| 2005-10-31 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05091394 |
| | ADD: 1801 S FLAGLER DR # 1209 |
| | CONT: AAA ALUMINUM DOORS & WINDOWS |
| | TEL: (561)533-9869 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | *** BOTH SEETS OF ENGINEERING MUST BE |
| | SIGNED & SEALED BY THE ENGINEER OF |
| | RECORD.61G15-23.002 / 471.025(1) |
| | |
| | 2)THE MIAMI-DADE REPORT SUBMITTED, PGT |
| | SLIDING GLASS DOOR REPORT WILL REQUIRE |
| | THE CONTRACTOR TO SELECT AND HIGHLIGHT |
| | WHICH GLASS TYPE WILL BE INSTALLED, |
| | PANEL WIDTH AND HEIGHT WITH THE |
| | ASSOCIATED POSITIVE & NEGATIVE PRESSURE. |
| | |
| | 3) THE FLORIDA COVERSHEET FL 239-R2 TIES |
| | TO A MIAMI-DADE REPORT, SHEET 2 OF THE |
| | FL REPORT LIST (6) MIAMI NOAS THAT ARE |
| | ASSOCIATED WITH THE COVER SHEET BUT NONE |
| | WERE SUBMITTED. A FENESTRATION TESTING |
| | REPORT WAS SUBMITTED. |
| | EITHER SUBMIT THE MIAMI NOA THAT |
| | TIES TO THE FLORIDA COVERSHEET OR SUBMIT |
| | THE FENESTRATION REPORT FOR LOCAL |
| | PRODUCT APPROVAL WITH THE REQUIRED THIRD |
| | PARTY QUALITY ASSURANCE ENTITY LISTED |
| | WITH THE STATE. |
| | WITHOUT THE PROPER REPORTS THE DESIGN |
| | PRESSURES CAN NOT BE DETERMINED, ONCE |
| | THE CORRECT PRODUCT APPROVAL ARE |
| | SUBMITTED THEY WILL BE REVIEWED FOR CODE |
| | COMPLIANCE. |
| | |
| | 4) THE SAME HOLDS TRUE FOR MULLIONS, NO |
| | REPORT (NOA) WAS SUBMITTED, ONLY THE FL |
| | COVERSHEET. |
| | 1707.4.5.1 MULLIONS OCCURRING |
| | BETWEEN INDIVIDUAL WINDOW AND GLASS |
| | DOOR ASSEMBLIES. TESTING REPORTS ARE |
| | REQUIRED BY AN APPROVED TESTING |
| | LABORATORY OR BE ENGINEERED. |
| | 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| | ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| | APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| | TO THE ROUGH OPENING SUBTRATE. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |