Plan Review Details - Permit 05091265
Plan Review Stops For Permit 05091265
Review Stop B BUILDING (STRUCTURAL)
Rev No 82 Status P Date 2008-11-21 Cont ID  
Sent By jwitmer Date 2008-11-21 Time 08:45 Rev Time 0.33
Received By jwitmer Date 2008-11-21 Time 08:45 Sent To PC
Notes
2008-11-21 08:46:52CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION/ REVIEWED
  
 SUBMITTAL NO. STEEL STAIR SHOP DRAWINGS AND
 CALCULATIONS
  
 JOSE A SANCHEZ PE
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 81 Status F Date 2008-11-18 Cont ID  
Sent By jwitmer Date 2008-11-18 Time 16:45 Rev Time 0.77
Received By jwitmer Date 2008-11-18 Time 16:45 Sent To PC
Notes
2008-11-18 16:51:41CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION/ DENIED
  
 SUBMITTAL NO. STEEL STAIR SHOP DRAWINGS AND
 CALCULATIONS
  
 1) THRESHOLD BUILDING REQUIRING 3 SETS OF ALL DOCUMENTS
 SUBMITTED.
  
 2) STAIR ELEVATION# 1 LOWER LEFT HAND CORNER, AT THE
 INTERMEDIATE LANDING THE HANDRAIL IS NOT CONTINUOUS
 PAST THE LAST RISER IN THE UPPER FLIGHT OF
 STAIRS.1009.11.4/ 1009.11.5.
 1009.11.4 CONTINUITY.
 HANDRAIL-GRIPPING SURFACES SHALL BE CONTINUOUS, WITHOUT
 INTERRUPTION BY NEWEL POSTS OR OTHER OBSTRUCTIONS.
  
 1009.11.5 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT. WHERE HANDRAILS ARE NOT
 CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL EXTEND
 HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND THE TOP
 RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF ONE TREAD
 BEYOND THE BOTTOM RISER.
  
 1012.2 HEIGHT.
 GUARDS SHALL FORM A PROTECTIVE BARRIER NOT LESS THAN 42
 INCHES (1067 MM) HIGH, MEASURED VERTICALLY ABOVE THE
 LEADING EDGE OF THE TREAD, ADJACENT WALKING SURFACE OR
 ADJACENT SEATBOARD.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 80 Status P Date 2008-09-11 Cont ID  
Sent By rbrown Date 2008-09-11 Time 08:16 Rev Time 0.00
Received By rbrown Date 2008-09-11 Time 08:16 Sent To  
Notes
2008-09-11 08:17:02FAIR HOUSING RAMP SPEC OK/STAMPED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 79 Status P Date 2008-09-10 Cont ID  
Sent By jwitmer Date 2008-09-10 Time 11:21 Rev Time 2.22
Received By jwitmer Date 2008-09-10 Time 11:21 Sent To FIRE
Notes
2008-09-10 11:22:54CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: 28 SHEETS A0.8, A1.15 & A1.16

Review Stop B BUILDING (STRUCTURAL)
Rev No 78 Status P Date 2008-09-10 Cont ID  
Sent By jwitmer Date 2008-09-10 Time 08:04 Rev Time 1.00
Received By jwitmer Date 2008-09-10 Time 08:01 Sent To  
Notes
2008-09-10 08:06:02CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 05-550-001 AMWERICAN STAIR SHOP DRAWINGS-
 OK
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 77 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 16:40 Rev Time 2.22
Received By jwitmer Date 2008-09-09 Time 16:40 Sent To PC
Notes
2008-09-09 16:42:13CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO. 10-400-001 ADA RAMP ACCESS.
 THE PROPOSED AGREEMENT IS OK, THE SUBMITTED RAMP IS NOT
 THE ONE AGREED UPON WITH THE BUILDING OFFICAIL, FAIR
 HOUSING GUIDELINES.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 76 Status P Date 2008-09-03 Cont ID  
Sent By jwitmer Date 2008-09-03 Time 14:43 Rev Time 2.22
Received By jwitmer Date 2008-09-03 Time 14:43 Sent To PC
Notes
2008-09-03 14:46:20CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: REVISION # 28 A0.1, A0.4A1.0, A1.5A2.0 &
 A6.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 75 Status P Date 2008-08-12 Cont ID  
Sent By jwitmer Date 2008-08-12 Time 09:33 Rev Time 0.77
Received By jwitmer Date 2008-08-12 Time 09:33 Sent To PC
Notes
2008-08-12 09:43:10CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 07-200-003
 FIRESTOPPING JUDGEMENT C-AJ-8093

Review Stop B BUILDING (STRUCTURAL)
Rev No 74 Status P Date 2008-08-08 Cont ID  
Sent By jwitmer Date 2008-08-08 Time 10:50 Rev Time 0.77
Received By jwitmer Date 2008-08-08 Time 10:50 Sent To PC
Notes
2008-08-08 10:52:39CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 10-340-002
 FAABRIC AWNING SUBMITTAL/CERTIFICATE OF FLAME
 RESISTANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 73 Status F Date 2008-08-08 Cont ID  
Sent By jwitmer Date 2008-08-08 Time 10:42 Rev Time 0.77
Received By jwitmer Date 2008-08-08 Time 10:42 Sent To PC
Notes
2008-08-08 10:46:10CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:DENIED
  
 SUBMITTAL NO. 05-550-001 AS-BUILT STAIR SHOP DRAWINGS
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. NOT RUBBER
 STAMPED.
  
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 61G15-23.002(2)FL. ADMIN. CODE. A COVER SHEET OR
 INDEX SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED
 AND THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF
 THE PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 72 Status P Date 2008-08-08 Cont ID  
Sent By jwitmer Date 2008-08-08 Time 08:55 Rev Time 0.77
Received By jwitmer Date 2008-08-08 Time 08:55 Sent To PC
Notes
2008-08-08 08:57:21CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 05-500-047
  
 VENT SHAFT COVER

Review Stop B BUILDING (STRUCTURAL)
Rev No 71 Status P Date 2008-08-08 Cont ID  
Sent By jwitmer Date 2008-08-08 Time 08:08 Rev Time 0.33
Received By jwitmer Date 2008-08-08 Time 08:08 Sent To PC
Notes
2008-08-08 08:09:24CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 08-300-002 OVERHEAD GARARE DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 70 Status P Date 2008-08-04 Cont ID  
Sent By jwitmer Date 2008-08-04 Time 08:25 Rev Time 1.22
Received By jwitmer Date 2008-08-04 Time 08:25 Sent To PC
Notes
2008-08-04 08:26:3820 GAUGE STORM PANELS 05-800-002

Review Stop B BUILDING (STRUCTURAL)
Rev No 69 Status F Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 16:16 Rev Time 1.11
Received By jwitmer Date 2008-06-26 Time 16:16 Sent To  
Notes
2008-06-26 16:42:30CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:DENIED
  
 SUBMITTAL NO.FIRESTOPPING JUDGEMENT/ C-AJ-8093
  
 THE SUBMITTAL FOR AN ENGINEERS JUDGEMENT IN REGARDS TO
 THE SYSTEM NO. C-AJ-8093 HAS BEEN DENIEDIT WILL NEED TO
 MEET THE INTENT OF 712.1.1 AND 712.1.2.WE WOULD NEED
 ADDITIONAL INFORMATION TO BE ABLE TO DO A COMPLETE
 REVIEW.
 1) THE STI DIAGRAM DOES NOT PROVIDE HOW LARGE THE HOLE
 IS IN THE WALL NOR THE DIMENSIONS OF THE BUSWAY. NUMBER
 7 OF THE STANDARD INDICATES THEY CAN BE 19 INCHES X 5
 INCHES DEEP.
  
 2) STI DIAGRAM ALSO IS NOT CLEAR AS TO HOW MANY BUSWAYS
 ARE PENETRATING THIS RATED WALL IS THERE TWO OR FOUR
 UNITS? THE COVER SHEET INDICATES THERE ARE THREE
 BUSWAYS THAT ACTUALLY ARE PENETRATING THIS WALL?
  
 3) STI DIAGRAM ALSO FAILS TO IDENTIFY THE CLEARENCES
 BETWEEN THE BUSWAYS WHERE AS THE C-AJ-8093 SYSTEM
 CLEARLY STATES THE SPACE BETWEEN THE BUSWAYS SHOULD BE,
 PLEASE PROVIDE THESE DEMINSIONS.
  
 PLEASE PROVIDE THIS ADDITIONAL INFORMATION SO A
 THOROUGH REVIEW CAN BE COMPLETED. THANK YOU.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 68 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 10:48 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 10:48 Sent To B
Notes
2008-06-03 10:50:28CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 10-300-002 FABRIC AWNINGS AND FRAME S/S
 AND LETTER FOR REMOVAL OF FABRIC IN A HIGH WIND EVENT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 67 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 10:44 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 10:44 Sent To PC
Notes
2008-06-03 10:48:17CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO. 05-500-046
 DECRATIVE LOUVER FOR CUPOLA TOWER

Review Stop B BUILDING (STRUCTURAL)
Rev No 66 Status F Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 10:39 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 10:38 Sent To PC
Notes
2008-06-03 10:42:18CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO.08-300-002
 GARAGE MAINTENCE DOOR: PLEASE HIGHLIGHT PRESSURES THAT
 ARE TO BE USED SEE SHEET# 4.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 65 Status F Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 10:33 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 10:33 Sent To PC
Notes
2008-06-03 10:37:14CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:DENIED
  
 SUBMITTAL NO. 05-500-047
 VENTILATION SHAFT COVERS: PLEASE INDICATE IF THESE
 SHAFT COVERS ARE TO THE INTERIORSIDE OF THE FAN ROOM
 OR ARE ACTUALLY EXTERIOR LOUVERS? ADDITIONAL
 INFORMATION REQUIRED 106.1.2.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 64 Status F Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 13:45 Rev Time 1.11
Received By jwitmer Date 2008-05-12 Time 13:45 Sent To Z
Notes
2008-05-12 13:52:54CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: / DENIED
  
  
 REVISION NO: 27 THE NEW FIRE SAFING DETAIL C-AJ-8093
 INDICATES LITERATURETO 3B PLEASE PROVIDE THE REST OF
 THE REPORT THROUGH 9D.THE PART 9 OF THIS SYSTEM IS
 THE FIRESTOP COMPONENTS THAT MAKE UP THIS SYSTEM, IT IS
 CURRENTLY INCOMPLETE AS DEPICTED. 712.4.1.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 63 Status P Date 2008-04-28 Cont ID  
Sent By jwitmer Date 2008-04-28 Time 15:32 Rev Time 2.22
Received By jwitmer Date 2008-04-28 Time 15:32 Sent To PC
Notes
2008-04-28 15:34:31CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO.
 07-200-002
 09-900-007
 REVISION NO:26 SHET A.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 62 Status P Date 2008-04-08 Cont ID  
Sent By jwitmer Date 2008-04-08 Time 15:32 Rev Time 0.77
Received By jwitmer Date 2008-04-08 Time 15:32 Sent To PC
Notes
2008-04-08 15:34:00CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
 REVISION NO: 15, S1.16 & S7.5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 61 Status P Date 2008-04-08 Cont ID  
Sent By jwitmer Date 2008-04-08 Time 08:05 Rev Time 1.22
Received By jwitmer Date 2008-04-08 Time 08:05 Sent To PC
Notes
2008-04-08 08:07:54CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: STRUCTURAL REVISON # 11,12 & 15

Review Stop B BUILDING (STRUCTURAL)
Rev No 60 Status F Date 2008-04-09 Cont ID  
Sent By jwitmer Date 2008-04-09 Time 09:37 Rev Time 0.55
Received By jwitmer Date 2008-04-09 Time 09:37 Sent To PC
Notes
2008-04-08 07:27:25CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL: NO 07-200-002 RESUBMITTAL, THERE ARE TWO
 AREAS OF CONCERN:
 1) THE ORIGINAL SUBMITTAL NUMBER DOES NOT APPEAR
 ANYWHERE ON THE PAPERWORK.
 2) THE ORIGINAL REVIEW ASK WHERETHIS PRODUCT WILL BE
 APPLIED. THE RESPONCE SHEET IS NOT
 WRITTEN ON THE DESIGN TEAMS LETTER HEAD, BUT ON THE
 CITIES' COMMENT SHEET. PLEASE HAVE THE DESIGNERS OF
 RECORD RESPOND
 ON THERE OWN LETTERHEAD.
  
 THE RESPONCE INDICATES APPLIED TO ROOF DECK SEE SHEET
 1.21 THIS IS THE FLOOR PLAN OF THE 6TH LEVEL WHICH IS
 THE POOL DECK AND HEALTH CLUB.
 PLEASE INDICATE A SECTION WHERE THIS PRODUCT IS ALREADY
 MENTIONED AS BEING USED FOR ROOF INSULATION FACTOR.
 106.1.2. ADDTIONAL INFORMATION REQUIRED.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 59 Status P Date 2008-04-08 Cont ID  
Sent By jwitmer Date 2008-04-08 Time 07:15 Rev Time 2.22
Received By jwitmer Date 2008-04-08 Time 07:15 Sent To  
Notes
2008-04-08 07:16:15CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
  
 REVISION NO: 24 & 25

Review Stop B BUILDING (STRUCTURAL)
Rev No 58 Status F Date 2008-02-27 Cont ID  
Sent By jwitmer Date 2008-02-27 Time 13:18 Rev Time 0.77
Received By jwitmer Date 2008-02-27 Time 13:18 Sent To PC
Notes
2008-02-27 13:21:19CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 05.500.037
 FABRIC AWNINGS:
  
 NO INFORMATION ON THE FABRIC PORTION OF THE AWNING.
 3105.3.1
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 BE FLAME RESISTANT IN ACCORDANCE WITH NFPA 701.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 57 Status F Date 2008-02-27 Cont ID  
Sent By jwitmer Date 2008-02-27 Time 12:57 Rev Time 0.33
Received By jwitmer Date 2008-02-27 Time 12:57 Sent To PC
Notes
2008-02-27 12:59:24CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 07-200.002PLEASE PROVIDE MORE
 INFORMATION WHERE THIS PRODUCT WILL BE APPLIED?
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 56 Status P Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 09:56 Rev Time 0.44
Received By jwitmer Date 2008-01-29 Time 09:56 Sent To PC
Notes
2008-01-29 09:57:53CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
 SUBMITTAL NO: 05-500.036 POMA ENTRANCE CANOPY

Review Stop B BUILDING (STRUCTURAL)
Rev No 55 Status P Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 09:45 Rev Time 0.55
Received By jwitmer Date 2008-01-29 Time 09:44 Sent To PC
Notes
2008-01-29 09:56:22CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO: 05.700.011 CLOCK TOWER DECRATIVE GRATE
 DESIGN, SHOP DRAWINGS SITE SPECIFIC (POMA)

Review Stop B BUILDING (STRUCTURAL)
Rev No 54 Status P Date 2008-01-29 Cont ID  
Sent By jwitmer Date 2008-01-29 Time 09:41 Rev Time 0.55
Received By jwitmer Date 2008-01-29 Time 09:40 Sent To PC
Notes
2008-01-29 09:44:43CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO: 05-700.010EGG CRATE AWNINGS POMA) SITE
 SPECIFIC
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 53 Status P Date 2008-01-25 Cont ID  
Sent By jwitmer Date 2008-01-25 Time 13:23 Rev Time 2.22
Received By jwitmer Date 2008-01-25 Time 13:23 Sent To PC
Notes
2008-01-25 13:25:34CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO: 08-500-015 SHOP DRAWINGS AND CALCULATIONS
 WINDOWS & DOORS
 REVISION NO:

Review Stop B BUILDING (STRUCTURAL)
Rev No 52 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 07:24 Rev Time 0.44
Received By jwitmer Date 2008-01-24 Time 07:24 Sent To PC
Notes
2008-01-24 07:26:25CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO: 05-500-034SCOSTA METAL TRUSSES SHOP
 DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 51 Status F Date 2008-01-15 Cont ID  
Sent By jwitmer Date 2008-01-15 Time 10:33 Rev Time 2.22
Received By jwitmer Date 2008-01-15 Time 10:33 Sent To  
Notes
2008-01-15 10:46:18CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
  
 REVISION NO: 22, SHEETS A0.3, A0.4, LS.1 & LS.2 DENIED,
 THESE SHEETS REFLECT THE STAIR NO. 3 AND THE LOBBY .
 THE STAIRWAY EXTENSION UNDER THE ALTERNATE MEANS AND
 MEETHODS DISCUSSED WITH THE DESIGN TEAM HAS NOT BEEN
 INDICATED ON THESE PLANS.
 SEE 403.13, EVERY REQUIRED STAIRWA SERVING FLOORS MORE
 THAN 75 FEET ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS SHALL COMPLY WITH SECTION 909.20 AND
 1019.8.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 50 Status P Date 2008-01-15 Cont ID  
Sent By jwitmer Date 2008-01-15 Time 10:30 Rev Time 5.55
Received By jwitmer Date 2008-01-15 Time 10:29 Sent To  
Notes
2008-01-15 10:33:12REVISION# 22 REVIEWED:
 A1.1, A1.2, A1.21, A1.31, A1.32, A1.33, A1.5, A4.1,
 A4.2,A4.5, A5.0, A5.1, A5.2 A5.6, A8.3, A8.5, A8.6 &
 A8.8

Review Stop B BUILDING (STRUCTURAL)
Rev No 49 Status P Date 2007-12-06 Cont ID  
Sent By jwitmer Date 2007-12-06 Time 14:56 Rev Time 0.77
Received By jwitmer Date 2007-12-06 Time 14:56 Sent To PC
Notes
2007-12-06 14:57:48CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: A-19 REVISION FOR SCUPPERS

Review Stop B BUILDING (STRUCTURAL)
Rev No 48 Status P Date 2007-11-20 Cont ID  
Sent By jwitmer Date 2007-11-20 Time 14:36 Rev Time 0.77
Received By jwitmer Date 2007-11-20 Time 14:36 Sent To PC
Notes
2007-11-20 14:38:31CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: 16 SHEET S4.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 47 Status P Date 2007-11-14 Cont ID  
Sent By jwitmer Date 2007-11-14 Time 10:17 Rev Time 0.77
Received By jwitmer Date 2007-11-14 Time 10:17 Sent To PC
Notes
2007-11-14 10:19:36CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO: 10-560-003 ACCESS PANELS
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 46 Status F Date 2007-11-14 Cont ID  
Sent By jwitmer Date 2007-11-14 Time 09:42 Rev Time 0.77
Received By jwitmer Date 2007-11-14 Time 09:42 Sent To  
Notes
2007-11-14 09:43:43CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 05-500-026
 TRUSS SHOP DRAWINGS
 NOTE THE PROJECT IS DESIGNED TO THE 2004 FBC , SCOSTA
 TRUSS DESIGN DRAWINGS ALSO INDICATE THE PROJECT TO BE
 DESIGNED TO THE 2004 FBC WHICH USES ASCE 7-02 NOT THE
 ASCE 7-98 LISTED ON THE TRUSS ENGINEERING COVER SHEET.
 PLEASE SEE CHAPTER 35 FOR REFERENCE STANDARDS. PLEASE
 CORRECT THE EDITION OF ASCE 7.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2007-11-08 Cont ID  
Sent By jwitmer Date 2007-11-08 Time 16:12 Rev Time 1.33
Received By jwitmer Date 2007-11-08 Time 16:12 Sent To  
Notes
2007-11-08 16:14:12CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 REVISION NO: 16 S2-4, S7-6 & S7-7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2007-11-08 Cont ID  
Sent By jwitmer Date 2007-11-08 Time 07:56 Rev Time 2.22
Received By jwitmer Date 2007-11-08 Time 07:56 Sent To  
Notes
2007-11-08 07:59:46CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
 STRUCTURAL SHEETS: S1-8, S1-8R, S7.2, & S7.7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status P Date 2007-11-05 Cont ID  
Sent By jwitmer Date 2007-11-05 Time 11:34 Rev Time 2.00
Received By jwitmer Date 2007-11-05 Time 11:34 Sent To  
Notes
2007-11-05 11:36:49CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 REVISION NO:13-18 :
 A0.1,A0.3, A0.15, A1.2, A2.0, A2.1, A2.11, A3.5, A5.9 &
 A7.2

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2007-10-30 Cont ID  
Sent By jwitmer Date 2007-10-30 Time 11:02 Rev Time 0.55
Received By jwitmer Date 2007-10-30 Time 11:02 Sent To PC
Notes
2007-10-30 11:02:52SUBMITTAL FOR EGGCRATE GRILLE

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2007-10-23 Cont ID  
Sent By jwitmer Date 2007-10-23 Time 11:13 Rev Time 0.77
Received By jwitmer Date 2007-10-23 Time 11:13 Sent To PC
Notes
2007-10-23 11:15:17SUBMITTALS;
 10-500-002 ACCESS PANEL
 SHORING LETTER GARAGE LEVEL 06 POOL NORTH POUR # 01

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2007-10-01 Cont ID  
Sent By jwitmer Date 2007-10-01 Time 21:00 Rev Time 1.00
Received By jwitmer Date 2007-10-01 Time 20:46 Sent To PC
Notes
2007-10-01 21:03:09STRUCTURAL SHEETS REV # 10 DATED 11-13-06
 SHEETS S-1.7, S-1.7R, S-1.8, S-1.8R, S-3.1, S-7.2,
 S-7.3 & S7.7

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 11:25 Rev Time 1.22
Received By jwitmer Date 2007-09-28 Time 11:25 Sent To PC
Notes
2007-09-28 11:30:26CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 SHORING LETTERGARAGE LEVEL 06SOUTH POUR 2
 SUBMITTAL# 09-500-028 MAGMA LOCK
 SHORING LETTER GARAGE LEVEL 06 POOL DECK
 SUBMITTAL 05-500-029-R01

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status F Date 2007-09-28 Cont ID  
Sent By jwitmer Date 2007-09-28 Time 11:16 Rev Time 0.56
Received By jwitmer Date 2007-09-28 Time 11:16 Sent To PC
Notes
2007-09-28 11:24:33CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
 SUBMITTAL NO:
 SHORING REPORT GARAGE LEVEL 06 POOL NORTH POUR# 07
 THE NOTARY HAS NOT FILLED OUT THE INFORMATION REQUIRED
 FOR THE NOTARY STAMP.
  
 JIM WITMER C. B. O.
 PLAN REVIEW II

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 15:32 Rev Time 1.00
Received By jwitmer Date 2007-09-14 Time 15:32 Sent To PC
Notes
2007-09-14 15:51:51CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:REVIEWED
  
 SUBMITTAL NO: 15-300-002
 TREMCO FIRESTOP SEALANT DRAWING NUMBER:
 TW-2176
 TR-1302
 TW-1158
 TW-2129
 TR-2184

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status F Date 2007-09-14 Cont ID  
Sent By jwitmer Date 2007-09-14 Time 14:59 Rev Time 1.55
Received By jwitmer Date 2007-09-14 Time 14:59 Sent To PC
Notes
2007-09-14 15:19:56CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 15-400-011 PRO-SLOPE
 1) PLEASE PROVIDE PRODUCT TESTING INFORMATION FROM A
 NATIONAL RECONIZED TESTING AGENCY IN REGARDS TO
 COMBUSTIBLITY OF THIS COMPOSITE MATERIAL.
 .717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR
 II CONSTRUCTION. COMBUSTIBLES SHALL NOT BE PERMITTED IN
 CONCEALED SPACES OF BUILDINGS OF TYPE I OR II
 CONSTRUCTION.
  
 PROVIDE INFORMATION ON THE COMBUSTIBILITY OF THIS
 PRODUCT.703.4 NONCOMBUSTIBILITY TESTS.
  
 THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2
 SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING
 MATERIALS AS SET FORTH IN SECTIONS 602.2 , 602.3 AND
 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM
 ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD
 CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A
 MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE
 BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN
 INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE
 LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF
 AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS.
  
 703.4.1 ELEMENTARY MATERIALS.
 MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED
 IN ACCORDANCE WITH ASTM E 136.
  
 703.4.2 COMPOSITE MATERIALS.
 MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE
 MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION
 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18
 MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 SHALL
 BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS.
  
 2) PLEASE ALSO PROVIDE TESTING INFORMATION AS TO THE
 DENSITY OF THIS POLYSTYRENE.
  
 3) 2603.2 LABELING AND IDENTIFICATION.
 PACKAGES AND CONTAINERS OF FOAM PLASTIC INSULATION AND
 FOAM PLASTIC INSULATION COMPONENTS DELIVERED TO THE JOB
 SITE SHALL BEAR THE LABEL OF AN APPROVED AGENCY SHOWING
 THE MANUFACTURER?S NAME, THE PRODUCT LISTING, PRODUCT
 IDENTIFICATION AND INFORMATION SUFFICIENT TO DETERMINE
 THAT THE END USE WILL COMPLY WITH THE CODE
 REQUIREMENTS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status F Date 2007-09-05 Cont ID  
Sent By jwitmer Date 2007-09-05 Time 07:38 Rev Time 16.00
Received By jwitmer Date 2007-09-02 Time 09:27 Sent To  
Notes
2007-09-05 07:39:14BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/* WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 REVISION # 13REVIEW
 ACTION: DENIED
  
 1) SHEET A0.3
 1A) PLEASE INDICATE ON THE PLAN WHERE THE NEWSROOM CAF?
 WILL BE THIS SHEET ONLY INDICATES A NEWSROOM AND ANY
 OTHER SHEETS THAT MAY BE INVOLVED.
  
 1B) FLOOR ELEVATIONS THERE ARE VARIOUS REVISIONS IN
 REGARDS TO FLOOR ELEVATION THAT DO NOT TAKE INTO
 ACCOUNT VERTICAL ACCESSIBILITY, IT WILL BE DISCUSSED IN
 DEPTH FURTHER IN THE REVIEW.
  
 1C) COMMERCIAL AREA CALCULATIONS NEED TO BE
 RECALCULATED FOR # 15. SHEET A1.5 MEZZANINE AREA HAS
 BEEN REDESIGNED FOR UNIT # 15.
  
 2) SHEET A0.15 MISSING SHEET
  
 3) SHEET A1.10
  
 3A) IDENTIFY WHAT AREA IS CONSIDERED THE NEWS ROOM
 CAF??
  
 4) SHEET A1.1
  
 A) COMMERCIAL SPACE # 14 AT THE REAR OF THE SPACE THERE
 IS A NEW 6? DROP OUT THE BACK EGRESS DOORS.1003.5.2
 WHERE CHANGE IN ELEVATION OF 12 INCHES (305 MM) OR LESS
 OCCURS IN EXIT ACCESS CORRIDORS, EXITS AND EXIT
 DISCHARGE, RAMPS COMPLYING WITH SECTION 1010 SHALL BE
 PROVIDED.
 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE
 SHALL BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A
 RAMP IN NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM
 RISE FOR RUN SHALL BE 30" (SEE FIGURE 16). 11-4.8.4.(2)
 LANDINGS. ALL LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60" CLEAR, & THE BOTTOM OF EACH RAMP SHALL HAVE NOT
 LESS THAN 72" OF STRAIGHT & LEVEL CLEARANCE.
  
  
 5) SHEET A1.2
  
 5A) THE ELEVATOR LOBBY HAS A NEW FINISH FLOOR HEIGHT OF
 18.75? NGVD IT ISN?T INDICATED AS A CHANGE WITH A DELTA
 OR CLOUD, IS THIS A MISTAKE? REVISION# 10 STILL
 INDICATED 18.5?.
  
 5B) THE ELEVATOR LOBBY REVISION# 13 AT DOOR # 30IS
 NOT CORRECTED IN DETAIL# 1 OF A7.2 GROUND FLOOR LEVEL.
  
  
 5C) DOOR # 23 TO AN A/C CLOSET IS ELIMINATED, M2.02
 INDICATES THAT AIR HANDLER UNIT # 15 IS LOCATED THERE.
  
 5D) THE SWITCH GEAR ROOM, FPL TRANSFORMER VAULT AND
 COMMERCIAL TENANT SPACE NOW ALL SHOW A 7? STEP, SHOW
 COMPLIANCE WITH VERTICAL ACCESSIBILITY. 11-4.1.3.
  
 5E) THE TRASH ROOM # 017 AND CORRIDOR ALSO HAVE
 ACCESSIBILITY ISSUES. THIS AREA IS 6? HIGHER THAN THE
 SURROUNDING TENANT SLABS CREATING ACCESSIBILITY
 PROBLEMS, THE PLAN INDICATES A 3? RAMP PLUS A 6? STEP
 AT THE FRONT OF THE BUILDING. PLEASE CORRECT THIS WHOLE
 AREA, AGAIN VERTICAL ACCESSIBILITY.
  
 5F)COMMERCIAL TENANT SPACE # 15 ALSO HAS A 6? STEP TO
 GAIN ACCESS INTO THIS UNIT, AGAIN PLEASE INDICATE
 COMPLIANCE WITH VERTICAL ACCESSIBILITY.11-4.1.2
 NOTHING IN THIS CODE SHALL BE CONSTRUED TO RELIEVE THE
 OWNER OF ANY BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS
 ABOVE AND BELOW THE OCCUPIABLE GRADE LEVEL, REGARDLESS
 OF WHETHER THE CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE OR FACILITY,
  
 6) THIS IS A COMMON COMMENT FOR ALL ELECTRICAL ROOMS ON
 ALL FLOORS WHERE THE BLOCK WALL INDICATES A REVISION#
 13 TO A METAL STUD WALL AND DRYWALL NO WALL
 IDENTIFICATION TAG IS PROVIDED INDICATING RATING.
  
 7) COMMON TO ALL SHEETS INDICATING A METAL AWNING, TO
 BE UNDER SEPARATE PERMIT WITH ASSOCIATED FEES AND
 REVIEWS. TO GET THE PLANS ISSUED SHEET A4.0 8/24/06 THE
 ARCHITECT SIGNED THE PLANS THAT THE BAHAMA STYLE METAL
 SHUTTERS WOULD BE UNDER A SEPARATE PERMIT NOT PART OF
 THE MASTER BUILDING. PLEASE PLACE NOT ON PLANS WHERE
 THIS TYPE AWNING IS LOCATED.
  
 8) SHEET A2.1 :
  
 8A) THE DOOR REMOVED AGAIN INDICATES THAT IT WENT TO
 AHU# 15 SEE SHEET M2.02
  
 8B) DOOR # 30 MOVED BEHIND THIS DOOR 4?-3? THERE IS A
 HEAVY LINE WHAT IS THIS LINE INDICATE?
  
 8C) FLOOR ELEVATION 18.75? ISN?T SHOWN AS A CHANGE SEE
 REVISION # 10 STILL AT 18.50?.
  
 9) SHEET A4.1;
  
 9A)AGAIN THIS DETAIL INDICATES EXTERIOR STEPS WITHOUT
 VERTICAL ACCESSIBILITY.NOTHING IN THIS CODE SHALL
 BE CONSTRUED TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL, REGARDLESS OF WHETHER THE CODE
 REQUIRES AN ELEVATOR TO BE INSTALLED IN SUCH BUILDING,
 STRUCTURE OR FACILITY,
 SWITCH GEAR
 TRANSFORMER VAULT
 EXTERIOR CORRIDOR
 COMMERCIAL TENANT# 15
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2007-08-24 Cont ID  
Sent By jwitmer Date 2007-08-24 Time 18:01 Rev Time 0.77
Received By jwitmer Date 2007-08-24 Time 18:01 Sent To  
Notes
2007-08-24 18:36:21CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 ROOF P/T SLAB AND BEAMS AREA B POUR# 1
 R.C. SERIES 200 ALUMINUM CASEMENT WINDOWS L. M. I.
 R C ALUMINUM SERIES HC200 ALUMINUM CASEMENTLMI
 RC SERIES 2400 ST ALUMINUM SLIDING GLASS DOORS LMI

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status P Date 2007-08-24 Cont ID  
Sent By jwitmer Date 2007-08-24 Time 17:48 Rev Time 0.77
Received By jwitmer Date 2007-08-24 Time 17:48 Sent To PC
Notes
2007-08-24 17:50:25CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
 SUBMITTAL NO:
 05-500-020 POMA RAILING AND CALCULATIONS -OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status F Date 2007-08-24 Cont ID  
Sent By jwitmer Date 2007-08-24 Time 16:25 Rev Time 0.77
Received By jwitmer Date 2007-08-24 Time 16:25 Sent To PC
Notes
2007-08-24 17:23:43CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 REVISION NO: SHEET S-7.7 DETAILS 12 & 13 BOTH INDICATE
 THE USE OF 14 GAUGE TRUSS ANCHORS POURED INTO THE BEAM
 AT THE EXTERIOR WALL LINE.A SECOND SET OF TRUSS
 ANCHOR TWISTED STRAPS ARE DEPICTED FUTHER IN ALONG THE
 BOTTOM CHORD OF THE TRUSS. THESE TRUSS ANCHORS ARE
 INDICATED TO USE TWISTED STRAPS AND TO USE THREE
 TAPCONS TO ANCHOR TO THE CONCRETE DECK. THE THREE
 TAPCONS ARE IN A ROW NOT IN UNISON WHERE THEY WILL TAKE
 THE LOAD EQUALLY.
  
 THE SECOND ISSUE IS THE METAL TRUSS LAYOUT SHEET (SHOP
 DRAWINGS) SHOWS THE SAME DETAIL REVIEWED BY THE
 DESIGNER OF RECORD SHOP DRAWING STAMPED WITH
 EMBEDS AT THE WALL LINE1 PAAIR OF TSWTC5 CLIPS THAT
 ARE WELDED TO THE EMBEDS, AND THE SECOND SET OF TRUSS
 ANCHORS BEING TSC2.75 OR TSC4.00 WITH 3 TAPCONS SECURED
 TO THE CONCRETE DECK TAKING THE LOAD EQUALLY.
  
 PLEASE COORDINATE THESE DETAILS SO ONE SYSTEM WILL BE
 SUBMITTED TO THE BUILDING DEPARTMENT.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2007-08-24 Cont ID  
Sent By jwitmer Date 2007-08-24 Time 16:21 Rev Time 3.33
Received By jwitmer Date 2007-08-24 Time 16:21 Sent To  
Notes
2007-08-24 16:25:33STTRUCTURAL SHEETS REVISION# 15, SHEETS:
 S1.16 & S1.16R
 S-1.17 & S1.17R
 S-1.19 & S1.19R
 S-1.34
 S-1.35
 S-3.1
 S-4.3
 S-7.3
 S-7.5
 S7.7- NOT REVIEWED / PROBLEMS WITH TRUSS ANCHORS
 S-8.4
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2007-08-22 Cont ID  
Sent By jwitmer Date 2007-08-22 Time 07:58 Rev Time 3.33
Received By jwitmer Date 2007-08-22 Time 07:58 Sent To  
Notes
2007-08-22 08:29:24CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 #08-110-002 MASONARY OPENINGS/ FRAME ELEVATIONS
 #05-500-004 PHASE 1 / STAIR'S 1-5
 #07-150-001 6 MIL VISQUEEN VAPOR BARRIER
 #07-200-001DYPLAST STYROFOAM / HI DENSITY STYROFOAM
 12"X18"
 #08-050-001 ALUM EXTRUSION COATINGS
 #08-500-004 BALCONIES SWING DOOR CONFIGURATION PACKAGE
 #09-210-001 BROCCO STUCCO, BOND AGENT LATH TRIM &
 WINDOW GUARD
 #08-110-001 HOLLOW METAL DOORS/ FRAMES
 #05-500-004 PHASE 1/ STAIRS 1-5 .
 #04-200-002 FRI LOAD BEARING MASONARY
 UNITSNOA06-02221.01
 #04-200-001 MASONRY PRODUCT DATA NOA 06-02221.01 FIRE
 LISTINGS
 #05-100-001 BOLLARDS, TRUSS, EMBEDS, COLUMNS, GUARDS,
 HOIST BEAMS ONLY 2 STS SUBMITTED
 #04-100-001 MOTTAR, WHITE PORTLAND CEMENT TITAN
 #11-450-001 GE RESIDEENTIAL APPLIANCES#14-560-001 TRASH
 CHUTEDETAILS
 #05-500-001 WELD PLATES FOR SEPERATION BEAMS
 #05-500-002 AMERICAN STAIR SHOP DRAWINGE7 OF E7
 #14-212-001 ELEVATOR PACK# 1, ELEVATOR PACK# 2, &
 ELEVATOR PACK# 2 REVISED
 #14-200-001 INCLINATOR SPECTRA-LIFT UNIT
 09-200-002 1HR FIRE RATED PARTITIONS
 08-500-001 PRODUCT APPROVALS WITH CALCS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2007-08-22 Cont ID  
Sent By jwitmer Date 2007-08-22 Time 07:58 Rev Time 3.33
Received By jwitmer Date 2007-08-16 Time 17:05 Sent To  
Notes
2007-08-16 18:58:36CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 03-250-006
 PTE 4TH-6TH MAIN TOWER PT DRGWS
  
 SUBMITTAL NO:
 03-250-005
 PTE 2ND TO 3RD LEVELS EAST TOWER
 LOSS CALCULATIONS & SUPPORT PLAN
  
 SUBMITTAL NO:
 03-250-004
 PT 2ND-3RD MAIN BUILDING TOWER
  
 SUBMITTAL NO:
 03-250-003
 MEZZANINE POST TENSION PLAN
  
 SUBMITTAL NO:
 003-250-002
 CONCRETE PLASTIC HOLE FORMS/SLEEVES
  
 SUBMITTAL NO:
 03-250-001
 DOVETAIL ANCHOR 24 GAUGE
  
 SUBMITTAL NO:
 03-250-015
 REVISED POUR #1-5 3RD LEVEL REBAR
 DAYS ELAPSED 13
  
 SUBMITTAL NO:
 03-250-015
 REVISED POUR #1-5 3RD LEVEL REBAR
 DAYS ELAPSED 28
  
 SUBMITTAL NO:
 03-250-014
 PT CALCS/SHOPS 6TH DECK PARKING
 LOSS CALCULATIONS
  
 SUBMITTAL NO:
 03-600-001
 F77 CONSTRUCTION GROUT
  
 SUBMITTAL NO:
 03-500-001
 ELEVATED DECK SHORING PLANS 20K
  
 BLDG SUBMITTAL:
 SHORING/RESHORING INSPECTION REPORTS
 2ND LEVEL POURS # 01-05
 3RD LEVEL POURS # 01-05
 4TH LEVEL POURS # 01-05
 5TH LEVEL POURS # 01-05
 6TH LEVEL POURS # 01-05
 7TH LEVEL POURS # 01-05
 8TH LEVEL POURS # 01-05
 9TH LEVEL POURS # 01-05
 10TH LEVEL POURS # 01-05
 ROOF LEVEL POURS # 01-05
  
 BLDG SUBMITTAL:
 SHORING/RESHORING INSPECTION REPORTS
 ROOF POURS # 1 - 5
 10TH FLOOR POURS # 1 - 5
 9TH FLOOR POUR # 5
 5TH ELEVATED SLAB POUR # 1
 MEZZANINE GARAGE POUR # 2
 RAMP - MEZZANINE POUR # 2
 GARAGE LEVEL 2 POUR # 1
 GARAGE LEVEL 2 POUR # 2
 RAMP 2ND FLOOR TO 3RD FLOOR
  
 BLDG SUBMITTAL:
 SHORING/RESHORING INSPECTION REPORTS
 GARAGE RAMP LEVEL4TH TO 5TH FLOOR
 GARAGE LEVEL5 POUR # 1
 GARAGE LEVEL 5 POUR # 2
 4TH LEVEL POUR # 1
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2007-08-22 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 19:26 Rev Time 4.44
Received By jwitmer Date 2007-08-15 Time 17:18 Sent To  
Notes
2007-08-15 19:26:26CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 03-200-014
 AREA A SHEARWALLS 2ND-11TH LEVEL
 REINFORCEMENT SHOP DRAWINGS
  
 SUBMITTAL NO:
 03-200-017
 REBAR MEZZANINE LEVEL POUR 1-5 SLAB
  
 SUBMITTAL NO:
 03-200-106
 2ND FLOOR POUR 1-5 SLAB REBAR
  
 SUBMITTAL NO:
 03-200-015
 COLUMNS 2ND LEVEL - 11TH
  
 SUBMITTAL NO:
 03-200-019
 4TH FLOOR P/T SLABS & BEAMS AREA "B"
  
 SUBMITTAL NO:
 03-200-021
 REBAR DRWGS 7TH FLOOR POURS 1-5
  
 SUBMITTAL NO:
 03-250-010
 PT CABLE SHOP DRAWINGS OF ROOF
 MAIN BUILDING TOWER & CALCULATIONS BY PTE
  
 SUBMITTAL NO:
 03-200-022
 GARAGE AREA "A" & "B" -WALLS @ RAMP
  
 SUBMITTAL NO:
 03-250-009
 PT CABLES ROOF EAST TOWER
 LOSS CALCULATIONS & SUPPORT PLAN DRWG
  
 SUBMITTAL NO:
 03-200-018
 5TH FLOOR P/T SLABS & BEAMS AREA "B"
  
 SUBMITTAL NO:
 03-250-007
 PTE 4TH TO 9TH LEVELS EAST TOWER PT
 LOSS CALCULATIONS & SUPPORT PLAN
  
 SUBMITTAL NO:
 03-250-006
 PTE 4TH - 6TH MAIN TOWER PT DRWG
 LOSS CALCULATIONS & SUPPORT PLAN
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status P Date 2007-08-08 Cont ID  
Sent By jwitmer Date 2007-08-08 Time 15:45 Rev Time 5.55
Received By jwitmer Date 2007-08-08 Time 15:45 Sent To PC
Notes
2007-09-28 11:19:41CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION:DENIED
  
 SUBMITTAL NO:
 ENGINEERS' SHORING LETTER
  
 GARAGE LEVEL 06 POOL NORTH POUR# 07
  
 NOTARY NEEDS TO FILL OUT INFORMATION ON STAMP.
  
 J WITMER CBO
 BUILDING PLAN REVIEWII
2007-08-08 16:46:21CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: REVIEWED
  
 SUBMITTAL NO:
 03-010-012 CORROSION INHIBITOR W? SUPER P 600
 03-010-014 THIN-TOP SUPREME & CONCRETE EUCLID
 03-150-001 JAC FORM RELEASE AGENT
 03-015-002 FIBRE EXPANSION JOINT FILLER
 03-180-001 FORMWORK EPOXY ULTRABOND
  
  
 03-2000-001 SHOP DRAWING # 1 PARTIAL FOUNDATION AREA C
 03-200-002 WWM 8X20, 6X6 10/10 WIRE MESH 03-200-003
 SHOP DRAWINGS REBAR REINFORCING AREA A FIRST LIFT
 VERTICALS
 03-200-004 REV 001 REBAR REINFORCING AREAB 1ST LIFT
 REINFORCING BAR AREA B 1ST LIFT VERTICALS
 REV REINFORCING AREA B 1ST LIFT
 REVISE REINFORCING REBAR AREA B 1ST LIFT VERTICALS
 03-200-006 001 REBAR REINFORCING AREA B FNDTN SHOP
 DRAWINGS
 03-200-005 REBAR REINFORCING- AREA A FOUNDATION SHOP
 DRAWINGS
 03-200-007 REBAR REIN 1ST LIFT COLUMNS AREA C
 03-200-008 REBAR REINFORCING AREA A SHEARWALLS
 03-200-009 REBAR REINFORCING AREA B SHEARWALL
 03-200-010 MEZZ MAT AREA C TOP/ BOT BARS 03-200-011
 MEZZ BEAMS / SECTION AREA C
 03-200-012 REBAR REINF SHEARWALL AREA B 2ND-11
 03-010-013 DWG FMI-1340
 015-400-001 CHEM SEAL, HANGERS PIPES
 15-400-004 FIRESTOPPING SUNTECH PLUMBING 15-400-009
 7TH-8TH LEVEL PENETRATION SHOP DRAWINGS 15-400-010
 PROGRESS SUBMITTALS
 15. SPECIFICATIONS OF STUDRAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 12:56 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 12:56 Sent To PC
Notes
2007-08-07 12:59:51CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 ) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ACTION: DENIED
  
 REVISION : GARGE DOOR- BEST ROLLING DOOR MODEL
 S10-6065
  
 1) THIS IS NOT S SUBMITTAL BUT A REVISION WITH
 ASSCIATED FEES, A $60.00 FEE HAS BEEN ATTACHED CODED
 (0808) REVISION# 8.
 THE ISSUED SET OF PLANS HADCORNELL ROLL-UP EXTERIOR
 DOOR FL # 5416 FOR A PRODUCT APPROVAL.
 THE SUBMITTED BESST ROLLING DOORS IS MISSING THE
 FLORIDA COVERSHEET.PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE STATE. IF THE
 PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC
 FORM PER RULE 9B-72.
  
