Plan Review Details - Permit 05091327
Plan Review Stops For Permit 05091327
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By lursu Date 2006-05-03 Time 11:39 Rev Time 0.00
Received By lursu Date 2006-04-25 Time 11:39 Sent To  
Notes
2006-05-03 00:00:00ADDRESS IS CORRECT AS 550 N QUADRILLE
 BLVD.THE UNITY OF TITLE WAS RECEIVED ON
 APRIL 7,2006 FOR ALL THE LOTS INSIDE
 PARCEL,74434321060150010.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2005-10-03 Cont ID  
Sent By jhiggins Date 2005-10-03 Time 15:52 Rev Time 0.00
Received By jhiggins Date 2005-10-03 Time 15:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-05-23 Cont ID  
Sent By shill Date 2006-05-23 Time 14:35 Rev Time 0.00
Received By shill Date 2006-05-23 Time 10:58 Sent To  
Notes
2006-05-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE NOC IN THE PACKAGE IS
 ACCEPTABLE BUT IS REQUIRED TO BE
 RECORDED WITH THE CLERK OF COURTS,
 FS713.13.
  
 2.)THIS WILL BE ISSUED AS AN AT-RISK
 PERMIT.
  
 3.)THE THRESHOLD INSPECTION PLAN DOES
 NOT INCLUDE ALL INSPECTIONS REQUIRED BY
 FBC*109.FOR INSTANCE, INSULATION AND
 ROOF.PLEASE REVISE.
  
 4.)FOUNDATION PERMIT CANNOT BE ISSUED
 UNTIL THE BUILDING PERMIT HAS BEEN
 APPLIED FOR, FBC104.4.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-04-20 Cont ID  
Sent By shill Date 2006-04-20 Time 18:24 Rev Time 0.00
Received By shill Date 2006-04-20 Time 17:44 Sent To  
Notes
2006-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 SECOND REVIEW - NOTE THAT THE NOC MUST
 BE SIGNED BY THE OWNER, WASSERMAN REAL
 ESTATE CAPITAL.
  
 FOURTH REVIEW - THE OLD SIGNATURE HAS
 BEEN CROSSED OFF AS WELL AS THE
 INFORMATION "PREPARED BY".THERE IS A
 NEW SIGNATURE AND NEW INFORMATION IN THE
 "PREPARED BY" SECTION.THIS IS NOT
 ACCEPTABLE FOR A LEGAL DOCUMENT.THE
 OWNER IS TO SIGN THE NOC AND HIS
 SIGNATURE IS TO BE NOTARIZED.THE NEW
 DOCUMENT IS TO BE RECORDED.IF YOU
 DISAGREE AND FEEL THAT THIS IS AN
 ACCEPTABLE LEGAL DOCUMENT, PLEASE
 PROVIDE A LETTER FROM THE ATTORNEY FOR
 THE PROJECT (RON KOLLINS) STATING SUCH.
  
 2-3.) ADDRESSED.PLEASE KEEP THE IMPACT
 FEE RECEIPT AND THE THRESHHOLD
 INSPECTION PLAN IN THE PACKAGE.
  
 4.)THE ORIGINAL PACKAGE WAS NOT A PART
 OF THE RESUBMITTAL.THE PLANS, SURVEY,
 PERMIT APPLICATION, ETC. ARE REQUIRED
 FOR PERMIT ISSUANCE.A COMPLETE REVIEW
 WAS NOT PERFORMED AS SOME NECESSARY
 INFORMATION IS IN THE PLANS.IF THE
 PLANS ARE SUBMITTED WITH CHANGES NOT
 SHOWN ON THE FIRST REVIEW (OTHER THAN
 THE REVISED S-1.1).
  
 (SECOND REVIEW) THE ORIGINAL PERMIT
 APPLICATION WITH THE
 CONTRACTOR SIGNATURE ON THE BACK IS NOT
 IN THE PACKAGE.ONLY A PHOTOCOPY OF THE
 FRONT OF THE APPLICATION WAS PROVIDED.
 A PERMIT APPLICATION IS REEQUIRED BY
 FLORIDA STATUTE FOR PERMIT ISSUANCE.
  
