Plan Review Details - Permit 05091299
Plan Review Stops For Permit 05091299
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-04 Time 11:31 Rev Time 1.75
Received By alange Date 2006-04-04 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-06 Cont ID  
Sent By alange Date 2006-03-06 Time 10:06 Rev Time 2.00
Received By alange Date 2006-03-06 Time 09:57 Sent To  
Notes
2006-03-06 00:00:00DENIED
  
 3.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 08:33 Rev Time 3.50
Received By alange Date 2005-12-13 Time 08:15 Sent To  
Notes
2005-12-13 00:00:00 
 DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SUBMIT TWO COMPLETE SETS OF PRODUCT
 APPROVALS WITH THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED TO EACH.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 PRODUCT APPROVALS ARE MISSING FOR
 HARDIE-PLANK SIDING AND LINTELS.
  
 4.SUBMIT DETAILS FOR SPIRAL STAIR
 CASES COMPLYING WITHFBC 1007.8.2.3
  
 5.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 REVISED AS FOLLOWS;
 6215SQ.FT X $76.96 = $478,306
 2158SQ.FT. X $41.60 = $89,772
 REVISED PERMIT VALUATION = $568,078
 SEE ATTACHED INVOICE.
  
 6.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS PER FBC 2309.6
  
 7.SHOW HOW ATTIC DRAFT STOPPING WILL
 COMPLY WITH FBC 2305.2.2
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 20:26 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 20:15 Sent To Z
Notes
2006-03-24 00:00:00PLANS STAMPED.
  
 POOL PANEL IS FUTURE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-24 Cont ID  
Sent By dpalmer Date 2006-02-24 Time 18:56 Rev Time 0.00
Received By dpalmer Date 2006-02-24 Time 13:51 Sent To M
Notes
2006-02-24 00:00:00********* UNSAT 2ND REVIEW **********
  
 ** PLEASE SEE SOMKE NOTES FROM PREVIOUS
 REVIEW WHICH STILL NEED TO BE ADDRESSED
 AND SOME NEW COMMENTS DUE TO INFORMATION
 ADDED OR CHANGED.
 PLEASE SEE NOTES BELOW WHICH ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO/ YES,PLEASE SEE SOME
 COMMENTS FOR RISER AND PANELS.
  
 **PLEASE PROVIDE MORE INFORMATION
 ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO
 ETC.215.5
 PLEASE SEE FOLLOWING COMMENTS.
  
 4)NOTE: NOTE #4 NO, PLEASE SEE RISER
 INDICATES PANEL "C" AS 100A'S, HOWEVER
 PANEL "C" IS SHOWN AS 200A'S?
  
 ** PLEASE SHOW AND IDENTIFY ALL
 PANELS, DISCONNECTS ETC ON PLANS.
 COULD NOT LOCATE DISCONNECT SHOWN ON
 RISER FOR PANEL "C" ON PLANS.
 COULD NOT LOCATE POOL PANEL?
 PLEASE SEE NEXT COMMENT.
  
 5)NOTE: NOTE #5 OK.
  
  
 6)NOTE: NOTE #6 NO? PLEASE SEE THE
 PANELS AT MAIN HOUSE SHOULD INDICATE
 MCB'S. (MAIN CIRCUIT BRKRS)
  
 **PLEASE SEE PANELS AT MAIN HOUSE
 SHALL INDICATE MAIN CIRCUIT BREAKER(S)
 (MCB) FOR DISCONNECTING MEANS AT MAIN
 HOUSE.225.31
 THE GROUNDING ELECTRODE ATTACHMENTS FROM
 PREVIOUS NOTE SHALL BE ATTACHED TO THESE
 PANELS.
  
 7)NOTE: NOTE #7, NO, PLEASE SEE THIS IS
 SHOWN AS 400A'S, HOWEVER THE MCB IS NOT
 SHOWN?
  