 2) PLEASE HAVE AT LEAST ONE SET OF PRODUCT APPROVALS
 WITH THE ORIGINAL SHOP DRAWING STAMP BE AN ORIGINAL ON
 THE PRODUCT APPROVAL ITSELF, NOT A BLANK PAPER. THIS
 WILL TIE BACK TO THE PRODUCT APPROVAL BEING REVIEWED.
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 3) THE PRODUCT TESTING SHEET # 4 HIGHLIGHT WHICHSYSTEMS
 TO BE USED IN THE INSTALATION, TO BE REVIEWED BY THE
 DESIGNER OF RECORD.WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 11:22 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 11:22 Sent To PC
Notes
2007-08-07 11:49:17CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO:TRANSMITTAL# 01465
 REFERENCE: SHIM GAP SLIDING GLASS DOORS
 R. C. ALUMINUM SERIES 2400 ST SLIDING GLASS DOORS NOA
 01-0927.05
 THIS PRODUCT APPROVAL STATES:
 NOTICE OF ACCEPTANCE: SPECIFIC CONDITIONS
 3. LIMITATIONS
 3.1 THIS APPROVAL APPLIES TO SINGLE UNIT APPLICATIONS,
 AS SHOWN APPROVED DRAWINGS.
 4. LIMITATIONS
 4.1 THE ALUMINUM SLIDING GLASS DOOR AND ITS COMPONENTS
 SHALL BE INSTALLED IN STRICT COMPLIANCE WITH THE
 APPROVED DRAWINGS.
  
 1) THE TRCHNICAL SHEET 1 OF 6 PROVIDES THE DESIGN LOADS
 WITH 1/4", 3/8" AND 1/2" SHIM ROOM, INTO THRESS TYPE OF
 SUBSTRATE THRU WOOD BUCKS DIRECTLY INTO MASONRY,
 DIRECTLY INTO MASONRY AND INTO METAL STRUCTURES.
  
 2) THE PRODUCT APPROVAL WAS TESTED IN STRICT COMPLIANCE
 WITH TAS-201, TAS-202 AND TAS-203 THE TEST CRITERIA AND
 LIMITATIONS ARE LISTED IN THE PRODUCT APPROVAL AND CAN
 NOT BE EXCEEDED.
  
 1714.5.2.1 TESTING AND LABELING.
 EXTERIOR WINDOWS AND GLASS DOORS SHALL BE TESTED BY AN
 APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE
 LABELED WITH AN APPROVED LABEL IDENTIFYING THE
 MANUFACTURER, PERFORMANCE CHARACTERISTICS AND APPROVED
 PRODUCT CERTIFICATION AGENCY, TESTING LABORATORY,
 EVALUATION ENTITY OR MIAMI-DADE PRODUCT APPROVAL TO
 INDICATE COMPLIANCE WITH THE REQUIREMENTS OF ONE OF THE
 FOLLOWING SPECIFICATIONS:
 ANSI/AAMA/NWWDA 101/I.S.2 OR 101/I.S. 2/NAFS OR
 AAMA/WDMA/CSA 101/I.S.2/A440 OR TAS 202 (HVHZ SHALL
 COMPLY WITH TAS 202 UTILIZING ASTM E 1300 -98 OR ASTM E
 1300-02 OR SECTION 2404 . )
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 08:32 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 08:32 Sent To PC
Notes
2007-08-07 08:40:56CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
  
 ACTION: DENIED
  
 SUBMITTAL NO: 05-500-020
  
 1) GENERAL NOTES, GOVERNING CODE:
 PLANS INDICATE THAT THE PLANS WERE DESIGNED TO
 WITHSTAND THE LOADS OF THE APPLICABLE LOADS, NOT THE
 2004 FBC, PLEASE CORRECT.
  
 2) ONE OF THE CONCERNS IS THAT THE SHOP DRAWING SIGNED
 BY THEDESIGN TEAM IS NOT ON ANY OF THE ACTUAL
 DRAWINGS TO BE REVIEWED. PLEASE HAVE THE DESIGN TEAM
 PLACE STAMP ON THE SHOP DRAWINGS TO BE REVIEWED. ALSO
 PROVIDE ONE ORIGANAL STAMPED AND SIGNED DRAWING IN EACH
 SUBMITTAL 2 COPIES WILL BE SENT BACK TO THE FIELD.
 106.1.2.* ADDITIONAL INFORMATION REQUIRED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 07:58 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 07:58 Sent To PC
Notes
2007-08-07 08:22:09CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 05-500-017
  
 ACTION: DENIED
  
 REFRENECE: LOUVERS
  
 1) PLEASE PROVIDE THE LOCATION WHERE THISA LOUVER WILL
 BE PLACED ON THE BUILDING. ADDITIONAL INFORMATION
 REQUIRED.106.1.2.
  
 2)2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3) RULE 9B-72 REQUIRES LOUVERS TO BE TESTED FOR WIND,
 PLEASE PROVIDE THE TESTING REPORT FROM EITHER FLORIDA
 WEBSITE OR A MIAMI-DADE NOA,(NOTICE OF ACCEPTANCE).
 RULE 9B-72 REQUIRES THIRD PARTY QUALITY ASSURANCE
 PROGRAM BY AN AGENCY LISTED ON THE STATE WEBSITE BOTH
 THE MIAMI-DADE AND STATE WEBSITE HAVE THIRD PARTY
 QUALITY ASSURANCE PROGRAMS. IF THE MANUFACTURER HASN'T
 WENT FOR PRODUCT APPROVAL
 AT EITHER OF THESE AGENCIES, THEY MAY APPLY FOR LOCAL
 PRODUCT APPROVAL. LOCAL PRODUCT APPROVAL WILL ALSO
 REQUIRE THIRD PARTY QUALITY ASSURANCE PROGRAM.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 07:51 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 07:51 Sent To PC
Notes
2007-08-07 07:56:39CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 05-500-019
  
 DENIED
 REFRENCE: SEALED SHOP DRAWINGS FOR ROOF BRACKETS
  
 THE ROOF BRACKET SHEET CREATED BY POMA INDICATES (2)
 BACKER BLOCKS F & G, THE PLANS INDICATE HOW THEY ARE
 ATTACHED TO THE WALLAND SOFFIT BUT NOT TO THE BRAKET
 (A).
 PLEASE PROVIDE ADDITIONAL INFORMATION 106.1.2*.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 07:27 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 07:26 Sent To PC
Notes
2007-08-07 07:33:22CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO:05-500-018
  
 DENIED:
  
 EGG CRATE AWNINGS:
 1) PLEASE PROVIDE WHERE THESE AWNINGS WILL BE PLACED ON
 THE BUILDING, AT WHAT HEIGTH? PLEASE INDICATE ON WHAT
 SHEET OF THE PLAN AND LOCATION.ADDITIONAL INFORMATION
 REQUIRED 106.1.2.*
  
 2) PLEASE PROVIDE THE DESIGN CRITERIA FOR THE AWNINGS
 ALSO. 2004 FL. BLD CODE 1603.1.4 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE SHOWN ON THE
 CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 10:13 Rev Time 0.77
Received By jwitmer Date 2007-08-06 Time 10:13 Sent To PC
Notes
2007-08-06 10:36:45CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: SHORING/ RE-SHORING
 REVIEWED
 SECOND LEVEL GARAGE POUR# 1
 MEZZANINE GARAGE LEVEL POUR# 2
 MEZZANINE GARAGE LEVEL POUR# 1
 GARAGE LEVEL 04 POUR# 3
 4TH FLOOR POUR# 3
 SECOND LEVEL GARAGE POUR# 02
 GARAGE LEVEL3 2, POUR# 2
 GARAGE LEVEL# 03 POUR# 02
 3RD FLOOR POUR# 2
 GARAGE LEVEL# 03, POUR# 01
 3RD FLOOR, POUR 1
 GARAGE RAMP LEVEL 03 TO 04
 RAMP 3RD TO 4TH FLOOR
 4TH FLOOR POUR# 2
 GARAGE RAMP LEVEL 02 TO 03
 GARAGE LEVEL 04 POUR# 02

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 09:54 Rev Time 0.77
Received By jwitmer Date 2007-08-06 Time 09:54 Sent To PC
Notes
2007-08-06 09:56:12CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 05-500-021
 REVIEWED :
 TRELLIS SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 09:03 Rev Time 0.55
Received By jwitmer Date 2007-08-06 Time 09:03 Sent To PC
Notes
2007-08-06 09:44:39CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO:SHORING
 REVIEWED:
 20K LAYOUT TYPICAL GARAGE PLAN VIEW
 DECK 6TH PARKING- TENDON & SUPPORT PLAN
 ROOF WEST TOWER UNIFORMS AND SUPPORTS
 FIRST LEVEL- MEZZANINE SUPPORT PLAN
 PT FRICTION LOSS CALS PTE STRAND 1 ST LEVEL PARKING
 MEZZANINE SHOP DRAWING
 PT CALCS SHOP 2-4TH FLOOR PARKING
 PTE STRAND FRICTION LOSS CALCS SHOP DRAWING 2ND-4TH OF
 THE PARKING GARAGE
 PT CALCS SHOP 5TH FLOOR PARKING
 PTE STRAND FRICTION LOSS CALS FOR 5TH FLOOR PARKING
 GARAGE AND SHOP DRAWINGS
 TWS (METAL TRUSSES) LAYOUT FRAMING PLAN
 SCOSTA CORP STEEL ROOF LAYOUT PLAN SCOSTA CORP COLD
 FORMED STEEL TRUSS PACKET 1 SET/ CITY SET

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 08:37 Rev Time 0.77
Received By jwitmer Date 2007-08-06 Time 08:37 Sent To PC
Notes
2007-08-06 08:44:42CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 09-200-003
  
 DENIED
  
 PLEASE PROVIDE MORE INFORMATION AS TO WHAT THIS
 SUBMITTAL IS DOING? IF THIS IS SUBSTITUTING DENSEGLASS
 FOR M.R. G. W.B. PLEASE INDICATE SUCH WITH A REVISION
 TO SHEET A.8 FOR THIS IS A REVISION. IF THIS IS TO ONLY
 OCCUR AT THE ELECTRICAL METER ROOMS CREATE A NEW WALL
 TYPE FOR SHEET 8.0, IN EITHER CASE THIS WILL BE A
 REVISION WWITH ASSCIATED FEES AND NEW ARCHITECTURAL
 SHEET.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 08:28 Rev Time 0.77
Received By jwitmer Date 2007-08-06 Time 08:28 Sent To PC
Notes
2007-08-06 08:31:59CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO:05-700-001
 REVISION NO:
 DENIED
  
 THE SHOP REVIEW STAMP FROM THE DESIGNER OF RECORD ON
 ALL THREE SUBMITTALS ARE COPIES, NEED AT LEAST ONE
 ORIGINAL SIGNED BY THE DESIGNER OF RECORD.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2007-08-06 Time 08:20 Sent To B
Notes
2007-08-06 08:24:08CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 05-500-003
 REVISION NO:
 DENIED
  
 THE SHOP REVIEW STAMP FROM THE DESIGNER OF RECORD ON
 ALL THREE SUBMITTALS ARE COPIES, NEED AT LEAST ONE
 ORIGINAL SIGNED BY THE DESIGNER OF RECORD.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 07:57 Rev Time 0.77
Received By jwitmer Date 2007-08-06 Time 07:57 Sent To PC
Notes
2007-08-06 08:15:17CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO:05-500-023 SS POOL GATE SHOP DRAWINGS
 REVISION NO:
 DENIED
  
 PLEASE PROVIDE DETAILS FOR THE MAGMA LATCH (GATE LOCK)
 INDICATE COMPLIANCE WITH 424.1.3.1.9 SELF LATCHING .
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2007-08-06 Cont ID  
Sent By jwitmer Date 2007-08-06 Time 07:48 Rev Time 0.00
Received By jwitmer Date 2007-08-06 Time 07:48 Sent To  
Notes
2007-08-06 07:55:40CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO:05-500-025
 REVISION NO:
 DENIED
 S.S. CLOCK TOWER LOUVER SHOP DRAWINGS
  
 THE PRODUCT APPROVALS SUBMITTED FOR LOUVERS DOES NOT
 INDICATE POMA CORPARATION AS ONE OF THE MANUFACTURERS,
 PLEASE SUBMIT THE FLORIDA APRROVAL OR MIAMI-DADE REPORT
 WHICH BOTH HAVE THE REQUIRED THIRD PARTY QUALITY
 ASSURANCE PROGRAM.
 IF THE CONTRACTOR IS GOING TO TRY TO SUBMIT POMA
 LOUVERS PROVIDE THE REQUIRED THIRD PARTY QUALITY
 ASSURANCE PROGRAM REQUIRED FOR STATE AS WELL
 AS FOR LOCAL APPROVAL. IF THE MANUFACTURER IS TO SUBMIT
 FOR LOCAL APPROVAL PLEASE CONTACT THIS OFFICE FOR MORE
 INFORMATION AND REQUIREDFORMS.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2007-08-03 Cont ID  
Sent By jwitmer Date 2007-08-03 Time 16:24 Rev Time 0.77
Received By jwitmer Date 2007-08-03 Time 16:24 Sent To  
Notes
2007-08-03 16:55:59 
 CITY PALMS SUBMITALS/ REVISIONS
 PERMIT:05091265
 ADDRESS: 480 HIBISCUS
 SUBMITTAL NO: 15-700-007
 S.S. COLONIAL SHUTTERS/ LSAL AWNINGS
 REVISION NO:
  
 DENIED:
  
 1) SEE SHEET A4.0 AND A4.1 OF PLANS ALL BAHAMA TYPE
 SHUTTERS TO BE UNDER SEPEERATE PERMIT WITH ASSCIATED
 FEES AND REVIEWS.
  
 2) FIXED ALUMINUM LOUVERS, THE PLAN DOES NOT INDICATE
 THELOCATION ON THE BUILDING, SHEET 4OF 4 INDICATES
 SEPERATE SHAPES OF ALUMINUM EXTRUSIONSBUT NO REASON WHY
 THEY ARE SHOWN,
 IS THIS TO BE FIXED FLAT AGAINST THE WALL? 106.1.2*
 ADDITIONAL INFORMATION REQUIRED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2007-08-03 Cont ID  
Sent By jwitmer Date 2007-08-03 Time 13:06 Rev Time 3.33
Received By jwitmer Date 2007-08-03 Time 13:06 Sent To PC
Notes
2007-08-03 15:04:49ARDAMAN RAILING LOAD TEAT: POMA & SONS PROTOTYPE PICKET
 RAILING SYSTEM
 SUBMITTAL # 05-500-022 S.S. SITE FENCE SHOP DRAWING
 SUBMITTAL # 05-500-24PROPERTY FENCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-07-12 Cont ID  
Sent By jwitmer Date 2007-07-12 Time 16:39 Rev Time 2.22
Received By jwitmer Date 2007-07-12 Time 16:39 Sent To PC
Notes
2007-07-12 16:47:13BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 STAIR CALCS & SHOP DRAWING REVIEW
 ACTION: DENIED
  
 1)SHOP DRAWINGS BY COHEN FREEDMAN ENCINOSA HAVE A
 PHOTO COPIED SEAL ANS OR PHOTO COPIED SIGNATURE.
 THE RAISED SEAL IS NOT SIGNED NOR DATED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
  
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 13:23 Rev Time 2.22
Received By jwitmer Date 2007-05-07 Time 13:23 Sent To PC
Notes
2007-05-07 13:40:13BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP
 TEL: (954)275-3592
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 THE SHORING / RESHORING INSPECTION REPORTS SUBMITTED TO
 THE CITY OF WEST PALM BEACH BY GARY BROWN ARE COPIES.
 DATED FROM NOV. 16, 2006 -APRIL 24, 2007.
 THESE REPORTS BEING COPIED WITH A NOTARY SEAL CREATES A
 SECOND DEGREE MISDEMEANOR, PUNISHABLE AS PROVIDED IN
 S.775.082 OR S 775.083.
  
 117.05((3)(E)ANY PERSON WHO UNLAWFULLY POSSESSES A
 NOTARY PUBLIC OFFICIAL SEAL OR ANY PAPERS OR COPIES
 RELATING TO NOTARIAL ACTS IS GUILTY OF A MISDEMEANOR OF
 THE SECOND DEGREE, PUNISHABLE AS PROVIDED IN S. 775.082
 OR S. 775.083.
  
 COPIES OF SAID DOCUMENTS WILL BE MAINTAINED AS EVIDENCE
 THAT MAY BE FORWARDED TO THE GOVERNORS NOTARY BOARD FOR
 DISCIPLINARY ACTIONS IF COPIES ARE SUBMITTED AGAIN TO
 THE CITY!
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 11:58 Rev Time 0.33
Received By jwitmer Date 2007-05-07 Time 11:58 Sent To  
Notes
2007-05-07 12:03:20BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP
 TEL: (954)275-3592
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 5TH ELEVATED SLAB, POUR # 1 REPORT IS A COPIED
 SIGNATURE WITH RAISED SEAL. PLANS, SPECIFICATIONS,
 REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 11:58 Rev Time 2.22
Received By jwitmer Date 2007-05-07 Time 10:58 Sent To  
Notes
2007-05-07 11:57:55BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP, INC
 TEL: (954)275-3592
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
  
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:
 SHORING & RESHORINGLETTERS;
 1ST ELEVATION POUR 1-5 MEZZANINE LEVEL
 2ND ELEVATION POUR 1-5
 3RD ELEVATION POUR 1-5
 4TH ELEVATION POUR 1-5
 5TH ELEVATION POUR 2-5NOTE: 5HT ELEVATIONPOUR# 1
 DENIED COPIED
 6HT ELEVATION POUR 1-5
 7TH ELEVATION POUR 1-5
 8TH ELEVATION POUR 1-2
 POUR 1, MEZZANINE 2, GARAGE
 9TH ELEVATION POUR 2-4
 8TH ELEVATION POUR 5
 9TH ELEVATION POUR 1
 L
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-03-19 Cont ID  
Sent By jwitmer Date 2007-03-19 Time 08:47 Rev Time 1.22
Received By jwitmer Date 2007-03-19 Time 08:47 Sent To PC
Notes
2007-03-19 09:23:57BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 480 HIBISCUS ST
 CONT: THE TOWER GROUP
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ROOFREVIEW-METAL ROOF "
 COPPER SALES UC-3 STANDING SEAM METAL ROOF PANELS ON
 22GA. B-DECK
  
 ACTION: REVIEWED
  
  
 NOTICE:3-19-07AT THIS TIME NO ROOFING PERMIT HAS BEEN
 APPLIED FOR,
 BEFORE A ROOFING PERMIT CAN BE ISSUED, THE FLAT ROOF
 REPORT SUBMITTED
  
 BEFORE THE ROOFING CONTRACTOR WILL BE ISSUED A ROOFING
 PERMIT THEJOHNS MANVILLE MODIFIED BITUMEN ROOFING
 OVER LIGHTWEIGHT CONCRETE DECKS WILL NEED TO PICK A
 SUB-SYSTEM, THE SUBSYSTEM IN MOST CASES WILL REQUIRE
 ENHANCED FASTENING SYSTEMS. LIGHTWEIGHT INSULATING
 CONCRETE SYSTEMS REQUIRE CALCULATIONS FROM AN AARCHITEC
 OR ENGINEER. SEE ACTUAL LIMITATION SHEET.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-12-07 Cont ID  
Sent By jwitmer Date 2006-12-06 Time 10:51 Rev Time 2.22
Received By jwitmer Date 2006-12-06 Time 10:51 Sent To  
Notes
2006-12-06 10:54:08BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS ST.
 CONT: THE TOWER GROUP
 TEL: (561)635-6935
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING PROVISO FOR REVISION DATED OR MARKED # 10.
  
 1) SHEET A3.5 INDICATES A NEW LOUVER WITH A M.O. OF
 8'-6" X 15'-0" THE LOUVERS
 SUBMITTED UNDER THE PRODUCT APPROVALS WILL NOT MEET
 THIS SIZE. PLEASE CORRECT
 OR PROVIDE ADDITIONAL INFORMATION.LOUVER SERIES
 SUBMITTED:
 CONSTRUCTION SPECIALTIES, INC.
 7000 SERIES LOUVER NOA 00-1107.03
 DC 5304 LOUVER 02-0621.03
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By jwitmer Date 2006-08-28 Time 09:58 Rev Time 2.22
Received By jwitmer Date 2006-08-28 Time 09:58 Sent To  
Notes
2006-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
  
 ***BUILDING PROVISO***
  
 1) WITHIN 30 WORKING DAYS OF PERMIT
 ISSUANCE THE STRUCTRAL ENGINEER SUBMITS
 REVISIONS INDICATING THE BUILDING IS
 DESIGNED TO ASCE 7-02.
  
 2) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSELY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 3) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-02 Cont ID  
Sent By jwitmer Date 2006-08-02 Time 12:16 Rev Time 7.77
Received By jwitmer Date 2006-08-01 Time 16:43 Sent To  
Notes
2006-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
 3RD REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) COMPLIED
  
 2) COMPLIED
  
 3) THIS WILL BE A NEW REQUEST SINCE THE
 REDESIGN OF THE CLUBHOUSE. AS DISCUSSED
 EARLIER IN PREVIOUS MEETINGS, A 2 HR
 FIRE RATING WILL NEED TO BE PROVIDED FOR
 THE STEEL ROOF FRAMING MEMBERS. TO DATE
 NO INFORMATION HAS BEEN PROVIDED.
  
 4) 2ND REQUEST, MOST OF THE SUBMITTALS
 ARE FILED UNDER THE 2001 FBC, THIS
 PROJECT IS FILED UNDER THE 2004 FBC,
 PLEASE SCROLL THROUGH THE 2004 REPORTS.
 NOT ALL PRODUCTS FILED UNDER THE 2001
 MEET THE 2004 STANDARDS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) 3RD REQUEST, FL BLD CODE 1606.1.5:
 COMPONENTS & CLADDING, PROVIDE 2
 COPIES(3 IF THRESH- OLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING
 REPORTS,MISSING REPORTS ARE AS FOLLOWS:
 A) EXTERIOR FIXED WINDOWS
 RC ALUMINIUM SUBMITED 2001 APPROVAL,
 SERIES FX 345 NOT FOUND UNDER THE
 FBC 2004. PLEASE HIGHLIGHT TYPE OF
 GLASS IF MULTIPLE SYSTEMS AVAILABLE.
 B) EXTERIOR WINDOWS OPERATABLE:
 RC ALUMINIUM SUBMITTED 2001 APPROVAL,
 C) MULLIONS: MAY OR MAY NOT BE INCLUDED
  
 IN NOA DEPENDING ON SPANS.
 D) EXTERIOR GLAZED DOORS:
 RC ALUMINIUM SUBMITTED 2001 APPROVAL
 E) EXTERIOR ROLL UP DOORS:
 CORNELL IRON WORKS, IS MISSING THE
 EVALUAATION REPORT ER-05-0003
 PAGES 1-3, PLUS 23 TECHNICAL SHEETS.
 HIGHLIGHT WHICH TABLE (PSF) AND SPANS
  
 USED.
 F) EXTERIOR SWING DOORS:
 BARON METAL IND. INC. 2004 COVERSHEET
 TIES TO THE NOA 04-0330.01 NOT THE
 REPORT SUBMITTED. NOTE REPORT IS ONLY
  
 GOOD FOR +/-75 PSF. END PRESSURES ARE
  
 PROFESSIONALS STAMP REVIEWED IF
 PRODUCT DOESN'T WORK!!!!!
 G) LOUVER: SUBMITTED 2001 REPORT.
 H) SHUTTERS: HURST PRINT OUT CURRENT
 REPORTTHAT IS APPROVED, SUBMITTED
 STATES PENDING.SUBMIT THE CURRENT NOA
 THAT TIES TO THIS REPORT. THE ONE
 SUBMITTED IS EXPIRED.
 I) ROOFING ASSEMBLIES:
 MODIFIED, PLEASE HIGHLIGHT WHICH
 SUBSYSTEM TO BE USED. PLEASE CHECK
 COMPONENTS TO MATCH SUBSYSTEM. ALSO
 SEE NOTE# 7 SYSTEMS LIMITATION & RAS
 117 CALCULATIONS FOR ADDITIONAL
 FASTENING.
 J) METAL ROOFING, SUBMITTED 2001 REPORT,
 HIGHLIGHT SUBSYSTEM TO BE USED.
 K) TRUSS ANCHOR NO REPORT SUBMITTED
 L) EXTERIOR RAILINGS: NO REPORT
 SUBMITTED
 6) ENERGY CALCS BOTH 2001 AND 2004 CALCS
  
 HAVE BEEN SUBMITTED.
  
 7) ONLY ONE SET OF SOILS REPORT
 SUBMITTED, COPIED NOT SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 8)STRUCTURAL PLANS:
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-14 Cont ID  
Sent By jwitmer Date 2006-04-14 Time 12:58 Rev Time 8.88
Received By jwitmer Date 2006-04-13 Time 15:17 Sent To  
Notes
2006-04-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) COMMENT# 21 FROM THE PREVIOUS REVIEW,
 A0.4 MEZZANINE LEVEL PROVIE THE
 SQUARE FOOT OF EACH COMMERCIAL TEANANT
 FOR THE FIRST FLOOR LEVEL AS WELL AS THE
 MEZZANINE LEVEL. 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
 1A) REVIEW THE SQ FT FOR FIRST FLOOR AND
 TOTAL FOR COMMERCIAL #1 & #2.
 1B) COMMERCIAL UNIT# 8 PLEASE
 RECALCULATE THE MEZZANINE LEVEL IT
 APPEARS TO BE OVER THE 1/3RD BY 20 SQ
 FT.
 NOTE!!!!!! 110.2* (F) THIS WILL BE A
 BUILDING SITULATION THAT MUST APPEAR ON
 THE C.O.!!!!!!!!!!!!!
 FBC 505.2 COMMERCIAL BUILDOUTS, NO WALLS
 CAN BE ADDED BENEATH THE MEZZANINE
 LEVEL.THE AGGREGATE AREA OF A MEZZANINE
 OR MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED.
  
 2) COMMENET# 22B) FROM THE PREVIOUS
 REVIEW, DOOR 14 & 36 BOTH ARE OVERHEAD
 DOORS ON THE REFUSE ROOMS. 707.1.13.4
 DOORS TO BE 3/4 HR AND SELF CLOSING OR
 AUTOMATICALLY TO CLOSE IF SMOKE IS
 DETECTED. HOW OR WHAT TYPE OF DEVICE
 WILL ACCOMPLISH THIS ACTION? PROVIDE
 SPEC SHEETS.
  
 3) COMMENT# 28D) THE HEALTH CLUB NOW
 INDICATES THE USE OF HEAVY TIMBER AND 1
 1/2 WOOD DECKING, TABLE 601 FORA TYPE
 1A CONSTRUCTION FOR ROOF CONSTRUCTION
 INCLUDING SUPPORTING BEAMS AND JOIST
 REQUIRE A 1 1/2 HR FIRE RESISTANCE
 RATING. FOOTNOTE "C"(2)(III)TYPE "1"
 OVER 2 STORIES DOES ALLOW FRT WOOD IF A
 20' CLEAR FROM THE UPPER FLOOR TO THE
 ROOFIS ALLOWED AS IN THE PENTHOUSE
 UNITS. THIS CASSE THERE IS N'T 20'-0"
 CLEAR.ALSO SEE 602.2 TYPE I & II.
  
 4) COMMENT# 31 FROM THE PREVIOUS REVIEW,
  
 31) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) COMMENT# 32 FROM THE PREVIOUS REVIEW
 32)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 6) COMMENT# 33 FROM THE PREVIOUS REVIEW
 33) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS FIXED
 B) EXTERIOR WINDOWS OPERATABLE
 C) MULLIONS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR ROLL UP DOORS
 F) LOUVERS
 G) TRUSS ANCHOR ATTACHMENTS
 H) STORM SHUTTERS
 I) EFIS SYSTEMS
 J) EXTERIOR RAILINGS
 K) ROOFING ASSEMBLIES FLAT AND SLOPED
 ALL OF THE ABOVE MENTIONED PRODUCTS
 WILL REQUIRE THE DESIGNER OF RECORD TO
 SIGN OFF THAT THE REPORTS HAVE BEEN
 REVIEWEDAND APROVED BY THEIR OFFICE.
  
 ---NEW COMMENTS---
  
 7)1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS
 OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE
 SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT
 APPLY TO DWELLING UNIT ENTRANCE DOORS;
 HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 8) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN
 THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT
 LESS THAN 50 (45 IF FIELD TESTED) WHEN
 TESTED IN ACCORDANCE WITH ASTM E 492.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By kstevens Date 2006-01-20 Time 07:07 Rev Time 0.00
Received By jwitmer Date 2006-08-01 Time 16:43 Sent To  
Notes
2006-01-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091265
 ADD: 430 HIBISCUS
 CONT:PROJECT
 TEL: (561)586-2913
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: COHEN, FREEDMAN, ENCINOSA
 & ASSOC. STUART COHEN/ GULLERMO ENCINOSA
 8085 N. W. 155 ST
 MIAMI, FL
 T(305)826-4155
  
 STRUCTURAL: DE LOS REYESENGINEERING, INC
 8726 S. W. 26 TH STREET SUITE 1&2
 HECTOR DE LOS REYES
 MIAMI, FL
 T(305)477-8826
  
 1ST REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 COMMENTS FROM THE FOUNDATION PERMIT WILL
 ALSO APPLY TO THIS PERMIT AS WELL.
  
 1ST REVIEW
 ACTION: DENIED
 FROM FOUNDATION PERMIT:
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE: 713.13.(2) IF WORK HASN'T STARTED
 WITHIN 90 DAYS OF THE NOC BEING RECORDED
 SUCH NOTICE WILL BE VOID AND NO FURTHER
 IN EFFECT CAUSING IT TO BE RE-RECORDED.
  
 2) THERE SEEMS TO BE A DISCREPANCY
 BETWEEN THE PERMIT APPLICATION AND PLANS
 AS TO THE ADDRESS AS WELL AS THE
 PROPERTY CONTROL NUMBER.
 2A) PERMIT APPLICATION INDICATES 430
 HIBISCUS WHERE AS THE PLANS INDICATE 480
 HIBISCUS.
 2B) THE PCN SUPPLIED ON THE PERMIT
 APPLICATION INDICATES A SINGLE LOT. A0.2
 APPEARS TO TAKE MOST OF THE BLOCK AND
 CROSSING THE ALLEYWAY. PROVIDE A REPLAT
 INDICATING A SINGLE LOT AND NEW PCN.
 2C) BEFORE THE FOUNDATION PLAN IS
 RESUBMITTED CORRALATE ALL PLANS INTO
 THREE COMPLETE SETS AND STAPLED.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 3A) 104.4.5. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT
 OR ENLARGE A BUILDING HAS BEEN FILED, &
 PENDING ISSURANCE OF SUCH PERMIT, THE
 BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR
 THE FOUNDATION ONLY, UPON WRITTEN RE-
 QUEST OF THE OWNER AND CONTRACTOR. THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PRO-
 CEEDING AT HIS OR HER OWN RISK AND WITH-
 OUT ASSURANCE THAT A PERMIT FOR THE
 REMAINDER OF THE WORK WILL BE GRANTED
 AND THAT CORRECTIONS WILL NOT BE RE-
 QUIRED IN ORDER TO MEET THE PROVISIONS
 OF THE TECHNICAL CODE.
 3B) WHEN A FOUNDATION PERMIT IS APPLIED
 FOR IT IS UNDERSTOOD THAT INCLUDES FLOOR
 SLABS REQUIRING MEP PLANS. IF LOOKING
 FOR A PERMIT TO START WORK WITHOUT THE
 REQUIRED MEP SHEETS INDICATE WHAT WORK
 WILL BE COMPLETED UNDER THIS PERMIT.
 THE PERMIT APPLICATION BOX DESCRIPTION
 OF PROJECT SHOULD INCLUDE WHAT TYPE OF
 WORK IS TO BE COMPLETED UNDER THIS
 FOUNDATION PERMIT.
  
 4)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 5) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 7)106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
 THE STRUCTURAL PLANS START WITH
 SHEET S-1.0 BUT THE STRUCTURAL NOTES
 START WITH NUMBER (4).
 THERE IS NO MENTION OF SOILS
 REQUIREMENTS, SOILS REPORTS,
 DENSEIFICATION, NOR AUGER PILE GRADE
 BEAMS, ETC?S1.1 SOIL NOTE SOIL TO BE
 DENSIFIED TO 8,000 BY VIBROFLOTATION,
 PROVIDE REPORT.
  
 8) SEE SHEET S-1.0 FOR IMPORTANCE
 FACTOR, ASCE 7-98 TABLE 1-1/ TABLE 6-1,
 BUILDINGS AND OTHER STRUCTURES WHERE
 MORE THAN 300 PEOPLE CONGREGATE IN ONE
 AREA WILL REQUIRE THE BUILDING CATEGORY
 BE A III AND THE IMPORTANCE FACTOR OF
 1.15. SEE POOL DECK AND WALKWAYS OF
 11,697 SQ FT / 30= 390 OCCUPANT LOAD.
  
 9) SHEET S1.1 FOOTING# 440140 NOT ON
 FOOTING SCHEDULE.STEEL?
  
 10) SHEET S1.1 FOOTING 200160 NOT ON
 FOOTING SCHEDULE. STEEL? THERE ARE
 NUMEROUS FOOTERS THAT ARE NOT ON THE
 SCHEDULE AND WILL REQUIRE STEEL PLEASE
 PROVIDE INFORMATION.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PERMIT:
 12) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSLY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT
 HISTORICSURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGNCOMPLYING
 WITH ENGINEERING STANDARDS TO PRESERVE
 THE POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 13) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGHWINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 14)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 15) A0.2 BUILDING DATA PLANS INDICATE
 ONLY A TYPE I BUILDING NOT GIVEN IF
 DESIGNED AS A TYPE IA OR IB.TABLE 601
 PROVIDE INFO TABLE 601.
  
 16) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 17) A0.2 BUILDING DATA THE WRONG CODE
 FOR ACCESSIBILITY, 2004 FBC CHAPTER 11
  
 18) A0.2 PARKING CALCULATIONS INDICATE
 (9) HANDICAPPED PARKING SPACES, INDICATE
 COMPLIANCE WITH 11-4.1.2(5)(B)
 IN PARKING STRUCTURES, ONE IN EVERY
 EIGHTACCESSIBLE SPACES, BUT NOT LESS
 THAN ONE, SHALL BE "VAN ACCESSIBLE"
 AND SHALL BE DESIGNED AS REQUIRED BY
 11-4.6.3.THE VERTICAL CLEARANCE AT
 SUCH SPACES SHALL COMPLY WITH 11-4.6.5.
 ALL SUCH SPACES MAY BE GROUPED ON ONE
 LEVEL OF A PARKING STRUCTURE.WHEN SUCH
 SPACES ARE PROVIDED IN A PARKING
 STRUCTURE AND ONLY ONE IN EIGHT MEET
 THE HEIGHT REQUIREMENT OF 11-4.6.5, THEY
 SHALL BE DESIGNATED AS REQUIRED BY
 11-4.6.4.
  
 19) A0.2 PARKING CALCULATION INDICATES
 COMPLIANCE WITH 11-4.1.2 WITH 8 H.C.
 SPACES SEE TABLE 401-500 SPACES REQUIRES
 9 H.C. SPACES, PLEASE CORRECT.
  
 20) LIFE SAFETY PLANS DOES NOT INDICATE
 THE OCCUPANT LOAD PER FLOOR AND HOW THIS
 OCCUPANT LOAD IS DISTRIBUTED THROUGH
 DOORWAYS NOR THROUGH STAIRWAYS TO THE
 EXIT DISCHARGE.PLEASE ILLUSTRATE.
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
  
 21) A0.4 MEZZANINE LEVEL PROVIE THE
 SQUARE FOOT OF EACH COMMERCIAL TEANANT
 FOR THE FIRST FLOOR LEVEL AS WELL AS THE
  
 MEZZANINE LEVEL. 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
  
 22)SHEET A1.0/ A1.1
 A) DOOR# 14 PLEASE SEE NOTE ON PLANS ALL
 COMMON AREA DOORS 45 MIN RATED BUT ON
 THE DOOR SCHEDULE ONLY THE 1 1/2 HR
 RATED DOORS SHOW ON SCHEDULE. THE DOOR
 SCHEDULE WILL NEED TO SHOW ALL DOOR
 RATINGS.
  
 B)DOOR 14 AND 36 BOTH ARE OVERHEAD DOORS
 ON THE REFUSE ROOM. 707.1.13.4 REQUIRES
 THESE OVERHEAD DOOR TO BE 3/4 RATED &
 THERE ENCLOSURE, SHOW COMPLIANCE. THE
 SECOND ISSUE IS THESE UNITS ARE TO BE
 EITHER SELF CLOSING OR AUTOMATICALLY TO
 CLOSE IF SMOKE IS DETECTED.
  
 23) A1.2
 A)DOORWAY# 7 HALLWAY DOOR TO OFFICE# 004
 IS MISSING THE 18" CLEARENCE ON THE PULL
 SIDE OF LATCHING DEVISE.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 B) PROVIDE INFORMATION ON THE H.C. LIFT?
 11-4.11.2IF PLATFORM LIFTS (WHEELCHAIR
 LIFTS) AREUSED, THEY SHALL COMPLY WITH
 11-4.2.4, 11-4.5, 11-4.27, AND ASME
 A17.1 SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, SECTION XX, 1990.
  
 C) EXTERIOR STAIRS @ DOOR# 35 MISSING
 THE MAEUVERING CLEARENCES ON THE PULL
 SIDE OF LATCH, 11-4.13.6
  
 D) DOOR # 30 MISSING THE 18" REQUIRED ON
 THE LATCH SIDE OF THE DOOR, PULL SIDE.
 11-4.13.6.
  
 E) THE ELECTRICAL PLAN AND ARCHITECTURAL
 FOR THIS PORTION OF THE BUILDING DOESN'T
  
 MATCH DOOR LOCATIONS SOME ARE MISSING OR
 PLACED IN VARIOUS AREAS DEPENDING ON THE
 PLAN THE SAME ISSUE WITH STAIRS.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 F) ROOM 024 IS LABELED THE EMERGENCY
 ROOM, ELECTRICAL PLANS INDICATE LARGE
 WALL VENTS WHEREAS THE BUILDING A SOLID
 WALL, CORRECT.
  
 24) A1.3: ELEVATOR# 3 PROVIDE A CROSS
 SECTION OF WALL ACROSS FROM ELEVATOR, IS
 THIS WALL A GLASS WALL OR IS IT ONLY A
 HANDRAIL? THE PLANS APPEAR TO BE A TRUE
 MEZZANINE WHICH WILL NOT REQUIRE ATRIUM
 REQUIREMENTS. SEE ATRIUM REQUIREMENTS IF
 APPLICABLE, SEE 404.5.
  
 25) A.14: ROOM 040 PROVIDE THE OCCUPANCY
 CLASSIFICATION ON PLAN S-1 MODERATE
 HAZARD.PROVIDE WALL AND DOOR RATINGS,
 OPEMNING PROTECTIVES. TABLE 705.4,
 TABLE 715.3. ROOM 040 IS NOT AN
 ANCILLARY TO THE PARKING GARAGE.
  
 26)A1.5: ELEVATOR# 1&2/ MEZZANINE LEVEL.
 SAME SITUATION AS QUESTION# 23.
  
 27) A1.6/ A1.8 THIS SITUATION DEALS WITH
 THE 2ND FLOOR THROUGH TO & INCLUDING THE
 TOP FLOOR.
 A) ELEVATORS 1/2 & 3/4 TO COMPLY WITH:
 707.14.1 ELEVATOR LOBBY.
 ELEVATORS OPENING INTO A
 FIRE-RESISTANCE-RATED CORRIDOR AS
 REQUIRED BY SECTION 1016.1 (R2> 10 OCC
 LOAD REQUIRES 1HR RATED CORRIDORS)
 SHALL BE PROVIDED WITH AN ELEVATOR LOBBY
 AT EACH FLOOR CONTAINING SUCH A
 CORRIDOR. THE LOBBY SHALL SEPARATE THE
 ELEVATORS FROM THE CORRIDOR BY FIRE
 PARTITIONS AND THE REQUIRED OPENING
 PROTECTION. ELEVATOR LOBBIES SHALL HAVE
 AT LEAST ONE MEANS OF EGRESS COMPLYING
 WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE.
  
 B) PLANS INDICATE STORAGE UNITS, WHEN
 YOU GO TO THE 1/4" SCALE PLAN 2.4 THE
 PLANS STILL DO NOT PROVIDE WALL SECTIONS
 AS TO TYPE OF CONSTRUCTION AS FOUND ON
 A2.37. PLANS ARE INCOMPLETE AS TO WALL
 TYPES FOR MOST OF THE FLOORS.CORRECT.
 S1 STORAGE REQUIRES A 3HR WALL AND
 OPENING PROTECTIVES. SEE FIRE BARRIER
 T 715.3
  
 28) A1.21:
 A) THE EAST SIDE OF THE COVERED VARANDA
 & HEALTH CLUB DOES NOT HAVE ANY
 DIMENSION AS TO THE PROPERTY LINE, &
 PLANS DO NOT PROVIDE IF TYPE IA OR IB,
 WHICH WILL MAKE A DIFFERENCE IN
 ALLOWABLE OPENINGS
  
 B) RAMP TO SPA,
 11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
 11-4.8.4(3) IF RAMPS CHANGE DIREC-
 TION AT LANDINGS, THE MINIMUM LANDING
 SIZE SHALL BE 60" X 60".
 11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 C) THE PLANS SHOW THE ELEVATION AT 0'-0"
 WITH NO CHANGE IN GRADE TO THE INTERIOR?
  
 D) PLANS INDICATE USE OF METAL TRUSSES
 ON THE HEALTH CLUB BUT NO MENTION OF
 TYPE OF DECKING ? SEE TABLE 601 FOR 1
 1/2 HR RATING.
  
 E) PLANS INDICATE FLOOR OR ROOF DRAINS
 SEE SECTION A8.7 DETAIL E, THIS DETAIL
 INDICATES SEE SEE MECH DRAWINGS? WHERE?
 THE PLUMBING SHEET 21.9 ALSO INDICATES
 FLOOR DRAINS BUT NO SECTION THROUGH THE
 SLAB INDICATING COMPLIANCE WITH 712.4.1
 THROUGH PENETRATIONS OF HORIZONTAL
 ASSEMBLIES.
 712.4.1.1PENETRATIONS SHALL BE
 INSTALLED AS TESTED IN AN APPROVED FIRE
 RESISTANCE-RATED ASSEMBLY. PROVIDE
 ADDITIONAL INFORMATION.
  
 29) A3.0
 A) THE DOOR SCHEDULE INDICATES (2) TYPES
 OF RATED DOORS #14 & #15. THE DETAILS ON
 THIS PAGE INDICATE FRAMES AND SILLS BUT
 NO MENTION TO DOORS 14 OR 15.
  
 708.6 OPENINGS IN FIRE PARTITIONS SHALL
 BE PROTECTEDIN ACCORDANCE WITH SECTION
 715.. 715.3.3 FIRE DOOR ASEMBLIES SHALL
 ALSO MEET THE REQUIREMENTS FOR A SMOKE
 AND DRAFT CONTROL DOOR ASSEMBLIES TESTED
 IN ACCORDANCE WITH UL 1784 WITH AN
 ARTIFICIAL BOTTOM SEAL INSTALLED ACROSS
 THE FULL WIDTH OF THE BOTTOM OF THE DOOR
 ASSEMBLY.
  
 710.5.2 SMOKE AND DRAFT CONTROL DOORS,
 DOORS IN SMOKE PARTITIONS SHALL BE
 TESTED IN ACCORDANCE WITH UL 1784 WITH
 AN ARTIFICIAL BOTTOM SEAL INSTALLED
 ACROSS THE FULL WIDTH OF THE BOTTOM OF
 THE DOOR ASSEMBLY.
  
 30) A1.31:
 A) PLANS INDICATE USSE OF METAL
 TRUSSES BUT NO MENTION AS TO THE TYPE OF
 DECKING MATERIAL? TABLE 601 1 1/2 HR
 RATING.
  
 B) PLANS INDICATE A STORAGE OCCUPANCY ON
 THE ROOF? WHAT TYPE OF MATERIALS WILL BE
 STORED THERE, S1 VS S2?
  
 31) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 32)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) EXTERIOR WINDOWS FIXED
 B) EXTERIOR WINDOWS OPERATABLE
 C) MULLIONS
 D) EXTERIOR GLAZED DOORS
 E) EXTERIOR ROLL UP DOORS
 F) LOUVERS
 G) TRUSS ANCHOR ATTACHMENTS
 H) STORM SHUTTERS
 I) EFIS SYSTEMS
 J) EXTERIOR RAILINGS
 K) ROOFING ASSEMBLIES FLAT AND SLOPED
 ALL OF THE ABOVE MENTIONED PRODUCTS
 WILL REQUIRE THE DESIGNER OF RECORD TO
 SIGN OFF THAT THE REPORTS HAVE BEEN
 REVIEWEDAND APROVED BY THEIR OFFICE.
  
 34)A3.2
 A) WHY DOES THE WINDOW TYPES INDICATE
 TOWNHOUSES?
 B) NOTE # 7 INDICATES THAT THE WINDOWS
 AND DOORS ARE GOING TO BE UNDER SEPERATE
 PERMIT. THIS MEANS THIS BUILDING IS
 ACTUALLY DESIGNED AS OPEN AND NOT
 CLOSED! THE WINDOW AND DOORS WILL BE
 REQUIRED TO BE SUBMITTED AND READY FOR
 PERMIT BEFORE THE BUILDING PERMIT WIL BE
 LET.
  
 35) A4.0,A4.1, A4.2 & A4.3
 A) ALL INDICATE WOOD TRIM BRACKETS SEE
 1406.2.2ARCHITECTURAL TRIM THAT
 EXCEEDS 40 FEET (12 192 MM) IN HEIGHT
 ABOVE GRADE PLANE SHALL BE CONSTRUCTED
 OF APPROVED NONCOMBUSTIBLE MATERIALS AND
 SHALL BE SECURED TO THE WALL WITH METAL
 OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
 NONCOMBUSTIBLE- MATERIALS WHICH PASS THE
 TEST PROCEDURE SET FORTH IN ASTM E 136.
  
 B)NOTE:STANDING SEAM METAL ROOF ON
 METAL TRUSSES FOR AWNING TYPE
 SHADES.PROVIDE ENGINEERING HOW THIS
 SYSTEM IS TO BE BUILT AND IF THIS SYSTEM
 IS TO STAY IN THE OPEN POSITION DURING A
 HIGH WINDEVENT PROVIDE CALCULATIONS.
  
 C) INDICATE ON THE ELEVATIONS, PRESSURE
 ZONES FOR OPENINGS +/- FOR THE INTERIOR
 AND END ZONES (ZONES 4 & 5). ALSO
 PROVIDE THE ROOF PRESSURE ZONES FOR
 ZONES 1,2& 3.
  
 D) ELEVATIONS DO NOT PROVIDE WHERE THE
 PROPERTY LINES ARE LOCATED?
  
 36)A7.4
 A) STAIRWELL# 4 INDICATES THE USE OF A
 MECHANICAL SHAFT BUT NO DESIGNATION AS
 TO WALL TYPE? 2 HR RATED.
  
 B) A7.5 SAME STAIRWELL# 4 INDICATES THE
 MECHANICAL SHAFT INTRUDING INTO THE
 STAIRWELL NOT STOPPING AT THE 2ND FLOOR
 LEVEL.707.4 SHAFT ENCLOSURES SHALL HAVE
 A FIRE-RESISTANCE RATING NOT LESS THAN
 THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS.
  
 37) A7.6/A7.7 ELEVATOR MACHINE ROOMS
 MISING INFORMATION ON VENTS:
 A)3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR
 OR FLOORS AT THE TOP OF THE HOISTWAY,
 AND SHALL OPEN EITHER DIRECTLY TO THE
 OUTER AIR OR THROUGH NONCOMBUSTIBLE
 DUCTS TO THE OUTER AIR. NONCOMBUSTIBLE
 DUCTS SHALL BE PERMITTED TO PASS THROUGH
 THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE
 THE HOISTWAY OR MACHINE ROOM ARE
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS
 THAN THE FIRE PROTECTION RATING REQUIRED
 FOR THE HOISTWAY. HOLES IN THE MACHINE
 ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO
 PROVIDE GREATER THAN 2 INCHES (51 MM) OF
 CLEARANCE ON ALL SIDES.
  
 B) 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION
 3004.3.1 , THE AREA OF THE VENTS SHALL
 NOT BE LESS THAN 3? PERCENT OF THE AREA
 OF THE HOISTWAY NOR LESS THAN 3 SQUARE
 FEET (0.28 M 2 ) FOR EACH ELEVATOR CAR,
 AND NOT LESS THAN 3? PERCENT NOR LESS
 THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY,
 WHICHEVER IS GREATER. OF THE TOTAL
 REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY
 OPEN TYPE UNLESS ALL VENTS ACTIVATE UPON
 DETECTION OF SMOKE FROM ANY OF THE
 ELEVATOR LOBBY SMOKE DETECTORS.
  
 38) A7.8 & A7.9 INDICATE USE OF 6" BLOCK
 FOR 2 HR WALL RATING. A U.L. LISTING OF
 WHAT TYPE OF BLOCK IS NOT PROVIDING THE
 FIRE RESISTANT RATING BASED ON
 EQUIVALENT THICKNESS OF THE MASONARY
 UNIT AND TYPE OF AGGREGATE USED. THIS
 SHALL BE PROVIDED BY THE BLOCK
 MANUFACTURER.
  
 39) A.80 DETAIL# 25 IS A SHAFT WALL
 PARTITION DESIGN UL U-415. THIS DESIGN
 IS MISSING THE REQUIRED C-H STUDS IN THE
 DESIGN. CORRECT.SAME DETAIL SHOWN ON
 LS.0 CORRECT.
  
 40) A8.1 DETAIL"N" IS FOR A ROLL DOWN
 FIRE RATED DOOR WITHIN A RATED WALL.
 PROVIDE THE UL RATING FOR THE WAY THE
 ROLL DOWN ASSEMBLY BOX TAKES THE PLACE
 OF THE RATED WALL?
  
 41) A8.3 DETAIL H APPEARS THIS DETAIL IS
 MISSING THE VERTICAL BARS AT THE BOTTOM
 OF THE DETAIL THAT WILL KEEP THE 4"
 SPHERE FROM PASSING THROUGH. 1012.3
 OPENING LIMITATION.
  
 42) S-1.0 AS STATED UNDER FOUNDATION
 PERMIT NOTES START WITH NOTE# 4 FOR
 CONCRETE.
  
 A) NOTE A REFRENCES ACI 301-99
 STRUCTURAL CONCRETE,1901.2/1901.3
 CORRECT TO ACI 318-02.
  
 B) MISSING WIND DESIGN:
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO
 WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL-FORCE-RESISTING SYSTEM OF
 THE BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST),
 MILES PER HOUR (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND
 BUILDING CLASSIFICATION FROM TABLE
 1604.5 OR TABLE 6-1, ASCE 7 AND BUILDING
 CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3.WIND EXPOSURE, IF MORE THAN ONE
 WIND EXPOSURE IS UTILIZED, THE WIND
 EXPOSURE AND APPLICABLE WIND DIRECTION
 SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE
 CLASSIFICATIONS AND, IF DESIGNING WITH
 ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE
 DESIGN WIND PRESSURES IN TERMS OF PSF
 (KN/M 2 ) TO BE USED FOR THE DESIGN OF
 EXTERIOR COMPONENT AND CLADDING
 MATERIALS NOT SPECIFICALLY DESIGNED BY
 THE REGISTERED DESIGN PROFESSIONAL.
  
 43) S1-3.4- S1-3.6 TRUSS DIAGRAMS
 MISSING THE MAGNITUDE OF LOADS TO BE
 REISTED, UPLIFT, HORIZONTAL AND GRAVITY
 LOADS.
  
 44) S-4.1 SAME COMMENT 9 & 10 FOUNDATION
 SCHEDULE NOT COMPLETE.
  
 45) S-8.1-S-8.3 ELEVATIONS WITH
 PRESSURES ZONES ARE SO SMALL THE NUMBERS
 BECOME SMUGED AND ILLEGIBLE.
  
 46) PROVIDE ENERGY CALCS FOR BUILDING:
 13-400.1 PRESCRIPTIVE REQUIREMENTS.
 WHERE A PRESCRIPTIVE REQUIREMENT
 SPECIFIC TO A METHOD IS MORE STRINGENT
 THAN THE BASIC PRESCRIPTIVE REQUIREMENT,
 THE MORE RESTRICTIVE REQUIREMENT SHALL
 BE MET.
  
 47) PLANS ARE CURRENTLY IN FOR PLAN
 REVIEW, BUT WHEN PLANS ARE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR PERMIT
 APPLICATION:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715

Review Stop E ELECTRICAL
Rev No 27 Status P Date 2008-12-09 Cont ID  
Sent By dpalmer Date 2008-12-09 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2008-12-09 Time 08:28 Sent To  
Notes
2008-12-09 08:29:14 
 ** REVIEW OF REVISIONS **
  
 *** THE SUBMITTED PLANS ARE IN FACT NOT RE-STAMPS. MANY
 OF THE SHEETS ARE IN FACT REVISIONS OF PLANS ALREADY ON
 FILE.
 IN THE ROLL OF PLANS SUBMITTED 37 SUBMITTED SHEETS ARE
 RE-STAMPS AND 33 ARE REVISIONS. THIS DOES NOT INCLUDE
 THE REVIEW OF THE FIRE ALARM SHEETS. IT IS NOT KNOWN
 WHETHER OR NOT THEY ARE REVISIONS, RE-STAMPS OR BOTH.
 THE FEE BALANCE DUE FOR THE REVISED SHEETS IS $230.00.
 THE FOLLOWING IS A LIST OF THE RE-STAMPED SHEETS AND A
 LIST OF THE REVISED SHEETS.
 NOT ALL SHEETS OF THE ON FILE SET WAS SUBMITTED FOR
 RE-STAMP OR REVISIONS. AN EXAMPLE IS SHEET 8.05 WHICH
 WAS NOT IN SETS FOR EITHER.
  
 **RE-STAMPS**
 E-1.01,2.01A,2.02,2.02A,2.03,2.03A,2.04,2.05,2.07,2.08,
 2.10,2.11,2.13,2.15,2.16,2.18,2.19,2.20,2.23,2.29,2.30,
 2.31,2.32,2.33,3.01,3.02,3.03,3.04,3.05,3.06,5.01,5.02,
 6.01,6.02,8.06,8.07A, 8.07B.
  
  
 ** REVISED
 E-
 0.01,1.01A, 2.01,2.06,2.09,2.12,2.14,2.17,2.20A,2.21,2.
 22,2.24,2.25,2.26,2.27,2.28,2.34,2.35,2.36,4.01,5.03,7.
 01,8.01,8.02,,8.03,8.04,8.05A,8.05B,8.08,8.09,8.10,8.11
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 26 Status F Date 2008-10-30 Cont ID  
Sent By dpalmer Date 2008-10-30 Time 14:28 Rev Time 0.00
Received By dpalmer Date 2008-10-30 Time 14:28 Sent To PC
Notes
2008-10-30 14:28:24** DENIED REVIEW**
  
 1) NOTE: PLANS SUBMITTED FOR *RE-STAMP* ARE NOT IN FACT
 RE-STAMPS BASED ON OUR FILE SET OF LATEST ELECTRICAL
 PLANS. PLEASE SUBMIT THREE SETS OF ALL REVISED SHEETS.
 THE FOLLOWING SHEETS NOTED BELOW ARE ONLY SOME EXAMPLES
 OF SHEETS WHICH ARE REVISED HOWEVER ARE NOT IN OUR
 RECORD SET OF ELECTRICAL PLANS.
  
 E.0.01, LAST REVISED ON FILE IS REV #18
 E.1.01A LAST REVISED ON FILE IS REV #10
 E2.01 LAST REVISED ON FILE IS REV #17
 E2.05 LAST REVISED ON FILE IS REV #16
 E2.06 LAST REVISED ON FILE IS REV #16
 E2.09 LAST REVISED ON FILE IS REV #5
  
 ** THE PLANS SUBMITTED WILL BE CHARGED FEES BASED ON
 REVISIONS. THE PLANS SUBMITTED WILL HAVE A $60 ADDED TO
 THIS ROLL AS THEY WERE NOT RE-STAMPS. BALANCE TO BE
 PAID WHEN RESUBMITTING FOR REVISIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
  

Review Stop E ELECTRICAL
Rev No 25 Status P Date 2008-09-24 Cont ID  
Sent By dpalmer Date 2008-09-24 Time 10:55 Rev Time 0.00
Received By dpalmer Date 2008-09-24 Time 10:54 Sent To  
Notes
2008-09-24 10:56:41SELECTIVE COORDINATION STUDY OK. DOES NOT MATCH PLANS.
 WILL NEED REVISED PLANS.

Review Stop E ELECTRICAL
Rev No 24 Status F Date 2008-09-16 Cont ID  
Sent By dpalmer Date 2008-09-16 Time 14:43 Rev Time 0.00
Received By dpalmer Date 2008-09-16 Time 14:43 Sent To PC
Notes
2008-09-16 14:44:00 
 ** DENIED REVIEW OF SELECTIVE COORDINATION STUDY**
  
 1) NOTE: PLEASE SEE THERE ARE MANY ITEMS ON THE SCS
 WHICH DO NOT COORDINATE WITH THE PLANS ON FILE. PLEASE
 SEE 240.12,700.27 AND 701.18.
 THE FOLLOWING WILL BE SOME EXAMPLES ONLY AND ARE IN NO
 WAY ALL ITEMS ON THE REPORT WHICH DOES NOT MATCH WITH
 PLANS.
  
 A) PLEASE SEE SECTION #5 OF THE REPORT AND OTHER
 SECTIONS WHICH DO NOT SEEM TO INDICATE THE EDPH PANEL
 AS CONTAINING A MAIN CIRCUIT BREAKER. PLANS SHOW A 100K
 RATED MCB.
  
 B) PLEASE SEE THE HEC PANEL LISTED IN SECTION #5 ON
 EDPH WHICH SHOWS A 300AMP BREAKER YET THE PLANS ON FILE
 INDICATE A 150AMP BREAKER. THE PANEL HEC IS NOT EVEN
 RATED FOR 300AMPS.
  
 C) PLEASE SEE DAPPER FAULT ANALYSIS INPUT REPORT.
 SWB MSBE SHOWS COPPER BUS DUCT STAB. PLEASE VERIFY.
 PLEASE SEE OTHERS SUCH AS ATS/MSBE SHOWS COPPER, EDPH
 COPPER, FIRE PUMP COPPER, ETC ETC
 PLEASE SEE THE SIZE OF CONDUCTORS FOR ITEMS SUCH AS
 FIRE PUMP WHICH ARE SHOWN AS 3/0 COPPER YET THE RISER
 ON FILE SHOWS 250MCM ALUMINUM.
 PLEASE SEE THE DISTANCE OF FEEDERS FOR THE FIRE PUMP
 UNDER NORMAL AND EMERGENCY WHICH IS SHOWN AS 500FEET.
 THIS IS NOT POSSIBLE.
 PLEASE SEE OTHER PANELS FOR FEEDERS, DISTANCE, WHICH
 DOES NOT MATCH.
 GEHB SHOWS 3/0 ON REPORT AND SHOWS 1/0 ON PLANS. THE
 DISTANCE ON THIS FEEDER ALONE CALLS FOR 75FEET HOWEVER
 BASED ON THE LOCATION OF THIS PANEL ON THE PLANS THE
 DISTANCE IS FAR GREATER.
 HEA, 3/0 ON REPORT, SHOWS 1/0 ON PLANS.
 HEC SHOWS 3/0 ON REPORT YET SHOWS 1/0 ON PLANS.
 REHA SHOWS 500 MCM ON REPORT AND 400MCM ON PLANS.
 REHC SHOWS 500MCM ON REPORT AND 400MCM ON PLANS.
  
 **** TO BE NOTED ONCE AGAIN. THESE ARE ONLY SOME
 EXAMPLES OF THE INCONSISTENCIES AND ARE NOT ALL
 POSSIBLE COORDINATION ISSUES.
 ONE COPY OF THE REPORT WILL BE RETAINED BY THIS OFFICE.
  
 2) NOTE: PLEASE KNOW A REVISION FEE OF $60 IS DUE. FBC
 108.3
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 23 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 14:57 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 14:57 Sent To PC
Notes
2008-09-04 15:00:38REVSIONS.
  
 ***REQUIRED BEFORE TCO.
 NEED COORDINATION STUDY OF EMERGECNY
 SYSTEMS/PANELS/EQUIPMENT PER 240.12, NFPA-110 6.5
 PROTECTION.
  
 6.5.1* GENERAL. THE OVERCURRENT PROTECTIVE DEVICES IN
 THE EPSS SHALL BE COORDINATED TO OPTIMIZE SELECTIVE
 TRIPPING OF THE CIRCUIT OVERCURRENT PROTECTIVE DEVICES
 WHEN A SHORT CIRCUIT OCCURS.
  
 6.5.2 SHORT CIRCUIT CURRENT. THE MAXIMUM AVAILABLE
 SHORT CIRCUIT CURRENT FROM BOTH THE UTILITY SOURCE AND
 THE EMERGENCY ENERGY SOURCE SHALL BE EVALUATED FOR
 ABILITY TO SATISFY THIS COORDINATION CAPABILITY.
  
 6.5.3* OVERCURRENT PROTECTIVE DEVICE RATING. THE
 OVERCURRENT PROTECTIVE DEVICE SHALL HAVE AN
 INTERRUPTING RATING EQUAL TO OR GREATER THAN THE
 MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT AT ITS
 LOCATION.
  
 6.5.4 ACCESSIBILITY. OVERCURRENT DEVICES IN EPSS
 CIRCUITS SHALL BE ACCESSIBLE TO AUTHORIZED PERSONS
 ONLY.
  
  
  

Review Stop E ELECTRICAL
Rev No 22 Status P Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 14:56 Sent To PC
Notes
2008-09-04 14:57:04REV PANEL SCHEDULES ON E6.02

Review Stop E ELECTRICAL
Rev No 21 Status P Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 10:42 Sent To  
Notes
2008-07-18 10:50:57REVISIONS OK, REDLINED FBC 11-4.27.4 FOR TIMER DEVICES.
 SHALL NOT BE DEVICES WHICH REQUIRE TWISTING,/GRASPING
 ETC.
 2.01, 2.02,3.01,3.02, 3.03,3.04,3.05,3.06

Review Stop E ELECTRICAL
Rev No 20 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 14:00 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 14:00 Sent To PC
Notes
2008-06-16 14:00:40REV 6.02 OK

Review Stop E ELECTRICAL
Rev No 19 Status F Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 13:59 Sent To PC
Notes
2008-06-16 14:00:12** DENIED / PASSED REVISIONS**
  
 1) NOTE: PLEASE SEE FEEDER F-8 IS SHOWN FROM GENERATOR
 TO FIRE PUMP WITH 250AMP OVER CURRENT PROTECTION.
 PLEASE SEE 250.122 AS THE EQUIPMENT GROUNDING CONDUCTOR
 IS REQUIRED TO BE SIZED FOR THE OCP>
 PLAN SHOWS #6 WHICH IS RATED FOR 200AMPS ONLY.
 THIS COULD HAVE BEEN REDLINED HOWEVER PLANS ARE FOR
 FINAL AS-BUILTS.
  
 2) NOTE: REVISED 6.01, 6.02, 6.03 OK, STAMPED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 18 Status P Date 2008-05-20 Cont ID  
Sent By dpalmer Date 2008-05-20 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2008-05-20 Time 13:52 Sent To PC
Notes
2008-05-20 13:53:07REV #18, 0.01,2.01A,2.02,2.05, 5.01, 6.01

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2008-04-18 Cont ID  
Sent By dpalmer Date 2008-04-18 Time 13:35 Rev Time 0.00
Received By dpalmer Date 2008-04-18 Time 13:46 Sent To PC
Notes
2008-04-18 13:37:50** DENIEDREVIEW OF REVISIONS **
  
 THE FOLLOWING IS FOR ELECTRICAL REVISIONS SUBMITTED
 3/19/08 AND 4/7/08.
  
 1) NOTE: PLEASE COORDINATE ALL REVISIONS ALONG WITH
 REVISED TITLE BLOCKS AND REVISIONS ON PLANS.
 FOR EXAMPLE:
 PLEASE SEE SHEETS E0.01, E5.1 ETC WHICH ARE SIGNED,
 DATED AND SEALED ABOUT 3WEEKS APART YET THE PLANS ARE
 THE SAME. THESE SHEETS SHOW THE SAME EXACT REVISIONS.
 SHEET E0.01 DATED 3/17/08 ARE SHOWING REVISIONS 16 AND
 17 AND REVISED SHEET E0.01 DATED 4/3/08 SHOW THE SAME.
  
 THIS IS THE SAME FOR SOME OF THE OTHER SHEETS AS WELL.
 PLEASE GO THOUGH BOTH SETS, REVISE PLANS, TITLE BLOCKS
 AND SUBMIT COMPLETED SETS FOR REVIEW.
 ** PLEASE KNOW ANY OTHER REVIEW COMMENTS FOR FEEDERS
 ETC SHOULD BE INCORPORATED INTO CHANGES.
  
 2) NOTE: PLEASE SEE THIS REVIEWER'S PREVIOUS COMMENT
 WITH RESPECT TO GROUND FAULT PROTECTION ON MAINS AND
 OTHER EQUIPMENT WAS THAT THE EDPH WAS NOT TO CONTAIN
 GFP. NOW THE MSBE HAS THE GROUND FAULT PROTECTION
 REMOVE WHICH WAS LOCATED ON ORIGINAL PLANS.
 PLEASE SEE 240.13, 230.95 ETC WHICH DOES REQUIRE GFP ON
 THE MAIN. THE CODE DOES NOT REQUIRE GFP ON THE
 EQUIPMENT AFTER THE MAIN IN THIS SITUATION. THERE ARE
 SOME CIRCUMSTANCES IN THE CODE WHICH DOES REQUIRE GFP
 ON THE EQUIPMENT AFTER THE MAIN HOWEVER NOT ON THE
 EMERGENCY SIDE AND NOT IN THIS OCCUPANCY.
 PLEASE PLACE THE GFP BACK ON MSBE AND PLEASE BE SURE
 GFP IS NOT ON EDPH.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CONTACT THIS
 OFFICE.
  
 3) NOTE: PLEASE KNOW THE REVISED ENERGY CALCULATIONS
 SUBMITTED WERE NOT REVIEWED. THESE ARE CONSIDERED A
 REVISION AND WOULD BE SUBMITTED ACCORDINGLY.
 BASED ON THE FACT THAT THERE ARE CHANGES BEING MADE TO
 PLANS AND PROJECT THE REVISED CALCULATIONS SHOULD ONLY
 BE SUBMITTED FOR FINAL REVIEW ONCE *ALL* CHANGES TO
 PROJECT ARE KNOWN AND WILL BE THE FINAL REVISION BEFORE
 FINAL/CO.
 PLEASE CALL IF THERE ARE ANY QUESTIONS ON THIS.
 ** PLEASE ALSO KNOW THAT ANY REVISED ENERGY
 CALCULATIONS WILL ALSO BE REVIEWED BY MECHANICAL,
 BUILDING AND POSSIBLY PLUMBING. PLEASE BE SURE ALL
 PLANS FOR OTHER TRADES HAVE BEEN UPDATE TO THE POINT
 FOR FINAL REVIEW SO THE PLANS ON FILE WILL COORDINATE
 WITH CALCULATIONS.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 16 Status P Date 2008-01-17 Cont ID  
Sent By dpalmer Date 2008-01-17 Time 12:30 Rev Time 0.00
Received By dpalmer Date 2008-01-15 Time 20:06 Sent To  
Notes
2008-01-17 12:30:21** PROVISO**
  
 1) NOTE: PLEASE SEE SHEET E206 WHICH STILL HAS LIGHTING
 CONTROL FOR STORAGE ROOM SHOWN AS MANUAL WHEN AUTOMATED
 MEANS IS REQUIRED PER FBC 13-415.1.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SEE GF PROTECTION ON EDPH IS NOT
 PERMITTED. (REDLINED)
  
 3) NOTE: PLEASE SEE PHOTO-METRICS WERE STILL NOT
 SUBMITTED AS REQUIRED PER PREVIOUS REVIEWS AND PER LS
 101 7.8 AND 7.9.
 THESE WILL BE REQUIRED.
  
 4) NOTE: PLEASE SEE REVISED ENERGY CALCULATIONS HAVE
 ALSO NOT BEEN SUBMITTED. THESE ARE REQUIRED DUE TO
 NUMEROUS CHANGES TO ELECTRICAL LIGHTING FIXTURES.
 13-415.1.A, 13-415.2
  
 5) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 ON RISER FROM MSBE TO EDPH STILL DOES NOT CORRELATE
 WITH THE EQUIPMENT GROUNDING ON MSBE SCHEDULE. 2/0,
 3/0.
  
 6) NOTE: PLEASE KNOW THE LOW VOLTAGE PERMIT WHICH WAS
 FINALLY PULLED FOR CATV AND PHONE SYSTEM WIRING IS NOW
 ON HOLD FOR INSPECTIONS. THE APPLIED VALUE FOR ALL CATV
 AND PHONE IN BUILDING IS SHOWN AS $10K. THIS VALUE IS
 EXTREMELY LOW. THE MATERIALS COST MORE THAN THIS
 AMOUNT. A COST ANALYSIS CAN BE ASSESSED USING MARSHALS
 & SWIFT GUIDE AS ADOPTED PER FBC 108.3 IF AN
 APPROPRIATE VALUE IS NOT ADJUSTED.
  
  
 7) NOTE: PLEASE BE SURE TO GO BACK THROUGH ALL
 ELECTRICAL COMMENTS MADE TO DATE. PLEASE SUBMIT REVISED
 INFORMATION AS NEEDED AND SUBMIT CORRECTIONS AS NEEDED
 FOR SEVERAL ITEMS WHICH TO DATE HAVE STILL NOT BEEN
 ADDRESSED.
 ** PLEASE KNOW THIS WILL HOLD UP TCO AND FINAL
 INSPECTIONS. IF INFORMATION DOES NOT MEET MINIMUM CODE
 COMPLIANCE CHANGES IN SCOPE OF WORK AS SHOWN MAY BE
 REQUIRED.
 SOME ITEMS AS PREVIOUSLY REQUESTED CAN NOT BE REVIEWED
 AT THIS TIME AS THEY WERE NOT SUBMITTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PAM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 15 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 18:53 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 15:59 Sent To PC
Notes
2007-09-22 18:53:16** DENIED REVISIONS **
  
  
 ** PLEASE SEE REVISIONS DATED THE SAME DATE OF 9/22/07
 WHICH NOTES WERE PROVIDED ON REVISIONS SUBMITTED ON
 8/23/07.
 PLEASE SEE SOME ITEMS BELOW FOR REVISIONS SUBMITTED
 9/20/07 NEED TO BE ADDRESSED.
  
 1) NOTE: PLEASE SEE THESE REVISIONS INDICATE A NEW 2500
 GALLON CON-VAULT YET NO PLANS OR SUBMITTALS COULD BE
 FOUND REVISING THESE ITEMS.
 PLEASE KNOW ANY MANUFACTURES SPECS/CUT SHEETS FOR FUEL
 TANK WILL BE REQUIRED TO BE REVIEWED BY FIRE AND
 MECHANICAL REVIEWERS.
 PLEASE ALSO KNOW REVISED PLANS FOR LOCATION ETC WILL
 NEED TO BE SUBMITTED.
  
 2) NOTE: THE NEW PLANS INDICATE THE GENERATOR WILL BE
 OPERATING AT A REDUCED LOAD FOR THE EXTENDED TIMES AS
 LISTED. THERE ARE SEVERAL ITEMS ON PANELS WHICH
 INDICATE A REDUCED LOAD HOWEVER NO DETAILS ON HOW THESE
 LOADS WILL BE SHED FROM THE PANEL(S) OR THE GENERATOR
 WAS SUBMITTED.
 HOW WILL LOADS BE TAKEN FROM THE PANELS?
 HOW WILL FANS, EXHAUST ETC BE SHED AND WILL THESE
 SYSTEMS FOR VENTILATION STILL BE OPERABLE IN THE EVENT
 OF LEVELS OF AIR GO INTO HIGH LEVELS ETC.
 PLEASE PROVIDE MORE INFORMATION ON SYSTEMS, WIRING,
 DETAILS, SHEDDING OF LOADS DOWN TO THE 255 AS NOTED
 ETC.
 FBC 106.1.2 ADMIN SECTION FOR INFORMATION NEEDED.
  
 3) NOTE: PLEASE SEE THE FEEDERS ON FEEDERS SCHEDULE FOR
 F-9 ARE NOT OF SUFFICIENT SIZE FOR THE 800AMP BREAKER
 AS SHOWN FROM GENERATOR.
 240.4, 310.16.
 PLEASE ALSO VERIFY THE NEW ALUM FEEDERS FOR F-8 WHICH
 IS ONLY RATED FOR 205AMPS PER 310.16 AND BREAKER OVER
 CURRENT PROTECTION IS 250AMPS.
  
 4) NOTE: PLEASE SEE THE EQUIPMENT GROUNDING CONDUCTOR
 AS SHOWN FOR THE FEEDERS FROM MSBE TO EDPH IS SHOWN AS
 2/0 ON RISER AND 1/0 ON MSBE SCHEDULE.
 PLEASE SEE THE 2/0 ON RISER IS OK, HOWEVER THE 1/0 IS
 NOT LARGE ENOUGH PER 250.122.
 PLEASE ADJUST.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 14 Status F Date 2007-09-22 Cont ID  
Sent By dpalmer Date 2007-09-22 Time 17:36 Rev Time 0.00
Received By dpalmer Date 2007-09-22 Time 14:21 Sent To  
Notes
2007-09-22 17:36:302007-09-22 17:36:30
  
 ** DENIED REVISIONS **
 ** PASSED REVISIONS **
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEWS FOR REVISIONS WHICH STILL NEED TO BE
 ADDRESSED.
 ** PLEASE SEE THERE ARE ONLY SOME SHEETS FOR REVISIONS
 SUBMITTED 8/21 WHICH ARE OK AND WILL BE STAMPED FOR
 ELECTRICAL. THERE IS A LIST BELOW AT THE END OF REVIEW
 NOTES OF SHEETS BEING STAMPED AS OK.
  
 1) NOTE: PLEASE SEE REVIEW COMMENTS OF 6/23/07 WHICH
 REQUESTED REVISED EGRESS PHOTO-METRICS AS THE LIGHTING
 ON PLANS HAD CHANGED. THE NOTES ON PLANS MENTIONS THE
 LIGHTING REVISIONS PER REVISED PHOTO-METRICS HOWEVER TO
 THE DATE NOT REVISED PHOTO-METRICS HAVE BEEN SUBMITTED
 INCLUDING THE LATEST REVISIONS SUBMITTED ON 9/20/07. LS
 101, 708 AND 7.9
  
 2) NOTE: PLEASE SEE SHEET E-7.01 AS THIS MENTIONS
 REVISION(S) IN TITLE BLOCK HOWEVER NOT REVISED
 NUMERICAL DESIGNATION COULD BE LOCATED ON SHEET FOR
 THIS.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES DATED 6/26/07
 WHICH MENTIONED THAT REVISED ENERGY CALCULATIONS AND
 INPUT DATA REPORT WILL BE REQUIRED FOR REVIEW OF ALL
 LIGHTING.
 PLEASE KNOW ANY REVISIONS TO ANY OTHER SYSTEMS WHICH
 WITH RESPECT TO THE ENERGY CALCULATIONS WILL ALSO BE
 REQUIRED TO BE REVISED.
 PLEASE KNOW THE INPUT DATA REPORT INFORMATION WILL BE
 REQUIRED TO COORDINATE WITH ALL ELECTRICAL AND OTHER
 SYSTEMS ON PLANS.
 FBC CHAPTER 13, 13-415.A.1
  
 4) NOTE: PLEASE SEE AS OF THIS REVIEW: NO PERMITS HAVE
 BEEN APPLIED FOR WITH RESPECT TO THE LOW VOLTAGE WORK
 AS SHOWN ON PLANS.
 SEPARATE PERMITS ARE REQUIRED FOR THE PHONE, CATV ETC.
 THESE PLANS MAY BE USED FOR REFERENCE AND A
 *TURN-AROUND* PERMIT HOWEVER APPLICATION AND FEES BASED
 ON THE SCOPE OF WORK FOR ALL LV SYSTEMS IS REQUIRED.
 PLEASE KNOW ANY SECURITY SYSTEMS (AKA ALARMS) ARE A
 SEPARATE PERMIT ALSO, HOWEVER NO PLANS ARE NEEDED FOR
 *ALARM SYSTEMS ONLY*. ANY CLOSED CIRCUIT TV, ACCESS
 CONTROLS ETC FOR OTHER TYPES OF SECURITY SYSTEMS DO
 REQUIRE PERMITS AND PLANS. NO SYSTEMS OF THIS NATURE
 ARE SHOWN ON PLANS.
 **PLEASE SEE SOME REVISED SHEETS IN SETS ARE BEING
 STAMPED OK, HOWEVER PERMITS NEED TO BE APPLIED FOR. IF
 PERMITS ARE NOT APPLIED, THEN ELECTRICAL PERMIT FOR
 BASE BUILDING MAY BE PLACED IN A HOLD STATUS FOR
 ELECTRICAL INSPECTIONS.
 INFORMATION WILL ALSO BE FORWARDED TO CHIEF ELECTRICAL
 INSPECTOR TO VERIFY PERMITS IN FIELD.
  
 5) NOTE: PLEASE SEE SHEET E-206 AS SOME SWITCHES ARE
 SHOWN AS STANDARD SWITCH DEVICES WHEN AUTOMATED ARE
 REQUIRED. IS THE T NEXT TO BOTH SWITCHES IN ALL THREE
 STORAGE ROOMS FOR BOTH SWITCHES?
 13-415.1.ABC.1.1, .1.2.
  
 6) NOTE: PLEASE SEE REVISIONS SUBMITTED AS OF SEPTEMBER
 20TH, 2007 WILL BE ENTERED UNDER THE NEXT REVISION #15
 IN OUR SYSTEM. THIS REVISION AND REVIEW WILL BE DONE ON
 THE SAME DATE OF 9/22/07 AS THIS REVISION.
 THESE REVIEWS COMMENTS ARE UNDER *REV #14* IN OUR
 SYSTEM.
  
 7) NOTE: PLEASE SEE SHEET E2.02 AS THERE ARE STILL EXIT
 LIGHTS WHICH WERE ADDED TO PLANS WITH NO CIRCUITING AND
 SHOWN DIRECTING OCCUPANTS INTO THE COMMERCIAL TENANT
 BUILD OUT SPACE WHICH IS NOT PERMITTED.
 THIS SHEET WILL NOT BE STAMPED PLEASE BE SURE TO
 COORDINATE WITH OTHER REVISIONS SUBMITTED SEPTEMBER
 20TH, 2007.
  
 8) NOTE: REDLINED EQUIPMENT GROUNDING FROM MSBE TO
 EDPH, AS THIS IS SHOWN AS 1/0 CU WHICH IS NOT RATED FOR
 THE 1000AMPS. REDLINED 2/0 MIN PER 250.122
 THIS WILL BE NOTED AND FAILED IN REVSIONS SUBMITTED ON
 9/20/07. REV #15 IN OUR SYSTEM.
  
  
 ** THE FOLLOWING SHEETS ARE STAMPED AND DO NOT NEED TO
 BE REVISED. SOME ARE SUBMITTED AS REVISIONS SUBMITTED
 9/20/07.
 E0.01, 2.012.01A, 2.02A, 2.03, 2.03A, 2.20A,
 2.31,2.32,2.33,6.01 AND 6.02
  
 SHEETS E3.03, 3.04, 3.05, 3.06 AND 5.02 ARE OK, HOWEVER
 AS NOTED ABOVE IN NOTE #4 LV PERMITS ARE STILL
 REQUIRED. THESE SHEETS ARE BEING STAMPED ON THE NOTICE
 OF PERMITS TO BE APPLIED FOR AS NOTED ABOVE.
  
 ** SHEETS E- 2.02, 2.04, 2.05, 2.06, 2.17, 2.19, 2.20
 AND 7.01 ARE NOT STAMPED PER NOTES ABOVE.
  
 *** IMPORTANT**
 ONCE FIRE REVIEW IS DONE AND OK, NEED TO KEEP ONE SET
 OF ELECTRICAL SHEETS WHICH ARE STAMPED AS OK, NEED TO
 BE KEPT FOR FILE COPY.
 PLEASE DO NOT RELEASE ALL THREE SETS OF ELECTRICAL **
 PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET SUBMITTED
 FOR REVIEW AND THE CHANGES WHICH WILL BE NEEDED FOR
 SERVICE A COMPLETE REVIEW CAN NOT BE DONE AT THIS
 TIME.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-22 14:21:452007-09-22 14:21:45
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 13 Status F Date 2007-09-09 Cont ID  
Sent By dpalmer Date 2007-09-09 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2007-09-09 Time 11:18 Sent To PC
Notes
2007-09-09 11:29:482007-09-09 11:29:48
  
 ** DENIED REVISIONS # 13, 14 ETC. **
  
 1) NOTE: PLEASE SEE THE REVISED SHEETS SUBMITTED HAVE
 NOT BEEN CORRECTED TO INCORPORATE COMMENTS FROM REVIEW
 DATED 6/26/07.
 PLEASE SEE THERE ARE SEVERAL AREAS ON PLANS WHICH
 CONTAIN COMMENTS.
 PLEASE SEE THE REVIEW NOTES FROM 6/26 HAVE BEEN
 ATTACHED. PLEASE SEE NOTE #12 AS NO TCO, CO, OR
 ELEVATOR CERTIFICATION WILL BE GRANTED UNLESS MEETING
 THE NEW STATE LAWS FOR EXISTING AND NEW HIGH-RISE
 RESIDENTIAL BUILDING.
 THIS STATE LAW INCLUDES ALL BUILDINGS, EVEN STRUCTURES
 PERMITTED BEFORE LAW WENT INTO EFFECT.
  
 ** PLEASE KNOW NO FURTHER REVISIONS WILL BE STAMPED
 UNTIL COMMENTS FROM ANY PREVIOUS REVIEWS ARE
 ADDRESSED.
  
  
 ** AS STATED ON PREVIOUS REVIEWS: IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN CONTACTING THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 12:58 Sent To PC
Notes
2007-08-28 13:00:03** DENIED **
  
 LIGHTING R SUBMITTALS
  
 1) NOTE: PLEASE MAKE CORRECTIONS AS NOTED BY THE
 ENGINEER AND CORRELATE WITH THE SUBMITTED STAMPED
 PLANS.
  
 2) NOTE: PLEASE SEE THAT ALL LIGHTING SUBMITTALS NEED
 TO CONTAIN THE LISTING FROM A NRTL ON EACH FIXTURE
 CLEARLY SHOWN ON EACH.
 PLEASE SUBMIT THE STAMPED SETS FROM THE ENGINEERS
 OFFICES AND ONLY SUBMIT THREE SETS FOR REVIEW AND
 STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 12:55 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 12:55 Sent To PC
Notes
2007-08-28 12:57:30** DENIED **
  
 SWITCH GEAR SUBMITTALS
  
 1) NOTE: PLEASE MAKE CORRECTIONS AS NOTED BY THE
 ENGINEER AND CORRELATE WITH THE SUBMITTED STAMPED
 PLANS.
  
 2) NOTE: A MCB MAY BE REQUIRED ON EDPH, AS THE ATS DOES
 NOT CONTAIN THE DISCONNECT NEEDED ON THE NORMAL AND
 EMERGECNY SIDE.
 PLEASE SEE THE STAMPED PLANS.
  
 PLEASE SUBMIT THE STAMPED SETS FROM THE ENGINEERS
 OFFICES AND ONLY SUBMIT THREE SETS FOR REVIEW AND
 STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 12:52 Sent To PC
Notes
2007-08-28 12:54:49** DENIED **
  
 GENERATOR SUBMITTALS
  
 1) NOTE: PLEASE MAKE CORRECTIONS AS NOTED BY THE
 ENGINEER AND CORRELATE WITH THE SUBMITTED STAMPED
 PLANS.
  
 PLEASE SUBMIT THE STAMPED SETS FROM THE ENGINEERS
 OFFICES AND ONLY SUBMIT THREE SETS FOR REVIEW AND
 STAMPING.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 9 Status N Date 2007-08-28 Cont ID  
Sent By dpalmer Date 2007-08-28 Time 11:41 Rev Time 0.00
Received By dpalmer Date 2007-08-28 Time 11:41 Sent To FIRE
Notes
2007-08-28 11:42:25FIRE PUMP SUBMITTAL FROM 4/07 SENT TO FIRE.
 REMOVED FROM ELEC SUBMITTALS.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-06-26 Cont ID  
Sent By dpalmer Date 2007-06-26 Time 09:04 Rev Time 0.00
Received By dpalmer Date 2007-06-24 Time 15:50 Sent To  
Notes
2007-06-26 09:04:53 
  
 *** UNSAT ***
  
 ** REVISIONS TO 480 HIBISCUS ST.
  
 1) NOTE: PLEASE SEE THERE ARE NUMEROUS SHEETS WHICH
 INDICATE REVISIONS ON TITLE BLOCK AS REV 11 BUT THE
 LAST REVISION SUBMITTED TO THIS OFFICE WAS REVISION #6.
 WHAT HAPPENED TO 7, 8, 9 AND 10?
 PLEASE SEE THERE ARE SEVERAL SHEETS WHICH INDICATE SOME
 CHANGES TO SHEETS AS NOTED IN THE REVISIONS HOWEVER
 THERE ARE ITEMS WHICH ARE REVISED ON PLANS HOWEVER
 THERE IS NO INDICATION ON PLANS AT THESE LOCATIONS
 WHERE THESE ARE REVISED. (NO CLOUDS/NO TRIANGLES).
 FBC 106.1.2 COORDINATION REQUIRED.
  
 2) NOTE: PLEASE CLARIFY NEW LAYOUT ON GROUND LEVEL AND
 MEZZ LEVEL AS WHAT USED TO BE THE PREVIOUS ELECTRICAL
 ROOM IS NOW SHOWN BLANK, WITH A MISSING RATED WALL.
 PLEASE SE NEW EXIT LIGHTS WHICH DIRECT PEOPLE INTO THIS
 CLOSED IN AREA ELECTRICAL ROOM. IT APPEARS TO INDICATE
 AN EGRESS FROM THE GARAGE INTO THE GROUND LEVEL
 COMMERCIAL TENANT SPACE?
 FBC 106.1.2 COORDINATION REQUIRED.
  