 (THIRD REVIEW) THE ORIGINAL PACKAGE IS
 STILL NOT A PART OF THE SUBMITTAL.
  
 (FOURTH REVIEW) THE PACKAGE WHICH WAS
 NOT IN THE PREVIOUS REVIEWS IS NOW IN
 THE PERMIT PACKAGE. IT CONTAINS A NEW
 STRUCTURAL SHEET.THIS SHEET IS TO BE
 PUT INTO THE PLAN AND THE OLD SHEET
 REMOVED.THE OLD SHEET IS TO BE MARKED
 VOID AND SUBMITTED SEPARATELY FOR
 REFERENCE.S1.1.
  
 5.)FBC*109.3.6.1, SPECIAL INSPECTOR
 REQUIRED FOR THRESHOLD BUILDINGS. ONE
 COPY OF THE THRESHOLD INSPECTION PLAN
 SUBMITTED HAS BEEN FORWARDED TO KEN
 CONRAD, 561-805-6666.APPROVAL OF THE
 PLAN AND AGREEMENT SIGNED BY ALL PARTIES
 REQUIRED PRIOR TO PERMIT ISSUANCE.
  
 PROVIDE A COPY OF THE SIGNED AGREEMENT.
 PLAN IS IN THE PACKAGE.
  
 6.)ADDRESSED.
  
 7.)FROM PREVIOUS REVIEW, THE SOILS
 REPORT CONFLICTS WITH THE
 STRUCTURALS.THERE IS A RECOMMENDATION
 FOR AUGERPILES, NONE SHOWN ON THE PLAN.
 THE ENGINEER RESPONDED WITH A LETTER
 INDICATING THAT THE AUGERPILES ARE NOT
 NEEDED DUE TO THE GROUND FLOOR
 ELEVATION.HOWEVER, THE STRUCTURAL
 DESIGN IS STILL IN CONFLICT WITH THE
 SOILS REPORT.PLEASE HAVE THE SOILS
 ENGINEER REVISE HIS SOILS RECOMMENDATION
 OR PROVIDE A LETTER OF CLARIFICATION AS
 DISCUSSED.THREE ORIGINAL SIGNED,
 SEALED COPIES REQUIRED.
  
 THE LETTER FROM THE SOILS ENGINEER
 ADDRESSING THE COMMENT IS IN THE PACKAGE
 BUT THE SOILS REPORT IS NOT.REQUIRED
 FOR PERMIT ISSUANCE FBC1804.2.2.
  
 (FOURTH REVIEW)THERE ARE SEVEN SOILS
 REPORTS AND TWO CLARIFICATION LETTERS
 FROM THE SOILS ENGINEER IN THE PACKAGE.
 THE SOILS REPORTS HAVE DIFFERENT DATES.
 THERE DOES NOT APPEAR TO BE CHANGES.
 SUBMIT ONLY THREE FOR REVIEW, AND THE
 THREE SHOULD BE THE SAME.THREE
 CLARIFICATION LETTERS REQUIRED.
  
 8.) THE APPLICATION STATES THAT
 UNDERGROUND UTILITES, MEP AND FIRE ALARM
 RISERS ARE UNDER A SEPARATE PERMIT
 APPLICATION.THIS PERMIT WILL BE ISSUED
 WITH A PROVISO THAT SEPARATE PERMITS
 WILL BE OBTAINED.
  
 9.) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS
 PROCEEDING AT HIS/HER OWN RISK AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.
  
 10.)ADDRESSED; PLEASE KEEP THE
 RECORDED COPY OF THE UNITY OF TITLE IN
 THE PACKAGE.
  
 11.)NEW COMMENT - YOU MUST APPLY FOR
 THE BUILDING PERMIT BEFORE A FOUNDATION
 PERMIT CAN BE ISSUED, FBC*104.4.5.
  
 12.)ADDITIONAL FEES DUE, SEE ATTACHED
 (3RD RESUB).
  