 **PLEASE SEE 400A METER/MAIN SHALL
 INDICATE 400A MCB. PLEASE SEE ONE 200A
 BRKR IN THIS PANEL IS SHOWN AS MAIN
 BREAKER??
 PLEASE ALSO SEE PANEL "C" IS NOT
 SHOWN/IDENTIFIED ON SCHEDULE FOR
 METER/MAIN.
 215.5
  
 8)NOTE: NOTE #8 OK,HOWEVER,
 PLEASE ALSO KNOW, SD'S ARE NOW SHOWN IN
 MANY LOCATIONS NOT REQUIRED, HOWEVER
 THEY ARE PERMITTED. PLEASE REVISE AT
 THIS TIME, IF OTHER LOCATIONS OTHER THAN
 WHAT IS REQUIRED ARE NOT GOING TO BE
 INSTALLED AS SHOWN? THIS IS ONLY A NOTE;
  
 ** PLEASE SEE PLANS FOR NUMEROUS
 SMOKE DETECTORS MISSING.
 PLEASE SEE NFPA-72 11.5.1.1 WHICH
 REQUIRES SD'S INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 RMS(THOSE WITH BATHS OR CLOSETS).
 PLEASE SEE SD'S REQUIRED ON ALL LEVELS
 OF A MULTI-LEVEL DWELLING.
 PLEASE SEE SD IN MASTER BEDRM SAHLL BE
 REQUIRED AT FIRST FLR AND SECOND FLR.
 SINCE THIS IS AN OPEN RM, SD FOR FIRST
 FLR SHALL BE WALL MOUNTED IN THE
 VICINITY OF STAIRS LEADING TO FLR ABOVE.
 PLEASE ALSO SEE AREA FOR OTHER STAIRS
 LEADING TO FLR ABOVE. MAIN HOUSE,
 DETACHED CABANA.
 PLEASE SEE SD'S HAVE BEEN REDLINED ON
 PLANS FOR ALL LOCATIONS REQUIRED.
  
 9)NOTE: NOTE #9 NO, PLEASE SEE ALL
 RECEPTS IN GARAGE SHALL BE GFI UNLESS
 FEEDING A DEDICATED CIRCUIT. PLEASE ALSO
 SEE NOTE WITH RESPECT TO THE
 WASHER/DRYER RECEPTS
  
 **PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE TO BE
 GFI.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE:NOTE #11 NO, PLEASE SEE
 REDLINED PLANS FOR KITCHEN AREA IN MAIN
 HOUSE. PLEASE ALSO SEE NOTE WITH RESPECT
 TO ITEMS ON PLANS WHICH DO NOT SHOW
 RECEPTS.
  
 **PLEASE SEE NUMEROUS GFI RECEPTS
 MISSING ALONG KITCHEN COUNTERSPACES.
 210.8A6, 210.52C1-5
 PLEASE SEE A GFI WILL BE REQUIRED ON 2ND
 FLR "NOOK" AREA OF CABANA ALSO ABOVE
 DISHWASHER.
  
 12)NOTE: NOTE #12, NO/YES, PLEASE SEE
 MOST ALL RECEPTS ADDED, HOWEVER PLEASE
 STILL SEE WALL SPACE NEXT TO FIREPLACE
 AS NOTED ON PERVIOUS REVIEW.
  
 **PLEASE SEE NUMEROUS MISSING
 RECEPTS REQUIRED PER 210.52. 2', 6', 12'
 OF WALL SPACES.
 PLEASE SEE RAIL AREA AT 2ND FLR IS
 CONSIDERED WALL SPACE AND FLR RECEPTS
 WILL BE REQUIRED PER 210.52
 PLEASE CLARIFY AREA T SUNK-IN LIV RM
 NEXT TO FIRE PLACE. ?? WALL SPACE??
 PLEASE SEE MANY OF THE ABOVE HAVE BEEN
 REDLINED ON PLANS WHERE REQUIRED. MANY
 OF MISSING.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 OK.
  
  
 16)NOTE: NOTE #16 OK.P
  
 17)NOTE: NOTE #17 OK.
  
  
 18)NOTE: NOTE #18 OK.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE PANEL
 SCHEDULE STILL DOES NOT LOST THIS
 DEDICATED CIRCUIT??
  
 ** PLEASE SEE SYMBOL FOR JACUZZI
 TUB/WHIRLPOOL TUB IS BEING SHOWN AS
 220V, HOWEVER THIS IS NOT LOCATED ON
 PANEL SCHEDULE(S) OR LOAD CALCS??
 PLEASE SEE 680.71, FOR REQUIRED GFI
 PROTECTION.
 PLEASE ALSO ADJUST LOAD CALCS.
  