 3) NOTE: PLEASE SEE THERE ARE SEVERAL NEW EXIT LIGHTS
 AND OTHER FIXTURES WITH NOT DESIGNATION FOR CIRCUITS,
 CONTROLS ETC.
 240.4.310.16.FBC 106.1.2, 106.3.5.1.2 ETC
  
 4) NOTE: PLEASE SEE TYPICAL CORRIDORS OUTSIDE STORAGE
 ROOMS WHICH NO AUTOMATED CONTROLS ARE INDICTED FOR
 LIGHTS. 13-415.1.ABC.1.1,.1.2. THIS IS TYPICAL OF
 MULTIPLE FLOORS.
  
 5) NOTE: PLEASE SEE SEVERAL NEW LIGHTING CONTROLS ADDED
 IN ROOMS WHICH INDICATE NOW A STANDARD LIGHTING SWITCH.
 PLEASE SEE MISSING CONTROLS PER 13-415.1.ABC.1.1, .1.2
  
 6) NOTE: PLEASE SEE ALL LIGHTING WHICH HAS BEEN REVISED
 ON PLANS WILL REQUIRE THE ENERGY CALCULATIONS TO BE
 COMPLETELY REVISED.
 13-415.1.AB.1.1, 13-415.2
  
 7) NOTE: PLEASE KNOW WITH THE REVISED LIGHTING ON PLANS
 WILL REQUIRE ALL THE REQUIRED EGRESS LIGHTING TO BE
 REVISED.
 PLEASE SUBMIT THE REVISED MINIMUM LEVELS UNDER NORMAL
 AND UNDER EMERGENCY.
 LS 101 7.8, 7.9
  
 8) NOTE: PLEASE SEE THERE ARE CHANGES TO POOL PATIO
 AREAS FOR LIGHTS WHICH ARE NOT NOTED ON EXPLANATION
 LETTERS AND LOCATIONS WHERE LIGHTS ARE NOT REMOVED?
 PLEASE CLARIFY WHERE THESE LIGHTS ARE? HOW ARE THESE
 AREAS GOING TO BE LIT? PLEASE SEE ELECTRICAL PANELS,
 TRANSFORMERS FOR POWER WHICH HAVE BEEN REMOVED BUT THE
 PLANS DO NOT INDICATE THIS OR NEW LOCATIONS?
 PLEASE SEE THE REVISION EXPLANATION LETTER DOES NOT
 MENTION SEVERAL OF THESE ITEMS.
 FBC 106.1.2 REQUIRED COORDINATION.
  
 9) NOTE: PLEASE SEE THE SUBMITTED EXPLANATION TO
 REVISIONS LETTER STATE SEVERAL SHEETS WHICH WERE NOT
 SUBMITTED IN PACKAGE AND THERE ARE SHEETS SUBMITTED
 WHICH ARE NOT LISTED.
 PLEAS COORDINATE.
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 221-233 APPEAR TO BE OK, HOWEVER
 INFORMATION FOR PHOTO-METRICS AND COORDINATION OF
 REVISION NUMBERS IN TITLE BLOCKS NEED TO BE ADDRESSED.
  
 11) NOTE: PLEASE SEE SHEETS 602 AND 603 WHICH LETTER
 STATES REVISED FEEDERS FOR ALUM, YET PLANS DO NOT SEEM
 TO HAVE ANY DESIGNATIONS OR REVISIONS FOR THIS?
  
 12) NOTE: *** IMPORTANT** PLEASE SEE ATTACHED INDUSTRY
 BULLETIN WITH RESPECT TO THE NEW HB 7121 WHICH REQUIRES
 FUEL FOR GENERATOR, EMERGENCY LIGHTS, EXIT LIGHTS, AND
 ONE STRETCHER ACCESSIBLE ELEVATOR FOR A PERIOD OF FIVE
 DAYS. PLEASE SEE THIS IS A NEW STATE LAW REQUIRED FOR
 NEW CONSTRUCTION, EXISTING CONSTRUCTION, EXISTING
 BUILDING WHICH MEET THE HIGH-RISE CRITERIA.
 THE SHEET IS ATTACHED AND THE ENTIRE HOUSE BILL CAN BE
 LOCATED ON THE STATE LEGISLATIVE WEBSITE.
  
 13) NOTE: PLEASE KNOW AS THERE ARE NUMEROUS SHEETS
 WHICH NEED COORDINATION OF REVISED ITEMS, NOT ALL CAN
 BE GIVEN IN DETAIL FOR EACH ITEM. ONE SET HAS REDLINED
 AREAS FOR SOME OF THESE LOCATIONS.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-24 15:53:05200-06-024 15:53:05
 ELEC SHEETS OF REVISIONS IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 19:53 Rev Time 0.00
Received By dpalmer Date 2006-12-07 Time 19:27 Sent To  
Notes
2006-12-09 19:54:55REVISION #10. STAMPED.
  
 *** SHEETS E204, 205 AND 206 NOT STAMPED AND VOIDED AS
 THESE SHEETS WERE NOT REVISED IN ANY FASHION AND NO
 REVISION WAS INDICATED ON TITLE BLOCKS. THE LAST
 REVISION FOR THESE SHEETS WERE #6 BEFORE PERMIT WAS
 ISSUED.
2006-12-09 19:22:53REVIEW IN PROGRESS

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2006-09-27 Cont ID  
Sent By dpalmer Date 2006-09-27 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2006-09-27 Time 07:23 Sent To E
Notes
2006-09-27 00:00:00*** PLEASE SEE THE RESUB FOR THE TEMP
 ELECTRICAL SERVICE WAS SUBMITTED AS A
 REVISION UNDER THIS PERMIT. PLANS ARE
 BEING GIVEN BACK TO NAT HEALY.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 07:02 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 07:02 Sent To  
Notes
2006-08-23 00:00:00ONLY NEED TO STAMP OTHER TWO SETS OF
 MEP'S.
 ELECTRICAL REVIEW HAS PASSSED.
 ALL THREE SETS STAMPED FOR ELECTRICAL.
 NOTICED SHEET P2.04 STILL MISSING FROM
 ONE SET. CALLED NAT HEALY FOR NEW SHEET
 TO COMPLETE SET.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 14:09 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 19:36 Sent To  
Notes
2006-08-21 00:00:00MOST ITEMS FROM NOTES ON 8/18 ARE
 ADDRESS, THREE SETS OF PLANS ARE NOW
 COMPLETE. NEED STAMPING AND THEN
 ELECTRICAL CAN GO INTO A PASSED STATUS.
2006-08-20 00:00:00** UNSAT **
  
 ** PLEASE SEE NOTES ADDED TO THIS REVIEW
 "IN" STOP ON FRIDAY 8/18/06.
 PLANS TO REMAIN IN "F" STATUS UNTIL ALL
 ITEMS FROM 8/18/06 ARE ADDRESSED AND
 SUBMITTED.
 PLEASE KNOW THIS REVIEWER IS UNABLE TO
 TO STAMP ALL THREEE SETS OF PLANS AS
 ONLY ONE SET IS COMPLETE AT THIS TIME.
  
  
 ** ALL ELECTRICAL COMMENTS ON PLANS ARE
 ADDRESSED AND THE ONE COMPLETE SET OF
 ELECTRICAL PLANS ARE STAMPED. OK.
  
 ** STILL NEED TO REVIEW ENERGY
 CALCULATIONS.
  
 ** TEMP IN "F" STATUS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-08-18 00:00:00CALLED ARCHITECT AND OWNER'S
 REPRESENATIVE AFTER GOING THROUGH ALL
 BOXES AND M>E>P>FA>AND FP PLANS.
 MENTIONED THE FOLLOWING WAS NEEDED AND
 WHAT WAS MISSING.
  
 1) NOTE: MISSING THE FOLLOWING SHEETS
 FROM SETSOF MEP'S.
  
 SET #1 MISSING
 E1.01, 2.09,2.12,2.15,2.18, 2.20A,
 2.21,2.24,2.27. ELECTRICAL SHEETS.
 P 2.04, 2.32 PLUMBING SHEETS.
  
 SET #2 MISSING
 E2.36 AND FA 1.03
  
  
 2) NOTE:PLEASE SEE ALL 6 SETS OF SOIL
 REPORTS (ONLY 3 NEEDED) ARE INFACT
 RAISED SEALS OF PHOTO-COPIED SIGNATURES
 FROM THE ENGINEER. THESE ARE REQUIRED TO
 HAVE AN ORIGINAL SIGNATURE PER FS
 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE ALL THREE COPIES OF
 SURVEY'S ALSO CONTAIN A RAISED SEAL OVER
 PHOTO-COPIED SIGNATURES.
 FS 472.025
  
 4) NOTE: PLEASE SEE NUMEROUS VOLUMES FOR
 STRUCTURAL CALCULATIONS WERE SUBMITTED.
 WE ONLY NEED THREE OF EACH, THE
 FOLLOWING WAS SUBMITTED:
  
 VOL I, 5 SETS, ONLY 2 SIGNED AND SEALED.
 VOL II, 6 SETS, NOT SIGNED, OR SEALED.
 VOL III, 4 SETS, NOT SIGNED OR SEALED.
 VOL IV, 5 SETS, NOT SIGNED, OR SEALED.
 VOL V, 3 SETS, NOT SIGNED OR SEALED.
 VOL VI, 3 SETS , NOT SIGNED OR SEALED.
 VOL VII, 3-SETS , NOT SIGNED OR SEALED.
 ** PLEASE KNOW, ONLY THREE OF EACH ARE
 NEEDED. ALL ADDITIONAL SETS/VOL'S WILL
 BE RETURNED.
  
 5) NOTE: MISSING THREE COMPLETE SETS OF
 FIRE PUMP AND FIRE PUMP CONTROLLER. ONLY
 ONE COMPLETE SET FOR ALL NEW WAS
 SUBMITTED.
 MADE COPIES OF THE ONE CORRECT SET, HOLE
 PUNCHED, PLACED IN BINDERS AND TABBED
 EACH FOR FP, FPC, GEN, AND ATS.
  
 6) NOTE: PLEASE SEE ALL THREE SETS OF
 THE 2004 FBC ENERGY CALCULATIONS ARE
 PHOTO-COPIES OF SIGNED AND SEALED
 CALCULATION SHEETS. ALL THREE BINDERS
 CONTAIN THE SAME.
 FS 471.025, FAC 61G15-23.002
  
 7) NOTE: RESPONSE'S FROM DEL LOS REYES
 ENGINEERING WHICH ALSO CONTAINS
 STRUCTURAL INFORMATION AND SOME OF THE
 VOL'S FOR STRUCTURAL CALCULATIONS STILL
 CONTAIN A SEAL WHICH IS NO LONGER VALID
 IN THE STATE OF FLORIDA PER RULING UNDER
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEER'S DATED FEB 04. 61G15-23.001
 ALL SEALS AFTER DEC 31ST, 2005 SHALL
 CONTAIN THE WORDING "LICENSE".
 "CERTIFICATE" IS NO LONGER ACCEPTABLE.
  
 ** A MEETING HAS BEEN SCHEDULE FOR
 MONDAY 8AM TO 12PM.
  
 ONE ROLL OF ELECTRICAL IS COMPLETE AND
 IN ELECTRIC FOR REVIEW.
 REVIEW IN PROGRESS.
  
 IF THERE ARE ANY QUESTIONS ON THE ABOVE
 PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-30 Cont ID  
Sent By dpalmer Date 2006-07-30 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2006-07-30 Time 14:07 Sent To  
Notes
2006-07-30 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
 REVIEW IN PROGRESS.
 *********** UNSAT 3RD REVIEW **********
  
  
 ** THIS OFFICE HAS STATED ON NUMEROUS
 OCCASIONS FOR THE DESIGN TEAM TO TAKE
 SOME ADDITIONAL TIME BEFORE RESUBMITTING
 PLANS AND EVEN AFTER RESUBMITTING PLANS
 TO GO OVER PLANS CAREFULLY. THIS OFFICE
 HAS STATED IF DESIGN TEAM FINDS ITEMS
 BEFORE REVIEWS ARE STARTED THEN THOSE
 SHEETS MAY BE CHANGED OUT. PLEASE SEE
 THE FOLLOWING COMMENTS BELOW.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES WHICH NEED TO
 BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE LOWER PORTION OF
 REVIEW COMMENTS.
  
  
 CITY PALMS
 10-STORY CONDO
  
 1)NOTE: NO. PLEASE SEE COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 NOTE #1, NO, PLEASE SEE NEW NOTE
 PERTAINING TO THE NEW 2004 FBC AND
 CHAPTER 13.
  
 ** PREVIOUS REVIEW **
 PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY AND WERE NOT
 SUBMITTED FOR PERMIT BEFORE THE CODE
 CHANGE OF OCT 1ST, 2005 TO THE NEW
 2004 FBC.
 PLEASE SEE THAT ANY CHANGES WILL BE
 NEEDED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: OK.
  
 3)NOTE: OK.
  
 4)NOTE: OK.
  
 5)NOTE: OK, HOWEVER PLEASE KNOW THE YEAR
 STATED ON PREVIOUS NOTE FOR NFPA-20 WAS
 1999 WHICH WAS MIS-STATED. THIS SHOULD
 HAVE BEEN 2003. IN EITHER CASE THIS CAN
 BE REDLINED AND NOTHING FROM THE 1999 TO
 THE 2003 APPEARED TO CHANGE DESIGN OR
 AFFECT PLANS.
  
  
 6)NOTE: OK.
  
 7)NOTE: NO, PLEASE SEE PHOTO-METRICS
 PROVIDED. PLEASE SEE SHEETS FOR CORIDORS
 AND STAIRS SHOW LEVELS 7-8 ONLY.
 SEE SHEETS WHICH INDICATE GRND FLOOR AND
 2-5 ONLY CONTAIN SOME AREAS. PLEASE SEE
 MSSING OTHER LEVELS ETC.
 PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR
 ALL COMMON AREA EGRESS PATHS.
 IF ALL CORRIDORS GOING UP THROUGH
 BUILDIGN ARE THE SAME, THESE CAN BE ON
 TYPICAL FLR DETAIL FOR FLRS "X"-"?".
  
 ** PREVIOUS REVIEW NOTE **
 NOTE #7NO, PLEASE SEE SOME
 WERE SUBMITTED FOR GARAGE AND CORRIDORS,
 HOWEVER STAIRWAYS COULD NOT BE LOCATED.
 PLEASE ALSO KNOW, LEVELS UNDER EM POWER
 SHALL BE PROVIDED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE COMPLETE "PHOTO-METRICS"
 FOR ALL CORRIDORS, STAIRWELLS AND EGRESS
 AREAS PER 2003 NFPA-101 7.8 AND 7.9.
 PLEASE SEE A MIN OF 10 FT CANDLES IS NOW
 REQUIRED FOR STAIR TOWERS UNDER NORMAL
 EGRESS CONDITIONS.
  
 8)NOTE: OK.
  
  
 8)NOTE: OK.
  
 9)NOTE: OK.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 14)NOTE: OK.
  
 15)NOTE: OK.
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
 18)NOTE: OK.
  
 19)NOTE: OK.
  
 20)NOTE: OK, HOWEVER SEE NEW NOTE.
  
 ** PREVIOUS NOTE **
 PLEASE SHOW CIRCUITING FOR ALL UNITS AND
 CORRELATE WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE KNOW, CODE COMPLIANCE
 FOR SOME ITEMS CAN NOT BE DONE AT THIS
 TIME.
  
 21)NOTE: OK.
  
 22)NOTE: OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: OK.
  
 26)NOTE: OK.
  
 27)NOTE: OK.
  
 28)NOTE: OK.
  
 29)NOTE: OK.
  
 30)NOTE: OK.
  
 31)NOTE: OK.
  
 32)NOTE: OK.
  
 33)NOTE: OK.
  
 34)NOTE: OK.
  
 35)NOTE: OK.
  
 36)NOTE: OK.
  
 37)NOTE: OK, HOWEVER NOTE PERTAINING TO
 THE GROUNDING AND THE GENERATOR BEING
 SEPARATELY DERIVED WAS REMOVED. THE NOT
 SHOULD HAVE REMAINED, ONLY ADJUSTED TO
 READ GENERATOR IS SEPARATELY DERIVED.
  
 ** PREVIOUS REVIEW NOTE **
 NOTE #37 NO, PLEASE SEE NO
 SPECS WERE SUBMITTED. PLEASE ALSO SEE
 RISER INDICATES THE 4-POLE ATS, HOWEVER
 NOTES MENITON THIS IS NOT A SEPARATELY
 DERIVED GENERATOR? PLEASE SEE AS A
 4-POLE ATS, THE GEN IS "SEP DERIVED" AND
 GROUNDING SHALL BE DONE ACCORDINGLY.
 PLEASE SEE MISSING BONDING AT FIRST
 MENAS OF DISCONNECT , EQUIPMENT GROUNDD
 ETC. PLEASE SEE NFPA-110 6.2.15*. PLEASE
 VERIFY WITH MANUFACTURE OF EQUIPMENT.
 PLEASE SEE NEW NOTES FOR ATS AND MAIN.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL INFORMATION
 FOR GENERATOR/ ATS. PLEASE SUBMIT THE
 SPECS/CUT FROM MANUFACTURE.
 PLEASE VERIFY OF THE ATS WILL BE A
 4-POLE SWITCH.
 PLEASE SEE 700.7D AND IF YOU HAVE THE
 HANDBOOK, SEE EXPLANATION OF ARTICLE.
 I HAVE ATTACHED BOTH, JUST IN CASE.
  
 (D) GROUND FAULT. TO INDICATE A GROUND
 FAULT IN SOLIDLY GROUNDED WYE
 EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS
 TO GROUND AND CIRCUIT-PROTECTIVE
 DEVICES RATED 1000 AMPERES OR MORE. THE
 SENSOR FOR THE GROUND-FAULT SIGNAL
 DEVICES SHALL BE LOCATED AT, OR AHEAD
 OF, THE MAIN SYSTEM DISCONNECTING
 MEANS FOR THE EMERGENCY SOURCE, AND THE
 MAXIMUM SETTING OF THE SIGNAL
 DEVICES SHALL BE FOR A GROUND-FAULT
 CURRENT OF 1200 AMPERES. INSTRUCTIONS
 ON THE COURSE OF ACTION TO BE TAKEN IN
 EVENT OF INDICATED GROUND FAULT
 SHALL BE LOCATED AT OR NEAR THE SENSOR
 LOCATION.
  
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT
 REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE
 OF THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT
 OF A GROUND FAULT IS INAPPROPRIATE.
 DETECTION OF SUCH A FAULT, HOWEVER, IS
 DESIRABLE SO THAT THE CONDITION CAN BE
 CORRECTED.
 IN MY READING AND THE INFORMATION FROM A
 COULE OF MANUFACURES OF ATS SWITCHES, A
 4-POLE ATS IS REQUIRED. PLEASE RESERCH
 THE INFORMATION AND ADJUST.
  
 38)NOTE: OK.
  
 39)NOTE:OK, HOWEVER SEE NOTE ABOVE
 ABOUT THE GEN BE SD.PLEASE ALSO SEE THAT
 SINCE ONLY ONE "DRAWING KEYNOTE RISER'
 IS SUBMITTED FOR REVIEW. PLEASE SEE NOTE
 #11 MISPRINTS STATING 230.79 TWICE.
  
 ** PREVIOUS REVIEW NOTE **
 NOTE #39 YES/ NO, PLEASE NOW
 SEE TWO SETS OF DRAWING KEYNOTES, WHICH
 AS NOTED IN ONE SET MOST DO NOT
 CORRELATE WITH RISER DIAGRAM. PLEASE SEE
 SOME COMMENTS FOR OTHER.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE DRAWING KEYNOTES TO
 CORRELATE WITH PLANS.
  
 40)NOTE: OK.
  
 41)NOTE: OK.
  
 42)NOTE: OK.
  
  
 **************************************
 *************************************
 ******** NEW NOTES 2ND REVIEW *********
  
  
 43) NOTE: NO, PLEASE SEEE THE ONLY TYPE
 WRITTEN RESPONSE WAS DATED FEB 2006.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, A FULL AND
 COMPLETE TYPE WRITTEN RESPONSE FROM THE
 DESIGN TEAM WHICH RESPONSES TO THE PLANS
 REVIEWERS COMMENTS WILL HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS. THIS
 NUMERICAL REPONSE WILL HELP TO
 ALLEAVIATE ANY BACK AND FORTH QUESTIONS
 OR CONFUSION.
 NO, RESPONSE LETTERS WERE SUBMITTED WHEN
 PLANS WERE BROUGHT BACK FOR REVIEW.
  
 44) NOTE: NO, SAME NOTE. PLEASE SEE THE
 SAME BOOKS AND CALCULATIONS WERE
 SUBMITTED BACK WITH ANY CORRECTIONS OR
 CHANGES.
 PLEASE SEE MOST OF THE BOOKS AND
 CALCULATIONS ARE NOT SIGNED, DATED OR
 SEALED AND THE ONES THAT ARE SIGN/SEALED
 ARE STILL THE SAME. PLEASE SEE THIS SEAL
 WITH THE WORDING OF "CERTIFICATE" IS NO
 LONGER ACCEPTABLE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ALL PLANS, SHEETS,
 DOCUMENTS BEING SIGNED, DATED OR SEALED
 BY A LICENSED PE, SHALL ONLY CONTAIN A
 SEAL WITH THE WORDING OF "LICENSE".
 PLEASE SEE A RULING BY THE FLORIDA BOARD
 OF PROFESSINAL ENGINEERS DATED IN
 FEBUARY "04", RULED IN 61G15-23.001,
 THAT ALL SEALS SHALL NO LONGER USE
 "CERTIFICATE" IN SAID SEAL. PLEAS KNOW,
 AN EXTENSION WAS GIVEN TO THE DATE OF
 DEC. 31ST , 2005.PLEASE SEE THIS IS
 NOT A COMMENT FOR STEVEN FELLER AS SEAL
 IS CORRECT. PLEASE SEE OTHER DOCUMENTS
 SUBMITTED DO CONTAIN THE SEAL WHICH IS
 NO LONGER ACCEPTABLE.
 PLEASE SEE DE LOS REYES ENG.AND ANY
 OTHERS WHICH MAY STILL BE UTILIZING OLD
 SEAL.
 PLEASE KNOW, THIS COMMENT IS MADE FOR
 ALL PLANS AND DOCUMENTS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 45) NOTE: NO, PLEASE SEE CALCULATIONS
 ARE STILL SHOWING ALL CALCULATIONS FROM
 THE 2001 FBC. PLEASE SEE THESE WERE
 SIGNED AND SEALED AFTER THE CODE CHANGE
 YET STILL WERE DONE UNDER THE 2001 FBC.
 PLEASE SEE CALCULATIONS CAN NOT BE
 VERIFIED FOR COMPLIANCE OF LIGHTING
 LEVELS, CONTROLS ETC.
 PLEASE BE SURE THE CALCUALTIONS MEET THE
 PERFORMANCE CALCULATIONS PER
 13-415.1.AB.1,13-415.2.ABC.1, TABLES
 415.2.C.1, 415.2.B.1 ETC
 PLEASE ALSO SEE NUMEROUS AREAS/ROOMS
 WHICH FALL UNDER SEPARATE SPACES ON
 MULTIPLE FLOORS WHICHSTIL DO NOT
 CONTAIN REQUIRED CONTROL DEVICES. PLEASE
 KNOW, IN A MEETING HELD BEFORE PLANS
 WERE SUBMITTED THE FUTURE RETAIL
 COMMERICAL SPACES WERE SHOWN WITH TIME
 CLOCKS AND OVER RIDES DEVICES AND THE
 COMMENT WAS MADE BY THIS REVIEWER THAT
 ONLY THE TC'S WERE NOT REQUIRED IF AN
 TIMED DEVICE OR OCCUPANCY SENSOR WAS
 PRESENT. PLEASE SEE ALL LIGHTING
 CONTROLS WERE REMOVED COMPLETELY>???
 PLEASE SEE SECTION BELOW FOR SEPARATE
 SPCES.
 MOST OF THESE AREAS HAVE BEEN REDLINED
 AND HIGHLIGHTED FOR MISSING CONTROLS
 REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER
 13, 13-415.1.ABC.1.1, &.2, &.3.
 PLEASE SHOW AND PROVIDE DEVICES,
 CONTROLS ETC FOR ALL AREAS NOW REQUIRED
 TO CONTAIN ENERGY CONSERVATION MEASURES.
 PLEASE SEE 13-413.1ABC.1 AND PROVIDE
 NOTES/WORST CASE FOR VOLTAGE DROP.
 PLEASE SEE 13-415.1.ABC.2 FOR AREA
 LIGHTING.
 PLEASE SEE THESE CHANGES ARE COMPLETELY
 DIFFERENT FORM THE 2001 FBC.
 THESE CHANGES BECAME FEDERALLY MANDATED
 FOR ALL STATES TO COMPLY IN THE NEXT
 CODE CYCLE/CHANGE. THIS FEDERAL MANDATE
 WAS PASSED JULY 2004
 PLEASE SEE NOTE #1 FROM PREVIOUS REVIE
 MENTIONED TO SEE ALL 2004 FBC FOR ALL
 CHANGES IN DESIGN AS PROJECT WAS NOT
 SUBMITTED FOR PERMIT UNDER THE 2001 FBC.
  
 46) NOTE: OK.
  
 47) NOTE: OK, HOWEVER SEE NEW NOTES DUE
 TO INFORMATION SUBMITTED FOR GENERATOR.
  
 ** PREVIOUS REVIEW NOTE **
 A) PLEASE SEE NFPA-110, 7.9.3.1,
 GALVANIZED LINES SHALL NOT BE USED FOR
 PIPNG TO GENERATOR. THIS IS NOTED FOR
 PLUMBING/ ENGINEERING AS SOME LOCATIONS
 IN THE JURISDICTION HAS INSTALLED THESE
 AND HAVE HAD TO CHANGE TYPES OF PIPING.
 PLEASE KNOW THIS IS A NOTE AT THIS TIME
 FOR INFORMATIONAL PURPOSE ONLY.
 B) PLEASE ALSO SEE NFPA-20, NFPA-110 ,
 NOTES AND SPECS FOR FUEL TYPE AND
 STORAGE WAS NOTE SUBMITTED, PLEASE SEE
 MIN RUNNING TIME CAN NOT BE VERIFIED.
 PLEASE SEE 6-6.2 FOR A MIN OF 8 HRS
 @100% ALONG WITH ALL OTHER MIN REQUIRED
 LIFE SAFETY LOADS.
 THE AMOUNT OF FUEL, AND GPH SHOULD BE
 NOTED ON PLANS. ONE OF THE DRAWING KEY
 NOTES MENTIONS 500 GAL TANK?TBD.
  
 48) NOTE: OK.
  
 49) NOTE: NO, PLEASE SEE SOME FIXTURE
 DESIGNATIONS ARE STILL NOT ON PLANS.
 PLEASE SEE REDLINED PLANS. EXAMPLE:
 PLEASE SEE FIXTURE ON 2.04, COMM #4
 SPACE. PLEASE SEE SOME FIXTURES ON
 PLANS DO NOT CONTAIN FIXTURE
 DESIGNATIONS.
 "REDLINED ON PLANS"
  
 50) NOTE: OK.
  
 51) NOTE: OK.
  
 52) NOTE: OK.
  
 53) NOTE: OK. SEE NEW NOTES.
  
 54) NOTE: OK.
  
 55) NOTE: NO, PLEASE SEE THAT THE
 GENERATOR IS A SD SYSTEM AND THE FIRST
 MEANS OF DISCONNECT PER 250.24B IS NOW
 THE BREAKER(S) LOCATED ON THE GEN.
 PLEASE SEE FEEDERS F-8 AND F-9 AS THESE
 WILL BOTH REQUIRED "EQUIPMENT GROUNDING
 CONDUCTORS".
 210.110,250.24B,250.122
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PREVIOUS NOTE WITH
 RESPECT TO THE ATS AND 4-POLE,
 SEPARATELY DERIVED SYSTEM.
 PLEASE SEE 250.6,250.24B AND 250.122 FOR
 SIZING ANY EQUIPMENT GORUNDING
 CONDUCTORS.
  
 56) NOTE: OK.
  
 57) NOTE: OK.
  
 58) NOTE: NO, SAME COMMENT, THIS WAS
 REDLINED ON PLANS ONCE AGAIN.
 PLEASE SEE "LOAD SUMMARY" ON E5.01,
 PLEASE SE "*" AS NOTE, AND ADDED "*"
 NEXT TO THE LINE FOR FIRE PUMP.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOAD SUMMARY FOR
 FIRE PUMP ON RISER WHICH CONTAINS AN "*"
 ASTERISK FOR NOTE OF MAGNETIC ONLY 6X
 LR, HOWEVER THIS "*" IS NOT ABOVE FOR
 FIRE PUMP. SEE REDLINES THIS IS NOTED AS
 PLANS ARE COMING BACK FOR COMMENTS.
  
 59) NOTE: OK.
  
 60) NOTE: OK.
  
 61) NOTE: NO, THIS IS YET TBD. THIS DOES
 NOT NEED TO BE DONE OR NOTED ON PLANS
 NOW. IF INFORMATION WAS OBTAINED FROM
 THE LAST MEETING PLEASE PLACE ON RISER.
 PLEASE KNOW THE ARCHITECT WAS GOING TO
 CALL TO FIND THIS OUT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ELEVATION FOR
 EPSS. PLEASE SEENFPA-110 7.2.3*,THE
 ELEVATION OF THE EPSS SHALL BE 6" ABOVE
 THE "SLOSH" PREDICATION LEVELS.
 "SEA, LAKE, OVERLAND SURGES BY
 HURRICANCES. CHARTS BASED ON SURGES FROM
 A CAT 4 STORM.
  
 62) NOTE: OK, HOWEVER PLEASE BE SURE TO
 DO THE SAME.
  
 ** PREVIOUS REVIEW NOTE **
 WHEN AND BEFORE RESUBMITTING
 PLANS, PLEASE COMPLETELY REMOVE ANY AND
 ALL OLD/VOIDED SHEETS FROM SETS. PLEASE
 ONLY INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 PLEASE KNOW, THIS WAS DONE ON THIS
 SUBMITTAL.
  
 ***************************************
 ****** NEW NOTES 3RD REVIEW *********
  
 63) NOTE: PLEASE KNOW,THIS IS THE FIRST
 REVIEW WHERE MANUFACTURE SPECS/CUT
 SHEETS HAVE BEEN SUBMITTED FOR A
 COMPLETE REVIEW OF THE GENERATOR. PLEASE
 SEE THAT PLANS AND DESIGN HAS CHANGED
 FROM PREVIOUS PLANS WHICH CONTAINED A
 DAY TANK LOCATED IN THE ROOM. PLEASE SEE
 NFPA-20 (2003)OR 1999 AS BOTH REQUIRE
 THE SAME.
 9.6.2.2 THE FUEL SUPPLY CAPACITY SHALL
 BE SUFFICIENT TO PROVIDE 8 HOURS OF FIRE
 PUMP OPERATION AT 100 PERCENT OF THE
 RATED PUMP CAPACITY IN ADDITION TO THE
 SUPPLY REQUIRED FOR OTHER DEMANDS.(2003)
 OR
 6-6.2* (1999)
 THESE POWER SOURCES SHALL COMPLY WITH
 SECTION 6-4 AND SHALL MEET THE
 REQUIREMENTS OF LEVEL 1, TYPE 10, CLASS
 X SYSTEMS OF NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS. THE
 FUEL SUPPLY CAPACITY SHALL BE SUFFICIENT
 TO PROVIDE 8 HOURS OF FIRE PUMP
 OPERATION AT 100 PERCENT OF THE RATED
 PUMP CAPACITY IN ADDITION TO THE SUPPLY
 REQUIRED FOR OTHER DEMANDS.
  
 ** PLEASE KNOW UPON THE REVIEW OF SPECS,
 THE GENERATOR SHOWS A CONSUMPTION OF
 119GPH OR 450LPH. PLEASE SEE BASED ON A
 500 GAL SUB- BASE TANK THIS WOULD ONLY
 PROVIDE ENOUGH FUEL FOR 4.20 HRS. PLEASE
 ADJUST GENERATOR FOR ONE THAT WILL RUN
 ON SUBSTANTIALLY LESS FUEL OR INCREASE
 TANK SIZE.
 PLEASE SUBMIT SPEC/MANUFACTURE SHEETS ON
 FUEL TANK IF GOING TO A LARGER TANK OR
 SUBMIT SPECS/MANIFACTURE SHEET IF
 CHANGING GENERATOR.
  
 64) NOTE: PLEASE SEE UNIT "B1" MISSING
 CIRCUIT #22 ON PANEL SCHEDULE. (THIS CAN
 BE REDLINED).
  
 65) NOTE: PLEASE SEE ATTACHED COPY OF
 THE FS 553.80(2)(B) WIHT RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 FOR CODE COMPLIAMCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
 66) NOTE: WHEN RESUBMITTING PACKAGES,
 PLEASE PLACE ALL SPEC/MANUFACTURES CUT
 SHEETS IN BINDERS WITH TABS/LABELS FOR
 EASY LOCATING AND REVIEW. PLEASE SEE
 MANY SHEETS ARE ONLY PLACED INDIVIDUALLY
 IN BOXES OR IN FOLDERS.
 PLACING PRODUCT APPROVALS AND SPEC IN
 BINDERS WOULD GREATLY HELP IN THE REVIEW
 PROCESS ALSO.
  
 ** PLEASE SEE LOCATIONS ON PLANS IN
 WHICH MANY OF THE ABOVE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS OF COMMENTS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-08 Cont ID  
Sent By dpalmer Date 2006-05-08 Time 19:48 Rev Time 0.00
Received By dpalmer Date 2006-05-04 Time 20:04 Sent To  
Notes
2006-05-08 00:00:00REVIEW IN PROGRESS
 *********** UNSAT ************
  
 ** 2ND REVIEW, 1ST REVIEW UNDER PERMIT.
 PLEASE KNOW, WILL ALSO HAVE ONE FREE
 RESUB FOR NEXT REVIEW.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES WHICH NEED TO
 BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED TO THE LOWER PORTION OF
 REVIEW COMMENTS.
  
 *** UNSAT ***
  
 CITY PALMS
 10-STORY CONDO
  
 1)NOTE: NOTE #1, NO, PLEASE SEE NEW NOTE
 PERTAINING TO THE NEW 2004 FBC AND
 CHAPTER 13.
  
 ** PREVIOUS REVIEW **
 PLEASE KNOW, PLANS WERE SUBMITTED FOR
 "PLAN REVIEW" ONLY AND WERE NOT
 SUBMITTED FOR PERMIT BEFORE THE CODE
 CHANGE OF OCT 1ST, 2005 TO THE NEW
 2004 FBC.
 PLEASE SEE THAT ANY CHANGES WILL BE
 NEEDED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 OK, HOWEVER SEE NOTE
 WITH RESPECT TO 110.26 AND ELECTRICAL
 ROOMS AND SOME ELECTRICAL EQUIPMENT AND
 REQ'D CLEARENCE.
  
 4)NOTE: NOTE #4 OK
  
 5)NOTE: NOTE #5 NO, PLEASE KNOW, PLANS
 SHALL BE SPECIFIC TO THE CODE IN EFFECT
 AND THE DESIGN IN WHICH THE BUILDING IS
 BUILT.
 PLEASE REFERENCE THE FOLLOWING CODES, AS
 THESE CODES WERE NOT FOUND ON THE
 ARCHITECTURAL PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-110, 1999 NFPA-20.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE PLANS ARE SPECIFIC TO
 THE 2002 NEC WHICH IS CURRENTLY IN
 EFFECT.
 PLEASE KNOW: DEPENDING ON WHEN PLANS ARE
 SUBMITTED FOR PERMIT, A CODE CHANGE TO
 THE 2005 NEC SHOULD BE COMING ABOUT IN
 MID 2006.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE #7NO, PLEASE SEE SOME
 WERE SUBMITTED FOR GARAGE AND CORRIDORS,
 HOWEVER STAIRWAYS COULD NOT BE LOCATED.
 PLEASE ALSO KNOW, LEVELS UNDER EM POWER
 SHALL BE PROVIDED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE COMPLETE "PHOTO-METRICS"
 FOR ALL CORRIDORS, STAIRWELLS AND EGRESS
 AREAS PER 2003 NFPA-101 7.8 AND 7.9.
 PLEASE SEE A MIN OF 10 FT CANDLES IS NOW
 REQUIRED FOR STAIR TOWERS UNDER NORMAL
 EGRESS CONDITIONS.
  
 8)NOTE: NOTE #8 OK, PLEASE SEE NEW
 COMMENTS FOR GEN RM.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE THERE ARE EMERGENCY
 BATTERY BACK UP TYPE FIXTURES LOCATED IN
 ALL ELECTRICAL ROOMS, ELEVATOR EQUIPMENT
 ROOMS, FIRE PUMP, GENERATOR, AND FIRE
 COMMAND ROOM.
 PLEASE KNOW, SOME OF THESE ARE ALREADY
 SHOWN ON PLANS, HOWEVER SOME AREAS MAY
 BE REDLINED FOR THESE.
 NFPA-101 7.8,7.9, NEC 700.16 ETC.
  
 8)NOTE: NOTE #8 ( # MISPRINT)NO, PLEASE
 SEE STAIRS INDICATE A BATTERY ABCK UP AT
 EVERY OTHER LEVEL WHICH IS OK. PLEASE
 SEE CORRIDORS AND GARAGES EGRESS PATHS
 ARE TO CONTAIN A MININUM OF SOME SORT OF
 BATTERY BACK UP TYPE FIXTURE TO PROVIDE
 A MINIMAL AMOUNT OF LIGHT TO ACCESS THE
 EGRESS TOWERS . LOCATIONS CAN BE GONE
 OVER IN A MEETING WHICH IS MOST CERTAIN
 FORTH COMING AFTER ALL REVIEWS ARE
 COMPLETED. PLEASE SEE COMMENT FOR
 FIXTURES AS THIS COMMENT MAY ALREADY BE
 ADDRESSED HOWEVER IS UNCLEAR DUE TO SOME
 FIXTURES SHOWN ON PLANS WHICH ARE NOT
 LISTED ON FIXTURES SCHEDULE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE THAT EGRESS CORRIDORS, AND
 STAIR TOWERS WILL BE REQUIRED TO CONTAIN
 A MIN BATTERY BACK UP TYPE OF FIXTURE
 FOR EMERGENCY EGRESS OF 1 FT CANDLE.
 7.9 LS 101 THE TRIPPING OF A SINGLE
 SWITCH OR BREAKER SHALL NOT LEAVE ANY
 ONE AREA IN TOTAL DARKNESS.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 12)NOTE:NOTE #12 NO, THIS NOTE COULD
 NOT BE LOCATED, ONLY A NOTE WITH
 REFERENCE TO POOL PERMIT.
 PLEASE PLACE NOTE ON PLANS FOR ALL MIN
 CLEARENCES 10' FOR 120V W/ GFI
 PROTECTION AND 5' FOR LV. 680.22,411.4.
  
 ** PREVIOUS NOTE **
 PLEASE NOTE ON PLANS THE MIN
 CLEARNECES FOR LT FIXTURES IN PROXIMITY
 OF POOL AND WATER FEATURES WATER'S EDGE.
 PLEASE SEE A MINOF 10' IS REQUIRED FOR
 FIXTURES OVER 30V.411.4
 PLEASE SEE 680.22 FOR A MIN OF 5' FROM
 WATER'S EDGE WITH EXCEPTIONS.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK, REMOVED FROM
 PLANS. SEE NEW NOTES.
  
 15)NOTE: NOTE #17 OK. MOST ALL FLR
 SUBMITTED. PLEASE SEE HOWEVER THERE
 STILL APPEARS TO BE A MISSING SHEET FOR
 INTERMEDIATE ROOF LAYOUT EAST/ SOUTHEAST
 LAYOUT.
  
 16)NOTE: NOTE #16 NO, COULD NOT LOCATE
 ANY NOTES ON ANY OF THE ROOF TOP PLANS.
 NOTE MUST BE ON PLANS.
 PLEASE KNOW, THERE ARE MANY "SYSTEMS"
 ON THE MARKET BEING PROPOSED AND
 ADVERISED AS BEING ACCEPTABLE AND
 MEETING CODE ETC. PLEASE KNOW, ONLY
 SYSTEMS CONTAINING THE RECOGNIZED UL
 LISTINGS/CERTIFICATIONS WHICH ARE UNDER
 NFPA-780 WILL BE PERMITTED TO BE
 INSTALLED.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE NOTE ON ROOF-TOP
 PLANS WHICH WILL STATE THAT ANY
 LIGHTNING PROTECTION SYSTEMS MUST BE IN
 COMPLIANCE WITH NFPA-780. (OR WORDS TO
 THAT AFFECT).
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18 NO, PLEASE SEE THERE
 ARE AREAS OF PLANS WHICH ARE STILL
 MISSING CIRCUITING AND SOME AREAS WHERE
 FIXTURES SEEM TO BE "LIGHT" ALTHOUGH AND
 CIRCUITING LINE IS SHOWN TO THESE
 FIXTURES.
 PLEASE SEE REDLINED PLANS.
  
 **PREVIOUS NOTE **
 PLEASE SEE NO CIRCUITING SHOWN FOR SOME
 "HOUSE AREAS". PLEASE SEE REDLINED PLANS
 ON 2.32, STORAGE RM ETC.
  
 19)NOTE: NOTE #19 NO, PLEASE SEE SOME
 ROOMS WHERE RECEPT CIRCUITS FEED MORE
 THAN ONE ROOM.
 PLEASE SEE REDLINED PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 680.23 AND 680.24 WHICH
 REQUIRES "NO OTHER" LIGHTING OR RECEPTS
 ON ELEVATOR MACHINE RMS CIRUITS OR ELEV
 PITS. PLEASE SEE 2.34,2.35 AND ANY OTHER
 ARES WHICH MAY BE FED FROM ANY OF THESE
 CIRCUITS.
  
 20)NOTE: NOTE 320 OK, HOWEVER SEE SOME
 NEW NOTES FOR CIRCUITING NOW THAT
 CIRCUITS ARE SHOWN.
  
 ** PREVIOUS NOTE **
 PLEASE SHOW CIRCUITING FOR ALL UNITS AND
 CORRELATE WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE KNOW, CODE COMPLIANCE
 FOR SOME ITEMS CAN NOT BE DONE AT THIS
 TIME.
  
 21)NOTE: NOTE #21 NO/YES, PLEASE SEE
 MOST WERE ADDRESSED, HOWEVER PLEASE SEE
 NOW UNTI B2 INDICATES 60A OCP FOR 5KW
 UNIT.
 PLEASE ALSO CORRELATE ALL KW HEAT STRIPS
 WITH MECHANICAL PLANS AND ADJUST LOADS
 AS ALL UNITS ON "M" SHEETS ARE SHOWN W/
 5KW HEAT.
  
 ** PREVIOSU NOTE **
 PLEASE SEE 424.3B FOR MIN OCP FOR AHU'S
 AND HEAT.
 PLEASE SEE MANY PANEL SCHEDULES INDICATE
 LOADS AT 11KW ETC @65%?? PLEASE CLARIFY
 AS 11KW SI SHOWN AS THE DERATED LOAD.
 PLEASE SEE IF 11KW IS THE DE-REATED
 LOAD, THEN THE ACTUAL KW RATING FOR AHU
 WOULD BE ALMOST 15KW??
  
  
 22)NOTE: NOTE #22 OK.
  
 23)NOTE: NOTE #23 OK.
  
 24)NOTE: NOTE #24 OK,HOWEVER SEE NOTES.
  
 25)NOTE: NOTE #25 OK.
  
 26)NOTE: NOTE #26 NO, PLEASE SEE PLANS
 STILL MENTIONS TO USE 310.15B, HOWEVER
 PLEASE KNOW, "B6" CAN NOT BE SUED IN
 DERATING.
 PLEASE ALSO SEE NEW NOTE MENTIONS THE
 CONTRACTOR MAY SUBSTITUTE W/ ALUM.
 PLEASE KNOW, THE CONTRACTOR MAY NOT MAKE
 THIS DECISION OR REVISION. PLEASE KNOW
 ONLY THE DESIGNER AND ENGINEER OF RECORD
 CAN MAKE ANY CHANGES TO CONDUCTORS WHICH
 MUST BE PROPOSED IN A REVISION, SIGNED
 DATED, SEALED AND SUBMITTED FOR REVIEW
 BEFORE CHANGES CAN BE MADE ON THE
 JOBSITE.
  