 13.)YOUR SIGN PERMIT APPLICATION AND
 PLANS WERE INSIDE OF THIS PACKAGE.I
 HAVE CALLED THE PERSON ON THAT
 APPLICATION AND INFORMED HIM THAT IT IS
 AT THE FRONT COUNTER.THE APPLICATION
 AND PLANS FOR THE BANNER SIGN WERE
 REMOVED AND SENT TO THE FRONT COUNTER
 SEPARATELY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-24 Cont ID  
Sent By shill Date 2006-03-24 Time 08:53 Rev Time 1.50
Received By shill Date 2006-03-24 Time 07:56 Sent To  
Notes
2006-03-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 NOTE THAT THE NOC MUST BE SIGNED BY THE
 OWNER, WASSERMAN REAL ESTATE CAPITAL.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 THIS HAS BEEN ADDRESSED.PLEASE KEEP
 THE IMPACT FEE RECEIPT IN THE PACKAGE.
  
 3.)A CERTIFICATE OF AUTHORIZATION
 NUMBER REQUIRED ON THE CALCULATION COVER
 PAGE AND THRESHOLD INSPECTION PLAN,
 FAC61G15-23.002 (ONM&J).
  
 THE PLAN IS NOT IN THE PACKAGE.PENDING
 MEETING 3/24/2006.
  
 4.)THE ORIGINAL PACKAGE WAS NOT A PART
 OF THE RESUBMITTAL.THE PLANS, SURVEY,
 PERMIT APPLICATION, ETC. ARE REQUIRED
 FOR PERMIT ISSUANCE.A COMPLETE REVIEW
 WAS NOT PERFORMED AS SOME NECESSARY
 INFORMATION IS IN THE PLANS.IF THE
 PLANS ARE SUBMITTED WITH CHANGES NOT
 SHOWN ON THE FIRST REVIEW (OTHER THAN
 THE REVISED S-1.1).
  
 THE ORIGINAL PERMIT APPLICATION WITH THE
 CONTRACTOR SIGNATURE ON THE BACK IS NOT
 IN THE PACKAGE.ONLY A PHOTOCOPY OF THE
 FRONT OF THE APPLICATION WAS PROVIDED.
 A PERMIT APPLICATION IS REEQUIRED BY
 FLORIDA STATUTE FOR PERMIT ISSUANCE.
  
 THE ORIGINAL PACKAGE IS STILL NOT A PART
 OF THE SUBMITTAL.
  
 5.)FBC*109.3.6.1, SPECIAL INSPECTOR
 REQUIRED FOR THRESHOLD BUILDINGS. ONE
 COPY OF THE THRESHOLD INSPECTION PLAN
 SUBMITTED HAS BEEN FORWARDED TO KEN
 CONRAD, 561-805-6666.APPROVAL OF THE
 PLAN AND AGREEMENT SIGNED BY ALL PARTIES
 REQUIRED PRIOR TO PERMIT ISSUANCE.
  
 PENDING.
  
 6.)A PRECONSTRUCTION MEETING INVOLVING
 THE OWNER, THRESHOLD INSPECTOR, JOB
 INSPECTOR, CONTRACTOR, AND ENGINEER WILL
 BE REQUIRED.PLEASE CONTACT KEN CONRAD,
 561-805-6666.
  
 PENDING.
  
 6.)PLEASE SEAL THE THRESHOLD
 INSPECTION PLANS, FAC61G15-23.002.
  
 PENDING.
  
 7.)FROM PREVIOUS REVIEW, THE SOILS
 REPORT CONFLICTS WITH THE
 STRUCTURALS.THERE IS A RECOMMENDATION
 FOR AUGERPILES, NONE SHOWN ON THE PLAN.
 THE ENGINEER RESPONDED WITH A LETTER
 INDICATING THAT THE AUGERPILES ARE NOT
 NEEDED DUE TO THE GROUND FLOOR
 ELEVATION.HOWEVER, THE STRUCTURAL
 DESIGN IS STILL IN CONFLICT WITH THE
 SOILS REPORT.PLEASE HAVE THE SOILS
 ENGINEER REVISE HIS SOILS RECOMMENDATION
 OR PROVIDE A LETTER OF CLARIFICATION AS
 DISCUSSED.THREE ORIGINAL SIGNED,
 SEALED COPIES REQUIRED.
  
