10-11 Time 08:36 Sent To B
Notes
2005-10-11 00:00:00*** DENIED ***
 1) NEED SPECIFICATIONS AND CUT SHEETS
 FOR GAS FIRE PLACE, AND COMBUSTION AIR
 CALCULATIONS.
 2) NEED SPECIFICATIONS FOR GAS BBQ GRILL
 IN COVERED LANAI.
 3) NEED MECHANICAL EQUIPMENT (A/C) LIST.
 4) NEED TO FILE A NOTICE OF
 COMMENCEMENT.
 IF YOU HAVE ANY QUESTIUNS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-30 Cont ID  
Sent By jleech Date 2007-07-30 Time 08:40 Rev Time 0.00
Received By jleech Date 2007-07-30 Time 08:29 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-09 Cont ID  
Sent By jleech Date 2007-07-09 Time 10:43 Rev Time 0.00
Received By jleech Date 2007-07-09 Time 10:43 Sent To B
Notes
2007-07-09 10:53:49DENIED;
 SANITARY RISER DIAGRAM DOES NOT MEET CODE.
 1. AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO BE 3".
 SECTION 406.3
 2. LUNDRY TUB BRANCH TO BE ABOVE DISCHARGE OF W/M.
 SECTION 706.3
 3. BATHROOM 3 TUB NOT VENTED.
 4. BIDET MISSING FROM RISER DIAGRAM BUT SHOWN ON FLOOR
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-15 Cont ID  
Sent By jleech Date 2006-02-15 Time 14:02 Rev Time 0.33
Received By jleech Date 2006-02-15 Time 14:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-08 Cont ID  
Sent By jleech Date 2005-10-08 Time 10:44 Rev Time 0.50
Received By jleech Date 2005-10-08 Time 10:44 Sent To M
Notes
2005-10-08 00:00:00DENIED;
 1.RISER DIAGRAM PAGE A-6;
 BATHROOM #4 TUB NOT VENTED.
 BATHROOM #2 TUB NOT VENTED.
 MASTER BATHROOM W/C NOT VENTED
 TO CODE FBC-2001 PLUMBING TABLE
 909.3 3" PIPE TO BE USED AFTER LAV.
 2.PLUMBING NOTE # 8; IS A RECIRCULATION
 SYSTEM TO BE USED? IF NOT PLEASE DELETE
 NOTE. IF A RECIRC. IS TO BE USED NOTE IN
 ON PAGE A-1 WITH WATER HEATER SIZE, ALSO
 AND A 110 OUTLET ON ELECTRICAL PAGE E-1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By choops Date 2008-06-27 Time 11:30 Rev Time 0.00
Received By choops Date 2008-06-27 Time 11:30 Sent To PC
Notes
2008-06-27 11:35:08***APPROVED - LANDSCAPE PLAN SUBMITTAL***
  
 PROVISOS:
 1)PLANT MATERIALS USED SHALL BE EQUAL TO OR BETTER
 THAN FLORIDA DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY
 GRADE STANDARD.
  
 2)THE REQUIRED IRRIGATION SYSTEM SHALL BE INSTALLED
 IN BOTH THE YARD AND SWALE/PARKWAY (IF APPLICABLE)
 AREAS.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By mmclean Date 2006-02-10 Time 18:20 Rev Time 0.00
Received By mmclean Date 2006-02-10 Time 18:20 Sent To I
Notes
2006-02-10 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE, WALL, GATE, PIERS, WITH EASEMENT
 APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.
  
 STRUCTURE WILL BE BUILT ACCORDING TO THE
 HEIGHT REQUIRMENT OF ZONING CODE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By mmclean Date 2005-10-06 Time 10:53 Rev Time 0.00
Received By mmclean Date 2005-10-06 Time 10:53 Sent To I
Notes
2005-10-06 00:00:00DENIED,
 1. NEED TO REDUCE THE HEIGHT OF
 STRUCTURE BY 1-2FT TO MEET THE HEIGHT
 REQUIREMENT
 OF 30FT + 10%= 33FT.
  
 ****************************************
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE, WALL, GATE, PIERS, WITH EASEMENT
 APPROVAL FROM CITY OF WEST PALM BEACH
 UTILITY DEPT.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720