 20)NOTE: NOTE #20, NO/YES, PLEASE SEE
 THESE CIRCUITS WERE MOVED TO THE
 DETACHED BLDG PANEL "C" HOWEVER , PLEASE
 SEE LOAD SHOWN INDCIATES 2400VA ON A
 1-POLE 20A CIRCUIT?? PLEASE KNOW, THIS
 WELL EXCEEDS RATING OF THIS CIRCUIT,
 PELASE VERIFY LOAD/HP RATING OF THESE
 MOTORS AS 2400VA IS NOT TYPICAL?
 PLEASE KNOW, MAX VA ON A 20A CIRCUIT IS
 1920VA.
  
 ** PLEASE SEE A GDO IS SHOWN ON
 LOAD CALCS FOR PANELS LOCATED ON MAIN
 HOUSE,HOWEVER NO GDO COULD BE LOCATED AT
 MAIN HOUSE?
 PLEASE SEE DETACHED "GARAGE" DOES NOT
 INDICATE OR SHOW A GARAGE DOOR OR GDO.
 PLEASE INCLUDE IN PANEL "C" , LOADS ETC.
 215.5
  
 21)NOTE: NOTE #21 OK.
  
 22)NOTE: NOTE #22 OK. SEE BELOW.
  
 23)NOTE: NOTE #23 OK.
  
  
 24)NOTE: NOTE #24 NO, PLEASE SEE NOW
 THAT LOADS AND OCP HAS BEEN REVISED,
 PLEASE SEE 60A OCP ON #8 AWG.
 PLEASE ADJUST REDLINED PLANS,
 240.4,310.16
  
  
 **PLEASE SEE PREVIOUS NOTE, ONCE
 A/C UNITS HAVE BEEN CORRELATED, PLEASE
 SEE 424.3B FOR MIN OCP OF 125% OF HEAT
 KW LOAD. PLEASE ALSO NOTE, MAX OCP OF
 150%
 PLEASE ADJUST OCP AND CONDUCTORS AS
 LISTED ON PLANS.
 PLEASE SEE LOAD CALCS AND KW RATING
 SHOWN.
  
 25)NOTE: NOTE #25, NO, PLEASE SEE PLANS
 STILL MISSING POOL PANEL SCHEDULE/LOADS.
  
 ** PLEASE PROVIDE LOADS ON EACH
 PANEL.PLEASE SEE MISSING POOL PANEL,
 PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN
 CALCS, HOWEVER THESE LOADS CAN NOT BE
 VERIFIED.
 PLEASE KNOW, ALL CONTINUOUS LOADS SHALL
 BE SHOWN AT 125%. (3 OR MORE HRS).
 POOL PUMP, HEAT PUMPS?
 215.3,230.42 ETC.
  
 26)NOTE: NOTE #26 OK
  
 27)NOTE:NOTE #27, NO, PLEASE SEE MANY
 ITEMS ON PLANS WHICH DO NOT CORRELATE
 WIHT PANELS, ETC. PLEASE SEE DISP, WINE
 FRIG, TRASH COMP ETC WHICH ARE ON PLANS,
 WITH OUT ANY ELECTRICAL DEVICES TO FEED
 THESE APPLIANCES??
 PLEASE ALSO SEE PLANS INDICATE TWO
 DISHWASHERS, ONLY ONE ONPANEL
 SCHEDULE? AND NO DEVICES ON PLANS?
 PLEASE KNOW, AS FOR LOADS OF DEDICATED
 CIRCUITS, NO MORE THAN 750VA OF
 MOTOR/FRIG LOADS ARE PERMITTED ON OTHER
 SMALL APPL CIRCUITS.
  
 **PLEASE CORRELATE ALL DEDICATED
 CIRCUITS WHICH ARE SHOWN ON PLANS,
 HOWEVER NOT ALL ARE LISTED ON PANEL
 SCHEDULES.
 COULD NOT LOCATE ELEC OVEN ON PLANS?
 PLEASE MOVE ANY 220V OUTLETS FOR
 OVENS/RANGES DIRECTLY BEHIND UNITS.
 PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR
 PANEL SCHEDULE ONLY SHOWS ONE??
 PLEASE SEE ZONING NOTES.
 PLEASE SEE # OF ICE MAKERS LISTED ON
 LOAD CALCS, YET ONLY ONE DEDICATED
 CIRCUIT IS SHOWN ON PANEL SCHEDULE?
 PLEASE CORRELATE OTHERS.
  