 ** PREVIOUS NOTE **
 PLEASE SEE NOTE #8, ON PANEL SCHEDULE
 NOTES. PLEASE SEE 310.15B6, WHICH DOES
 NOTES INLCUDE 120/208V SYSTEMS.THIS IS
 FOR INFORMATION ONLY.
  
 27)NOTE: NOTE #27 OK.
  
 28)NOTE: NOTE #28 OK.
  
 29)NOTE: NOTE #29 OK, HOWEVER SEE NOTES
 FOR 210.52/210.52C1 REDLINED
  
 ** PREVIOUS NOTE **
 PLEASE SEE UNIT A-8 FOR MISSING RECEPT
 PER 210.52. PLEASE BE SURE TO CHECK
 REDLINED PLANS FOR ANY OTHER POSSIBLE
 LOCATIONS WHICH MAY REQUIRE A RECEPT.
  
 30)NOTE: NOTE #30 OK.
  
 31)NOTE: NOTE #31 OK.
  
 32)NOTE: NOTE #32 OK.
  
 33)NOTE: NOTE #33 OK, HOWEVER SEE NEW
 NOTES FOR CORRELATION OF NOTES AND
 RISER.
  
 34)NOTE: NOTE #34 OK, HOWEVER SEE NEW
 NOTES DUE TO CHANGES IN RISER/PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE COMPLETE RISER DIAGRAM WITH
 LABELING OF FEEDERS FOR FEEDER SCHEDULE
 AND CORRELATING ALL NUMERCICAL
 IDENTIFICATION.
  
 35)NOTE: NOTE #35 OK.
  
 36)NOTE: NOTE #36 NO, NO SUBMITTIALS
 WERE SUBMITTED FOR REVIEW. PLEAS EKNOW,
 SPECS FOR THESE ITEMS MUST BE SUBMITTED
 TO REVIEW FOR CODE COMPLIANCE. PLEASE
 SEE THERE ARE MANY ITEMS IN NFPA-20
 CHAPTER 6 AND NFPA-110 WHICH CAN NOT BE
 VERIFIED AT THIS TIME AND FURTHER
 COMMENTS MAY ARISE AS CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO PROVIDE MANUFACTURES
 SPECS/CUT SHEETS FOR ABOVE.
  
 37)NOTE: NOTE #37 NO, PLEASE SEE NO
 SPECS WERE SUBMITTED. PLEASE ALSO SEE
 RISER INDICATES THE 4-POLE ATS, HOWEVER
 NOTES MENITON THIS IS NOT A SEPARATELY
 DERIVED GENERATOR? PLEASE SEE AS A
 4-POLE ATS, THE GEN IS "SEP DERIVED" AND
 GROUNDING SHALL BE DONE ACCORDINGLY.
 PLEASE SEE MISSING BONDING AT FIRST
 MENAS OF DISCONNECT , EQUIPMENT GROUNDD
 ETC. PLEASE SEE NFPA-110 6.2.15*. PLEASE
 VERIFY WITH MANUFACTURE OF EQUIPMENT.
 PLEASE SEE NEW NOTES FOR ATS AND MAIN.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL INFORMATION
 FOR GENERATOR/ ATS. PLEASE SUBMIT THE
 SPECS/CUT FROM MANUFACTURE.
 PLEASE VERIFY OF THE ATS WILL BE A
 4-POLE SWITCH.
 PLEASE SEE 700.7D AND IF YOU HAVE THE
 HANDBOOK, SEE EXPLANATION OF ARTICLE.
 I HAVE ATTACHED BOTH, JUST IN CASE.
  
 (D) GROUND FAULT. TO INDICATE A GROUND
 FAULT IN SOLIDLY GROUNDED WYE
 EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS
 TO GROUND AND CIRCUIT-PROTECTIVE
 DEVICES RATED 1000 AMPERES OR MORE. THE
 SENSOR FOR THE GROUND-FAULT SIGNAL
 DEVICES SHALL BE LOCATED AT, OR AHEAD
 OF, THE MAIN SYSTEM DISCONNECTING
 MEANS FOR THE EMERGENCY SOURCE, AND THE
 MAXIMUM SETTING OF THE SIGNAL
 DEVICES SHALL BE FOR A GROUND-FAULT
 CURRENT OF 1200 AMPERES. INSTRUCTIONS
 ON THE COURSE OF ACTION TO BE TAKEN IN
 EVENT OF INDICATED GROUND FAULT
 SHALL BE LOCATED AT OR NEAR THE SENSOR
 LOCATION.
  
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT
 REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE
 OF THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT
 OF A GROUND FAULT IS INAPPROPRIATE.
 DETECTION OF SUCH A FAULT, HOWEVER, IS
 DESIRABLE SO THAT THE CONDITION CAN BE
 CORRECTED.
 IN MY READING AND THE INFORMATION FROM A
 COULE OF MANUFACURES OF ATS SWITCHES, A
 4-POLE ATS IS REQUIRED. PLEASE RESERCH
 THE INFORMATION AND ADJUST.
  
 38)NOTE: NOTE #38, OK.P
  
 39)NOTE: NOTE #39 YES/ NO, PLEASE NOW
 SEE TWO SETS OF DRAWING KEYNOTES, WHICH
 AS NOTED IN ONE SET MOST DO NOT
 CORRELATE WITH RISER DIAGRAM. PLEASE SEE
 SOME COMMENTS FOR OTHER.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE DRAWING KEYNOTES TO
 CORRELATE WITH PLANS.
  
 40)NOTE:NOTE #40 OK, PLEASE SEE SEC'S
 ARE NOW SHOWN AS UNDER GROUND. SEE NEW
 NOTES FOR ROOM LAYOUT.
  
 **PREVIOUS NOTE **PLEASE VERIFY RISER
 DIAGRAM SEC'S AND CONDUITS FOR FIRE
 PUMP, RISER APPEARS TO SHOW FEED
 OVERHEAD?
 PLEASE SEE NFPA-20, 70 WHICH REQUIRES
 COMPLETE ENCASEMENT OF FEEDS.
  
 41)NOTE: NOTE #41 OK, PLEASE SEE MORE
 INFORMATION ON PLANS WAS COMPLETED AND
 SUBMITTED FOR REVIEW, PLEASE SEE ANY NEW
 COMMENTS FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE COMPLETE ALL PANELS, WITH
 INFORMATION ON PANELS, SIZE, MLO,
 MCB ETC.
 PLEASE COMPLETE LOAD CALCULATIONS FOR
 REVIEW.
  
 42)NOTE: NOTE #42 ?? NO?, PLEASE SEE
 PLANS NOTE WIND LOAD PRESSURES TO MEET
 140 MPH, HOWEVER IT IS NOT KNOWN WHERE
 THESE ARE FOR REVIEW.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW OF ANY SITE
 LIGHTING/ROOF TOP LT POLES.
  
 **************************************
 *************************************
 ********* NEW NOTES *****************
  
  
 43) NOTE: PLEASE KNOW, A FULL AND
 COMPLETE TYPE WRITTEN RESPONSE FROM THE
 DESIGN TEAM WHICH RESPONSES TO THE PLANS
 REVIEWERS COMMENTS WILL HELP IN
 EXPEDITING THE PLAN REVIEW PROCESS. THIS
 NUMERICAL REPONSE WILL HELP TO
 ALLEAVIATE ANY BACK AND FORTH QUESTIONS
 OR CONFUSION.
 NO, RESPONSE LETTERS WERE SUBMITTED WHEN
 PLANS WERE BROUGHT BACK FOR REVIEW.
  
 44) NOTE: PLEASE SEE ALL PLANS, SHEETS,
 DOCUMENTS BEING SIGNED, DATED OR SEALED
 BY A LICENSED PE, SHALL ONLY CONTAIN A
 SEAL WITH THE WORDING OF "LICENSE".
 PLEASE SEE A RULING BY THE FLORIDA BOARD
 OF PROFESSINAL ENGINEERS DATED IN
 FEBUARY "04", RULED IN 61G15-23.001,
 THAT ALL SEALS SHALL NO LONGER USE
 "CERTIFICATE" IN SAID SEAL. PLEAS KNOW,
 AN EXTENSION WAS GIVEN TO THE DATE OF
 DEC. 31ST , 2005.PLEASE SEE THIS IS
 NOT A COMMENT FOR STEVEN FELLER AS SEAL
 IS CORRECT. PLEASE SEE OTHER DOCUMENTS
 SUBMITTED DO CONTAIN THE SEAL WHICH IS
 NO LONGER ACCEPTABLE.
 PLEASE SEE DE LOS REYES ENG.AND ANY
 OTHERS WHICH MAY STILL BE UTILIZING OLD
 SEAL.
 PLEASE KNOW, THIS COMMENT IS MADE FOR
 ALL PLANS AND DOCUMENTS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 45) NOTE: PLEASE SEE FBC 2004 CHAPTER
 13, 13-415.1.ABC.1.1, &.2, &.3.
 PLEASE SHOW AND PROVIDE DEVICES,
 CONTROLS ETC FOR ALL AREAS NOW REQUIRED
 TO CONTAIN ENERGY CONSERVATION MEASURES.
 PLEASE SEE 13-413.1ABC.1 AND PROVIDE
 NOTES/WORST CASE FOR VOLTAGE DROP.
 PLEASE SEE 13-415.1.ABC.2 FOR AREA
 LIGHTING.
 PLEASE SEE THESE CHANGES ARE COMPLETELY
 DIFFERENT FORM THE 2001 FBC.
 THESE CHANGES BECAME FEDERALLY MANDATED
 FOR ALL STATES TO COMPLY IN THE NEXT
 CODE CYCLE/CHANGE. THIS FEDERAL MANDATE
 WAS PASSED JULY 2004
 PLEASE SEE NOTE #1 FROM PREVIOUS REVIE
 MENTIONED TO SEE ALL 2004 FBC FOR ALL
 CHANGES IN DESIGN AS PROJECT WAS NOT
 SUBMITTED FOR PERMIT UNDER THE 2001 FBC.
  
 46) NOTE: PLEASE SEE NFPA-110,7.3.3 FOR
 MIN LIGHTING LEVELS IN GENERATOR ROOM TO
 BE 30FT CANDLES. PLEASE SEE
 PHOTO-METRICS FOR THIS AREA SHOULD BE
 SHOWN.
  
 47) NOTE:
 A) PLEASE SEE NFPA-110, 7.9.3.1,
 GALVANIZED LINES SHALL NOT BE USED FOR
 PIPNG TO GENERATOR. THIS IS NOTED FOR
 PLUMBING/ ENGINEERING AS SOME LOCATIONS
 IN THE JURISDICTION HAS INSTALLED THESE
 AND HAVE HAD TO CHANGE TYPES OF PIPING.
 PLEASE KNOW THIS IS A NOTE AT THIS TIME
 FOR INFORMATIONAL PURPOSE ONLY.
 B) PLEASE ALSO SEE NFPA-20, NFPA-110 ,
 NOTES AND SPECS FOR FUEL TYPE AND
 STORAGE WAS NOTE SUBMITTED, PLEASE SEE
 MIN RUNNING TIME CAN NOT BE VERIFIED.
 PLEASE SEE 6-6.2 FOR A MIN OF 8 HRS
 @100% ALONG WITH ALL OTHER MIN REQUIRED
 LIFE SAFETY LOADS.
 THE AMOUNT OF FUEL, AND GPH SHOULD BE
 NOTED ON PLANS. ONE OF THE DRAWING KEY
 NOTES MENTIONS 500 GAL TANK?TBD.
  
 48) NOTE: PLEASE SEE THERE ARE FIXTURES
 ON PLANS WHICH ARE NOTE ON FIXTURE
 SCHEDULE? R-1, R-2, W-1,,
  
 49) NOTE: PLEASE SEE SOME FIXTURES ON
 PLANS DO NOT CONTAIN FIXTURE
 DESIGNATIONS.
 "REDLINED ON PLANS"
  
 50) NOTE: PLEASE SEE LAYOUT ON MEZZ LVEL
 FOR DOM PUMP RM AND FIRE PUMP RM. PLEASE
 SEE THESE SEEM TO BE MISSING
 WALLS/SEPARATION FROM GARAGE/RAMP
 AREAS.? 2.05
 215.5
  
 51) NOTE:PLEASE INDICATE IF GHB
 CONTAINS "FEED-THRU LUGS" OR DOES THIS
 PANEL CONTAIN OCP TO FEED "GHB2"?
 215.5
  
 52) NOTE: PLEASE SEE "LA", DOES THIS
 PANEL ALSO CONTAIN "FEED-THRU LUGS" OR
 DOES IT CONTAIN OCP TO FEED"LA2"?
 IF SO, PLEASE INDICATE THE OCP AND AWG
 SIZES.
 215.5
  
 53) NOTE: PLEASE SEE CORRELATION FOR
 "KEYNOTES" AS RISER CONTAINS #11,10,
 12,13 ETC WHICH DO NOT MATCH AS NOTED
 ABOVE.
  
 54) NOTE: PLEASE SEE PANELS "HB", LB",
 AND TRANSFORMER, AS LAYOUT DOES NOT SEEM
 TO MEET 110.26
 4.01
  
 55) NOTE: PLEASE SEE PREVIOUS NOTE WITH
 RESPECT TO THE ATS AND 4-POLE,
 SEPARATELY DERIVED SYSTEM.
 PLEASE SEE 250.6,250.24B AND 250.122 FOR
 SIZING ANY EQUIPMENT GORUNDING
 CONDUCTORS.
  
 56) NOTE: PLEASE SEE DINING AREAS IN
 A4A, A5, C1 WHICH SHOW RECEPT ON LIVING
 RM CIRCUIT.
 210.52B1
 PLEASE VERIFY ALL DINING AREAS AS SHOWN
 AS IDENTIFY AS NEEDED FOR AREA
 DESIGNATIONS. MOST ARE OK.
 SEE REDLINED.
  
 57) NOTE: PLEASE SEE AREA IN UNIT "B3"
 WHICH SEEMS TO SHOW COUNTERSPACE AND
 WALL AREA ?
 PLEASE SEE 210.52 IF WALL , AND 210.52C1
 IF COUNTER SPACE. (GFI)210.8A6
  
 58) NOTE: PLEASE SEE LOAD SUMMARY FOR
 FIRE PUMP ON RISER WHICH CONTAINS AN "*"
 ASTERISK FOR NOTE OF MAGNETIC ONLY 6X
 LR, HOWEVER THIS "*" IS NOT ABOVE FOR
 FIRE PUMP. SEE REDLINES THIS IS NOTED AS
 PLANS ARE COMING BACK FOR COMMENTS.
  
 59) NOTE: PLEASE SEE EM MAIN SHOLD NOT
 BE LOCATED DIRECTLY NEXT TO EXISTING
 MAIN DISTRIBTUTION EQUIPMENT. THIS MAY
 BE IN THE SAME ROOM, HOWEVER SHOULD BE
 LOCATED ON THE OTHER SIDE OF ROOM.
 PLEASE SEE IF THE ATS IS 4-POLE AND
 SERVICE ENTRANCE RATED, THE MSBE WOULD
 NOT BE NEEDED, THE EDPH COULD CONTAIN A
 MCB AND WOULD MEET THE NEC.
 PLEASE KNOW, IN EITHER CASE A MEANS OF
 DISCONNECT ON THE LOAD OR LINE SIDE OF
 ATS FOR FEED COMING FROM GENERARATOR
 WOULD BE NEEDED GROUPED IN CLOSE
 PROXIMITY TO THE ATS, EM MAIN. PLEASE
 CALL TO GO OVER. SOME ITEMS ARE NOT
 KNOWN AT THIS TIME.
  
 60) NOTE: PLEASE SEE RISER AND OTHER
 PANELS INDICATE PANELS "HP AND LP" ,
 HOWEVER NEITHER OF THESE ARE SUBMITTED
 TO VERIFY AT THIS TIME. PLEASE SHOW.
 215.5
  
 61) NOTE: PLEASE PROVIDE ELEVATION FOR
 EPSS. PLEASE SEENFPA-110 7.2.3*,THE
 ELEVATION OF THE EPSS SHALL BE 6" ABOVE
 THE "SLOSH" PREDICATION LEVELS.
 "SEA, LAKE, OVERLAND SURGES BY
 HURRICANCES. CHARTS BASED ON SURGES FROM
 A CAT 4 STORM.
  
 62) NOTE: WHEN AND BEFORE RESUBMITTING
 PLANS, PLEASE COMPLETELY REMOVE ANY AND
 ALL OLD/VOIDED SHEETS FROM SETS. PLEASE
 ONLY INSERT ONLY NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STMAPING.
 PLEASE KNOW, THIS WAS DONE ON THIS
 SUBMITTAL.
  
 ** PLEASE SEE LOCATIONS ON PLANS IN
 WHICH MANY OF THE ABOVE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS OF COMMENTS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 **
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
2006-05-04 00:00:00ROLLS OF MEP IN ELEC FOR REVIEW TO
 COMMENCE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-28 Cont ID  
Sent By dpalmer Date 2005-11-29 Time 13:48 Rev Time 24.00
Received By dpalmer Date 2005-11-22 Time 15:17 Sent To  
Notes
2005-11-28 00:00:00*** UNSAT ***
  
 CITY PALMS
 10-STORY CONDO
  
 1)NOTE: PLEASE KNOW, PLANS WERE
 SUBMITTED FOR "PLAN REVIEW" ONLY AND
 WERE NOT SUBMITTED FOR PERMIT BEFORE THE
 CODE CHANGE OF OCT 1ST, 2005 TO THE NEW
 2004 FBC.
 PLEASE SEE THAT ANY CHANGES WILL BE
 NEEDED WHEN SUBMITTING FOR PERMIT.
  
 2)NOTE: PLEASE BE SURE ALL PLANS
 SUBMITTED FOR PERMITTING ARE SIGNED,
 DATED AND SEALED BY THE ENGINEER OF
 RECORD.
 FS 471.025
  
 3)NOTE: PLEASE SEE 110.26 FOR MEANS OF
 EGRESS FROM MAIN ELECTRICAL ROOM.
 PLEASE SEE THIS HAD BEEN GONE OVER IN A
 MEETING PRE-SUBMITTAL OF PLANS AND
 DESIGN FOR DOOR AND STAIR LOCATIONS WERE
 DICUSSED FOR A CHANGE.
 PLEASE KNOW, THAT IT IS THE UNDER
 STANDING OF THIS OFFICE THAT THE DOOR
 WOULD INCREASE TO A 6' OPENING AND ONLY
 ONE MEANS OF EGRESS WOULD BE PROVIDED
 AND STAIRS WOULD BE REMOVED?
 PLEASE VERIFY THIS AND ADJSUT PLANS FOR
 THESE CHANGES.
 THE STAIRS AS A MEANS OF EGRESS INSIDE
 THE MAIN ELECTRICAL ROOM WOULD PROPOSE A
 TRIPPING HAZARD IN A SITUATION OF
 SOMEONE BEING BLINDED OR HAVING TO EXIT
 THE ROOM IN AN EMERGENCY SITUATION.
 PLEASE INCLUDE "NOTES" ON SHEET FOR MAIN
 ELECTRICAL ROOM FOR ALL MIN CLEARNECES
 OER 110.26, PANIC HARDWARE FOR DOORS
 ETC.
 PLEASE ALSO SEE MIN CLEARENCE FOR OTHER
 ELECTRICAL ROOMS SHOWN ON ROOM LAYOUT
 PLAN.
  
 4)NOTE: PLEASE SEE PLANS CALL FOR
 BLUIDING TO BE LOCATED AT 480 HIBISCUS,
 HOWEVER OUR SYSTEMWITH PCN # PROVIDED
 INCIDICATES "430". PLEASE CORRELATE AND
 ADJUST PLANS/APPLICATION. ETC.
  
 5)NOTE: PLEASE BE SURE PLANS ARE
 SPECIFIC TO THE 2002 NEC WHICH IS
 CURRENTLY IN EFFECT.
 PLEASE KNOW: DEPENDING ON WHEN PLANS ARE
 SUBMITTED FOR PERMIT, A CODE CHAMGE TO
 THE 2005 NEC SHOULD BE COMING ABOUT IN
 MID 2006.
  
 6)NOTE: PLEASE SEE 1.01 AND ADDITIONAL
 SHEETS WHICH REFERENCE ABCK TO 3.02 FOR
 ELECTRICLA ROOM LAYOUTS, HOWEVER 3.02
 DOES NOT SHOW ROOM LAYOUTS.
 PLEASE CORRELATE.
  
 7)NOTE: PLEASE PROVIDE COMPLETE
 "PHOTOMETRICS" FOR ALL CORRIDORS,
 STAIRWELLS AND EGRESS AREAS PER 2003
 NFPA-101 7.8 AND 7.9.
 PLEASE SEE A MIN OF 10 FT CANDLES IS NOW
 REQUIRED FOR STAIR TOWERS UNDER NORMAL
 EGRESS CONDITIONS.
  
 8)NOTE: PLEASE BE SURE THERE ARE
 EMERGENCY BATTERY BACK UP TYPE FIXTURES
 LOCATED IN ALL ELECTRICAL ROOMS,
 ELEVATOR EQUIPMENT ROOMS, FIRE PUMP,
 GENERATOR, AND FIRE COMMAND ROOM.
 PLEASE KNOW, SOME OF THESE ARE ALREADY
 SHOWN ON PLANS, HOWEVER SOME AREAS MAY
 BE REDLINED FOR THESE.
 NFPA-101 7.8,7.9, NEC 700.16 ETC.
  
 8)NOTE: PLEASE SEE THAT EGRESS
 CORRIDORS, AND STAIR TOWERS WILL BE
 REQUIRED TO CONTAIN A MIN BATTERY BACK
 UP TYPE OF FIXTURE FOR EMERGENCY EGRESS
 OF 1 FT CANDLE.
 7.9 LS 101
 THE TRIPPING OF A SINGLE SWITCH OR
 BREAKER SHALL NOT LEAVE ANY ONE AREA IN
 TOTAL DARKNESS.
  
 9)NOTE: PLEASE SEE WOMENS AND MENS
 RESTRMS IN COMMON AREAS CONTAINING
 RECEPTS LOCATED IN CLOSE PROXIMITY OF
 LAVATORYS. PLEASE BE SURE TO INDICATE
 GFI PROTECTIONS FOR THESE.
 210.8B1
  
 10)NOTE: PLEASE SEE "CLUB RM" AND ALL
 RECEPTSWITHIN 6' OF SINKS SAHLL BE
 INDICATED AS GFI/GFI PROTECTED.
 210.8B
  
 11)NOTE: PLEASE SEE RETAIL SPACE #14,
 WHICH INDICATES A TRANSFORMER AND PANEL
 AS "FUTURE", HOWEVER PLEASE SEE THERE IS
 AN ADDITIONAL PANEL SHOWN BUT NOT CLEAR
 FOR USE ETC?
 215.5
  
 12)NOTE: PLEASE NOTE ON PLANS THE MIN
 CLEARNECES FOR LT FIXTURES IN PROXIMITY
 OF POOL AND WATER FEATURES WATER'S EDGE.
 PLEASE SEE A MINOF 10' IS REQUIRED FOR
 FIXTURES OVER 30V.
 PLEASE SEE 680.22 FOR A MIN OF 5' FROM
 WATER'S EDGE WITH EXCEPTIONS.
  
 13)NOTE: PLEASE SEE POSSIBLE NOTES FROM
 REVIEWS FROM FIRE, BLDGMECH ETC, WITH
 RESPECT TO THE LOCATION OF GENERATOR
 INTAKE AND EXHAUST. THESE SEEMS TO BE
 LOCATED IMEDIATELY ADJACENT TO THE PUBLE
 RIGHT OF WAY/SIDE WALK.
 PLEASE KNOW, THIS IS ONLY A COMMENT FOR
 ELECTRICAL REVIEW , HOWEVER MAY CHANGE
 ELECTRICAL LAYOUT??
  
 14)NOTE: PLEASE SEE PANELS "HP AND "LP".
 TRANSFORMER LOCATED AT ELEC RM ON 2.17.
 PLEASE SEE MIN CLEARENCES PER 110.26
  
 15)NOTE: PLEASE SEE SHEETS 2.21 WHICH
 STATES 6TH FLR, THEN 2.22GOES TO A
 "TYPICAL PARTIAL FLR" AND THEN PLANS GO
 BACK TO A 9TH FLR DETAIL ON 2.25?
 PLEASE VEIRFY IF THESE ARE FLRS 7,8?
  
 16)NOTE: PLEASE PROVIDE NOTE ON ROOF-TOP
 PLANS WHICH WILL STATE THAT ANY
 LIGHTNING PROTECTION SYSTEMS MUST BE IN
 COMPLIANCE WITH NFPA-780. (OR WORDS TO
 THAT AFFECT).
  
 17)NOTE: PLEASE PROVIDE DISCONNECTS OR A
 "TYPICAL DETAIL" FOR ROOF-TOP CU'S.
 440.11
  
 18)NOTE: PLEASE SEE NO CIRCUITING SHOWN
 FOR SOME "HOUSE AREAS". PLEASE SEE
 REDLINED PLANS ON 2.32, STORAGE RM ETC.
  
 19)NOTE: PLEASE SEE 680.23 AND 680.24
 WHICH REQUIRES "NO OTHER" LIGHTING OR
 RECEPTS ON ELEVATOR MACHINE RMS CIRUITS
 OR ELEV PITS. PLEASE SEE 2.34,2.35 AND
 ANY OTHER ARES WHICH MAY BE FED FROM ANY
 OF THESE CIRCUITS.
  
 20)NOTE: PLEASE SHOW CIRCUITING FOR ALL
 UNITS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 PLEASE KNOW, CODE COMPLIANCE FOR SOME
 ITEMS CAN NOT BE REVIEWED AT THIS TIME.
 215.5
  
 21)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU'S AND HEAT.
 PLEASE SEE MANY PANEL SCHEDULES INDICATE
 LOADS AT 11KW ETC @65%?? PLEASE CLARIFY
 AS 11KW IS SHOWN AS THE DERATED LOAD.
 PLEASE SEE IF 11KW IS THE DE-RATED LOAD,
 THEN ACTUAL KW RATING FOR AHU WOULD BE
 ALMOST 15KW??
  
 22)NOTE: PLEASE SEE WATER HEATERS SHOW
 #8 AWG? PLEASE KNOW THIS IS ONLY A
 COMMENT AS #8 IS OK, HOWEVER MAY NOT BE
 REQUIRED.
 PLEASE SEE THE FOLLOWING COMMENT**
  
 23)NOTE: PLEASE VERIFYOCP SHOWN FOR
 SOME WATER HEATERS AS 2POLE 30A AND SOME
 AS 2-POLE 40A??
 PLEASE SEE 4.5KW IS THE SAME LOAD FOR
 BOTH AT 208V.
 PLEASE KNOW, THE CODE REQUIRES A MIN OCP
 AT 125% (422.13) , HOWEVER THE CODE ALSO
 LIMITS THE OCP AT 150%. 422.11.
 PLEASE ADJUST OCP AND ANY AWG.
  
 24)NOTE: PLEASE SEE PANEL SCHEDULE NOTES
 LISTEDON EACH SHEET, HOWEVER THE NOTES
 ARE NOT LABLED TO PANELS.
 215.5
  
 25)NOTE: PLEASE SEE MEDIA BOXES/PANELS
 ARE SHOWN IN CLOSETS ABOVE STORAGE
 SHELVES.
 PLEASE KNOW, ANY RECEPT REQUIRED FOR ANY
 TYPE OF PLUG-IN TRANSFORMER MAYNOT BE
 AT THIS LOCATION ABOVE OR IN CLOSE
 PROXIMITY TO ANY COMBUSTIBLES.
 110.26,240.24
 * NOTE:, ANY RECEPTS FOR ANY PLUG-IN
 TYPE OF TRANSFORMERS, MAY BE LOCATED
 ABOVE DOOR WAY.*
  
 26)NOTE: PLEASE SEE NOTE #8, ON PANEL
 SCHEDULE NOTES. PLEASE SEE 310.15B6,
 WHICH DOES NOTES INLCUDE 120/208V
 SYSTEMS.THIS IS FOR INFORMATION ONLY.
  
 27)NOTE: PLEASE VERIFY PLANS INDICATE
 BOTH A WASHER AND A DRYER, HOWEVER PLANS
 SEEM TO INDICATE LOCATION FOR STACKABLE
 UNITS ONLY.?
 WILL ELECTRICAL BE INSTALLED FOR BOTH?
  
 28)NOTE: PLEASE SEE UNIT A-6 AS IT SEEMS
 WASHER/DRYER IS LOCATED ON KITCHEN
 COUNTERSPACE?
  
 29)NOTE: PLEASE SEE UNIT A-8 FOR MISSING
 RECEPT PER 210.52.
 PLEASE BE SURE TO CHECK REDLINED PLANS
 FOR ANY OTHER POSSIBLE LOCATIONS WHICH
 MAY REQUIRE A RECEPT.
  
 30)NOTE: PLEASE PROVIDE NOTES FOR
 PLACEMENT OF ALL SD'S PER 2002 NFPA-72
 11.8.3
  
 31)NOTE: PLEASE SEE MANY UNITS DO NOT
 INDICATE THE LV MEDIA BOXES AS SHOWN IN
 OTHER UNITS? PLEASE SEE UNITS, B1,
 B1B,B1F, B1E ETC.
 PLEASE VERIFY
  
 32)NOTE: PLEASE SEE UNIT B1F, WHICH
 SEEMS TO INDICATE THE AN ENTIRE RECEPT
 AS BEING SWITCHED? PLEASE KNOW, THE CODE
 PERMITS A 1/2 SW RECEPT IF USING THE
 RECEPT FOR 210.70, 210.52 OR PLEASE ADD
 RECEPT TO MEET 210.52.
 SEE REDLINED PLANS.
  
 33)NOTE: PLEASE SEE MSBH ON 5.01 SHOWS
 AS 2000A'S , YET 6.01 SHOWS 1200A WITH
 1000A MCB.
 PLEASE CORRELATE:
  
 34)NOTE: PLEASE SEE COMPLETE RISER
 DIAGRAM WITH LABELING OF FEEDERS FOR
 FEEDER SCHEDULE AND CORRELATING ALL
 NUMERCICAL IDENTIFICATION.
  
 35)NOTE: PLEASE PROVIDE THE FOLLOWING
 FOR COMPLETETION OF GROUNDIOG ELECTRODE
 SYSTEM.
 PLEASE PROVIDE DETAIL FOR MAIN GROUNDING
 ELECTRODE SYSTEM TO ALSO INCLUDE THE
 REQUIRED FOOTER STEEL.250.50
  
 PLEASE PROVIDE A GROUND RISER FOR
 CONNECTION OF ALL OTHER SEPARATELY
 DERIVED SYSTEMS/TRANSFORMER ATTACHMENTS
 TO THE MAIN GROUNDIGN ELECTRODE SYSTEM.
 250.30
 PLEASE PROVIDE THIS ON THE RISER DIAGRAM
 SHEET.
  
 36)NOTE:PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE ALSO PROVIDE MANUFACTURES
 SPECS/CUT SHEETS FOR ABOVE.
  
 37)NOTE: PLEASE SUBMIT ALL INFORMATION
 FOR GENERATOR/ ATS. PLEASE SUBMIT THE
 SPECS/CUT FROM MANUFACTURE.
 PLEASE VERIFY OF THE ATS WILL BE A
 4-POLE SWITCH.
 PLEASE SEE 700.7D AND IF YOU HAVE THE
 HANDBOOK, SEE EXPLANATION OF ARTICLE.
 I HAVE ATTACHED BOTH, JUST IN CASE.
  
 (D) GROUND FAULT. TO INDICATE A GROUND
 FAULT IN SOLIDLY GROUNDED WYE
 EMERGENCY SYSTEMS OF MORE THAN 150 VOLTS
 TO GROUND AND CIRCUIT-PROTECTIVE
 DEVICES RATED 1000 AMPERES OR MORE. THE
 SENSOR FOR THE GROUND-FAULT SIGNAL
 DEVICES SHALL BE LOCATED AT, OR AHEAD
 OF, THE MAIN SYSTEM DISCONNECTING
 MEANS FOR THE EMERGENCY SOURCE, AND THE
 MAXIMUM SETTING OF THE SIGNAL
 DEVICES SHALL BE FOR A GROUND-FAULT
 CURRENT OF 1200 AMPERES. INSTRUCTIONS
 ON THE COURSE OF ACTION TO BE TAKEN IN
 EVENT OF INDICATED GROUND FAULT
 SHALL BE LOCATED AT OR NEAR THE SENSOR
 LOCATION.
  
 ALTHOUGH 700.26 INDICATES THAT
 GROUND-FAULT PROTECTION OF EQUIPMENT IS
 NOT
 REQUIRED ON THE ALTERNATE SOURCE FOR
 EMERGENCY SYSTEMS, GROUND FAULTS CAN
 OCCUR ON SUCH SYSTEMS, AND THEY CAN
 RESULT IN EQUIPMENT BURNDOWN. BECAUSE
 OF THE EMERGENCY NATURE OF SUCH SYSTEMS,
 AUTOMATIC DISCONNECT IN THE EVENT
 OF A GROUND FAULT IS INAPPROPRIATE.
 DETECTION OF SUCH A FAULT, HOWEVER, IS
 DESIRABLE SO THAT THE CONDITION CAN BE
 CORRECTED.
 IN MY READING AND THE INFORMATION FROM A
 COUPLE OF MANUFACTURES OF ATS SWITCHES,
 A 4-POLE ATS IS REQUIRED. PLEASE RESERCH
 THE INFORMATION AND ADJUST.
  
 38)NOTE: PLEASE PROVIDE OCP LOCATED AT
 GENERATOR.
 THIS INFORMATION COULD NOT BE FOUND ON
 PLANS/OR RISER DIAGRAM.
  
 39)NOTE: PLEASE COMPLETE DRAWING
 KEYNOTES TO CORRELATE WITH PLANS.
  
 40)NOTE: PLEASE VERIFY RISER DIAGRAM
 SEC'S AND CONDUITS FOR FIRE PUMP, RISER
 APPEARS TO SHOW FEED OVERHEAD?
 PLEASE SEE NFPA-20, 70 WHICH REQUIRES
 COMPLETE ENCASEMENT OF FEEDS.
  
 41)NOTE: PLEASE COMPLETE ALL PANELS,
 WITH INFORMATION ON PANELS, SIZE, MLO,
 MCB ETC.
 PLEASE COMPLETE LOAD CALCULATIONS FOR
 REVIEW.
  
 42)NOTE: PLEASE PROVIDE WIND LOAD
 CALCUALTIONS FOR BLDG REVIEW OF ANY SITE
 LIGHTING/ROOF TOP LT POLES.
  
 ** PLEASE SEE LOCATIONS ON PLANS IN
 WHICH MANY OF THE ABOVE ITEMS HAVE BEEN
 REDLINED AT LOCATIONS OF COMMENTS.
  
 ** PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT COMPLETED PLANS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
  
  
  
  
2005-11-17 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.
  
  
 **************************************
 PLEASE KNOW, PLANS ONLY SUBMITTED FOR
 "PLAN REVIEW" BEFORE OCT 1ST, 2005 AND
 THE CODE CHANGE TO THE 2004 FBC.
  
 PLEASE KNOW THE EXSITNG "PROJECT" NUMBER
 MAY CHANGE WHEN PLANS ARE SUBMITTED FOR
 PERMIT AFTER OCT 1ST.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2006-06-06 Time   Rev Time 2.00
Received By   Date 2006-06-06 Time   Sent To  
Notes
2006-06-06 00:00:00PROJECT EXEMPT FROM SFWMD ERP DUE TO
 ACREAGE.
  
 SEPERATE ROW PERMIT WITH MOT WILL BE
 REQUIRED.CONTACT WINDEL PALMER.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-11-09 Cont ID  
Sent By mamini Date 2005-11-09 Time 08:40 Rev Time 1.00
Received By mamini Date 2005-11-09 Time 08:40 Sent To  
Notes
2005-11-09 00:00:00FAILED:
  
 1. PLEASE NOTE THAT CIVIL PLAN FOR THIS
 PROJECT MUST BE REVIEWD AND APPROVED BY
 THE PUBLIC UTILITIES AND ENGINEERING FOR
 ALL THE CONNECTIONS TO THE CITY SERVICES
 AND FOR ANY UNDERGROUND UTILITY UPGRADE
 OR ANY EASEMENT AS REQUIRED IN VICINITY
 OF THE PROJECT.
 2. VERTICAL CLEARANCES FOR CROSSING
 UNDERGROUND UTILITIES FOR BOTH ON-SITE
 AND OFF-SITE MUST BE SHOWN.
 3. SHEET WS1 OF 5, PLEASE VERIFY EX. 6"
 CIP AND EX. 15" VCP AND EX. 10" SAN.
 SEWER MAIN.
 4. PLEASE SUBMIT STORM WATER CALCULATION
 WHICH INCLUDE PERVIOUS AND IMPERVIOUS,
 BUILDING AREA FOR OUR REVIEW.
 5. PLEASE SUBMIT A COPY OF SFWMD PERMIT
 IF APPLIED, FOR OUR RECORD.
 6. SHEET PD1 & PD2 OF 5, PLEASE VERIFY
 WEIR ELEVATION FOR THE PROPOSED CONTROL
 STRUCTURE.
 7. PLEASE VERIFY, I.E(11.45')FOR
 STRUCTURE 7 AND I.E(13.0')FOR STRUCTURE
 6.
 8. A SEPARATE PERMIT FOR ALL THE WORK
 WITHIN PUBLIC R.O.W AT NO COST FROM
 PUBLIC UTILITIES AND ENGINEERING IS
 REQUIRED, PLEASE SUBMIT MOT AT THE TIME
 OF APPLICATION, 494-1086 WINDEL PALMER.
 9. ACCESS RAMP PER INDEX 304 FDOT AT ALL
 SURROUNDING INTERSECTIONS MUST BE
 PROVIDED, PLEASE VERIFY.
 10. STREETSCAPINGAND SIDEWALKS, ETC.
 MUST BE COORDINATED WITH LATEST FDOT
 PLANS FOR THE RECONSTRUCTION OF DIXIE
 AND SIDE STREETS.
 11. PLEASE NOTE THAT CIVIL PLANS MUST BE
 SIGNED AND SEALED BY THE CIVIL E.O.R AT
 THE TIME OF ACTUAL PERMITTING.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 17 Status P Date 2008-12-09 Cont ID  
Sent By mawillia Date 2008-12-09 Time 15:47 Rev Time 0.00
Received By mawillia Date 2008-12-09 Time 14:03 Sent To  
Notes
2008-12-09 15:47:00*****REVISION AND/OR RESTAMP APPROVED*****
  
  
 PLAN SHEETS FA1.01 THRU FA1.12 WERE STAMPED, INITIALED,
 AND DATED; ONLY SHEET FA1.01 WAS AN ACTUAL REVISION,
 WHILE THE OTHERS WERE A RESTAMP OF REVISED SHEETS
 PREVIOUSLY FIRE-STAMPED ON 01/17/08.

Review Stop FIRE FIRE DEPARTMENT
Rev No 16 Status P Date 2008-09-10 Cont ID  
Sent By mwennerg Date 2008-09-10 Time 14:26 Rev Time 0.00
Received By mwennerg Date 2008-09-10 Time 14:26 Sent To  
Notes
2008-09-10 14:27:26REVISION #28 DATED 8/18/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 15 Status P Date 2008-08-12 Cont ID  
Sent By mawillia Date 2008-08-12 Time 10:01 Rev Time 0.00
Received By mawillia Date 2008-08-12 Time 09:51 Sent To  
Notes
2008-08-12 10:01:11*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEET M2.03 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 14 Status P Date 2008-07-02 Cont ID  
Sent By mwennerg Date 2008-07-02 Time 14:25 Rev Time 0.00
Received By mwennerg Date 2008-07-02 Time 14:25 Sent To  
Notes
2008-07-02 14:26:06REVISED SHEET FA1.01 DATED 6/18/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status P Date 2008-04-09 Cont ID  
Sent By mwennerg Date 2008-04-09 Time 15:49 Rev Time 0.00
Received By mwennerg Date 2008-04-09 Time 15:49 Sent To  
Notes
2008-04-09 15:51:00REVISION #24 AND #25 TO ARCHITECTURAL SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 17:56 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 16:35 Sent To  
Notes
2008-01-17 17:56:23*****APPROVED, REVISION #16, 11/10/2007*****
  
  
 REVISED PLAN SHEETS E2.01, E2.02, E2.03, AND FA1.01
 THRU FA1.13 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status F Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 16:24 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 16:04 Sent To  
Notes
2008-01-17 16:23:52*****DENIED, REVISION #22*****
  
  
 SEE BUILDING REVIEW COMMENT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status N Date 2007-11-01 Cont ID  
Sent By mawillia Date 2007-11-01 Time 16:49 Rev Time 0.00
Received By mawillia Date 2007-11-01 Time 16:39 Sent To  
Notes
2007-11-01 16:49:29******NOT REQUIRED*****
  
  
 NO FIRE-STAMPING NEEDED FOR HE REVISED S-1.8, S-1.8R,
 S-7.2, AND S-7.7 PLAN SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status N Date 2007-10-30 Cont ID  
Sent By mwennerg Date 2007-10-30 Time 10:54 Rev Time 0.00
Received By mwennerg Date 2007-10-30 Time 10:54 Sent To  
Notes
2007-10-30 10:55:38REVISIONS ADDRESS BUILDING REVIEW WITH NO RESPONSE TO
 THE LAST FIRE REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status F Date 2007-09-21 Cont ID  
Sent By mwennerg Date 2007-09-21 Time 10:52 Rev Time 0.00
Received By mwennerg Date 2007-09-21 Time 10:52 Sent To  
Notes
2007-09-21 11:06:58***DENIED***
  
 1) PLEASE SEE ELECTRICAL COMMENT #2 AND CLARIFY EXIT
 SIGN LOCATION. ANY CHANGE TO MEANS OF EGRESS SHOULD BE
 REFLECTED ON LIFE SAFETY SHEETS WHERE PROVIDED.
  
 2) MANY REVISIONS IDENTIFY CHANGES TO FLOOR ELEVATIONS.
 IN ADDITION TO APPLICABLE BUILDING CODES, PLEASE SHOW
 COMPLIANCE WITH NFPA 101, CHAPTER 7 WITH REGARDS TO
 WALKING SURFACES THAT IMPACT REQUIRED MEANS OF EGRESS.
  
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2007-09-17 Cont ID  
Sent By mawillia Date 2007-09-17 Time 17:06 Rev Time 0.00
Received By mawillia Date 2007-09-17 Time 16:47 Sent To  
Notes
2007-09-17 16:59:59*****APPROVED*****
  
  
 FIRE PUMP SUBMITTALS

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-08-31 Cont ID  
Sent By mwennerg Date 2007-08-31 Time 11:39 Rev Time 0.00
Received By mwennerg Date 2007-08-31 Time 11:39 Sent To  
Notes
2007-08-31 11:40:32FIRE EXTINGUISHER PACKAGE SUBMITTAL DATED 8/17/07.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 15:45 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 14:08 Sent To  
Notes
2007-06-12 15:44:18***** UNSAT SUBMITTAL*****
  
  
 THE SUBMITTALS WHICH WERE REVIEWED BY THIS WRITER WERE
 DATE STAMPED WITH THE EXCEPTION OF THE HYDRAULIC
 CALCULATIONS FOR THE STANDPIPE WHICH SHOWS 4.462 PSI AS
 THE SAFETY MARGIN.AS PER WEST PALM BEACH FIRE
 PREVENTION, A SAFETY MARGIN OF AT LEAST 5.0 PSI IS
 REQUIRED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-10 Cont ID  
Sent By mawillia Date 2007-01-10 Time 12:48 Rev Time 0.00
Received By mawillia Date 2007-01-10 Time 12:48 Sent To  
Notes
2007-01-10 13:08:56*****APPROVED*****
  
  
 **REVISED PLAN SHEETS DATED 11/10/2006:FP-2.01, 2.02,
 2.03, 2.04, 2.05,A-2.1.1,LS-1, AND LS-2 WERE
 STAMPED, INITIALED, AND DATED.**
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 09:27 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 09:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By mwennerg Date 2006-05-30 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2006-05-30 Time 10:36 Sent To  
Notes
2006-05-30 00:00:00***DENIED***
  
 PLEASE NOTE THAT WHEN RESUBMITTING
 PLANS, A RESPONSE LETTER INDICATING
 SHEET NUMBER WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS. SOME REVISION
 CLOUDS ARE SHOWN, HOWEVER IT IS UNCLEAR
 WHAT THE CHANGE IS REFERENCING.
  
