Plan Review Details - Permit 05091307
Plan Review Stops For Permit 05091307
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-11-14 Cont ID  
Sent By mjacobs Date 2005-11-14 Time 10:00 Rev Time 2.50
Received By mjacobs Date 2005-11-14 Time 07:38 Sent To PC
Notes
2006-01-23 00:00:00BUILDING PROVISO:
 TO BE IN PLACE AT C.O.:
  
 1) 424.2.17.1 OUTDOOR SWIMMING POOLS.
 OUTDOOR SWIMMING POOLS SHALL BE PROVIDED
 WITH A BARRIER COMPLYING WITH
 424.2.17.1.1 THROUGH 424.2.17.1.14.
  
 424.2.17.1.5 CHILD SAFETY BARRIER
 ASTM D5034 100 LB TENSILE STRNGTH
 ASTM D3787 150 LB BALL BURST
 STRENGTH
  
 2) 13-612.1.ABC.2.3.2 COVERS REQUIRED.
 SPAS AND HEATED SWIMMING POOLS SHALL BE
 EQUIPPED WITH A COVER DESIGNED TO
 MINIMIZE HEAT LOSS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By jleahy Date 2006-01-20 Time 22:01 Rev Time 0.30
Received By jleahy Date 2006-01-20 Time 22:01 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-13 Cont ID  
Sent By btrobaug Date 2005-10-13 Time 12:01 Rev Time 0.50
Received By btrobaug Date 2005-10-13 Time 10:03 Sent To P
Notes
2005-10-13 00:00:00IF THE "PANEL" SHOWN ON THE SCHEMATIC
 IS INSTALLED UNDER THIS PERMIT, PLEASE
 SUBMIT DETAILS FOR THE PANEL SHOWN ON
 THE SCHEMATIC, FEEDER AND CONDUIT SIZE
 AND TYPE, PANEL RATING AND OCP, PANEL
 SCHEDULE AND COMPUTED LOAD, AS A
 REVISION TO THIS PLAN , PRIOR TO CALLING
 FOR AN ELECTRICAL INSPECTION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 09:18 Sent To P
Notes
2006-01-09 00:00:00TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 14:58 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 14:58 Sent To Z
Notes
2005-12-16 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 15:45 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 15:45 Sent To E
Notes
2005-10-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 09:53 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 09:53 Sent To Z
Notes
2005-09-30 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 09:02 Rev Time 0.33
Received By jleech Date 2006-01-23 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-15 Cont ID  
Sent By jleech Date 2005-10-15 Time 14:04 Rev Time 0.75
Received By jleech Date 2005-10-15 Time 14:04 Sent To B
Notes
2005-10-15 00:00:00DENIED;
 1) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS.
 (DETAIL)LOCATION AND SIZE OF MAIN DRAIN
 VENTS NOT ON PLAN. (SHOW DETAIL)
 2) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) FBC-2001424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4) FBC-2001424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 5) FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA BLDG CODE, PLUMBING.THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL.SEC 424.2.8.2 FULL WAY VALVES
 SHALL BE INSTALLED TO INSURE PROPER
 FUNCTION OF THE FILTRATION AND PIPING
 SYSTEMS.SEC 424.2.8.3 WHERE CHECK
 VALVES ARE INSTALLED THEY SHALL BE OF
 THE SWING OR VERTICAL CHECK PATTERNS.
 SEC 424.2.8.4 COMBINATION VALVES SHALL
 REQUIRE APPROVAL OF THE ADMINISTRATIVE
 AUTHORITY PRIOR TO THEIR INSTALLATION.
 6) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 7)424.2.9 WATER SUPPLY, LOCAL ORD. #
 2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE. (ADD TO NOTES)
 8) 424.2.13.2 JOINTS AND CONNECTIONS,
 FBC-2001 PLUMBING SEC. 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 9) 424.2.14.2 WATER RETENTION, PROVIDE A
 POSITIVE MEANS OF RETAINING WATER IN
 HEATER WHEN PUMP IS OFF. (MANUFACTURE
 CUT SHEETS)
 10) 424.2.14.4 CONNECTIONS, ALL WATER
 HEATING EQUIPMENT SHALL BE INSTALLED
 WITH FLANGES OR UNION CONNECTIONS
 AJACENT TO HEATER. (ADD TO NOTES)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 07:02 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 07:02 Sent To I
Notes
2006-01-07 00:00:00NOTE: THE DECK CANNOT BE BUILT IN THE
 EASMENT IN REARE & SIDE.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By mmclean Date 2005-10-11 Time 11:51 Rev Time 0.00
Received By mmclean Date 2005-10-11 Time 11:51 Sent To I
Notes
2005-10-11 00:00:00DENIED,
 1. NEED TO PROVIDE TWO COPY OF CURRENT
 SURVEY, SHOWING THE POOL & DECK WITH
 SETBACKS FROM PROPERTY LINE.
 2. SITEPLAN PROVIDED IS INSUFFICIENT FOR
 A COMPLETE ZONING REVIEW.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720