 28)NOTE: NOTE #28 OK, 220V RECEPT
 REMOVED. PLEASE BE AWARE OF USE OF THE
 120A RECEPT SHOWN NEXT TO FRIG.
  
 29)NOTE: NOTE #29OK.
  
  
 30)NOTE: NOTE #30 OK/NO, PLEASE SEE PAT
 OF THIS NOTE DONE, PLEASE SEE MAIN HOSUE
 WHICH STILL SHOWS A MICRO ON PANEL
 SCHEDULE, BUT NO ON PLANS/
  
 **PLEASE SEE DISHWASHER IS SHOWN
 ON PLANS FOR CABANA, HOWEVER PANEL
 SCHEDULE AND LOAD CALCS DO NOT INDICATE
 THE SAME.??
 PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL
 SCHEDULE, BUT NOT ON PLANS FOR DEDICATED
 CIRCUIT??
  
 31)NOTE: NOTE #31 PLEASE SEE AREA OF W/D
 AT DETACHED GARAGE, WHICH SEEMS TO
 INDICATE A DEDICATED RECEPT FOR A
 WASHER? HOWEVER PANEL SCHEDULE MENTIONS
 DRYER ONLY AND PLANS SHOWS WHAT APPEARS
 TO BE A STACKABLE UNIT??
 PLEASE KNOW, IF THERE IS A WASHER, THEN
 THIS WOULD NOT BE A GFI FOR A DEDICATED
 CIRCUIT.
 PLEASE ALSO SEE THIS IN MAIN HOUSE
 LANUDRY RM.
 PLEASE ADJUST PANEL SCHEDULE AND ANY
 LOADS ACCORDINGLY IF NEEDED.
  
 ** PLEASE SEE GFI SHOWN ON
 COUNTERSPACE IN DETACHED CABANA, IS
 SHOWN AS "WP" ?? THIS IS PERMITTED,
 HOWEVER NOT REQUIRED.
 210.8A6
  
 32)NOTE: NOTE #32 OK. THESE WERE REMOVED
  
  
 ************************
  
 ADDITIONAL NEW NOTES,
  
 33)NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO PLANS REVIEWS AND REPEAT
 COMMENTS. PLEASE KNOW THIS IS ONLY
 NOTICE GIVEN AT THIS TIME.
  
 34)NOTE: PLEASE SEE RISER WHICH IS
 MISSING THE SIZE OF THE FEEDERS TO SUB
 PANELS "C" AND "POOL PANEL". PLEASE SEE
 RISER SHOWS 3#(?) THIS IS BLANK?
 240.4,310.16,215.5
 PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED ON PLANS AT LOCATIONS
 OF NOTES.
  
 35)NOTE: PLEASE SEE SOME NEW NOTES WERE
 PART OF THE NOTES ABOVE 1-32
  
 ** PLEASE SEE ONE SET OF PLANS ARE
 REDLINED FOR MOST OF THE ABOVE COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE SET OF
 OLD/VOIDED SHEETSREQUIRED FOR
 REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By dpalmer Date 2005-10-06 Time 18:16 Rev Time 2.00
Received By dpalmer Date 2005-10-06 Time 17:20 Sent To M
Notes
2005-10-06 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SEE BUILDING REVIEW
 COMMENTS FOR ADJUSTED VALUE FOR SCOPE OF
 WORK.
 104.6.5, FBC, CITY-WIDE ADMINISTRATIVE
 CODE.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATING FOR MAIN WAS SUBMITTED,
 HOWEVER PLEASE INDICATE PANELS ALSO.
 PLEASE SEE FOLLWING COMMENT.
  
 3)NOTE: PLEASE PROVIDE MORE INFORMATION
 ON PANELS. TYPE, VOLTAGE, ETC. MCB, MLO
 ETC.215.5
 PLEASE SEE FOLLOWING COMMENTS.
  
 4)NOTE: PLEASE SHOW AND IDENTIFY ALL
 PANELS, DISCONNECTS ETC ON PLANS.
 COULD NOT LOCATE DISCONNECT SHOWN ON
 RISER FOR PANEL "C" ON PLANS.
 COULD NOT LOCATE POOL PANEL?
 PLEASE SEE NEXT COMMENT.
  