 PREVIOUS REVIEW COMMENTS:
  
 1) BUILDING SHALL MEET THE REQUIREMENTS
 FOR HIGHRISE IN ACCORDANCE WITH NFPA
 101, CHAPTER 11 AND APPLICABLE BUILDING
 CODES.
  
 2) PARKING GARAGES SHALL MEET THE
 SEPARATION AND ALL OTHER REQUIREMENTS OF
 NFPA 88A AND FBC.
  
 3) OK
  
 4) DO TRASH CHUTES OBSTRUCT CORRIDORS
 GREATER THAN 1/2 THE WIDTH?
  
 5) ILLUMINATED EXIT SIGNS TO BE MOUNTED
 AT DISTANCES NOT TO EXCEED 100' BETWEEN
 SIGNS.
  
 6) OK
  
 7) PLEASE PROVIDE QUANTITY AND TYPE OF
 STORAGE THAT WILL BE KEPT IN POOL
 EQUIPMENT ROOM.
  
 8) EXIT STAIRS TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) OK
  
 10) OK
  
 11) OK
  
 12) OK
  
 13) THE SQUARE FOOTAGE REQUIREMENT IS
 CALLED OUT ON PLANS. FIRE EXTINGUISHERS
 TO BE MOUNTED AT DISTANCES NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT.
  
 14) OK
  
 15) WARNING SIGNS REQUIRED IN ELEVATOR
 LOBBIES.
  
 16) NO STORAGE PERMITTED IN ELECTRICAL
 AND MECHANICAL EQUIPMENT ROOMS.
  
 17) OK
  
 18) FIRE EXTINGUISHERS REQUIRED FOR EACH
 COMMERCIAL SPACE.
  
 19) PLANS INDICATE THAT ALL INTERIOR
 FINISH IS CLASS A. DOES THAT INCLUDE ALL
 SPACES IE, EXIT ENCLOSURES, LOBBIES AND
 CORRIDORS, AND OTHER SPACES?
  
 20) OK
  
 21) OK
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM TO MEET SURVIVABILITY
 REQUIREMENTS OF NFPA 72.
  
 24) NOTE SHOULD READ: FIRE ALARM SYSTEM
 SHALL BE UL CERTIFIED FOR 'CENTRAL
 STATION SERVICE'.
  
 25) OK
  
 26) FIRE ALARM PLANS STILL DON'T SHOW
 SMOKE DETECTOR IN FIRE COMMAND ROOM.
  
 27) OK
  
 28) OK
  
 29) OK
  
 30) OK
  
 31) OK
  
 32) PLEASE ILLUSTRATE THE FIRE
 PROTECTION LAYOUT FOR THE TRASH CHUTES.
  
 33) SEPARATE SHOP DRAWINGS, PERMIT AND
 MANUFACTURER SPEC SHEETS REQUIRED FOR
 FIRE PUMP AND ASSOCIATED EQUIPMENT.
  
 34) OK
  
 35) OK
  
 36) OK
  
 NEW COMMENTS
  
 37) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION
  
 38) PLEASE INDICATE FIRE RATING OF DOORS
 IN TERMS OF HOURS OR MINUTES.
  
 39) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS. SHT FA 1.13 NOTE 17.
  
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By mwennerg Date 2005-11-29 Time 13:42 Rev Time 0.00
Received By mwennerg Date 2005-11-29 Time 13:42 Sent To  
Notes
2005-11-29 00:00:00******DENIED******
  
 1) BUILDING SHALL MEET THE REQUIREMENTS
 FOR HIGHRISE IN ACCORDANCE WITH NFPA
 101, CHAPTER 11 AND APPLICABLE BUILDING
 CODE.
  
 2) PARKING GARAGES SHALL MEET SEPARATION
 AND ALL OTHER REQUIREMENTS IN ACCORDANCE
 WITH FBC AND NFPA 88-A.
  
 3) HANDRAILS REQUIRED ON STAIRS LEADING
 TO MEZZANINE. OK ON STAIR DETAIL.
  
 4) DO TRASH CHUTE DOORS OBSTRUCT
 CORRIDORS GREATER THAN 1/2 THE WIDTH?
  
 5) ILLUMINATED EXIT SIGNS SHALL BE
 MOUNTED NOT MORE THAN 100' APART.
  
 6) IS THE ROOM LABELED TRASH CHUTE
 CORRECT? SHT. A- 0.3.
  
 7) PLEASE PROVIDE QUANTITY AND TYPE OF
 STORAGE THAT WILL BE KEPT IN POOL
 EQUIPMENT ROOM.
  
 8) EXIT STAIRS TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) SIGNS ARE REQUIRED IN STAIRWELLS
 INDICATING TOP, BOTTOM, FLOOR # AND ROOF
 ACCESS.
  
 10) PLEASE PROVIDE OCCUPANT LOAD FOR
 POOL AREA AND HEALTH CLUB.
  
 11) PLEASE NOTE ON PLANS THAT WALKING
 SURFACE AT POOL DECK TO BE SLIP
 RESISTANT.
  
 12) PLEASE PROVIDE MORE INFORMATION
 REGARDING EMERGENCY ROOM. USE?
  
 13) 2A-10 B,C RATED FIRE EXTINGUISHERS
 ARE REQUIRED AND SHALL BE MOUNTED TO
 SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
 14) PLEASE INDICATE WHAT ELEVATORS ARE
 STETCHER ACCESSIBLE.
  
 15) WARNING SIGNS REQUIRED FOR ELEVATOR
 LOBBIES.
  
 16) NO STORAGE IN ELECTRICAL AND
 ELEVATOR MACHINE ROOMS.
  
 17) EXIT SIGN ON LS SHTS NEAR STAIR #1
 IS NOT AT THE STAIRWELL, BUT IS OK ON
 ELECTRICAL SHTS.
  
 18) FIRE EXTINGUISHERS ARE REQUIRED FOR
 EACH COMMERCIAL SPACE.
  
 19) NOTE A ON LS SHTS INDICATES THAT ALL
 INTERIOR FINISH TO BE CLASS A. PLEASE
 CLARIFY.
  
 20) TRAVEL DISTANCE ON LS SHTS
 ILLUSTRATES 278'. PLEASE SEE NFPA 101,
 2003 EDITION SECTION 30.2.6.4 THAT
 STATES THAT TRAVEL DISTANCE SHALL NOT
 EXCEED 250' IN SPRINKLERED BUILDING.
  
 21) PLEASE NOTE THAT SOME EXIT SIGNS ON
 LS SHTS ARE IN DIFFERENT LOCATIONS.
 PLEASE CORRULATE.
  
 22) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 23) FIRE ALARM SYSTEM TO MEET
 SURVIVABILITY REQUIREMENTS IN ACCORDANCE
 WITH NFPA 72.
  
 24) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 25) KNOX BOX LOCKING CAPS REQUIRED FOR
 FDC'S. HIGHRISE BUILDINGS SHALL HAVE NOT
 LESS THAN (2) FDC'S.
  
 26) PLANS DON'T SHOW SMOKE DETECTOR IN
 FIRE ALARM CONTROL ROOM.
  
 27) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 28) IT APPEARS THAT SOME SMOKE DETECTORS
 ARE MISSING IN SOME OF THE EQUIPMENT
 ROOMS AND STORAGE AREAS.
  
 29) SMOKE DETECTORS ARE REQUIRED IN ALL
 COMMON AREA CORRIDORS. NOT SHOWN ON
 PLANS.
  
 30) STANDPIPES TO BE 2 1/2" WITH 1 1/2"
 REDUCERS.
  
 31) TEMPORARY STANDPIPES REQUIRED WHEN
 BUILDING REACHED 3 STORIES OR 30" IN
 HEIGHT.
  
 32) PLEASE INDICATE THE FIRE PROTECTION
 LAYOUT WITHIN THE TRASH CHUTES.
  
 33) SEPARATE SHOP DRAWINGS, PERMIT AND
 MANUFACTURER SPEC SHTS REQUIRED FOR FIRE
 PUMP.
  
 34) NFPA 13, 2002 EDITION TO BE
 REFERENCED. SHT FP 4.02.
  
 35) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA
 51-B.
  
 36) IN ADDITION TO ELECTRONIC SWITCHES,
 DOUBLE CHECK DETECTOR ASSEMBLY TO BE
 SECURED WITH LOCK AND CHAIN.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 6 Status P Date 2008-09-02 Cont ID  
Sent By kstevens Date 2008-09-02 Time 12:28 Rev Time 0.00
Received By kstevens Date 2008-09-02 Time 11:10 Sent To  
Notes
2008-09-02 12:29:24REVISION OK -- SHT P3.16 GAS ONLY

Review Stop G GAS REVIEW
Rev No 5 Status F Date 2008-08-21 Cont ID  
Sent By kstevens Date 2008-08-21 Time 08:12 Rev Time 0.00
Received By kstevens Date 2008-08-20 Time 16:47 Sent To  
Notes
2008-08-21 08:40:55REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****SEPARATE GAS PERMIT REQUIRED*****
  
 ****FROM PREVIOUS REVISION REVIEW:
  
 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A
 LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE
 BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE
 GAS.
 ****RESPONSE NOTED, BUT THE GAS METER PIPING SCHEMATIC
 SHOWS A TEE ON THE OUTLET SIDE OF THE METER WITH A
 CAPPED LINE. PLEASE INDICATE WHAT THIS LINE IS FOR. IF
 IT IS FOR FUTURE USE, A SHUT OFF VALVE IS REQUIRED
 BETWEEN THE TEE AND THE CAP. ALSO DOWNSTREAM OF THE TEE
 ON THE PIPING TO THE BUILDING, (2PSI), SHOWS A SHUT OFF
 VALVE, A 90 DEG FITTING AND THEN ANOTHER SHUT OFF
 VALVE. PLEASE EXPLAIN WHY TWO SHUT OFF VALVES ARE
 NEEDED. SECTIONS 106.1.2, 106.1.1 & 409.
  
 2. OK
 3. OK
 4. OK
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS.
 INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL
 LOAD OF ALL APPLIANCES COMBINED.
 ****RESPONSE NOTED, BUT THE MAXIMUM CAPACITY FOR THE
 GAS REGULATOR IS NOT INDICATED. 410.2(3)
  
 6. OK
  
 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF
 PERMIT FOR THE BUILD COM:
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED AT
 THE TIME OF BUILD-0UT OF KITCHEN, AND AT
 THE TIME OF APPLICATION FOR THE GAS
 PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION
 SHEET ALSO REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
 ****RESPONSE NOTED, BUT THERE IS NO LISTING INDICATED
 ON THE SUBMITTALS FOR THE REGULATORS. THE SUBMITTALS
 SHOW REGULATORS MANUF. IN ENGLAND. THERE IS A JEAVONS
 J48 REGULATOR MADE BY AMERICAN METER THAT IS LISTED AND
 APPROVED AY AGA & CAGA THAT CAN BE USED. SECTION
 410.2(1).
  
  
 REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.
 ****RESPONSE NOTED, BUT THE REVISION FOR THE POOL
 BOILER EQUIPMENT INFORMATION BLOCK STILL SHOWS THE MOST
 REMOTE POOL HEATER/BOILER TO BE 10 FEET FROM THE
 REGULATOR. THE RISER DIAGRAM INDICATES AT LEAST 20
 FEET. PLEASE CORRELATE. SECTION 106.1.1.
  
 ***********NEW COMMENT***********
  
 1B. SHT P3.16 THE GAS METER PIPING SCHEMATIC DOES NOT
 REFLECT THE RISER DIAGRAMS. PLEASE INDICATE IF THE
 PIPING SCHEMATIC IS FOR BOTH METERS OR FOR ONE METER.
 IF FOR BOTH METERS THEN THE RISER DIAGRAMS SHALL
 REFLECT THE PIPING SCHEMATIC FOR THE GAS METERS.
  
 2B. SHT P3.16 REGULATOR SCHEDULE SHOWS 5 REGULATORS,
 BUT ONLY 2 REGULATORS ARE SHOWN ON THE RISER DIAGRAMS.
 PLEASE SHOW WHERE EACH REGULATOR IS LOCATED ON THE
 RISER DIAGRAMS. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2008-08-06 Cont ID  
Sent By kstevens Date 2008-08-06 Time 12:39 Rev Time 0.00
Received By kstevens Date 2008-08-06 Time 12:39 Sent To  
Notes
2008-08-06 14:40:24REVISION DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****SEPARATE GAS PERMIT REQUIRED*****
  
 1. SHT P3.16 GAS METER PIPING SCHEMATIC NOT APPROVED. A
 LETTER FROM FLORIDA PUBLIC UTILITIES AUTHORIZING THE
 BYPASS OF THE GAS METER IS REQUIRED AS PROVIDER OF THE
 GAS.
  
 2. SHT P3.1.6 THERE ARE CHANGES TO THE PLANS FROM
 PREVIOUS REVISION, (13), THAT ARE NOT INDICATED WITH A
 CLOUD OR A REVISION NUMBER. PLEASE CLOUD AND NUMBER ALL
 REVISIONS. SECTION 106.1.3.
  
 3. SHT P3.1.6 PIPE SIZING DOWNSTREAM OF THE REGULATOR
 TO THE POOL/SPA BOILERS IS NOT CORRECT PER TABLE
 402.4(2). EACH STUBOUT & VALVE FOR THE POOL BOILERS
 SHALL BE 1". (3/4" IS SHOWN). 1" IS REQUIRED TO THE
 LAST POOL HEATER. (3/4" IS SHOWN). 1-1/4" IS REQUIRED
 TO POOL BOILER #2. (1" IS SHOWN). 1-1/2" IS REQUIRED
 FROM THE REGULATOR TO THE SPA BOILER. (1" IS SHOWN).
 PLEASE SEE RED LINE CORRECTION ON SUBMITTED REVISION.
  
 4. SUBMIT MANUF. SPECIFICATIONS FOR THE POOL/SPA
 BOILERS. INDICATE MODEL NUMBER, LISTING & BTU LOAD FOR
 EACH.
  
 5. SUBMIT MANUF. SPECIFICATIONS FOR THE REGULATORS.
 INDICATE MODEL NUMBER AND SHOW MAX CAPACITY FOR TOTAL
 LOAD OF ALL APPLIANCES COMBINED.
  
 6. SHT P3.1.6 GAS RISER DIAGRAM. UNIONS ARE REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVE FOR THE GAS
 REGULATORS. PLEASE SHOW ON RISER DIAGRAM.
  
 7. SEE BELOW FOR PROVISO FROM PLANS STAMPED AT TIME OF
 PERMIT FOR THE BUILD COM:
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED AT
 THE TIME OF BUILD-0UT OF KITCHEN, AND AT
 THE TIME OF APPLICATION FOR THE GAS
 PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION
 SHEET ALSO REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
  
  
 REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-08-28 Cont ID  
Sent By kstevens Date 2006-08-28 Time 16:40 Rev Time 0.00
Received By kstevens Date 2006-08-26 Time 17:29 Sent To  
Notes
2006-08-28 00:00:00 
  
 PASSED/PROVISO
  
 MANUF. SPECIFICATION SHEETS REQUIRED AT
 THE TIME OF BUILD-0UT OF KITCHEN, AND AT
 THE TIME OF APPLICATION FOR THE GAS
 PERMIT FOR THE POOL HEATERS. - MANUF. SPECIFICATION
 SHEET ALSO REQUIRED FOR
 THE GAS REGULATORS. INDICATE THE MODEL
 NUMBER FOR REGULATORS. REGULATORS SHALL
 BE LISTED.
  
  
 REVISION REQUIRED FOR SHT P3.16
 INDICATING THE CORRECT INLET PRESSURE
 FROM THE METER, AND SHOWING UNIONS
 DOWNSTREAM OF THE SHUT OFF VALVES FOR
 THE REGULATORS.-PIPE SIZING SHALL BE
 CHECKED WHEN INLET PRESSURE IS
 CLARIFIED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By kstevens Date 2006-08-04 Time 08:35 Rev Time 0.00
Received By kstevens Date 2006-08-04 Time 08:34 Sent To  
Notes
2006-08-07 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PLUMBING REVIEW:
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE GAS LINE TO
 THE POOL HEATER APPEARS TO BE RUN IN THE
 5TH FLOOR CEILING. WILL THE POOL HEATER
 BE LOCATED IN THE CEILING, OR WILL THERE
 BE A DROP TO THE HEATER. PLEASE CLARIFY.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 ****RESPONSE NOTED, BUT THE TABLE SHOWN
 IS FROM FBC-2001 FUEL GAS CODE. PLEASE
 DESIGN AND INDICATE TABLE FROM FBC-2004
 FUEL GAS CODE.
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
  
 G. AT KITCHEN BUILD-0UT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-05-27 Cont ID  
Sent By kstevens Date 2006-05-27 Time 08:25 Rev Time 0.00
Received By kstevens Date 2006-05-27 Time 08:25 Sent To  
Notes
2006-05-27 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM BUILDING PLAN REVIEW:
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (EACH
 SYSTEM).
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (FOR
 KITCHEN SYSTEM ONLY).
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 127 Status N Date 2008-12-23 Cont ID  
Sent By adarroug Date 2008-12-23 Time 16:05 Rev Time 0.00
Received By adarroug Date 2008-12-23 Time 16:05 Sent To P
Notes
2008-12-23 16:05:51TO "P" BOX/ 2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 126 Status N Date 2008-12-08 Cont ID  
Sent By adarroug Date 2008-12-08 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-12-08 Time 15:47 Sent To P
Notes
2008-12-08 15:47:43TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 125 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 13:04 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 13:04 Sent To  
Notes
2008-11-06 13:05:24TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 124 Status N Date 2008-11-06 Cont ID  
Sent By adarroug Date 2008-11-06 Time 12:55 Rev Time 0.00
Received By adarroug Date 2008-11-06 Time 12:55 Sent To P
Notes
2008-11-06 12:56:03TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 123 Status N Date 2008-11-03 Cont ID  
Sent By adarroug Date 2008-11-03 Time 09:41 Rev Time 0.00
Received By adarroug Date 2008-11-03 Time 09:41 Sent To B
Notes
2008-11-03 09:42:23TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 122 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 10:09 Sent To E
Notes
2008-10-06 10:09:41TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 121 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 08:58 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 08:58 Sent To M
Notes
2008-10-06 08:58:24TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 120 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 13:05 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 13:05 Sent To E
Notes
2008-09-25 13:05:43TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 119 Status N Date 2008-09-25 Cont ID  
Sent By adarroug Date 2008-09-25 Time 09:59 Rev Time 0.00
Received By adarroug Date 2008-09-25 Time 09:59 Sent To M
Notes
2008-09-25 09:59:28TO "M" BOX/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 118 Status N Date 2008-09-22 Cont ID  
Sent By adarroug Date 2008-09-22 Time 14:23 Rev Time 0.00
Received By adarroug Date 2008-09-22 Time 14:23 Sent To E
Notes
2008-09-22 14:23:58TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 117 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 13:57 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 13:57 Sent To E
Notes
2008-09-15 13:58:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 116 Status N Date 2008-09-11 Cont ID  
Sent By adarroug Date 2008-09-11 Time 08:39 Rev Time 0.00
Received By adarroug Date 2008-09-11 Time 08:39 Sent To E
Notes
2008-09-11 08:40:14TO "DPALMER" DESK/RESTAMP

Review Stop I INCOMING/PROCESSING
Rev No 115 Status N Date 2008-09-05 Cont ID  
Sent By adarroug Date 2008-09-05 Time 10:25 Rev Time 0.00
Received By adarroug Date 2008-09-05 Time 10:25 Sent To B
Notes
2008-09-05 10:25:58TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 114 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 14:05 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 14:05 Sent To Z
Notes
2008-08-28 14:06:04TO "ZONING"BOX.

Review Stop I INCOMING/PROCESSING
Rev No 113 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 10:59 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 10:59 Sent To B
Notes
2008-08-27 11:00:13TO "BUILD" JIM W.

Review Stop I INCOMING/PROCESSING
Rev No 112 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 11:00 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 11:00 Sent To P
Notes
2008-08-27 11:01:01TO "PLUMB" KEN S.

Review Stop I INCOMING/PROCESSING
Rev No 111 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 08:58 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 08:58 Sent To G
Notes
2008-08-27 08:59:39TO "GAS" KEN S.

Review Stop I INCOMING/PROCESSING
Rev No 110 Status N Date 2008-08-27 Cont ID  
Sent By tgordon Date 2008-08-27 Time 08:51 Rev Time 0.00
Received By tgordon Date 2008-08-27 Time 08:51 Sent To Z
Notes
2008-08-27 08:52:15TO "ZONING" BOX.

Review Stop I INCOMING/PROCESSING
Rev No 109 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 15:00 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 15:00 Sent To  
Notes
2008-08-25 15:01:06TO "COMM" BD #2.

Review Stop I INCOMING/PROCESSING
Rev No 108 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 12:40 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 12:40 Sent To B
Notes
2008-08-21 12:41:12TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 107 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 16:21 Sent To P
Notes
2008-08-18 16:22:01TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 106 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 14:14 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 14:14 Sent To E
Notes
2008-08-08 14:14:37TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 105 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 10:34 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 10:34 Sent To M
Notes
2008-08-06 10:34:27TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 104 Status N Date 2008-08-06 Cont ID  
Sent By adarroug Date 2008-08-06 Time 09:27 Rev Time 0.00
Received By adarroug Date 2008-08-06 Time 09:27 Sent To E
Notes
2008-08-06 09:27:47TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 103 Status N Date 2008-08-04 Cont ID  
Sent By adarroug Date 2008-08-04 Time 11:15 Rev Time 0.00
Received By adarroug Date 2008-08-04 Time 11:15 Sent To B
Notes
2008-08-04 11:16:11TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 102 Status N Date 2008-08-01 Cont ID  
Sent By adarroug Date 2008-08-01 Time 09:46 Rev Time 0.00
Received By adarroug Date 2008-08-01 Time 09:46 Sent To M
Notes
2008-08-01 09:46:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 101 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 14:59 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 14:59 Sent To B
Notes
2008-07-29 15:00:07TO "JWITMER" DESK/4 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 100 Status N Date 2008-07-22 Cont ID  
Sent By adarroug Date 2008-07-22 Time 10:40 Rev Time 0.00
Received By adarroug Date 2008-07-22 Time 10:40 Sent To B
Notes
2008-07-22 10:40:46TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 99 Status N Date 2008-07-17 Cont ID  
Sent By adarroug Date 2008-07-17 Time 11:30 Rev Time 0.00
Received By adarroug Date 2008-07-17 Time 11:30 Sent To M
Notes
2008-07-17 11:31:21TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 98 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 09:28 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 09:28 Sent To Z
Notes
2008-07-10 09:28:45TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 97 Status N Date 2008-06-24 Cont ID  
Sent By adarroug Date 2008-06-24 Time 16:57 Rev Time 0.00
Received By adarroug Date 2008-06-24 Time 16:57 Sent To B
Notes
2008-06-24 16:58:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 96 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 15:13 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 15:13 Sent To E
Notes
2008-06-19 15:13:29TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 95 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 15:10 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 15:10 Sent To M
Notes
2008-06-19 15:10:28TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 94 Status N Date 2008-06-19 Cont ID  
Sent By adarroug Date 2008-06-19 Time 15:01 Rev Time 0.00
Received By adarroug Date 2008-06-19 Time 15:01 Sent To FIRE
Notes
2008-06-19 15:01:35TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 93 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 14:50 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 14:50 Sent To E
Notes
2008-06-06 14:51:14TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 92 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 11:19 Sent To B
Notes
2008-05-30 11:20:25TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 91 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 10:09 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 10:09 Sent To  
Notes
2008-05-30 10:10:31TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 90 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 09:45 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 09:45 Sent To E
Notes
2008-05-30 09:45:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 89 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 14:35 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 14:35 Sent To B
Notes
2008-05-21 14:36:19TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 88 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 10:55 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 10:55 Sent To E
Notes
2008-05-08 10:56:15TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 87 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 09:21 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 09:21 Sent To  
Notes
2008-04-30 09:25:30TO "COMM" BD#13

Review Stop I INCOMING/PROCESSING
Rev No 86 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 10:50 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 10:50 Sent To  
Notes
2008-04-17 10:50:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 85 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 09:08 Sent To B
Notes
2008-04-17 09:09:02TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 84 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 15:10 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 15:09 Sent To E
Notes
2008-04-07 15:10:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 83 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 15:09 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 15:09 Sent To M
Notes
2008-04-07 15:09:17TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 82 Status N Date 2008-04-07 Cont ID  
Sent By adarroug Date 2008-04-07 Time 14:49 Rev Time 0.00
Received By adarroug Date 2008-04-07 Time 14:49 Sent To Z
Notes
2008-04-07 14:50:22TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 81 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 15:05 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 15:05 Sent To  
Notes
2008-03-26 15:09:42TO "COMM" BD#11

Review Stop I INCOMING/PROCESSING
Rev No 80 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 14:43 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 14:43 Sent To B
Notes
2008-03-26 14:44:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 79 Status N Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 11:58 Rev Time 0.00
Received By shill Date 2008-03-19 Time 11:58 Sent To B
Notes
2008-03-19 11:59:15TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 78 Status N Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 11:38 Rev Time 0.00
Received By shill Date 2008-03-19 Time 11:38 Sent To E
Notes
2008-03-19 11:40:49TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 77 Status N Date 2008-03-13 Cont ID  
Sent By adarroug Date 2008-03-13 Time 09:24 Rev Time 0.00
Received By adarroug Date 2008-03-13 Time 09:24 Sent To  
Notes
2008-03-13 09:24:23TO "COMM" BD#15

Review Stop I INCOMING/PROCESSING
Rev No 76 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 16:54 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 16:54 Sent To G
Notes
2008-03-12 16:54:58TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 75 Status N Date 2008-03-05 Cont ID  
Sent By adarroug Date 2008-03-05 Time 12:11 Rev Time 0.00
Received By adarroug Date 2008-03-05 Time 12:11 Sent To  
Notes
2008-03-05 12:14:44TO "COMM" BD#24

Review Stop I INCOMING/PROCESSING
Rev No 74 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 14:24 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 14:24 Sent To  
Notes
2008-03-03 14:24:43TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 73 Status N Date 2008-02-21 Cont ID  
Sent By adarroug Date 2008-02-21 Time 10:04 Rev Time 0.00
Received By adarroug Date 2008-02-21 Time 10:04 Sent To M
Notes
2008-02-21 10:05:01TO "M" BOX/1 REV AND 1 SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 72 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 16:05 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 16:05 Sent To M
Notes
2008-02-12 16:05:55TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 71 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 15:29 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 15:29 Sent To B
Notes
2008-02-12 15:29:33TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 70 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 08:35 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 08:35 Sent To M
Notes
2008-01-29 08:35:50TO "RREGUIERO" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 69 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 11:33 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 11:33 Sent To P
Notes
2008-01-28 11:33:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 68 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 11:22 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 11:22 Sent To B
Notes
2008-01-24 11:23:08TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 67 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 12:06 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 12:06 Sent To B
Notes
2008-01-18 12:06:36TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 66 Status N Date 2008-01-14 Cont ID  
Sent By adarroug Date 2008-01-14 Time 13:47 Rev Time 0.00
Received By adarroug Date 2008-01-14 Time 13:47 Sent To B
Notes
2008-01-14 13:54:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 65 Status N Date 2008-01-09 Cont ID  
Sent By adarroug Date 2008-01-09 Time 17:04 Rev Time 0.00
Received By adarroug Date 2008-01-09 Time 17:04 Sent To M
Notes
2008-01-09 17:04:45TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 64 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 16:46 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 16:46 Sent To  
Notes
2007-12-13 16:47:18TO "COMM" BD#39--ELECT AND FIRE ALARM REV

Review Stop I INCOMING/PROCESSING
Rev No 63 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 16:26 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 16:26 Sent To  
Notes
2007-12-13 16:30:12TO "COMM" BD#40--"Z", "BLDG" AND "F" REV

Review Stop I INCOMING/PROCESSING
Rev No 62 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 16:16 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 16:16 Sent To M
Notes
2007-12-13 16:16:59TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 61 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 10:40 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 10:40 Sent To M
Notes
2007-11-28 10:41:08TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 60 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 10:34 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 10:34 Sent To P
Notes
2007-11-28 10:34:34TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 59 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 14:34 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 14:34 Sent To B
Notes
2007-11-19 14:35:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 58 Status N Date 2007-11-19 Cont ID  
Sent By adarroug Date 2007-11-19 Time 14:22 Rev Time 0.00
Received By adarroug Date 2007-11-19 Time 14:22 Sent To M
Notes
2007-11-19 14:22:32TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 57 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 16:28 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 16:28 Sent To M
Notes
2007-11-06 16:29:10TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 56 Status N Date 2007-11-06 Cont ID  
Sent By adarroug Date 2007-11-06 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-11-06 Time 16:25 Sent To B
Notes
2007-11-06 16:26:04TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 55 Status   Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 11:31 Sent To  
Notes
2007-11-05 11:32:22TO "COMM" BD#29

Review Stop I INCOMING/PROCESSING
Rev No 54 Status N Date 2007-10-19 Cont ID  
Sent By adarroug Date 2007-10-19 Time 10:10 Rev Time 0.00
Received By adarroug Date 2007-10-19 Time 10:10 Sent To  
Notes
2007-11-05 10:19:52TO "COMM" BD#16
2007-10-19 10:10:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 53 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 12:37 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 12:37 Sent To  
Notes
2007-10-12 16:23:10TO "COMM" BD#36
2007-10-11 12:37:55WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 52 Status N Date 2007-10-11 Cont ID  
Sent By adarroug Date 2007-10-11 Time 12:02 Rev Time 0.00
Received By adarroug Date 2007-10-11 Time 12:02 Sent To P
Notes
2007-10-11 12:03:44TO "P" BOX

Review Stop I INCOMING/PROCESSING
Rev No 51 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 09:34 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 09:34 Sent To B
Notes
2007-10-10 09:35:01TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 50 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 13:49 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 13:49 Sent To  
Notes
2007-10-17 16:51:31TO "COMM" BD#51
2007-09-28 13:50:12WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 49 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:53 Sent To B
Notes
2007-09-28 09:54:24TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 48 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 09:51 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 09:51 Sent To B
Notes
2007-09-28 09:51:48TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 47 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:48 Sent To P
Notes
2007-09-27 10:48:41TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 46 Status N Date 2007-09-27 Cont ID  
Sent By adarroug Date 2007-09-27 Time 10:44 Rev Time 0.00
Received By adarroug Date 2007-09-27 Time 10:44 Sent To B
Notes
2007-09-27 10:45:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 45 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 13:20 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 13:20 Sent To P
Notes
2007-09-20 13:20:52TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 44 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 13:15 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 13:15 Sent To M
Notes
2007-09-20 13:15:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 43 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 11:54 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 11:54 Sent To E
Notes
2007-09-20 11:54:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 42 Status N Date 2007-09-20 Cont ID  
Sent By adarroug Date 2007-09-20 Time 09:54 Rev Time 0.00
Received By adarroug Date 2007-09-20 Time 09:54 Sent To  
Notes
2007-09-24 16:28:49TO "COMM" BD#9
2007-09-20 09:54:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 41 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 11:20 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 11:20 Sent To FIRE
Notes
2007-09-04 11:21:19TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 40 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 16:49 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 16:49 Sent To E
Notes
2007-08-31 16:49:52TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 39 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 16:43 Sent To E
Notes
2007-08-31 16:43:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 38 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 16:38 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 16:38 Sent To  
Notes
2007-08-31 16:38:43WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2007-08-27 Cont ID  
Sent By adarroug Date 2007-08-27 Time 10:16 Rev Time 0.00
Received By adarroug Date 2007-08-27 Time 10:16 Sent To  
Notes
2007-09-18 14:38:45TO "COMM" BD#24
2007-08-27 10:17:15WAITING FOR "COMM" BD-- "MECH" AND "PLUMB" REV

Review Stop I INCOMING/PROCESSING
Rev No 36 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 13:41 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 13:39 Sent To  
Notes
2007-09-19 14:14:45TO "COMM" BD#15/PLANS ON RACK-4 ROLLS--2 REV'S
2007-08-24 13:41:51WAITING FOR "COMM' BD

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2007-08-23 Cont ID  
Sent By adarroug Date 2007-08-23 Time 10:17 Rev Time 0.00
Received By adarroug Date 2007-08-23 Time 10:17 Sent To B
Notes
2007-08-23 10:17:40TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 14:50 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 14:50 Sent To B
Notes
2007-08-21 14:50:54TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:57 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:57 Sent To B
Notes
2007-08-21 09:57:31TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2007-08-21 Cont ID  
Sent By adarroug Date 2007-08-21 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-08-21 Time 09:49 Sent To FIRE
Notes
2007-08-21 09:50:10TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2007-08-08 Cont ID  
Sent By mmiller Date 2007-08-08 Time 18:27 Rev Time 0.00
Received By mmiller Date 2007-08-08 Time 18:27 Sent To B
Notes
2007-08-08 18:27:26SENT TO JIM WITMER'S DESK MMILLLER

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 15:12 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 15:12 Sent To Z
Notes
2007-07-30 15:13:02TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 15:09 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 15:09 Sent To P
Notes
2007-07-30 15:09:51TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 15:04 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 15:04 Sent To M
Notes
2007-07-30 15:04:36TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 15:00 Sent To B
Notes
2007-07-30 15:01:20TO "JWITMER" DESK/SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 10:40 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 10:40 Sent To B
Notes
2007-07-26 10:41:00TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2007-07-09 Cont ID  
Sent By adarroug Date 2007-07-09 Time 10:31 Rev Time 0.00
Received By adarroug Date 2007-07-09 Time 10:31 Sent To M
Notes
2007-07-09 10:31:35TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 13:38 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 13:38 Sent To B
Notes
2007-07-06 13:38:50TO "JWITMER" DESK/3 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2007-06-14 Cont ID  
Sent By adarroug Date 2007-06-14 Time 10:45 Rev Time 0.00
Received By adarroug Date 2007-06-14 Time 10:45 Sent To B
Notes
2007-06-14 10:46:07TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2007-06-04 Cont ID  
Sent By adarroug Date 2007-06-04 Time 09:12 Rev Time 0.00
Received By adarroug Date 2007-06-04 Time 09:12 Sent To B
Notes
2007-06-04 09:12:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 10:16 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 10:16 Sent To B
Notes
2007-05-25 10:16:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2007-05-24 Cont ID  
Sent By adarroug Date 2007-05-24 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-05-24 Time 11:49 Sent To  
Notes
2007-06-14 13:40:54TO "COMM" BD#3
2007-05-24 11:50:03WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2007-05-18 Cont ID  
Sent By adarroug Date 2007-05-18 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-05-18 Time 08:55 Sent To B
Notes
2007-05-18 08:55:28TO "KCONRAD" DESK/SUBMITTAL--FOR JERALD SMITH

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 10:48 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 10:48 Sent To B
Notes
2007-04-27 10:48:30TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 10:47 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 10:47 Sent To P
Notes
2007-04-27 10:48:00TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 14:16 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 14:16 Sent To P
Notes
2007-04-19 14:16:28TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 14:06 Sent To E
Notes
2007-04-19 14:07:25TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 14:03 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 14:03 Sent To FIRE
Notes
2007-04-19 14:03:59TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 14:02 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 14:02 Sent To B
Notes
2007-04-19 14:02:49TO "JWITMER" DESK/SUBMITTAL/3 BOXES

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 11:52 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 11:52 Sent To B
Notes
2007-04-19 11:52:48TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-16 Cont ID  
Sent By adarroug Date 2007-04-16 Time 15:51 Rev Time 0.00
Received By adarroug Date 2007-04-16 Time 15:51 Sent To B
Notes
2007-04-16 15:52:14TO "JIWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 17:29 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:29 Sent To B
Notes
2007-04-03 17:29:33TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 19:55 Sent To P
Notes
2007-03-29 19:55:33TO KS DESK

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 13:40 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 13:40 Sent To B
Notes
2007-03-01 13:43:44TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-31 Time 10:36 Rev Time 0.00
Received By adarroug Date 2007-01-31 Time 10:36 Sent To  
Notes
2007-02-07 16:47:45TO "COMM" BD#8
2007-01-31 10:36:39WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 08:45 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 08:44 Sent To  
Notes
2006-11-17 13:19:14TO "COMM" BD#40
2006-11-16 08:46:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-23 Cont ID  
Sent By adarroug Date 2006-09-23 Time 16:48 Rev Time 0.00
Received By adarroug Date 2006-09-23 Time 16:48 Sent To E
Notes
2006-09-23 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-17 Cont ID  
Sent By adarroug Date 2006-08-11 Time 10:37 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 10:37 Sent To  
Notes
2006-08-17 00:00:00TO "COMM" BD#38/PLANS ON RACK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-30 Cont ID  
Sent By adarroug Date 2006-06-30 Time 10:56 Rev Time 0.00
Received By adarroug Date 2006-06-30 Time 10:56 Sent To  
Notes
2006-07-18 00:00:00TO "COMM" BD#35
2006-06-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-30 Cont ID  
Sent By adarroug Date 2006-03-15 Time 09:10 Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 09:10 Sent To  
Notes
2006-04-06 00:00:00TO "COMM" BD#32/PLANS ON RACK-11 ROLLS
 AND 3 BOXES
2006-03-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-27 Cont ID  
Sent By adarroug Date 2005-09-27 Time 09:03 Rev Time 0.00
Received By adarroug Date 2005-09-27 Time 09:03 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#41/PLANS ON RACK
2005-09-27 00:00:00WAITING FOR "COMM" BD

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2008-09-09 Cont ID  
Sent By rkussner Date 2008-09-09 Time 11:41 Rev Time 0.00
Received By rkussner Date 2008-09-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 35 Status P Date 2008-11-03 Cont ID  
Sent By hmoser Date 2008-11-03 Time 10:06 Rev Time 0.00
Received By hmoser Date 2008-11-03 Time 10:06 Sent To  
Notes
2008-11-03 10:09:3311/03/08
 SUBMITTAL'S FOR CLOTH TAPE OK.

Review Stop M MECHANICAL (A/C)
Rev No 34 Status P Date 2008-10-18 Cont ID  
Sent By rregueir Date 2008-10-18 Time 17:44 Rev Time 0.00
Received By rregueir Date 2008-10-18 Time 17:43 Sent To PC
Notes
2008-10-18 17:44:10RESTAMP OF FULL MECH SET OF PLANS M0.0 THRU M8.01

Review Stop M MECHANICAL (A/C)
Rev No 33 Status P Date 2008-09-22 Cont ID  
Sent By hmoser Date 2008-09-22 Time   Rev Time 0.00
Received By hmoser Date 2007-04-18 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 32 Status P Date 2008-08-11 Cont ID  
Sent By rregueir Date 2008-08-11 Time 16:39 Rev Time 0.00
Received By rregueir Date 2008-08-11 Time 16:32 Sent To PC
Notes
2008-08-11 16:39:32PAGE M7.01 REVISION 19 SUPERSEDES REVISION 18. REVISION
 19 STAMPED AND INCORPORATED INTO PERMIT SET OF PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 31 Status P Date 2008-08-05 Cont ID  
Sent By rregueir Date 2008-08-05 Time 08:56 Rev Time 0.00
Received By rregueir Date 2008-08-05 Time 08:55 Sent To FIRE
Notes
2008-08-05 08:56:44REVISION 20 PG M2.03. PBC DERM APPROVED SHEET FOR
 ADDITION OF 2000 GALLON FUEL TANK IN GENERATOR ROOM
 WITH SHOP DRAWINGS FOR FUEL FILLING SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 30 Status P Date 2008-07-08 Cont ID  
Sent By rregueir Date 2008-07-08 Time 11:20 Rev Time 0.00
Received By rregueir Date 2008-07-08 Time 10:49 Sent To PC
Notes
2008-07-08 11:21:25REVISION #21 PAGES M2.01 AND M2.04

Review Stop M MECHANICAL (A/C)
Rev No 29 Status P Date 2008-05-16 Cont ID  
Sent By rregueir Date 2008-05-16 Time 09:58 Rev Time 0.00
Received By rregueir Date 2008-05-16 Time 08:05 Sent To PC
Notes
2008-05-16 09:57:59REVISION 20 PAGES: M2.02, M2.05, M2.07 THROUGH M2.30,
 M4.01, M4.02

Review Stop M MECHANICAL (A/C)
Rev No 28 Status P Date 2008-05-15 Cont ID  
Sent By rregueir Date 2008-05-15 Time 16:05 Rev Time 0.00
Received By rregueir Date 2008-05-15 Time 16:01 Sent To PC
Notes
2008-05-15 16:02:46REV.19 PAGE M5.02 - ADD AHU/CU SGR1 TO DUCTLESS SPLIT
 SYSTEM SCHEDULE.

Review Stop M MECHANICAL (A/C)
Rev No 27 Status F Date 2008-05-15 Cont ID  
Sent By rregueir Date 2008-05-15 Time 13:29 Rev Time 0.00
Received By rregueir Date 2008-05-15 Time 13:28 Sent To PC
Notes
2008-05-15 13:29:09REV.27 PG LS.15 FIRESTOP DETAIL. PLEASE SEE BUILDING
 REVIEW COMMENTS DATED 5/12/08.

Review Stop M MECHANICAL (A/C)
Rev No 26 Status P Date 2008-03-25 Cont ID  
Sent By hmoser Date 2008-03-25 Time 19:12 Rev Time 0.00
Received By hmoser Date 2008-03-25 Time 19:12 Sent To  
Notes
2008-03-25 19:13:57SUBMITTAL 15-500-002 4" HOOD VENT

Review Stop M MECHANICAL (A/C)
Rev No 25 Status P Date 2008-03-25 Cont ID  
Sent By hmoser Date 2008-03-25 Time 18:54 Rev Time 0.00
Received By hmoser Date 2008-03-25 Time 18:54 Sent To E
Notes
2008-03-25 18:55:53SUBMITTAL # 15-840-001GARAGE AIR

Review Stop M MECHANICAL (A/C)
Rev No 24 Status P Date 2008-03-25 Cont ID  
Sent By hmoser Date 2008-03-25 Time 18:12 Rev Time 0.00
Received By hmoser Date 2008-03-25 Time 18:12 Sent To  
Notes
2008-03-25 18:14:08SUBMITTAL # 15-700-15FANS

Review Stop M MECHANICAL (A/C)
Rev No 23 Status F Date 2008-03-25 Cont ID  
Sent By hmoser Date 2008-03-25 Time 18:04 Rev Time 0.00
Received By hmoser Date 2008-03-25 Time 18:04 Sent To  
Notes
2008-03-25 18:09:01SUBMITTAL # 15-700-16 DENIED
 PLEASE SHOW TYPE OF ANCHORS USED ON STRAP TO WALL.
 HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 22 Status P Date 2008-03-05 Cont ID  
Sent By rregueir Date 2008-03-05 Time 15:52 Rev Time 0.00
Received By rregueir Date 2008-03-05 Time 15:37 Sent To PC
Notes
2008-03-05 15:52:48REV 18 PAGES M0.00, M2.01, M2.02, M2.04, M2.05
 PAGE M2.03 HAS A NEW FUEL STORAGE TANK ADDED AND IS
 REQUIRED TO BE SUBMITTED TO PALM BEACH COUNTY DERM.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 21 Status P Date 2008-03-04 Cont ID  
Sent By rregueir Date 2008-03-04 Time 14:01 Rev Time 0.00
Received By rregueir Date 2008-03-04 Time 13:59 Sent To PC
Notes
2008-03-04 14:00:52SMOKE CONTROL RATIONAL ANALYSIS REPORT BY WCIS
 CONSULTING, LLC.

