Plan Review Details - Permit 05091281
Plan Review Stops For Permit 05091281
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 15:58 Rev Time 1.00
Received By alange Date 2005-10-17 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-03 Cont ID  
Sent By dpalmer Date 2005-10-03 Time 11:52 Rev Time 0.33
Received By dpalmer Date 2005-10-03 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mwennerg Date 2005-10-04 Time 13:53 Rev Time 0.00
Received By mwennerg Date 2005-10-04 Time 13:53 Sent To  
Notes
2005-10-04 00:00:00PLANS RED LINED REF: NFPA-13.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 12:16 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:16 Sent To E
Notes
2006-01-22 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-02 Cont ID  
Sent By adarroug Date 2005-12-02 Time 13:24 Rev Time 0.00
Received By adarroug Date 2005-12-02 Time 13:24 Sent To M
Notes
2005-12-02 00:00:00TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 15:58 Rev Time 0.00
Received By alange Date 2005-09-28 Time 15:08 Sent To  
Notes
2005-09-28 00:00:00TO "BOB"#4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-05 Cont ID  
Sent By tgordon Date 2005-12-05 Time 11:16 Rev Time 0.25
Received By tgordon Date 2005-12-05 Time 11:16 Sent To  
Notes
2005-12-05 00:00:00MECH. REV. TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-30 Cont ID  
Sent By prafter Date 2005-09-30 Time 07:48 Rev Time 1.00
Received By prafter Date 2005-09-30 Time 07:48 Sent To  
Notes
2005-09-30 00:00:00MECH. PLAN REVIEW:
  
 PROVISO:RATED WALLS WITH R/A OPENINGS
 REQUIIRE APP.FIRE DAMPERS.
  
 PAT RAFTER 561/805/6728 OR 8056719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
 MECH. PLAN REVIEW:
 PROVISO:
  
 1.RATED WALLS WITH R/A OPENINGS,
 REQUIRE APP. FIRE DAMPERS.
  
 2. A/C IN REMODEL SPACE MUST NOT BE
 USED DURING CONSTRUCTION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 08:11 Rev Time 0.50
Received By jleech Date 2005-10-01 Time 08:11 Sent To  
Notes
2005-10-01 00:00:00NO PLUMBING WORK SHOWN ON DRAWINGS. PLAN
 SHOWS BREAK ROOM WITH NO SINK.