 5)NOTE: PLEASE SEE PLANS WHICH INDICATE
 METER/MAIN AT DETACHED BLDG, HOWEVER
 PANEL "C" SEEMS TO BE SHOWN WITH THE
 GROUNDING ELECTRODE SYSTEM WHICH IS
 ACTUALLY REQUIRED FOR PANELS "A" AND "B"
 AT MAIN HOUSE.
 250.32
  
 6)NOTE: PLEASE SEE PANELS AT MAIN HOUSE
 SHALL INDICATE MAIN CIRCUIT BREAKER(S)
 (MCB) FOR DISCONNECTING MEANS AT MAIN
 HOUSE.225.31
 THE GROUNDING ELECTRODE ATTACHMENTS FROM
 PREVIOUS NOTE SHALL BE ATTACHED TO THESE
 PANELS.
  
 7)NOTE: PLEASE SEE 400A METER/MAIN SHALL
 INDICATE 400A MCB. PLEASE SEE ONE 200A
 BRKR IN THIS PANEL IS SHOWN AS MAIN
 BREAKER??
 PLEASE ALSO SEE PANEL "C" IS NOT
 SHOWN/IDENTIFIED ON SCHEDULE FOR
 METER/MAIN.
 215.5
  
 8)NOTE: PLEASE SEE PLANS FOR NUMEROUS
 SMOKE DETECTORS MISSING.
 PLEASE SEE NFPA-72 11.5.1.1 WHICH
 REQUIRES SD'S INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 RMS(THOSE WITH BATHS OR CLOSETS).
 PLEASE SEE SD'S REQUIRED ON ALL LEVELS
 OF A MULTI-LEVEL DWELLING.
 PLEASE SEE SD IN MASTER BEDRM SAHLL BE
 REQUIRED AT FIRST FLR AND SECOND FLR.
 SINCE THIS IS AN OPEN RM, SD FOR FIRST
 FLR SHALL BE WALL MOUNTED IN THE
 VICINITY OF STAIRS LEADING TO FLR ABOVE.
 PLEASE ALSO SEE AREA FOR OTHER STAIRS
 LEADING TO FLR ABOVE. MAIN HOUSE,
 DETACHED CABANA.
 PLEASE SEE SD'S HAVE BEEN REDLINED ON
 PLANS FOR ALL LOCATIONS REQUIRED.
  
 9)NOTE: PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE TO BE
 GFI.
  
 10)NOTE: PLEASE SEE MISSING GFI RECEPTS
 FOR A/C EQUIPMENT.
 210.8A, 210.63
  
 11)NOTE: PLEASE SEE NUMEROUS GFI RECEPTS
 MISSING ALONG KITCHEN COUNTERSPACES.
 210.8A6, 210.52C1-5
 PLEASE SEE A GFI WILL BE REQUIRED ON 2ND
 FLR "NOOK" AREA OF CABANA ALSO ABOVE
 DISHWASHER.
  
 12)NOTE: PLEASE SEE NUMEROUS MISSING
 RECEPTS REQUIRED PER 210.52. 2', 6', 12'
 OF WALL SPACES.
 PLEASE SEE RAIL AREA AT 2ND FLR IS
 CONSIDERED WALL SPACE AND FLR RECEPTS
 WILL BE REQUIRED PER 210.52
 PLEASE CLARIFY AREA T SUNK-IN LIV RM
 NEXT TO FIRE PLACE. ?? WALL SPACE??
 PLEASE SEE MANY OF THE ABOVE HAVE BEEN
 REDLINED ON PLANS WHERE REQUIRED. MANY
 OF MISSING.
  
 13)NOTE: PLEASE SEE MISSING HALLWAY
 RECEPTS PER 210.52H
 REDLINED.
  
 14)NOTE: PLEASE SEE MISSING GFI RECEPTS
 PER 210.52D,210.11C3,210.8
  
 15)NOTE: PLEASE SEE ALL RECEPTS WITIN 6'
 OF SINKS SHALL BE GFI/GFI PROTECTED.
 (LAUNDRY RM )210.8A
  
 16)NOTE:PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL AT LOCATION OF MASTER
 BEDRM, HALL/LIVING RM ETC.
 210.70
 PLEASE CORRELATE SWITCHES SHOWN FOR
 MASTER BEDRM LTS, SCONCES ETC.
 STAIR-WAY LT CONTROL. GRADE LEVEL
 ACCESS. MOST HAVE BEEN REDLINED ON PLANS
 AT LOCATIONS MENTIONED.
 LS 101 7.8
  
 17)NOTE: PLEASE LIST THE REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3. PLEASE SEE THESE ARE
 REQUIRED TO BE 20A AND #12 AWG.
  