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2008-03-05 Cont ID  
Sent By rregueir Date 2008-03-05 Time 15:35 Rev Time 0.00
Received By rregueir Date 2008-03-04 Time 09:23 Sent To PC
Notes
2008-03-04 13:59:45REVISION 17 OK ALL PAGES EXCEPT M2.03.
 M2.03 REQUIRES SUBMITTAL TO PALM BEACH COUNY DERM.
 PAGES M2.01, M2.02, M2.04 AND M2.05 WERE SUPERCEDED BY
 REVISION 18 AND ARE MARKED "SEE REVISED"
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2008-02-26 Cont ID  
Sent By hmoser Date 2008-02-26 Time 17:39 Rev Time 0.00
Received By hmoser Date 2008-02-26 Time 17:39 Sent To  
Notes
2008-02-26 17:40:47SUBMITTAL # 15.500.003 SMOKE FIRE DAMPERS.

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2008-02-26 Cont ID  
Sent By hmoser Date 2008-02-26 Time 17:08 Rev Time 0.00
Received By hmoser Date 2008-02-26 Time 17:08 Sent To  
Notes
2008-02-26 17:11:20SUBMITTAL # 15-700-008 MITSUBISHI A/C

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2008-02-26 Cont ID  
Sent By hmoser Date 2008-02-26 Time 16:33 Rev Time 0.00
Received By hmoser Date 2008-02-26 Time 16:33 Sent To  
Notes
2008-02-26 16:55:35SUBMITTAL # 15-700-009 DAIKINA/C UNITS

Review Stop M MECHANICAL (A/C)
Rev No 16 Status   Date 2008-02-13 Cont ID  
Sent By hmoser Date 2008-02-13 Time 07:19 Rev Time 0.00
Received By hmoser Date 2008-02-13 Time 07:19 Sent To  
Notes
2008-02-13 07:21:43SUBMITTAL # 15-700-006 AIR DISTRIBUTION

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2008-02-12 Cont ID  
Sent By hmoser Date 2008-02-12 Time 16:22 Rev Time 0.00
Received By hmoser Date 2008-02-12 Time 16:22 Sent To  
Notes
2008-02-12 16:24:28SUBMITTLE # 15.700.013 ACME FANS
 SUBMITTLE # 15.700.010 WALL VENTS

Review Stop M MECHANICAL (A/C)
Rev No 14 Status P Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 15:40 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 15:39 Sent To PC
Notes
2008-01-22 15:40:18SUBMITTAL #15-700.011 MITSUBISHI MINI-SPLIT UNITS

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2008-01-22 Cont ID  
Sent By rregueir Date 2008-01-22 Time 15:39 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 14:50 Sent To PC
Notes
2008-01-22 15:39:11SUBMITTAL #15-500.005 FIRE/SMOKE DAMPERS

Review Stop M MECHANICAL (A/C)
Rev No 12 Status F Date 2007-12-18 Cont ID  
Sent By rregueir Date 2007-12-18 Time 09:19 Rev Time 0.00
Received By rregueir Date 2007-12-12 Time 15:49 Sent To PC
Notes
2007-12-18 09:19:33REVIEW #: REV.16
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 PAGES RELATED TO OUTSTANDING REVIEW COMMENTS WHICH HAVE
 NOT BEEN ADDRESSED WILL NOT BE STAMPED UNTIL ALL
 OUTSTANDING ISSUES ARE ADDRESSED. PLEASE SEE REVIEW
 COMMENTS PUBLISHED ON 6/26/07 AND 10/21/07.
  
 1 THROUGH 4: OK FROM PREVIOUS REVIEW.
  
 5. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 6. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 7. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 8. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 9 THROUGH 11: OK FROM PREVIOUS REVIEW.
  
 12. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 13. THE MAJORITY OF ISSUES RAISED IN PREVIOUS REVIEWS
 AS COMMENT #13 HAVE NOT BEEN ADDRESSED. THE NOTE ON
 M0.00, M2.01, M2.03 CLAIMING NATURAL VENTILATION FOR
 SMOKE CONTROL UNDER THE 2001 CODE HAS NOT BEEN REMOVED.
 SEE FBC 403.15 FOR REQUIREMENTS UNDER FBC 2004. THERE
 HAS BEEN NO RATIONAL ANALYSIS SUBMITTED FOR THE SMOKE
 CONTROL SYSTEM AS REQUIRED BY FBC 909.2, 909.4 AND FBC,
 M 513.4, 513.4. NO INFORMATION HAS BEEN PROVIDED
 REGARDING THE SUITABILITY OF AHU 12 AND RELATED SUPPLY
 DUCTWORK FOR USE AS PART OF THE SMOKE CONTROL SYSTEM
 (APPARENTLY) TO DELIVER MAKE-UP AIR. IT WAS REQUESTED
 IN PREVIOUS REVIEW TO SHOW THESE COMPONENTS TO BE IN
 COMPLIANCE WITH FBC, M 513.10.2 AND FBC 513.10.5.
  
 ALSO, IS MECHANICAL ROOM 051 TO BE USED AS A PLENUM FOR
 BOTH AIR CONDITIONING AND SMOKE CONTROL MODES? IN SMOKE
 CONTROL MODE, THIS ROOM APPEARS TO BE SERVING AS AN
 EXHAUST DUCT. THE SUITABILITY OF THIS ROOM FOR USE AS A
 PART OF THE SMOKE EXHAUST DUCT SYSTEM SHOULD BE PART OF
 THE RATIONAL ANALYSIS FOR THE FOLLOWING REASON: AMONG
 OTHER REQUIREMENTS, 513.10.2 REQUIRES EXHAUST DUCTS TO
 BE CONSTRUCTED IN ACCORDANCE WITH FBC, M CHAPTER 6.
 FBC, M 602.2 LIMITS THE USE OF GYPSUM PLENUMS TO
 SYSTEMS WHERE THE AIR TEMPERATURE DOES NOT EXCEED 125
 DEGREES F.
 NOTE: THESE REQUIREMENTS APPLY TO ALL DUCT AND
 EQUIPMENT WHICH WILL BE USED AS PART OF THE SMOKE
 CONTROL SYSTEM, SUCH AS AHUS 13 AND 14.
  
 IN ADDITION, THE DESIGN OF THE SUPPLY, RETURN AND
 EXHAUST DUCT AND DAMPER SYSTEMS RELATED TO SEF-5,
 SEF-7, AHU-13 AND AHU-14 IS UNCLEAR ON THE PLANS DUE TO
 THE AMOUNT OF INTERSECTING DUCTS, REFRIGERANT LINES AND
 WALLS WITHIN THIS SMALL AREA. PLEASE PROVIDE A CLEAR
 DEPICTION OF THIS AREA (PERHAPS A LARGER SCALE DETAIL
 OF THIS AREA) TO DISCERN THE DESIGN INTENT IN ORDER TO
 FACILITATE A COMPLETE REVIEW FOR COMPLIANCE WITH FBC, M
 513.
 NOTE: SEVERAL DUCT PENETRATIONS OF RATED WALL AND
 FLOOR/CEILING ASSEMBLIES ARE SHOWN TO BE PROTECTED WITH
 FIRE DAMPERS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC, M 607.2.1. IN ADDITION TO FIRE PROTECTION,
 DUCTS AND AIR TRANSFER OPENINGS ARE REQUIRED TO BE
 PROTECTED WITH A MINIMUM CLASS II, 250DEGREE F SMOKE
 DAMPER COMPLYING WITH THE FLORIDA BUILDING CODE,
 BUILDING IN ACCORDANCE WITH FBC, M 513.2.1.
  
 FURTHERMORE, THE SMOKE CONTROL MAKE-UP AIR INTAKE AND
 EXHAUST OUTLET LOCATIONS ASSOCIATED WITH SEF-5 AND
 SEF-7 ARE NOT LOCATED SO AS TO MINIMIZE THE POTENTIAL
 FOR INTRODUCING SMOKE OR FLAME INTO THE BUILDING.
 EXHAUST OUTLETS SHALL BE SO LOCATED AS TO MINIMIZE
 REINTRODUCTION OF SMOKE INTO THE BUILDING IN ACCORDANCE
 WITH FBC, M 513.10.3.
 PLEASE ADDRESS ALL THESE ISSUES, WITH SUPPORTING
 DOCUMENTATION IF APPLICABLE, WHEN RESUBMITTING.
  
 14. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 15. REGARDING SMOKE CONTROL AS SHOWN ON M2.02 AND
 M2.05, PLEASE SEE COMMENT 13 ABOVE AS ALL RELATED
 COMMENTS APPLY IN THESE AREAS. FBC, M SEC.513.
  
 16 AND 17: OK
  
 18. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 19. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 20. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
  
 21. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 22 AND 23: OK
  
 24. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 25. OK
  
 26. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 27. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: THE CONDITIONS RELATED TO PREVIOUS COMMENT ALSO
 APPLY TO PG M2.16.
  
 28. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 29 AND 30: OK
  
 31. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 32. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 33. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 34. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 35. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: SEE THE SUPPLY DUCT CROSSING THE CORRIDOR AT
 MEN?S AND WOMEN?S LOCKER ROOMS.
  
 36. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 37. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 38. OK
  
 39. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: SEVERAL PAGES RELATED TO THIS COMMENT WERE NOT
 RESUBMITTED WITH THIS REVISION.
  
 40. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: THE PAGE RELATED TO THIS COMMENT WAS NOT
 RESUBMITTED WITH THIS REVISION.
  
 41. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: SEVERAL PAGES RELATED TO THIS COMMENT WERE NOT
 RESUBMITTED WITH THIS REVISION.
  
 42 THROUGH 44: OK
  
 45. NO PAGES RELATED TO THIS COMMENT WERE RESUBMITTED.
 IF THERE ARE NO CHANGES FROM THE PERMIT SET,
 RESUBMISSION IS NOT NECESSARY.
  
 46. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 47. OK EXCEPT, M4.01 RISER OAR-4 STILL HAS NO SIZE
 SHOWN FOR BRANCH OFFS ON MEZZANINE AND GROUND LEVELS.
  
 48 AND 49: OK
  
 A: M2.01: BASED ON THE LATEST REVISED ARCHITECTURAL
 PLANS ON FILE IN THE PERMIT SET (REV.18 DATED 9-18-07),
 THE LOCATIONS OF FIRE DAMPERS SHOWN ON THIS PAGE STILL
 DO NOT CORRESPOND WITH THE LOCATIONS OF RATED WALLS.
 EXAMPLES: 1) 12X12 TRANSFER DUCT FROM COPY 004 TO
 RECEPTION 004 SHOWS FD IN A NON-RATED WALL. 2) 6 INCH
 FLEX DUCT ENTERING CONFERENCE 008 THROUGH A RATED WALL
 WITH NO FD. 3) 12X8 SUPPLY FEEDING RECEPTION 004 SHOWS
 A FD WHERE THERE IS NO WALL OF ANY KIND. THERE ARE
 SEVERAL OTHER LOCATIONS. PLEASE CHECK THE ENTIRE AREA
 AND COORDINATE LOCATIONS OF REQUIRED FIRE DAMPERS WITH
 LOCATIONS OF RATED WALLS ON ARCHITECTURAL PLANS. DO NOT
 SHOW FDS IN NON-RATED WALLS AS THEY WOULD NOT BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING AS REQUIRED
 BY FBC, M 607.2.
  
 B. OK
  
 C. OK
  
 D. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 E. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 F. M2.04: SEF-5 DUCT (AND POSSIBLY SEF-7 DUCT) STILL
 SHOWS FIRE DAMPERS. SHOW OPENING PROTECTIVES WHICH ARE
 IN COMPLIANCE WITH FBC, M 607.2.1.
  
 G. M2.06: O.A. DUCT HAS BEEN ADDED. HOWEVER, O.A. RATE
 FOR AHU ST-11 IS NOT SHOWN ON EQUIPMENT SCHEDULE. SEE
 M-5.01. ALSO, VENTILATION SYSTEMS SHALL BE DESIGNED TO
 BE CAPABLE OF REDUCING THE SUPPLY OF OUTDOOR AIR TO THE
 MINIMUM VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF
 ASHRAE 62 IN COMPLIANCE WITH FBC 13-409.1.ABC.1.1.
 THERE IS NO VOLUME DAMPER ON O.A. DUCT.
  
 H. THIS HAS GENERALLY BEEN CORRECTED. HOWEVER, ON M2.07
 AND M2.08 THE C.O. SENSORS HAVE A DESIGNATION FOR
 ?GEF-5&R.? PLEASE SHOW A DESIGNATION WHICH CORRESPONDS
 WITH THE FANS SERVING THE FLOOR WHERE THE C.O. SENSORS
 ARE LOCATED.
  
 I. OK
  
 J. O.A. RATES FOR AHU 18 IS NOW ON PLANS. HOWEVER,
 COOLING LOAD CALCS, AS PREVIOUSLY REQUESTED, WERE NOT
 PROVIDED AS REQUIRED BY FBC 13-407.1.ABC.1. ALSO, THE
 ENERGY CALCULATION FORM SUBMITTED IS NOT THE CORRECT
 VERSION. AS THIS PERMIT APPLICATION WAS SUBMITTED PRIOR
 TO DEC. 8, 2006 THE CORRECT FORM IS 400A V2.11. IN
 ADDITION, THE ADDRESS ON THE PROJECT SUMMARY SHEET IS
 INCORRECTLY STATED AS 430 HIBISCUS, RATHER THAN THE
 PERMITTED ADDRESS OF 480 HIBISCUS. PLEASE ALSO SEE THAT
 THE OWNER/AGENT HAS NOT SIGNED THE FORM AS REQUIRED BY
 FBC 13-103.1. PLEASE MAKE ALL NECESSARY CORRECTIONS AND
 RESUBMIT ENERGY CALCULATIONS.
  
 K. OK
  
 L.PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
 NOTE: PG M2.33 WAS NOT RESUBMITTED WITH REV.16.
  
 M. OK EXCEPT, M2.31 WAS NOT RESUBMITTED WITH REV.16.
 THE CURRENT M2.31 (REV.4) SHOWS THE RELIEF VENT FOR
 STAIR #3 AS 36X36 WHILE THE RISER DIAGRAM FOR STAIR #3
 ON M4.03 (REV.16) SHOWS THE RELIEF VENT AS 18X18. WHICH
 IS CORRECT? PLEASE CLARIFY.
  
 N. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 O. OK. HAVE THESE SHAFT ENCLOSURES BEEN INCORPORATED
 INTO THE ARCHITECTURAL PLANS?
  
 P. THIS PAGE WILL BE REVIEWED IN CONJUNCTION WITH
 RESUBMITTED ENERGY CALCULATIONS.
  
 Q. COMMENT 33(A) WAS NOT ADDRESSED.
  
 R. M6.02 WAS NOT RESUBMITTED AS PART OF REV.16.
  
 S. OK
  
 T. OK
  
 U. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 V. PREVIOUS COMMENT(S) NOT ADDRESSED IN WRITING OR ON
 PLANS. SHOW ALL REQUIRED/REQUESTED INFORMATION AND
 COMPLIANCE WITH CITED CODE SECTION AS STATED IN
 PREVIOUS REVIEW COMMENTS.
  
 NOTE: REVISIONS TO MECHANICAL PLANS CONTINUE TO BE
 ADDED WITHOUT PREVIOUS REVIEW COMMENTS BEING ADEQUATELY
 ADDRESSED. THESE CHANGES HAVE NOT BEEN INCORPORATED
 INTO THE PERMIT SET OF PLANS. WE ARE NOW AT A POINT
 WHERE IT BECOMES IMPRACTICAL TO REVIEW FOR CHANGES
 UNTIL ALL OUTSTANDING REVIEW COMMENTS HAVE BEEN
 ADDRESSED AND THE RELATED CODE DEFICIENCIES ARE
 CORRECTED. NO FURTHER CHANGES TO MECHANICAL PLANS WILL
 BE REVIEWED UNTIL ALL OUTSTANDING COMMENTS HAVE BEEN
 ADEQUATELY ADDRESSED.
  
 AS THE ABOVE COMMENTS INDICATE, THE MAJORITY OF
 PREVIOUS REVIEW COMMENTS ARE STILL OUTSTANDING. PLEASE
 PROVIDE A WRITTEN RESPONSE TO EACH COMMENT WITH A
 DESCRIPTION OF HOW EACH COMMENT HAS BEEN ADDRESSED.
 THIS WILL HELP TO FACILITATE A TIMELY REVIEW. ONE SET
 OF REV.16 PLANS WILL BE RETAINED BY THIS OFFICE FOR THE
 PURPOSE OF DOCUMENTING REPEAT CODE DEFICIENCIES AND TO
 ASSIST IN IDENTIFYING CHANGES DURING SUBSEQUENT
 REVIEWS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 11 Status F Date 2007-10-21 Cont ID  
Sent By rregueir Date 2007-10-21 Time 17:05 Rev Time 0.00
Received By rregueir Date 2007-10-10 Time 17:02 Sent To  
Notes
2007-10-21 17:04:17REV.13 AND REV.15
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 WITH ONE COPY RETAINED TO BE INCLUDED IN PERMIT SET OF
 PLANS:
 M2.09
 M2.12
 M2.15
 M2.18
 M2.21
 M2.24
 M2.27
 M2.30
 M6.01
  
 THE REMAINING PAGES FROM REV.13 AND REV.15 ARE DENIED
 AND RETURNED WITH COMMENTS TO FOLLOW. TWO DIFFERENT
 SETS OF REVISIONS WERE SUBMITTED FOR REVIEW: REV.13 AND
 REV.15. PAGES M0.00, 2.01, 2.04, 2.31, 2.32, 5.02 HAVE
 BEEN REMOVED FROM REV.13 SUBMITTAL AND REPLACED BY
 REV.15. ALL CHANGES FROM BOTH REVISIONS WILL BE
 COMPARED TO THE PERMIT PLANS AND BE REVIEWED FOR CODE
 COMPLIANCE AS WELL AS FOR RESPONSES TO PREVIOUS REVIEW
 COMMENTS DATED 6/26/07.
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW COMMENTS
 GENERATED BY ADDITIONAL CHANGES IN THESE REVISIONS WILL
 APPEAR AT THE END OF REVIEW AND BE GIVEN LETTER, RATHER
 THAN NUMBER, DESIGNATIONS.
  
 1 THROUGH 4: OK
  
 5. M2.01: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
  
 6. M2.01: PROVIDE WALL MOUNTING DETAIL WHICH WORKS IN
 CONJUNCTION WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS RELATED TO AIRFLOW AND SERVICE CLEARANCES.
 FBC,M 303.1 AND 303.4
  
 7. M2.02: A) NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
 B) PROVIDE WALL MOUNTING DETAIL WHICH WORKS IN
 CONJUNCTION WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS RELATED TO AIRFLOW AND SERVICE CLEARANCES.
 FBC,M 303.1 AND 303.4
  
 8. M2.02: THE DESIGNATION OF THIS ROOM HAS BEEN CHANGED
 TO "STORAGE 014" ON PG A1.1. PLEASE COORDINATE
 DRAWINGS. FBC 106.1.1.
  
 9 THROUGH 11: OK
  
 12. M2.04: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
  
 13. M2.04: A) WRITTEN RESPONSE FROM DESIGNER (DRAFTED
 8/7/07, PRIOR TO THIS REVISION) INDICATES "NATURAL
 VENTILATION" WILL BE USED FOR THE REMOVAL OF SMOKE IN
 THE LOBBY AREA. HOWEVER, M2.04 SHOWS PORTIONS OF THE
 LOBBY AREA PROVIDED WITH MECHANICAL SMOKE CONTROL
 PROVIDED BY THE EXHAUST METHOD. SMOKE CONTROL NOTE ON
 M0.00 AND M2.01 IS CLAIMING 412.5 OF THE 2001 FBC FOR
 USE OF "NATURAL VENTILATION" AS SMOKE CONTROL. THAT
 CODE SECTION IS NOT APPLICABLE TO THIS PERMIT AS THIS
 JOB IS UNDER THE 2004 FBC W/ 2005 REVISIONS. UNDER THIS
 CODE, FBC 403.15 (HIGH RISE BUILDINGS) REQUIRES SMOKE
 CONTROL BE PROVIDED IN ACCORDANCE WITH FBC SEC.909.
 THIS SECTION ALLOWS FOR THREE POSSIBLE METHODS OF SMOKE
 CONTROL. SEE FBC 909.6 THROUGH 909.8. GIVEN THAT A
 "NATURAL VENTILATION" METHOD IS NOT LISTED IN THE 2004
 FBC, THERE ARE SEVERAL AREAS OF THE BUILDINGWHICH ARE
 NOT PROVIDED WITHSMOKE CONTROL. SHOW ON PLANS HOW
 AREAS PREVIOUSLY COVERED BY "NATURAL" MEANS WILL NOW BE
 COVERED AS REQUIRED BY FBC 909. HAS A RATIONAL ANALYSIS
 FOR THE SYSTEM BEING USED BEEN PREPARED AND SUBMITTED
 AS PART OF THE PERMIT RECORD? PLEASE SEE FBC 909.2 AND
 909.4 FOR SPECIFIC REQUIREMENTS.
 B) IS AHU 12 AND RELATED SUPPLY DUCTWORK TO BE USED AS
 PART OF THE SMOKE CONTROL SYSTEM FOR THE LOBBY AREA?
 DUCTS SHALL BE CONSTRUCTED TO MEET THE REQUIREMENTS OF
 FBC,M 513.10.2 AND FANS SHALL COMPLY WITH FBC,M
 513.10.5. SHOW COMPLIANCE WITH THESE SECTIONS.
  
 14. M2.05: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
  
 15. M2.05: SEE COMMENT 13 ABOVE RELATED TO SMOKE
 CONTROL REQUIREMENTS.
  
 16 AND 17: OK
  
 18. M2.07: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
  
 19. M2.07: 24X8 SMOKE EXHAUST DUCTS FROM RISER SE-1 ON
 FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 20. M2.08: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5 INCLUDING FOR CU-19. ALSO, PROVIDE WALL
 MOUNTING DETAIL WHICH WORKS IN CONJUNCTION WITH
 MANUFACTURER'S INSTALLATION INSTRUCTIONS RELATED TO
 AIRFLOW AND SERVICE CLEARANCES. FBC,M 303.1 AND 303.4
  
 21. M2.08: SE-2 AND SE-3 INTAKE AND OA-4 OUTLET DUCTS
 ARE SHOWN WITH FIRE DAMPERSAT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 22 AND 23: OK
  
 24. M2.10: A) NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5.
 B) 24X8 SMOKE EXHAUST DUCTS FROM RISER SE-1 ON FLOOR
 PLAN WITH FIRE DAMPERS AT RATED WALL PENETRATIONS.
 WHERE THE INSTALLATION OF A FIRE DAMPER WILL INTERFERE
 WITH THE OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM
 IN ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE
 PROTECTION SHALL BE UTILIZED IN ACCORDANCE WITH FBC,M
 607.2.1.
  
 25. OK
  
 26. M2.11: SE-2 AND SE-3 INTAKE AND OA-4 OUTLET DUCTS
 ARE SHOWN WITH FIRE DAMPERSAT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 27. M2.13: NO BOLLARDS ARE SHOWN ON MECHANICAL OR
 ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH FBC,M 303.4
 AND 304.5. ALSO, 24X8 SMOKE EXHAUST DUCTS FROM RISER
 SE-1 ON FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 28. M2.14 AND M2.17: NO BOLLARDS ARE SHOWN ON
 MECHANICAL OR ARCHITECTURAL PLANS. SHOW COMPLIANCE WITH
 FBC,M 303.4 AND 304.5 INCLUDING FOR CU-19. ALSO, SE-2
 AND SE-3 INTAKE AND OA-4 OUTLET DUCTS ARE SHOWN WITH
 FIRE DAMPERSAT RATED WALL PENETRATIONS. WHERE THE
 INSTALLATION OF A FIRE DAMPER WILL INTERFERE WITH THE
 OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM IN
 ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE
 PROTECTION SHALL BE UTILIZED IN ACCORDANCE WITH FBC,M
 607.2.1.
  
 29 AND 30: OK
  
 31. M2.17: PROVIDE DETAIL AND LISTED ASSEMBLY
 (THROUGH-PENETRATION FIRESTOP SYSTEM) TO BE USED FOR
 TYPE-B FLUE PIPE. ALSO, FIRE DAMPER FOR EXHAUST DUCT IS
 NOT SHOWN ON PLANS. SEE FBC,M 607.8.
  
 32. M2.17: BOILER ROOM CALCULATIONS CALL FOR 1 SQ.IN.
 PER 2000 BTU/H. THIS METHOD REQUIRES TWO PERMANENT
 OPENINGS COMMUNICATING DIRECTLY WITH THE OUTDOORS, EACH
 WITH MIN. 525 SQ.IN. FREE AREA, BASED ON TH 1,050,000
 TOTAL BTU/H SHOWN ON PLAN. SEE FBC.FG 304.6.1. FLOOR
 PLAN SHOWS ONE 36X12 LOUVER WHICH DOES NOT COMMUNICATE
 WITH THE OUTDOORS SINCE IT IS LOCATED INSIDE AN
 ENCLOSED PARKING GARAGE.
  
 33. A) BOILER ROOM FLOOR PLAN SHOWS THREE FANS. NONE OF
 THESE FANS ARE LISTED ON EQUIPMENT SCHEDULE. HOW DO
 THESE FANS WORK IN CONJUNCTION WITH COMBUSTION AIR
 REQUIREMENTS? MECHANICAL COMBUSTION AIR IS NOT
 INDICATED IN BOILER ROOMCALCULATIONS. IF MECHANICAL
 COMBUSTION AIR IS TO BE USED, IT SHALL BE DESIGNED IN
 ACCORDANCE WITH FBC,FG 304.9. SHOW ALL RELEVANT
 CALCULATIONS AND REQUIRED CONTROLS IF APPLICABLE. B) EF
 "EXHAUSTO BESB" ATTACHED TO 12 INCH ROUND DUCT GOES TO
 36X30 LOUVER. FLOOR PLAN INDICATES THIS IS AN INTAKE
 LOUVER. IS THIS AN INTAKE OR EXHAUST SYSTEM? IF IT IS
 EXHAUST, IT SHALL BE AT LEAST 10 FEET FROM GARAGE
 INTAKE LOUVERS IN ACCORDANCE WITH FBC,M 401.5.1 AND IT
 SHALL BE ORIENTED SO AS NOT TO BE READILY DRAWN IN BY
 GARAGE VENTILATION SYSTEM IN ACCORDANCE WITH FBC,M
 501.2.
 C) FLOOR PLAN AT BOILER ROOM WALL CALLS FOR "HIGH TEMP"
 FIRE DAMPERS IN EXHAUST DUCTS. WHAT IS TO BE THE DESIGN
 TEMPERATURE OF THE ACTUATING DEVICES? WHAT IS TO BE THE
 NORMAL AIR TEMPERATURE WITHIN THE DUCTS? THE OPERATING
 TEMPERATURE SHALL BE APPROXIMATELY 50 DEG.F ABOVE THE
 NORMAL TEMPERATURE WITHIN THE DUCT SYSTEM, BUT NOT LESS
 THAN 160 DEG.F IN ACCORDANCE WITH FBC,M 607.3.1.1(1).
 SHOW EXPECTED AIR TEMPERATURE AND REQUIRED TEMPERATURE
 SETTING FOR FIRE DAMPER ACTUATING DEVICES (FUSIBLE
 LINKS). FBC 106.1.2
  
 34. M2.19: 24X8 SMOKE EXHAUST DUCTS FROM RISER SE-1 ON
 FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 35. M2.19: ALL DUCT PENETRATIONS OF FIRE RESISTANCE
 RATED CORRIDORS SHALL BE PROTECTED WITH SMOKE DAMPERS
 IN ACCORDANCE WITH FBC,M 607.5.4. SEE ALSO FBC 715.3.3.
 SMOKE DAMPERS SHALL BE ACTUATED BY ONE OF THE
 PRESCRIBED METHODS LISTED UNDER FBC,M 607.5.4.1.
  
 36. M2.19: REFRIGERANT LINES FOR AHU-17 ARE STILL NOT
 SHOWN ON PLANS. SHOW ROUTING OF REFRIGERANT LINES ON
 PLANS. FBC 106.1.1.
  
 37. M2.19: 24X8 SMOKE EXHAUST DUCTS FROM RISER SE-1 ON
 FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 38. OK
  
 39. M2.20, 2.23, 2.26, 2.29: SE-2 AND SE-3 INTAKE AND
 OA-4 OUTLET DUCTS ARE SHOWN WITH FIRE DAMPERSAT RATED
 WALL PENETRATIONS. WHERE THE INSTALLATION OF A FIRE
 DAMPER WILL INTERFERE WITH THE OPERATION OF A REQUIRED
 SMOKE CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513,
 APPROVED ALTERNATIVE PROTECTION SHALL BE UTILIZED IN
 ACCORDANCE WITH FBC,M 607.2.1.
  
 40. M2.22: 24X8 SMOKE EXHAUST DUCTS FROM RISER SE-1 ON
 FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 41. M2.25, 2.28: 24X8 SMOKE EXHAUST DUCTS FROM RISER
 SE-1 ON FLOOR PLAN WITH FIRE DAMPERS AT RATED WALL
 PENETRATIONS. WHERE THE INSTALLATION OF A FIRE DAMPER
 WILL INTERFERE WITH THE OPERATION OF A REQUIRED SMOKE
 CONTROL SYSTEM IN ACCORDANCE WITH SECTION 513, APPROVED
 ALTERNATIVE PROTECTION SHALL BE UTILIZED IN ACCORDANCE
 WITH FBC,M 607.2.1.
  
 42 THROUGH 44: OK
  
 45. M3.01A THROUGH M3.03F: ALL OF THESE PAGES ARE
 MARKED AS PART OF REV. 13 BUT THERE ARE NO AREAS ON
 PLANS MARKED ANS HAVING BEEN REVISED. WITHOUT ANY
 INDICATION OF CHANGES, THESE PAGES WILL NOT BE
 REVIEWED.
  
 46. M4.01: RISERS 2A,2B,3A,3B SHOW TYPICAL OUTLET SIZES
 OF 12X6. HOWEVER, FLOOR PLANS SHOW THESE OUTLETS TO BE
 8X6. COORDINATE RISER PLANS WITH FLOOR PLANS AND
 RESUBMIT.
  
 47. M4.02: OA-4 RISER SHOWS ONE OUTLET WITH ONE FSD AND
 NO SIZE AT MEZZANINE AND GROUND LEVELS. FLOOR PLAN ON
 MEZZANINE LEVEL SHOWS TWO OUTLETS WITH TWO FSD'S.
 COORDINATE FLOOR PLANS AND RISER PLANS. ALSO, SHOW
 SIZES OF ALL RISER INLETS AND OUTLETS WHICH DO NOT
 MATCH THE "TYPICAL" DESIGNATION.
  
 48 AND 49: OK
  
 NEW COMMENTS:
  
 A. M2.01: THROUGHOUT THIS FLOOR PLAN THERE ARE
 UNPROTECTED OPENINGS IN RATED WALLS, FIRE DAMPERS IN
 NON-RATED WALLS AND FIRE DAMPERS WHERE THERE ARE NO
 WALLS. COORDINATE THE LOCATIONS OF REQUIRED OPENING
 PROTECTIVES WITH THE LOCATIONS OF RATED WALL ASSEMBLIES
 AS SHOWN ON ARCHITECTURAL PLANS. SHOW OPENING
 PROTECTIVES WHERE THEY ARE REQUIRED AND REMOVE THEM
 WHERE THEY ARE NOT. FBC,M 607.8
  
 B. M2.01: A TRANSFER DUCT HAS BEEN ADDED TO COPY ROOM
 004 FOR BALANCED RETURN BUT HAS NOT BEEN ADDED FOR
 OFFICE 004, WHICH IS A HABITABLE ROOM REQUIRING
 BALANCED RETURN IN ACCORDANCE WITH FBC,M 601.4. SHOW
 COMPLIANCE AND RESUBMIT.
  
 C. M2.XX: THE SYMBOL "EM" HAS BEEN ADDED TO SEVERAL
 PAGES, BUT THS SYMBOL HAS NOT BEEN ADDED TO
 ABBREVIATION OR SYMBOL LEGENDS ON M0.00. PLEASE CLARIFY
 THE MEANING OF THE ABBREVIATION/SYMBOL. FBC 106.1.1
  
 D. M2.03: BASED ON FLOOR PLAN A1.2, THERE ARE SOME
 DUCTS SHOWN PENETRATING RATED WALL ASSEMBLIES.
 COORDINATE WITH ARCHITECTURAL PLANS AND SHOW OPENING
 PROTECTIVES AT ALL DUCT PENETRATIONS OF RATED WALLS IN
 ACCORDANCE WITH FBC,M 607.5.
  
 E. M2.03: IS THE SUPPLY A/C SYSTEM TO ALSO SERVE AS
 MAKE-UP AIR FOR THE SMOKE CONTROL OF THE SOUTH BLOCK?
 IF SO, DUCTS SHALL BE CONSTRUCTED TO MEET THE
 REQUIREMENTS OF FBC,M 513.10.2 AND AHU-16 SHALL BE
 DESIGNED TO MEET THE REQUIREMENTS OF FBC,M 513.10.5.
  
 F. M2.03: SOME AREAS IN AND AROUND LOBBY ARE PROTECTED
 BY FIRE RESISTANCE RATED ASSEMBLIES SUCH AS WALLS AND
 POSSIBLY CEILINGS. DUCTS ARE SHOWN PENETRATING SUCH
 ASSEMBLIES WITHOUT OPENING PROTECTIVES AS REQUIRED BY
 FBC,M 607.5. EXAMPLE: 6X6 DUCT FEEDING THE FIRE COMMAND
 ROOM. SHOW PENETRATIONS TO BE PROTECTED AS REQUIRED BY
 THIS SECTION. COORDINATE WITH ARCHITECTURAL PLANS.
 ALSO, SEF-5 DUCT IS SHOWN WITH MULTIPLE FIRE DAMPERS.
 WHERE THE INSTALLATION OF A FIRE DAMPER WILL INTERFERE
 WITH THE OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM
 IN ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE
 PROTECTION SHALL BE UTILIZED IN ACCORDANCE WITH FBC,M
 607.2.1.
  
 G. M2.06: WHAT IS THE SOURCE OF VENTILATION FOR STORAGE
 AREAS? NOTE: STORAGE ROOMS FOR RETAIL STORES AND SALES
 FLOORS ARE REQUIRED TO HAVE VENTILATION AT A RATE OF
 0.15 CFM PER SQ.FT IN ACCORDANCE WITH FBC,M TABLE 403.3
 AND ASHRAE 62-2001 TABLE 2.1.
  
 H. M2.04 THROUGH M2.17: FLOOR PLAN INDICATES EACH C.O.
 SENSOR IS DESIGNATED FOR ONE GARAGE FAN. GARAGE
 VENTILATION SCHEDULE SHOWS THAT BOTH FANS ARE REQUIRED
 TO PROVIDE THE MINIMUM VENTILATION RATE OF 1.5 CFM PER
 SQ.FT. WHEN CO LEVELS REACH 25 PPM. THEREFORE, IF ANY
 CO SENSOR ON A FLOOR DETECTS 25 PPM, BOTH FANS ON THAT
 FLOOR SHOULD BE ACTUATED. SHOW COMPLIANCE WITH FBC,M
 SEC.404.
  
 I. M2.19: WOMEN'S LOCKER ROOM, FLOOR PLAN SHOWS 220 CFM
 SUPPLY AIR WITH ONLY 120 CFM OF EXHAUST. ALL AIR
 SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1(3). SHOW EXHAUST TO BE
 EQUAL OR GREATER THAN THE AIR BEING SUPPLIED TO THESE
 SPACES. ALSO, FAN SCHEDULE ON M5.02 SHOWS TEF 1-4
 CONTROLLED BY SWITCH. SHOW HOW THIS WILL ENSURE ALL AIR
 SUPPLIED TO THESE SPACES BY AHU-17 IS EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1(3). TEF'S MAY BE
 INTERLOCKED WITH AHU OR RUN CONTINUOUS AS EXAMPLES OF
 POSSIBLE METHODS OF COMPLIANCE.ALSO, SHOW COMPLIANCE
 WITH FBC,M 401.3.
  
 J. M2.20: AHU/CU 18 IS NEW TO PLANS. SHOW THE O.A. RATE
 ON SHCEDULE (M5.01). ALSO, PROVIDE COOLING LOAD
 CALCULATIONS OR SYSTEM SIZING SUMMARY AS PART OF
 REVISED ENERGY CALCULATIONS IN ACCORDANCE WITH FBC
 13-407.1.ABC.1.
  
 K. M2.20: FLOOR PLAN SHOWS 75 CFM SUPPLY IN HEALTH CLUB
 TOILET ROOMS WITH ONLY 50 CFM OF EXHAUST. ALL AIR
 SUPPLIED TO SUCH SPACES SHALL BE EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1(3). SHOW EXHAUST TO BE
 EQUAL OR GREATER THAN THE AIR BEING SUPPLIED TO THESE
 SPACES. ALSO, FAN SCHEDULE ON M5.02 SHOWS TX-1
 CONTROLLED BY SWITCH. SHOW HOW THIS WILL ENSURE ALL AIR
 SUPPLIED TO THESE SPACES BY AHU-18 IS EXHAUSTED IN
 ACCORDANCE WITH FBC,M 403.2.1(3). TX'S MAY BE
 INTERLOCKED WITH AHU OR RUN CONTINUOUS AS EXAMPLES OF
 POSSIBLE METHODS OF COMPLIANCE.ALSO, SHOW COMPLIANCE
 WITH FBC,M 401.3.
  
 L. M2.33: KITCHEN EXHAUST GREASE DUCT, WHY IS IT
 TERMINATING AT A WALL WITH A PLENUM AND LOUVER? GREASE
 DUCT TERMINATIONS SHALL COMPLY WITH FBC,M 506.3.12.
 ALSO, PROVIDE DETAIL FOR SUPPORT OF HORIZONTAL AND
 VERTICAL SECTIONS OF GREASE DUCTS IN ACCORDANCE WITH
 FBC,M 506.3.3. PROVIDE SUBMITTAL/INSTALLATION
 INSTRUCTIONS FOR 2-HOUR RATED DUCT WRAP SYSTEM TO BE
 USED.
  
 M. M4.03: RISER PLAN AND ROOF PLANS DO NOT CORRELATE.
 IT APPEARS THAT SPF 4 AND SPF 3 HAVE BEEN REVERSED.
 ALSO, ROOF PLAN ON M2.31 DOES NOT SHOW ANY BAROMETRIC
 OR RELIEF DAMPERS AS SHOWN ON RISER PLAN. PLEASE
 CORRECT.
  
 N. M4.03: STAIR SHAFTS ARE SHOWN WITH RELIEF DAMPERS
 SET TO 0.05" W.G. HOW WILL THESE WORK TO ACHIEVE THE
 REQUIRED PRESSURIZATION LEVEL OF 0.15" TO 0.35" AS
 SHOWN IN FBC 909.20.5? IF THIS IS THE INTENDED DESIGN,
 SHOW JUSTIFICATION WITHIN THE SMOKE CONTROL RATIONAL
 ANALYSIS AS REQUIRED BY FBC 909.4.
  
 O. M4.04: THIS PAGE HAS A TABLE IN THE UPPER RIGHT
 CORNER WHICH IS NOT LEGIBLE. PROVIDE THIS TABLE IN A
 LEGIBLE FORM AND RESUBMIT. FBC 106.1.1 AND 106.1.3.
  
 P. M5.01: CHANGES ON THIS PAGE WILL BE REVIEWED WHEN
 SUBMITTED WITH REVISED ENERGY CALCULATIONS REFLECTING
 EQUIPMENT CHANGES SHOWN ON PLAN. SEE COMMENT K.
  
 Q. M5.02: THIS PLAN WILL BE REVIEWED IN CONJUNCTION
 WITH RESPONSES TO COMMENTS 33(A), I AND K, WHICH MAY
 EFFECT THE EXHAUST FAN SCHEDULE AND CONTROLS.
  
 R. M6.02: THE THROUGH-PENETRATION FIRESTOP SYSTEM HAS
 BEEN REPLACED BUT IT IS OF POOR VISUAL QUALITY AND IS
 NOT LEGIBLE. PLEASE CORRECT AND RESUBMIT.
  
 S. M7.01: NOTE 1-D HAS BEEN DELETED FROM PAGE. PLEASE
 SEE COMMENTS I AND K AND PROVIDE CONTROL INFO AS NEEDED
 TO CORRELATE WITH THOSE CONDITIONS.
  
 T. M7.01: SEE COMMENT H REGARDING GARAGE EXHAUST FAN
 CONTROLS.
  
 U. M7.01: CORRIDOR PRESSURIZATION NOTE D CALLS FOR THE
 FLOOR OF INCIDENCE TO BE PRESSURIZED. THIS APPEARS TO
 BE COUNTER TO THE INTENT OF THE PRESSURIZATION METHOD
 OF SMOKE CONTROL AS STATED IN FBC 909.6. PROVIDE
 RATIONAL ANALYSIS WHICH CORRESPONDS WITH SEQUENCE OF
 OPERATION SHOWING HOW SMOKE CONTROL SYSTEM IS TO
 FUNCTION. SEE FBC 909.2 AND 909.4.
  
 V. M7.01: STAIL PRESSURIZATION NOTE B, PRESSURES SHALL
 BE IN ACCORDANCE WITH FBC 909.20.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2007-08-14 Cont ID  
Sent By rregueir Date 2007-08-14 Time 10:57 Rev Time 0.00
Received By rregueir Date 2007-08-10 Time 13:52 Sent To  
Notes
2007-08-14 10:57:09SUBMITTAL WITH NEW REFRIGERANT RISER CALCULATIONS,
 SHOWING LOCATIONS OF REQUIRED SHAFTS BASED ON
 REFRIGERANT QUANTITIES AND THE THROUGH-PENETRATION
 FIRESTOP SYSTEMS TO BE USED WHERE SHAFTS WILL NOT BE
 REQUIRED. ONLY ONE COPY HAS BEEN SUBMITTED. THEREFORE,
 IT WILL BE RETAINED PENDING RECEIPT OF REVISED PLANS
 SHOWING LOCATION OF SHAFTS. AT THAT TIME, THE SUBMITTAL
 WILL BE USED TO ENSURE THAT SHAFT LOCATIONS ARE ORRECT
 IN CONJUNCTION WITH RISER CALCULATIONS IN THE
 SUBMITTAL.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
2007-08-10 13:52:38REFRIGERANT CHASES - UPDATED 8/14/07
  
 8/13/07 - AS OF THIS TIME, THE SUBMITTAL STATES THAT A
 DETAIL FOR A TREMCO THROUGH-PENETRATION FIRESTOP SYSTEM
 IS SINCLUDED IN THE PACKAGE. HOWEVER, NONE COULD BE
 LOCATED IN THE PACKAGE. A CALL WAS PLACED TO TONY
 SPEZZA AT THE FELLER OFFICE. TONY SUPPLIED A DETAIL OF
 A SYSTEM INTENDED FOR USE IN THIS APPLICATION. HOWEVER,
 THE ASSEMBLY PROVIDED DOES NOT MEET THE F AND T RATING
 OF THE FLOOR BEING PENETRATED AS IS REQUIRED BY FBC
 712.4.1.2.
  
 PER THE REQUEST OF JACK NEDLIN, A COPY OF PREVIOUS PLAN
 REVIEW COMMENTS IS BEING FAXED TO HIS OFFICE. THE
 REVIEW OF THIS SUBMITTAL IS BEING PLACED ON HOLD, AGAIN
 AT THE REQUEST OF JACK NEDLIN, UNTIL A RESPONSE IS
 PROVIDED BY JACK NEDLIN OR OTHER AUTHORIZED AGENT FOR
 STEVEN FELLER, PE.
  
