| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} ALL DRAWINGS SHALL BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN. 104.2.1 FBC. |
| | IF A ARCHITECT OR THE ENGINEER WHO'S |
| | TITLE BLOCK APPEARS ON THE PLAN, COMPLY |
| | WITH ARTICLES 481 AND 471 RESPECTIVELY. |
| | |
| | 2} SUBMIT THE AIC CALCULATIONS FOR THE |
| | SERVICE AND INDICATE THE AIC RATING OF |
| | THE EQUIPMENT PER 110.9 & 10. |
| | |
| | 3}THE GROUNDING ELECTRODE SYSTEM NEEDS |
| | TO ORIGINATE FROM ONE POINT. THE RISER |
| | HAS TWO, ONE FROM THE METER AND ONE FROM |
| | THE PANEL. SEE 250.36(F) FOR LOCATION |
| | PERMITTED. |
| | |
| | 4} THE DINING ROOM CIRCUIT MUST COMPLY |
| | WITH 210.52(B)(1), 20 AMP #12 WIRE, SEE |
| | CIRCUIT #1 ON THE PANEL SCHEDULE. |
| | |
| | 5} THE "JACUZZI TUB" MUST BE GFI |
| | PROTECTED PER 680.71. PLEASE INDICATE |
| | SAME ON PLANS. |
| | |
| | 6} PLEASE VERIFY THE WATER HEATER AT |
| | 2500 WATTS. SEE LOAD CALC. |
| | |
| | 7} THE PENINSULA RECEPTACLE(S) MUST |
| | COMPLY WITH 210.52(C)(3). |
| | |
| | 8} SMOKE DETECTORS ARE REQUIRED PER |
| | NFPA-72, AND 905.2 FBC. |
| | |