 18)NOTE: PLEASE SEE NO SWITCHES SHALL BE
 LOCATED WITHIN THE 3' ZONE OF A
 TUB/JACUZZI TUB. PLEASE SEE NO RECEPTS
 SHALL BE LOCATED WITH 3' OF TUB.
 PLEASE SEE REDLINED PLANS FOR MASTER
 BATH RM LT CONTROLS, BEDRM #3.
 680.71, 410.4
  
 19)NOTE: PLEASE SEE SYMBOL FOR JACUZZI
 TUB/WHIRLPOOL TUB IS BEING SHOWN AS
 220V, HOWEVER THIS IS NOT LOCATED ON
 PANEL SCHEDULE(S) OR LOAD CALCS??
 PLEASE SEE 680.71, FOR REQUIRED GFI
 PROTECTION.
 PLEASE ALSO ADJUST LOAD CALCS.
  
 20)NOTE: PLEASE SEE A GDO IS SHOWN ON
 LOAD CALCS FOR PANELS LOCATED ON MAIN
 HOUSE,HOWEVER NO GDO COULD BE LOCATED AT
 MAIN HOUSE?
 PLEASE SEE DETACHED "GARAGE" DOES NOT
 INDICATE OR SHOW A GARAGE DOOR OR GDO.
 PLEASE INCLUDE IN PANEL "C" , LOADS ETC.
 215.5
  
 21)NOTE: PLEASE SEE MISSING DISCONNECTS
 REQUIRED FOR WATER HEATERS.
 422.31
  
 22)NOTE: PLEASE SEE MISSING
 DISCONNECTING MEANS REQUIRED FOR AHU'S ,
 PER 440.11
 PLEASE SEE MIN CLEARENCES REQUIRED PER
 110.26.
 PLEASE ALSO SEE DISCONNECT CLEARENCE
 REQUIRED FOR CU'S OUTSIDE.
 PLEAS ADJUST.
  
 23)NOTE: PLEASE CORRELATE ALL A/C LOADS
 ON LOAD CALCS, NUMBER OF UNITS INDICATED
 ON PANEL SCHEDULE(S) AND NUMBER OF UNITS
 SHOWN ON PLANS.
 PLEASE SEE LOAD CALCS FOR MAIN HOUSE
 INDICATE 4-5 AHU'S??? WHEREAS PLANS SHOW
 3-CU'S AND PANEL SCHEDULES ONLY INDICATE
 2 UNITS TOTAL???
 215.5 ETC.
  
 24)NOTE: PLEASE SEE PREVIOUS NOTE, ONCE
 A/C UNITS HAVE BEEN CORRELATED, PLEASE
 SEE 424.3B FOR MIN OCP OF 125% OF HEAT
 KW LOAD. PLEASE ALSO NOTE, MAX OCP OF
 150%
 PLEASE ADJUST OCP AND CONDUCTORS AS
 LISTED ON PLANS.
 PLEASE SEE LOAD CALCS AND KW RATING
 SHOWN.
  
 25)NOTE: PLEASE PROVIDE LOADS ON EACH
 PANEL.PLEASE SEE MISSING POOL PANEL,
 PANEL SCHEDULE. LOADS ARE SHOWN ON MAIN
 CALCS, HOWEVER THESE LOADS CAN NOT BE
 VERIFIED.
 PLEASE KNOW, ALL CONTINUOUS LOADS SHALL
 BE SHOWN AT 125%. (3 OR MORE HRS).
 POOL PUMP, HEAT PUMPS?
 215.3,230.42 ETC.
  