 THE LETTER FROM THE SOILS ENGINEER
 ADDRESSING THE COMMENT IS IN THE PACKAGE
 BUT THE SOILS REPORT IS NOT.REQUIRED
 FOR PERMIT ISSUANCE FBC1804.2.2.
  
 8.) THE APPLICATION STATES THAT
 UNDERGROUND UTILITES, MEP AND FIRE ALARM
 RISERS ARE UNDER A SEPARATE PERMIT
 APPLICATION.THIS PERMIT WILL BE ISSUED
 WITH A PROVISO THAT SEPARATE PERMITS
 WILL BE OBTAINED.
  
 9.) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS
 PROCEEDING AT HIS/HER OWN RISK AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.
  
 10.)SEE THE FIRST LIST IN REGARDS TO A
 RECORDED UNITY OF TITLE.THE DOCUMENT
 PROVIDED IS NOT A RECORDED COPY AND I
 WAS UNABLE TO LOCATE IT ON THE CLERK?S
 OFFICE WEBSITE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By shill Date 2005-12-14 Time 15:08 Rev Time 2.00
Received By shill Date 2005-12-14 Time 13:46 Sent To  
Notes
2005-12-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)A CERTIFICATE OF AUTHORIZATION
 NUMBER REQUIRED ON THE CALCULATION COVER
 PAGE AND THRESHOLD INSPECTION PLAN,
 FAC61G15-23.002 (ONM&J).
  
 4.)THE ORIGINAL PACKAGE WAS NOT A PART
 OF THE RESUBMITTAL.THE PLANS, SURVEY,
 PERMIT APPLICATION, ETC. ARE REQUIRED
 FOR PERMIT ISSUANCE.A COMPLETE REVIEW
 WAS NOT PERFORMED AS SOME NECESSARY
 INFORMATION IS IN THE PLANS.IF THE
 PLANS ARE SUBMITTED WITH CHANGES NOT
 SHOWN ON THE FIRST REVIEW (OTHER THAN
 THE REVISED S-1.1).
  
 5.)FBC*109.3.6.1, SPECIAL INSPECTOR
 REQUIRED FOR THRESHOLD BUILDINGS. ONE
 COPY OF THE THRESHOLD INSPECTION PLAN
 SUBMITTED HAS BEEN FORWARDED TO KEN
 CONRAD, 561-805-6666.APPROVAL OF THE
 PLAN AND AGREEMENT SIGNED BY ALL PARTIES
 REQUIRED PRIOR TO PERMIT ISSUANCE.
  
 6.)A PRECONSTRUCTION MEETING INVOLVING
 THE OWNER, THRESHOLD INSPECTOR, JOB
 INSPECTOR, CONTRACTOR, AND ENGINEER WILL
 BE REQUIRED.PLEASE CONTACT KEN CONRAD,
 561-805-6666.
  
 6.)PLEASE SEAL THE THRESHOLD
 INSPECTION PLANS, FAC61G15-23.002.
  
 7.)FROM PREVIOUS REVIEW, THE SOILS
 REPORT CONFLICTS WITH THE
 STRUCTURALS.THERE IS A RECOMMENDATION
 FOR AUGERPILES, NONE SHOWN ON THE PLAN.
 THE ENGINEER RESPONDED WITH A LETTER
 INDICATING THAT THE AUGERPILES ARE NOT
 NEEDED DUE TO THE GROUND FLOOR
 ELEVATION.HOWEVER, THE STRUCTURAL
 DESIGN IS STILL IN CONFLICT WITH THE
 SOILS REPORT.PLEASE HAVE THE SOILS
 ENGINEER REVISE HIS SOILS RECOMMENDATION
 OR PROVIDE A LETTER OF CLARIFICATION AS
 DISCUSSED.THREE ORIGINAL SIGNED,
 SEALED COPIES REQUIRED.
  