 26)NOTE: PLEASE SEE 250.66, 310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR.
 PLEASE SEE 1/0 MIN AT MAIN SERVICE AT
 DETACHED GARAGE. PLEASE ALSO SEE MIN AT
 MAIN HOUSE SHALL BE #2
  
 27)NOTE: PLEASE CORRELATE ALL DEDICATED
 CIRCUITS WHICH ARE SHOWN ON PLANS,
 HOWEVER NOT ALL ARE LISTED ON PANEL
 SCHEDULES.
 COULD NOT LOCATE ELEC OVEN ON PLANS?
 PLEASE MOVE ANY 220V OUTLETS FOR
 OVENS/RANGES DIRECTLY BEHIND UNITS.
 PLEASE SEE PLANS SHOW TWO RANGES, HOWEVR
 PANEL SCHEDULE ONLY SHOWS ONE??
 PLEASE SEE ZONING NOTES.
 PLEASE SEE # OF ICE MAKERS LISTED ON
 LOAD CALCS, YET ONLY ONE DEDICATED
 CIRCUIT IS SHOWN ON PANEL SCHEDULE?
 PLEASE CORRELATE OTHERS.
  
 28)NOTE: PLEASE VERIFY WHAT APPEARS TO
 BE A 220V RECEPT SHOWN IN PANTRY.??
 PLEASE ALSO CALRIFY RECEPTS SHOWN IN
 CLOSETS? ABOVE? BELOW? COMBUSTIBLES.?
 PLEASE BE AWARE OF INTENDED USE OF THESE
 WHICH MAY NOT PERMIT THESE TO BE LOCATED
 IN CLOSETS.
 240.24 ETC
  
 29)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 30)NOTE: PLEASE SEE DISHWASHER IS SHOWN
 ON PLANS FOR CABANA, HOWEVER PANEL
 SCHEDULE AND LOAD CALCS DO NOT INDICATE
 THE SAME.??
 PLEASE ALSO SEE MICROWAVE SHOWN ON PANEL
 SCHEDULE, BUT NOT ON PLANS FOR DEDICATED
 CIRCUIT??
  
 31)NOTE: PLEASE SEE GFI SHOWN ON
 COUNTERSPACE IN DETACHED CABANA, IS
 SHOWN AS "WP" ?? THIS IS PERMITTED,
 HOWEVER NOT REQUIRED.
 210.8A6
  
 32)NOTE: PLEASE IDENTIFY OTHER 220V
 RECEPTS SHOWN ON PLANS , HOWEVER THESE
 ARE NO LISTED IN LOAD CALCS OR ON PANEL
 SCHEDULES??
 PLEASE SEE CABANA AND MAIN HOUSE.
  
  
 PLEASE CORRELATE ALL A/C EQUIPMENT WITH
 MECHANICAL PLANS.
 THESE DO NOT MATCH.
  
 PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED ON PLANS AT LOCATIONS
 OF NOTES.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE SET OF
 OLD/VOIDED SHEETSREQUIRED FOR
 REFERENCE.
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS ,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 09:40 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 09:40 Sent To P
Notes
2006-03-30 00:00:00PLANS TO JOHN L.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-23 Time 14:17 Rev Time 0.00
Received By dpalmer Date 2006-03-23 Time 14:16 Sent To E
Notes
2006-03-24 00:00:00TO DP'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 11:16 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 11:16 Sent To E
Notes
2006-02-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-15 Cont ID  
Sent By adarroug Date 2006-02-15 Time 17:36 Rev Time 0.00
Received By adarroug Date 2006-02-15 Time 17:36 Sent To Z
Notes
2006-02-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 14:32 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 14:32 Sent To E
Notes
2005-10-06 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 08:33 Rev Time 0.00
Received By alange Date 2005-09-28 Time 16:53 Sent To  
Notes
2005-09-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-27 Cont ID  
Sent By tgordon Date 2006-02-27 Time 09:12 Rev Time 0.30
Received By tgordon Date 2006-02-27 Time 09:12 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By tgordon Date 2005-10-12 Time 16:06 Rev Time 0.30
Received By tgordon Date 2005-10-12 Time 16:06 Sent To B
Notes
2005-10-12 00:00:00*** DENIED ***
 1) EQUIP. INFO. FOR A/C SYSTEM RHEEM
 COND. RMAB-048J IS MISSING ON PLANS.
 2) NEED MANUFACTURE'S SPEC. SHEETS FOR
 GAS FIREPLACE.
 3) NEED COMBUSTION AIR CALCULATIONS FOR
 GAS FIREPLACE.
 4) SUPPLY AIR DUCT ON 2ND. FLOOR MAIN
 HOUSE, FROM AHU TO 1ST. FLOOR IS NOT
 SIZED.
 5) PROVIED AUXILIARY DRAIN PANSWITH
 DRAIN PROTECTION UNDER AHU'S PER 2001
 FBC/M 307.2.3 .
 6) DRAIN LINES FOR AHU'S NOT SHOWING ON
 PLANS PER 2001 FBC/M 307.2 .
 7) DRYER TO BE VENTED PER 2001 FBC/M 504
 .
 8) PLEASE SEE ELECTRICAL REVIEW
 REGUARDING A/C SYSTEMS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-03 Cont ID  
Sent By jleech Date 2006-04-03 Time 09:31 Rev Time 0.00
Received By jleech Date 2006-04-03 Time 09:31 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-02 Cont ID  
Sent By jleech Date 2006-03-02 Time 09:50 Rev Time 0.00
Received By jleech Date 2006-03-02 Time 09:50 Sent To B
Notes
2006-03-02 00:00:00RISER DIAGRAM; BATHROOM 3 SHOWS 3 LAV'S
 AND NO W/C DELETE 2 LAV'S AND ADD A W/C.
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-08 Cont ID  
Sent By jleech Date 2005-10-08 Time 12:13 Rev Time 1.00
Received By jleech Date 2005-10-08 Time 12:13 Sent To M
Notes
2005-10-08 00:00:00DENIED;
 RISER DIAGRAM DOES NOT MATCH FLOOR PLAN,
 HAS CODE VIOLATIONS, IS MISSING
 FIXTURES, AND FIXTURES ARE NOT PROPERLY
 LABELED. SHOW BACK BUILDING LINE ON
 RISER DIAGRAM AND LABLE BATHROOMS.
 IF ONE WATER METER IS FOR BOTH BUILDING
 A BACKFLOW PREVENTOR IS REQUIRED. NOTE
 ON PLAN. ONE SET OF PLANS MARKED IN RED
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2006-03-30 Cont ID  
Sent By mmclean Date 2006-03-30 Time 07:32 Rev Time 0.00
Received By mmclean Date 2006-03-30 Time 07:32 Sent To  
Notes
2006-03-30 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-02-21 Cont ID  
Sent By mmclean Date 2006-02-21 Time 17:04 Rev Time 0.00
Received By mmclean Date 2006-02-21 Time 17:04 Sent To I
Notes
2006-02-21 00:00:00DENIED,
 1. THE HEIGHT OF THE PROPOSED STRUCTURE
 MUST BE 33FT FROM THE GRADE TO THE TOP
 OF CHIMNEY. (NOT FINISH FLOOR).
  
  
 NOTE: THE SITEPLAN MUST MATCH THE SURVEY
 WITH SETBACKS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By mmclean Date 2005-10-05 Time 14:26 Rev Time 0.00
Received By mmclean Date 2005-10-05 Time 14:25 Sent To I
Notes
2005-10-05 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF SURVEY
 SHOWING THE PROPOSED STRUCTURE WITH
 SETBACKS.
 2. SITEPLAN PROVIDED DOES NOT SHOW ALL
 INFORMATION NEEDED TO COMPLETE A ZONING
 REVIEW.
 3. MAXIMUM HEIGHT ALLOWED FOR PROPOSED
 STRUCTURE MUST BE 33FT (WITH CHIMNEY).
 REQUIRED HEIGHT IS 30FT WITH 10% FOR
 CHIMNEY.
 4. ACCESSORY STRUCTURE CAN ONLY BE
 1000SQ FT OR LESS. (PROPOSED ACCESSORY
 STRUCTURE IS OVER THE REQUIRED SQ FT).
 5. NO KITCHEN IS ALLOWED IN ACCESSORY
 STRUCTURE, ZONED SF7, MUST REMOVE
 MICROWAVE, STOVE.
 6. ACCESSORY STRUCTURE CANNOT BE
 CONNECTED BY A DECK (MUST REMOVE), CAN
 ONLY BE CONNECTED BY A CANVAS COVERING
 BREEZEWAY SEC 94-304(B).
 7. NO SEPERATE SERVICE FOR ACCESSORY
 STRUCTURE, SERVICE MUST BE FEED OFF MAIN
 HOUSE. (PLEASE REFER TO ELECTRICAL
 COMMENTS).
  
 ****************************************
 ****************************************
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK & SCREEN ENCLOSURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720