 8.) THE APPLICATION STATES THAT
 UNDERGROUND UTILITES, MEP AND FIRE ALARM
 RISERS ARE UNDER A SEPARATE PERMIT
 APPLICATION.THIS PERMIT WILL BE ISSUED
 WITH A PROVISO THAT SEPARATE PERMITS
 WILL BE OBTAINED.
  
 9.) FBC* 104.4.5 SPECIAL FOUNDATION
 PERMIT. THE BUILDING OFFICIAL MAY, AT
 HIS DISCRETION, ISSUE A SPECIAL PERMIT
 FOR THE FOUNDATION ONLY, UPON WRITTEN
 REQUEST BY THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH SPECIAL PERMIT IS
 PROCEEDING AT HIS/HER OWN RISK AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE
 REQUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By shill Date 2005-11-29 Time 13:15 Rev Time 2.00
Received By shill Date 2005-11-23 Time 16:58 Sent To PC
Notes
2005-11-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)PROVIDE A COPY OF THE RECORDED
 UNITY OF TITLE.
  
 4.)A CERTIFICATE OF AUTHORIZATION
 NUMBER REQUIRED ON THE SOILS REPORT,
 FAC61G15-23.002.
  
 5.)A0.2 AND S12.1 MAKE DESIGN
 REFERENCE TO FBC2001.SEE ATTACHED.
 PLEASE PROVIDE SIGNED, SEALED
 CALCULATIONS.
  
 6.)S-1.1, NOTES, DOES NOT PROVIDE A
 FFE NGVD.
  
 7.)FBC*109.3.6.1, SPECIAL INSPECTOR
 REQUIRED FOR THRESHOLD BUILDINGS.
 PLEASE SUBMIT AN INSPECTION PLAN AND
 CONTACT HAROLD PISKURA, 561-805-6711.
  
 8.)A PRECONSTRUCTION MEETING INVOLVING
 THE OWNER, THRESHOLD INSPECTOR, JOB
 INSPECTOR, CONTRACTOR, AND ENGINEER WILL
 BE REQUIRED.PLEASE CONTACT HAROLD
 PISKURA, 561-805-6711.
  
 9.)THE SOILS REPORT CONFLICTS WITH THE
 STRUCTURALS.THERE IS A RECOMMENDATION
 IS FOR AUGERPILES, NONE SHOWN ON THE
 PLAN.
  
 10.) THE APPLICATION STATES THAT
 UNDERGROUND UTILITES, MEP AND FIRE ALARM
 RISERS ARE UNDER A SEPARATE PERMIT
 APPLICATION.ENGINEERING APPROVAL
 REQUIRED PRIOR TO ISSUANCE OF THIS
 PERMIT.AT THIS TIME I AM UNABLE TO
 LOCATE AN APPLICATION FOR THE UTILITIES.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-19 Cont ID  
Sent By ptjomsto Date 2006-05-19 Time 17:02 Rev Time 0.00
Received By ptjomsto Date 2006-05-19 Time 17:02 Sent To  
Notes
2006-05-19 00:00:003RD RESUB GIVEN TO SAMANTHA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-20 Cont ID  
Sent By shill Date 2006-04-20 Time 17:43 Rev Time 0.00
Received By shill Date 2006-04-20 Time 17:43 Sent To B
Notes
2006-04-20 00:00:00TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-10 Cont ID  
Sent By shill Date 2005-12-10 Time 15:05 Rev Time 0.00
Received By shill Date 2005-12-10 Time 15:05 Sent To  
Notes
2005-12-10 00:00:00TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 08:53 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 08:53 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#60
2005-09-29 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-19 Cont ID  
Sent By mflis Date 2005-10-19 Time 09:25 Rev Time 0.00
Received By mflis Date 2005-10-19 Time 09:25 Sent To  
Notes
2005-10-19 00:00:00BUILDING FOUNDATION ONLY;
 LANDSCAPING PROVISIONS (ESP. QUADRILLE
 BLVD) SHOULD BE REVIEWED WITH RELEVANT
 SUBMITTALS: CURRENTLY DO NOT MATCH
 APPROVED PPRC. MF