 8/14/07 - RECEIVED MISSING INFORMATION FROM MARC
 COLEMAN AT HH DEVELOPMENT. THE SUBMITTAL IS CURRENTLY
 UNDER REVIEW.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-07-14 Cont ID  
Sent By rregueir Date 2007-07-14 Time 16:12 Rev Time 0.00
Received By rregueir Date 2007-07-14 Time 11:47 Sent To  
Notes
2007-07-14 16:12:17NEW SHEETS M3.01A THROUGH M3.03F
 APARTMENT LAYOUTS FOR 2ND THROUGH 7TH FLOORS
 REVISION OF EQUIPMENT SCHEDULE TO MATCH THESE FLOOR
 PLANS IS PENDING.\
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2007-06-28 Cont ID  
Sent By rregueir Date 2007-06-28 Time 19:41 Rev Time 0.00
Received By rregueir Date 2007-06-28 Time 19:31 Sent To  
Notes
2007-06-28 19:40:32RESPONSE TO LETTERS SUBMITTED BY STEVEN FELLER, PE
  
 LETTER 1:
 A) REGARDING THE LETTER RELATED TO REFRIGERANT
 QUANTITIES, THERE ARE INCONSISTENCIES BETWEEN THE
 ESTIMATED LINE LENGTHS AND THOSE SHOWN ON PLANS.
 EXAMPLE 1: RISER 1, 6TH FLOOR HAS AN ESTIMATED LINE
 LENGTH OF 70 FT. ON THE 6TH FLOOR THERE IS AN
 ADDITIONAL LENGTH (APPROXIMATELY 20 FT.) OF HORIZONTAL
 PIPE TO TRAVEL FROM APT A6 TO THE CHASE, WHICH DOES NOT
 APPEAR TO HAVE BEEN TAKEN INTO ACCOUNT. ALSO ON RISER
 1, HOW IS THERE ONLY 20 FEET DIFFERENCE BETWEEN THE 6TH
 FLOOR AND THE 10TH FLOOR? THAT IS ONLY 5 FEET PER
 FLOOR.
 EXAMPLE 2: RISER 4 ON M2.04 SHOWS 43 FT OF HORIZONTAL
 PIPE WHICH DOES NOT APPEAR TO BE TAKEN INTO ACCOUNT IN
 THE ESTIMATED LENGTH. ALSO, PLEASE PROVIDE COOLING LOAD
 CALCULATIONS FOR COMMERCIAL SPACES 1 AND 2 (ACCOUNTING
 FOR 1ST FLOOR AND MEZZANINE LEVELS) SHOWING 5 TONS TO
 BE SUFFICIENT FOR FUTURE USE OF THIS SPACE.
  
 B) WHY WERE NO CALCULATIONS GIVEN FOR RISER 2? NO SHAFT
 REQUIREMENT IS SHOWN ON THE CHART ON ANY LEVEL AND IT
 IS LIKELY TO HAVE A HIGHER QUANTITY OF REFRIGERANT THAN
 RISER 4.
  
 C) PLEASE PROVIDE A BASIS FOR THE REFRIGERANT
 QUANTITIES USED. THE REFRIGERANT CHARGE QUANTITIES
 SHOWN ON THE CALCULATIONS APPEAR TO BE BASED ON THE
 CARRIER MODEL 24ABR, WHICH IS THE EQUIPMENT SHOWN ON A
 RECENTLY SUBMITTED REVISED EQUIPMENT SCHEDULE. HOWEVER,
 THE EQUIPMENT SIZES SHOWN IN THE CALCULATIONS REFLECT
 THOSE ON THE PERMIT SET OF PLANS AND NOT THOSE ON THE
 REVISED SCHEDULE. PLEASE CLARIFY WHICH INFORMATION IS
 TO BE USED TO VERIFY THE CALCULATIONS.
  
 PLEASE SEE THE LATEST CARRIER LONG-LINE APPLICATION
 GUIDE WHICH STATES THE FACTORY CHARGE IS FOR THE FIRST
 15 FT AND 0.6 OZ SHALL BE ADDED FOR EACH ADDITIONAL
 FT.
  
 NOTE: THE DESIGN OF STARTING THE SHAFT CONSTRUCTION AT
 THE FLOOR LEVEL WHERE THE REFRIGERANT QUANTITY EXCEEDS
 THE ASHRAE 15 ALLOWABLE LIMIT IS AGREED TO IN CONCEPT,
 BUT A MORE ACCURATE DETERMINATION OF WHERE THAT LIMIT
 IS TO BE REACHED AT EACH RISER IS NEEDED.
  
 LETTER 2:
 THE USE OF A THROUGH-PENETRATION FIRESTOP SYSTEM AS
 STATED IN FBC 712.4.1.2 IS FOUND TO BE THE CORRECT
 APPLICATION FOR THE CONDITION WHEN THE REFRIGERANT
 CHASE IS NOT ENCLOSED IN A SHAFT. HOWEVER, THE DETAILS
 ON M6.02 OF THE PERMIT SET OF PLANS SHOWS TWO POSSIBLE
 SYSTEMS, NEITHER OF THEM ARE APPLICABLE TO THE FIELD
 CONDITIONS UNDER WHICH THEY WOULD BE EMPLOYED.
  
 THE FIRST SYSTEM FOR INSULATED PIPE CAN ONLY MEET THE
 ANNULAR SPACE LIMITATIONS SHOWN IN THE DETAIL IF THERE
 IS A SINGLE INSULATED PIPE IN A SINGLE, CORRECTLY SIZED
 FLOOR (OR WALL) OPENING. THE SIZE OF THE PIPE IS
 LIMITED TO A MAXIMUM OF 1? WHEN IN MANY CASES THE
 INSULATED PIPE WILL BE 1 1/8? OR POSSIBLY LARGER.
 PLEASE ALSO NOTE THAT 712.4.1.2 REQUIRES THAT THE
 THROUGH-PENETRATION FIRESTOP SYSTEM SHALL HAVE AN F AND
 T RATING NOT LESS THAN 1 HOUR BUT NOT LESS THAN THE
 REQUIRED RATING OF THE FLOOR BEING PENETRATED.
  
 THE SECOND SYSTEM IS LIMITED IN AREA AND CAN NOT HAVE A
 MAXIMUM DIMENSION OVER 24?. IT IS LIMITED TO A MAXIMUM
 OF 3 PIPES, NONE OF WHICH ARE SHOWN TO BE INSULATED.
 THIS SYSTEM ALSO DOES NOT MEET THE T RATING AS REQUIRED
 BY 712.4.1.2 AS IT STATES THE T RATING AT 0 HOUR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.671.
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-06-26 Cont ID  
Sent By rregueir Date 2007-06-26 Time 16:54 Rev Time 0.00
Received By rregueir Date 2007-06-23 Time 15:35 Sent To  
Notes
2007-06-26 14:27:42FBC 2004 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISED MECHANICAL PLANS DATED 5/18/07. THE FOLLOWING
 PAGES PASSED REVIEW:
 M2.12, M2.18, M2.21, M2.24, M2.27, M2.30, M2.31, M2.34,
 M2.35
  
 THE BALANCE OF PAGES SUBMITTED FOR REVISION ARE DENIED.
 THE FOLLOWING COMMENTS ARE ORGANIZED BY PAGE NUMBER.
 SOME COMMENTS ARE REFERENCED MORE THAN ONCE IF THE
 ISSUE IS FOUND ON MORE THAN ONE PAGE.
  
 1. M2.01: THE ACCESS DOOR FOR GEF-1 APPEARS TO BE IN
 CONFLICT WITH THE FAN HOUSING AND WILL NOT OPEN
 COMPLETELY. SEE FBC,M 306.5 FOR SERVICE ACCESS
 REQUIREMENTS.
  
 2. M2.01: THE INTAKE LOUVER FOR GEF-1 IS SHOWN ON PLANS
 TO BE APPROXIMATELY 7' WIDE. IN ORDER TO ACHIEVE 94
 SQ.FT., AS NOTED ON PLANS, THE LOUVER WOULD NEED TO BE
 OVER 13 FEET TALL. IS THERE SUFFICIENT CLEARANCE? FBC
 106.1.2
  
 3. M2.01, M2.04, M2.07, M2.10, M2.13, M2.16: WHAT ARE
 THE ACTUAL DIMENSIONS OF THE INTAKE LOUVERS FOR THE
 GEF'S? WHY IS THE FREE AREA OF THE EXHAUST LOUVERS
 (23.375 SQ.FT) LESS THAN HALF THE AREA OF THE INTAKE
 LOUVERS AT THE FANS (51.7 SQ.FT)? ALSO, PLEASE SHOW HOW
 THE REQUIRED MINIMUM VENTILATION RATE (CONTINUOUS) OF
 0.05 CFM PER SQ.FT. IS TO BE PROVIDED IN ACCORDANCE
 WITH FBC,M 404.2.
  
 4. M2.01: GARAGE VENTILATION NOTE ON PLAN STATES "2
 EXHAUST FANS," BUT THIS FLOOR USES ONLY ONE FAN. PLEASE
 REVISE NOTE SHOWING ONE FAN PROVIDING 44,000 CFM. FBC
 106.1.1
  
 5. M2.01: WHAT IS THE ELEVATION OF CU-T1 AND AMF-1?
 APPLIANCES LOCATED IN PUBLIC GARAGES, MOTOR
 FUEL-DISPENSING FACILITIES, REPAIR GARAGES OR OTHER
 AREAS FREQUENTED BY MOTOR VEHICLES, SHALL BE INSTALLED
 A MINIMUM OF 8 FEET ABOVE THE FLOOR. WHERE MOTOR
 VEHICLES EXCEED 6 FEET IN HEIGHT AND ARE CAPABLE OF
 PASSING UNDER AN APPLIANCE, APPLIANCES SHALL BE
 INSTALLED A MINIMUM OF 2 FEET HIGHER ABOVE THE FLOOR
 THAN THE HEIGHT OF THE TALLEST VEHICLE.
 EXCEPTION: THE REQUIREMENTS OF THIS SECTION SHALL NOT
 APPLY WHERE THE APPLIANCES ARE PROTECTED FROM MOTOR
 VEHICLE IMPACT AND INSTALLED IN ACCORDANCE WITH NFPA
 88B.
  
 6. M2.01: PROVIDE WALL MOUNTING DETAIL FOR CU-T1 WHICH
 WORKS IN CONJUNCTION WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS, ESPECIALLY RELATED TO REQUIRED CLEARANCES
 FOR AIRFLOW, AND IS PROTECTED FROM MECHANICAL DAMAGE
 PER FBC,M 303.1 AND 303.4.
  
 7. M2.02: FOR CU-T2, CU-T3, CU-G1, CU-G@, CU-SGR1 AND
 AMF-1 PLEASE SEE COMMENTS 5 AND 6.
  
 8. M2.02: PLEASE SHOW HOW SERVICE ROOM 019 IS TO BE
 MAINTAINED AT A POSITIVE PRESSURE IN ACORDANCE WITH
 FBC,M 404.3 AND PROVIDED VENTILATION AS REQUIRED BY
 FBC,M 403.3.
  
 9. M2.02: FUTURE TENANT COMMERCIAL SPACE #14 FRESH AIR
 INTAKE LOUVER IS INSIDE THE PARKING GARAGE. THE AIR
 REQUIRED BY FBC,M 403.3 SHALL NOT BE RECIRCULATED PER
 403.2.1. ALSO, INTAKE OPENING LOCATIONS SHALL BE IN
 COMPLIANCE WITH FBC,M 401.5.1.
  
 10. M2.03: ARE INTAKE LOUVERS FOR THE GENERATOR MINIMUM
 10' FROM EXHAUST LOUVERS ON MEZZANINE LEVEL (M2.06)?
 FBC,M 401.5.1. ALSO, WHAT IS THE HEIGHT OF THE
 GENERATOR EXHAUST OUTLET? IS IT ON GROUND LEVEL OR
 MEZZANINE LEVEL? IT IS SHOWN ON BOTH PLANS. PLEASE
 CLARIFY AND SHOW COMPLIANCE WITH FBC,M 401.5.2 AND
 501.2.
  
 11. M2.03: WHERE IS THE CONTINUATION OF THE 8" ROUND
 EXHAUST DUCT FROM BATHROOMS AND JANITOR'S CLOSET? THERE
 IS NO CONTINUATION ON M2.06 AS THERE WAS ON PREVIOUS
 PLAN. FBC 106.1.1
  
 12. M2.04: FOR AMF-1, PLEASE SEE COMMENT #5.
  
 13. M2.04: PLEASE MARK THE SMOKE EXHAUST RISER SERVING
 THE MAIN LOBBY AREA. ALSO, IS IT THE INTENT OF THIS
 DESIGN TO CONVER THE SUPPLY DUCT SYSTEM FOR AHU-12 INTO
 A SMOKE EXHAUST DUCT WHEN THE AREA GOES INTO SMOKE
 CONTROL MODE? IF SO, THERE ARE SEVERAL ISSUES WHICH
 NEED TO BE ADDRESSED:
 A) SUPPLY DUCT APPEARS TO BE A STANDARD DUCTBOARD AND
 FLEX SYSTEM. THIS TYPE OF DUCT MAY NOT BE USED FOR ANY
 TYPE OF EXHAUST PER FBC,M 501.4 AND MUST BE DESIGNED TO
 MEET THE REQUIREMENTS FOR A SMOKE EXHAUST DUCT PER
 FBC,M 513.10.2.
 B) IF SUPPLY REGISTERS AND DIFFUSERS ARE TO BE USED FOR
 SMOKE EXHAUST, PLEASE PROVIDE SUBMITTAL DATA SHOWING
 THEIR SUITABILITY FOR USE IN A SMOKE EXHAUST SYSTEM. C)
 PLAN SHOWS FIRE DAMPERS IN SUPPLY DUCT WHICH APPEARS TO
 BE INTENDED FOR USE AS SMOKE EXHAUST DUCT. WHERE THE
 INSTALLATION OF A FIRE DAMPER WILL INTERFERE WITH THE
 OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM IN
 ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE
 PROTECTION SHALL BE UTILIZED. FBC,M 607.2.1
 D) WHAT IS THE AIR BALANCE DESIGN FOR THE DUCT SYSTEM
 WHEN IN SMOKE CONTROL MODE? FBC 106.1.2. IS THERE
 MAKE-UP AIR FOR THE 2000 CFM OF EXHAUST?
 E) PLEASE ALSO CHECK SMOKE EXHAUST DUCTS ON M2.05 TO
 VERIFY COMPLIANCE WITH THE ABOVE REQUIREMENTS.
  
 14. M2.05: FOR AMF-1, PLEASE SEE COMMENT #5.
  
 15. M2.05: THERE ARE SOME DUCTS RELATED TO THE SMOKE
 EXHAUST WHICH ARE MISSING SIZES ON PLANS. PLEASE
 CLARIFY. FBC 106.1.1
  
 16. M2.06: THERE IS NO SEPARATION BETWEEN AREAS MARKED
 AS "COMMERCIAL #15 AND "STORAGE." ARE THERE WALLS
 MISSING FROM THE PLAN? THIS MAY IMPACT THE NEED FOR
 FIRE DAMPERS PER FBC,M 607.5.
  
 17. M2.06: WHAT IS THE DESIGNATION, SIZE AND CFM OF
 RETURN GRILL IN THE 18X10 DUCT IN "STORAGE?"
  
 18. M2.07 REGARDING AMF-1 AND CU-E1, PLEASE SEE COMMENT
 #5.
  
 19. M2.07: ACORDING TO THE REFLECTIVE CEILING PLAN, THE
 ELEVATOR LOBBY AND CORRIDOR HAVE THE SAME CEILING
 HEIGHT. HOW IS IT POSSIBLE TO HAVE SIDEWALL GRILLS (TWO
 36X6) FOR SMOKE EXHAUST UNDER THESE CONDITIONS? HOW
 DOES THE FIRE WRAP INTERACT WITH THE RATED
 CORRIDOR/ELEVATOR LOBBY WALLS? HOW ARE THE OPENINGS AT
 THE END OF THE FIRE WRAP PROTECTED AT THE 36X6 GRILLS?
 THIS WOULD ESSENTIALLY BE UNPROTECTED OPENINGS IN A
 2-HOUR SHAFT. THE OVERALL INTENT OF THE DESIGN OF THIS
 AREA IS UNCLEAR AND MAY BE LACKING COORDINATION WITH
 ARCHITECTURAL PLANS.
  
 20. M2.08: REGARDING AMF-1 AND CU-19, PLEASE SEE
 COMMENT #5. REGARDING CU-E2, PLEASE SEE COMMENTS 5 AND
 6.
  
 21. M2.08: FOR SMOKE EXHAUST DUCT IN CORRIDOR ACROSS
 FROM ELECTRICAL ROOM, PLEASE SEE COMMENT #19.
  
 22. M2.08: PLEASE SHOW VENTILATION (OUTDOOR AIR) RATE
 OF 0.05 CFM PER SQ.FT FOR STORAGE AREA AND SHOW HOW THE
 AREA WILL BE MAINTAINED AT A POSITIVE PRESSURE PER
 FBC,M 404.3.
  
 23. M2.09: ARE SHOWN AS BEING REVISED ON PLAN IS
 CLOUDED AND MARKED AS REVISION 6, BUT REVISIONS LISTED
 IN TITLE BLOCK AREA ONLY GO TO REVISION 4. PLEASE
 CLARIFY. FBC 106.1.3.
  
 24. M2.10: PLEASE SEE COMMENTS 5 AND 19.
  
 25: M2.10: ELECTRICAL ROOM IN CORRIDOR SHOWS AN
 UNDERCUT DOOR FOR AIRFLOW. HOWEVER, THERE IS NO
 MECHANICAL EQUIPMENT OR MEANS TO CAUSE AIRFLOW INTO THE
 ELECTRICAL ROOM. ALSO, THE ELCTRICAL ROOM DOOR IS PART
 OF A FIRE AND SMOKE BARRIER (CORRIDOR) AND THEREFORE
 SHOULD NOT BE UNDERCUT OR HAVE ANY GAP WHICH IS NOT
 PART OF A LISTED RATED DOOR ASSEMBLY..
  
 26. M2.11: PLEASE SEE ALL COMMENTS FOR PAGE M2.08
 (20,21,22). ALSO, SEE COMMENT #25 RELATED TO ELECTRICAL
 AND STORAGE ROOMS.
  
 27. M2.13 AND M2.16: PLEASE SEE COMMENTS 5, 19 AND 25.
  
 28. M2.14 AND M2.17: PLEASE SEE COMMENTS 20,21,22.
 ALSO, PLEASE SEE COMMENT #25 FOR ELECTRICAL AND STORAGE
 ROOMS.
  
 29. M2.15: AREA CLOUDED AS REVISED IS MARKED A REVISION
 7, HOWEVER THE REVISION SCHEDULE SHOWN IN TITLE BLOCK
 AREA ONLY GOES TO REVISION 4. PLEASE CLARIFY PER FBC,M
 106.1.3.
  
 30. M2.17: THERE IS A "BOILER ROOM" LOUVER CALCULATION
 BOX ADDED TO PLAN BUT IT IS NOT MARKED AS PART OF THIS
 REVISION. PLEASE CLARIFY. ALSO, THE BOILER/POOL
 EQUIPMENT ROOM HAS A NOTE WHICH STATES "DESIGN
 PENDING." THIS AREA CAN NOT BE FULLY REVIEWED WITH
 INCOMPLETE INFORMATION.
  
 31. M2.17: HOW ARE DUCT PENETRATIONS AT THE BOTTOM OF
 THE SHAFT FOR POOL ROOM VENT DUCT AND BOILER FLUE TO BE
 PROTECTED? FBC 707.11 AND FBC,M 606.5.5.1
  
 32. M2.17: COMBUSTION AIR DUCT FOR BOILER ROOM SHOULD
 BE DESIGNED PER FBC,FG 304.6.1 OR 304.6.2. IF TWO
 OPENINGS ARE USED, THEN BOTH OPENINGS ARE TO
 COMMUNICATE DIRECTLY WITH THE OUTDOORS. SEE FIG.
 304.6.1(3).
  
 33. M2.17: PLEASE PROVIDE INFORMATION ON TYPE OF
 VENTING TO BE USED FOR THE BOILER. THE HORIZONTAL
 LENGTH OF THE VENT CONNECTOR IS PROHIBITED BY FBC, FG
 TABLE 504.2.
  
 34. M2.19: PLEASE SEE COMMENTS 5 AND 19.
  
 35. M2.19: DOES THE RATING OF THE CORRIDOR CONTINUE
 INTO THE DECK LOBBY AREA? IF SO, ALL PENETRATIONS SHALL
 BE PROTECTED PER FBC,M 607.5. ALSO, THE CORRIDOR (EXIT
 ENCLOSURE) VENTILATION SYSTEM SHALL BE INDEPENDENT OF
 OTHER BUILDING VENTILATION SYSTEMS PER FBC,M 401.4.
  
 36. M2.19: WHERE ARE THE REFRIGERANT LINES AND MEANS OF
 CONDENSATE DISPOSAL FOR AHU 17? FBC 106.1.1.
  
 37. M2.19: PLEASE SEE COMMENT #19 RELATED TO SMOKE
 EXHAUST DUCT ACROSS FROM THE ELECTRICAL ROOM.
  
 38. M2.20: PLEASE PROVIDE CONTINUATION OF ROOM ON POOL
 DECK WITH AHU 18. NONE COULD BE FOUND ON PLANS. FBC
 106.1.1.
  
 39. M2.20,M2.23, M2.26, M2.29: PLEASE SEE COMMENT #19
 REGARDING SMOKE EXHAUST DUCT ACROSS FROM ELECTRICAL
 ROOM AND COMMENT #25 REGARDING ELECTRICAL AND STORAGE
 ROOM DOORS.
  
 40. M2.22: PLEASE SEE COMMENT #19.
  
 41. M2.25, M.28: PLEASE SEE COMMENTS 19 AND 25.
  
 42. M2.32: SEF-2 SHOWS A FIRE DAMPER IN THE DUCT. WHERE
 THE INSTALLATION OF A FIRE DAMPER WILL INTERFERE WITH
 THE OPERATION OF A REQUIRED SMOKE CONTROL SYSTEM IN
 ACCORDANCE WITH SECTION 513, APPROVED ALTERNATIVE
 PROTECTION SHALL BE UTILIZED. FBC,M 607.2.1
  
 43. M2.33: PLEASE PROVIDE SIZE AND OTHER RELEVANT DATA
 FOR INTAKE SIDE DUCT FOR SPF-1 AND SPF-2. FBC 106.1.1
  
 44. M2.33: RELIEF DAMPER APPEARS TO BE INSIDE THE STAIR
 ENCLOSURE. SHOULD IT BE AN AN EXTERIOR WALL?
  
 45. M3.01 THROUGH M3.06: MANY CHANGES ON PAGES, NONE
 ARE MARKED AS REVISIONS. PLEASE CLEARLY MARK ON PLANS
 THE AREAS WHICH ARE BEING REVISED AND INDICATE A DATE
 AND REVISION NUMBER. FBC 106.1.1 AND FBC 106.1.3.
  
 46. M4.01: THERE HAVE BEEN SEVERAL REVISIONS TO THIS
 PAGE SINCE THE PERMITTED SET. PLEASE CLEARLY MARK ALL
 CHANGES WHICH HAVE TAKEN PLACE SINCE THE PERMITTED SET
 OF PLANS. FBC 106.1.3.
  
 47. M4.02: THE DESIGNATED CFM OF EXHAUST ON EACH FLOOR
 DO NOT MATCH THE CFM AS SHOWN ON FLOOR PLANS. PLEASE
 COORDINATE DRAWINGS.
  
 48. M5.01: THIS PAGE GOES FROM REVISION 1 TO REVISION
 3. PLEASE SHOW WHAT CHANGES HAVE BEEN MADE RELATED TO
 REVISION 2. FBC 106.1.3.
  
 49. M5.02: THIS PAGE CONTAINS 2 PAGES OF SCHEDULES AND
 HAVE BEEN REDUCED IN SIZE AND QUALITY TO A POINT WHERE
 MUCH OF THE INFORMATION IS NOT LEGIBLE. PLEASE CORRECT.
 FBC 106.1.3
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-02-22 Cont ID  
Sent By hmoser Date 2007-02-22 Time 18:22 Rev Time 0.00
Received By hmoser Date 2007-02-22 Time 18:22 Sent To  
Notes
2007-02-22 18:27:58PASS PROVISOPLEASE PROVIDE A COPIE OF MANUFATURERS
 INSTALLATION INSTRUCTIONS FOR CONDENSORS IN THE
 GARAGE.
 PLEASE REFER TO SECTION 303.4 FBC(M) 2004 PROTECTION
 FROM DAMAGE.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-12-19 Cont ID  
Sent By hmoser Date 2006-12-19 Time 13:29 Rev Time 0.00
Received By hmoser Date 2006-12-19 Time 13:28 Sent To  
Notes
2006-12-19 13:33:10PLANS DENIED
 PLANS SUBMITED FOR MECHANICAL ARE NO GOOD.I CALLED
 STEVEN FELLER HE IS GO TO SUBMIT NEW REVISIONS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-31 Cont ID  
Sent By pkrauss Date 2006-08-31 Time 14:43 Rev Time 0.00
Received By pkrauss Date 2006-08-25 Time 11:02 Sent To  
Notes
2006-09-01 00:00:00PROVISO:
 1.PLEASE NOTE, CO SENSORS LOCATED IN
 THE GARAGE SHALL BE CONNECTED TO
 EMERGENCY POWER.
  
 2.PLEASE VERIFY WITH THE MANUFACTURER,
 THE DISTANCE OF THE LINE SETS TO THE
 CONDENSING UNITS LOCATED ON THE ROOF.
 PLEASE SUBMIT VERIFICATION.
  
 3.SPECIFIC DRYERS ARE TO BE INSTALLED
 AT FINAL INSPECTION. PLEASE NOTE THE
 FOLLOWING UNITS EXCEED THE
 MANUFACTURER'S RECOMMENDED EXHAUST
 LENGTH; A4, A4A, A4B, & A7.PLEASE
 PROVIDE REVISION ADDRESSING THIS ISSUE
 WITHIN 30 DAYS OF THE PERMIT BEING
 ISSUED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-01 Cont ID  
Sent By pkrauss Date 2006-08-01 Time 08:10 Rev Time 0.00
Received By pkrauss Date 2006-08-01 Time 07:40 Sent To  
Notes
2006-08-01 00:00:00DENIED:
 RESPONSE LETTER DATED 6/9/06TO COMMENTS
 DATED 5/9/06 & 12/27/05:
  
 COMMENT 1:OK
  
 COMMENT 2:RESPONSE INDICATES O.A.
 CALCS PROVIDED ON PLAN SHEET M5.02.
 O.A. CALCULATIONS ARE ALSO REQUIRED FOR
 THE RESIDENTIAL UNITS IN ACCORDANCE WITH
 2004 FMC 403.3.PLEASE NOTE, OUTSIDE
 AIR CALC SCHEDULE INDICATED ON PLAN
 SHEET M5.02 NOTE 2 REFERENCES ASHRAE
 62-89.THIS SHOULD READ ASHRAE 62-01.
  
 COMMENT 3:OK
  
 COMMENT 4:RESPONSE INDICATES SMOKE
 CONTROL WAS REMOVED FROM THE RETAIL
 AREAS. PLEASE ANNOTATE ON THE PLANS
 SEQUENCE OF OPERATION IN THE EVENT OF A
 FIRE.SHOW COMPLIANCE WITH 2004 FBC
 909.
  
 COMMENT 5:RESPONSE STATES THE AHU'S
 HAVE BEEN RELOCATED TO THE MEZZANINE
 LEVEL.COMMENT ALSO REFERS TO THE FLOOR
 DRAIN LOCATED IN THE RETURN AIR PLENUM
 WHICH IS NOT IN ACCORDANCE WITH 2004 FPC
 901.2 & ASHRAE 62-01, 8.4.1.11.
  
 COMMENT 6:OK
 COMMENT 7:OK
 COMMENT 8:OK
 COMMENT 9:OK
 COMMENT 10: OK
 COMMENT 11: OK
 COMMENT 12: OK
 COMMENT 13: OK
 COMMENT 14: OK
  
 COMMENT 15: GENERATOR INFORMATION IS OK
 HOWEVER THE EXHAUST IS WITHIN 10 FT OF
 THE INTAKE LOUVERAND THE SWITCHGEAR
 DOOR.PLEASE CLARIFY.
  
 COMMENT 16: OK
 *****************NEW COMMENT************
 17. PLAN SHEET M6.02 THE DETAIL SHOWING
 THE VERTICAL AHU SHOWS CPVC CONDENSATE
 TERMINATING 2" ABOVE A FLOOR DRAIN IN
 THE MECHANICAL CLOSET.THIS MECHANICAL
 CLOSET IS A RETURN AIR PLENUM.PER 2004
 FMC 602.2.1, COMBUSTIBLES ARE NOT
 ALLOWED IN THE RETURN AIR PLENUM.
 PROVIDE MANUFACTURER SUBMITTAL ON THE
 CPVC INDICATING IT MEETS THE DEFINITION
 OF NONCOMBUSTIBLE IN ACCORDANCE WITH THE
 ABOVE REFERENCED CODE.PLEASE ALSO SEE
 COMMENT #5 WITH REGARDS TO THE FLOOR
 DRAIN IN THE RETURN AIR PLENUM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By pkrauss Date 2006-05-09 Time 07:20 Rev Time 0.00
Received By pkrauss Date 2006-05-09 Time 07:20 Sent To  
Notes
2006-05-09 00:00:00DENIED:
 PLEASE NOTE, A RESPONSE LETTER TO
 COMMENTS GENERATED 12/27/05 WAS NOT
 SUBMITTED.PLEASE PROVIDE RESPONSE
 LETTER WITH THE NEXT RESUBMITTAL TO HELP
 EXPEDITE PLANS.
  
 THE FOLLOWING COMMENTS FROM REVIEW DATED
 12/27/05 WERE NOT ADDRESSED:
  
 COMMENT #1:MECHANICAL PLANS ARE
 SIGNED, SEALED, AND DATED BY THE
 ENGINEER.THE ARCHITECT'S SEAL IS NOT
 LEGIBLE.
  
 COMMENT #2:OK
  
 COMMENT #3:OK
  
 COMMENT #4:SMOKE EXHAUST/CONTROL FOR
 THE RETAIL SPACE.PLAN SHEET M2.01,
 2.02, & 2.03 ALL INDICATE FIRE SMOKE
 DAMPERS AND SUPPLY & RETURN DUCTS.PLAN
 SHEET M0.00 & M2.03 STATE "SMOKE EXHAUST
 THROUGH NATURAL VENTILATION" FROM
 WINDOWS AND PANELS OPERABLE FROM THE
 FIRE FLOOR OR PANELS OF APPROVED, FIXED,
 FULLY TEMPERED GLASS LOCATED AROUND THE
 PERIMETER.THIS IS NOT DEMONSTRATED.
 PLEASE CLARIFY.PLEASE SPECIFY WHAT
 "OAFR" & SXFR" STAND FOR.PLEASE NOTE,
 PLAN SHEET M2.01 "OAFR" DEPICTS SUPPLY
 GRILLES TO THE RETAIL SPACE & SXFR
 DEPICTS RETURN WITH BOTH RUNS TO RETAIL
 SPACE 3 THROUGH 7 TERMINATING INTO THE
 ENCLOSED PARKING GARAGE.PER 2004 FMC
 401.5.1, INTAKE OPENINGS SHALL BE
 LOCATED A MINIMUM OF 10 FT FROM ANY
 HAZARDOUS OR NOXIOUS CONTAMINANT SUCH AS
 PARKING LOTS & LOADING DOCKS.PLEASE
 ALSO REFERENCE 2004 FMC 510.5.5, MAKEUP
 AIR SHALL BE LCOATED SO AS TO AVOID
 RECIRCULATION OF CONTAMINATED AIR.
  
 COMMENT #5:OK.PLEASE NOTE,
 MECHANICAL ROOMS USED AS RETURN AIR
 PLENUM, NO FLOOR DRAINS PERMITED IN
 MECHANICAL ROOMS PER 2004 FPC 901.2 &
 ASHRAE 62-01 8.4.1.11.
  
 COMMENT #6:OK
  
 COMMENT #7:WAS NOT ADDRESSED - PLAN
 SHEET M2.01 (ROOM #006 &011) FLEX DUCTS
 PENETRATING WALLS/PARTITIONS WITH FIRE
 RATING.FIRE DAMPERS ARE NOT INDICATED
 ON THE PLAN SHOW COMPLIANCE WITH 2004
 FMC 607.5.3 #2 OR PROVIDE FIRE DAMPERS.
 LOCATION OF ALL FIRE DAMPERS ARE TO
 INDICATED ON PLANS 2004 FMC 607.8.
  
 COMMENT #8:INDICATE LOCATION OF ALL
 FIRE DAMPERS & ACCESS DOORS PER 2004 FMC
 607.8.
  
 COMMENT #9:ADDRESSED ON PLAN SHEET
 M6.02.
  
 COMMENT #10: OK
  
 COMMENT #11: SUBMITTALS ON EQUIPMENT WAS
 NOT SUBMITTED.
  
 COMMENT #12: ENERGY CALCULATIONS WERE
 NOT SUBMITTED.
  
 COMMENT #13: SUBMITTAL ON THE GENERATOR
 WAS NOT SUBMITTED.
 ****************************************
 NEW COMMENTS:
 14. PLAN SHEET M2.01, AIR MAKE-UP TO THE
 SMOKE CONTROL SYSTEM FOR THE RETAIL
 AREAS IS COMING FROM THE GARAGE.PER
 FMC 401.5.1 & 510.5.5, FRESH AIR INTAKES
 SHALL BE LOCATED A MINIMUM OF 10 FT FROM
 PARKING LOTS OR LOADING DOCKS AND AVOID
 THE RECIRCULATION OF OF CONTAMINTED AIR.
 PLEASE NOTE THE OAFR LOCATED IN RETAIL
 SPACE #7, INDICATES EXHAUST NOT INTAKE.
  
 15. PLAN SHEET M2.03, PLEASE PROVIDE THE
 ELEVATION FOR THE MUFFLER & RADIATOR
 EXHAUST TERMINTION (BOTTOM OF PIPE &
 BOTTOM OF LOUVER).PLEASE NOTE, PER
 2004 NFPA 37 6.3.5.4.2, EXHAUST
 VENTILATION SHALL BE TO A SAFE LOCATION
 OUTSIDE THE BUILDING, WITHOUT
 RECIRCULATION OF THE EXHAUST AIR.
 PLEASE NOTE, EXHAUST IS WITHIN 10 FT OF
 THE INTAKE LOUVER AND THE SWITCHGEAR
 ROOM DOOR.
  
 16. PLAN SHEET M2.04, PLEASE CLARIFY THE
 RATING OF THE MECHANICAL CLOSET IN WHICH
 AHU-12 IS LOCATED. PLAN SHEET A1.3 DOES
 NOT SPECIFY RATING AT THE MEZZANINE
 LEVEL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By pkrauss Date 2005-12-27 Time 16:47 Rev Time 0.00
Received By pkrauss Date 2005-12-27 Time 16:47 Sent To  
Notes
2005-12-27 00:00:00DENIED:CITY PALMS/10 STORY
 2004 FLORIDA BUILDING CODE
  
 1.PLANS ARE TO SIGNED, SEALED AND
 DATED BY THE ENGINEER OF RECORD IN
 ACCORDANCE WITH FS 471.025.
  
 2.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2004 FMC TABLE 403.3.
  
 3.PLAN SHEET A1.0 DOES NOT INDICATE
 TENANT SEPARATION BETWEEN THE RETAIL
 SPACES.
  
 4.PLAN SHEET M2.01 INDICATES FBC 412.5
 SMOKE EXHAUST THROUGH NATURAL
 VENTILATION FOR RETAIL SPACE.PLEASE
 NOTE, SMOKE CONTROL & EXHAUST UNDER THE
 2004 FLORIDA BUILDING CODE IS NOW
 ADDRESSED IN 513 OF THE FLORIDA
 MECHANICAL CODE.PLEASE INDICATE METHOD
 AND CALCULATIONS FOR SMOKE CONTROL.
  
 5.PLAN SHEET M2.01 AHU-12, 13 & 14 ARE
 LOCATED IN A STORAGE ROOM, PLEASE
 CLARIFY.
  
 6.AHU-13 IS NOT INDICATED ON THE
 EQUIPMENT SCHEDULE (M5.01).
  
 7.PLAN SHEET M2.01 (ROOM #006 & 011)
 FLEX DUCTS PENETRATING WALLS/PARTITIONS
 WITH FIRE RATING & FIRE DAMPERS ARE NOT
 INDICATED.DUCT SHALL COMPLY WITH 2004
 FMC 607.5.3 #2.
  
 8.PLEASE INDICATE ALL FIRE & FIRE
 SMOKE DAMPERS ON PLAN IN ACCORDANCE WTIH
 2004 FMC 607.5.3.
  
 9.PLEASE CLARIFY DETAIL OF THE
 REFRIGERANT LINE SETS ON PLAN SHEET
 M5.01.WILL LINE SETS BE IN A SHAFT?.
 DETAIL INDICATES GOOSE NECK THAT APPEARS
 TO END AT THE SLAB, BUT THE NOTE STATES
 "SLEEVE TO PROVIDE VENTILATION PER
 ASHRAE 15".PLEASE INDICATE WHERE
 SHAFTS WILL BE VENTILATED.
  
 10. PROVIDE CALCULATION FOR THE
 REFRIGERANT PER TABLE 1103.1 OF THE 2004
 FMC.
  
 11. PROVIDE MANUFACTURER'S
 SPECIFICATIONS FOR EQUIPMENT.
  
 12. PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2004 FBC CHAPTER 13.
  
 13. PLEASE PROVIDE SUBMITTAL FOR THE
 GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  

Review Stop P PLUMBING
Rev No 38 Status P Date 2008-12-23 Cont ID  
Sent By kstevens Date 2008-12-23 Time 17:51 Rev Time 0.00
Received By kstevens Date 2008-12-23 Time 17:51 Sent To  
Notes
2008-12-23 17:52:11REVISION APPROVED -- SHTS P2.31, P3.10 & P3.11

Review Stop P PLUMBING
Rev No 37 Status F Date 2008-12-17 Cont ID  
Sent By kstevens Date 2008-12-17 Time 17:13 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 18:59 Sent To  
Notes
2008-12-17 17:30:56REVSIONS DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.31 REVISION 2 ADDENDUM #3 DATED 4-17-06 AS
 SHOWN ON THE FILE SET OF PLANS FOR PUBLIC RECORD HAS
 BEEN CHANGED TO REVISION 4. ALL REVISIONS SHALL BE
 INDICATED ON THE REVISION INDEX FOR THE LIFE OF THE
 PROJECT. NEW REVISIONS SHALL BE INDICATED WITH CLOUDS
 AND A NEW REVISION NUMBER. SECTION 106.1.3.
  
 2. SHT P3.10 THE DRAIN LINE FROM THE THERMAL EXPANSION
 VALVE IS SHOWN CONNECTING DIRECTLY TO THE PAN DRAIN
 LINE. PER SECTION 608.1 POTABLE WATER SHALL BE
 DESIGNED, INSTALLED, INSTALLED AND MAINTAINED TO
 PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS
 OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY
 THROUGH CROSS-CONNECTIONS. AN AIR GAP OR AIR GAP
 FITTING IS REQUIRED. TABLE 608.1. -- KEY NOTES #5 SHOWS
 NOT CHANGE & KEY NOTE #7 HAS BEEN ADDED WITHOUT A CLOUD
 TO INDICATE A REVISION NOR A REVISION NUMBER. PLEASE
 CLOUD AND NUMBER ALL REVISIONS. SECTION 106.1.3.
  
 3. SHT P3.11 THE DRAIN LINE FROM THE THERMAL EXPANSION
 VALVE IS SHOWN CONNECTING DIRECTLY TO THE PAN DRAIN
 LINE. PER SECTION 608.1 POTABLE WATER SHALL BE
 DESIGNED, INSTALLED, INSTALLED AND MAINTAINED TO
 PREVENT CONTAMINATION FROM NONPOTABLE LIQUIDS, SOLIDS
 OR GASES BEING INTRODUCED INTO THE POTABLE WATER SUPPLY
 THROUGH CROSS-CONNECTIONS. AN AIR GAP OR AIR GAP
 FITTING IS REQUIRED. TABLE 608.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 36 Status P Date 2008-12-16 Cont ID  
Sent By kstevens Date 2008-12-16 Time 18:58 Rev Time 0.00
Received By kstevens Date 2008-12-16 Time 18:58 Sent To  
Notes
2008-12-16 18:59:37REVISION OK -- SHTS P2.05, P2.06, P2.17, P2.18, P2.21,
 P2.22, P2.25, P2.28. P2.33, P3.01, P3.14 & P4.01

Review Stop P PLUMBING
Rev No 35 Status F Date 2008-12-01 Cont ID  
Sent By kstevens Date 2008-12-01 Time 08:57 Rev Time 0.00
Received By kstevens Date 2008-12-01 Time 08:57 Sent To  
Notes
2008-12-01 10:09:27REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.05 REVISION NUMBER 12, KEY NOTES 12 & 13 NOT
 FOUND ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1
  
 2. SHT P2.05 CHANGES TO THE CONDENSATE ARE NOT CLOUDED
 OR INDICATED WITH A REVISION NUMBER. PLEASE CLOUD AND
 NUMBER ALL REVISIONS TO THE PREVIOUSLY REVIEWED AND
 STAMPED SHEET. SECTION 106.1.3. (ALSO SEE KEY NOTES 12,
 13 & 14 ADDED WITHOUT CLOUD/NUMBER).
  
 3. SHT P2.05 REVISION NUMBER 13 INDICATED ON THE
 REVISION INDEX IS NOT FOUND ON THE FLOOR PLAN AND
 REVISION NUMBER 6 PREVIOUSLY INDICATED IN THE REVISION
 INDEX ON SHEET PREVIOUSLY REVIEWED AND STAMPED HAS BEEN
 DELETED. THE REVISION INDEX HISTORY SHALL BE MAINTAINED
 FROM REVISION TO REVISION. PLEASE CORRELATE. SECTION
 106.1.1.
  
 4. SHT P2.06 REVISIONS 7 & 9 INDICATED ON THE REVISION
 INDEX WERE NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE. ALSO CLOUD AND NUMBER ALL KEY NOTE CHANGES
 OR REVISIONS ON THE FLOOR PLAN. SECTION 106.1.3.
  
 5. SHT P2.17 REVISION 14 INDICATED ON THE REVISION
 INDEX WAS NOT FOUND ON THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.3.
  
 6. SHT P2.17 NEW KEY NOTES 18, 19 & 20 WERE NOT CLOUDED
 OR NUMBERED AND KEY NOTE 18 WAS NOT FOUND ON THE FLOOR
 PLAN. PLEASE CORRELATE AND CLOUD ALL CHANGES SECTION
 106.1.3.
  
 7. SHT P2.17 KEY NOTE NUMBER 16 TO THE RIGHT OF COL.
 LINE "K" DESIGNATION & LEFT OF COL. LINE 11-1 SHOWS NO
 PIPING. PLEASE CLARIFY. SECTION 106.1.1.
  
 8. SHT P2.18 REVISION NUMBER 6 INDICATED ON THE ISSUED
 SET OF PLANS HAS BEEN BEEN DELETED. NO NEW REVISION
 NUMBER HAS BEEN ADDED. THE COMPLETE HISTORY OF
 REVISIONS SHALL BE MAINTAINED FROM REVISION TO
 REVISION. SECTION 106.1.3.
  
 9. SHT P2.21 REVISION NUMBER 6 INDICATED ON THE ISSUED
 SET OF PLANS HAS BEEN BEEN DELETED. NO NEW REVISION
 NUMBER HAS BEEN ADDED. THE COMPLETE HISTORY OF
 REVISIONS SHALL BE MAINTAINED FROM REVISION TO
 REVISION. SECTION 106.1.3.
  
 10. SHT P2.22 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 11. SHT P2.25 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 12. SHT P2.28 SUBMIT A U/L RATING & DETAIL OF FIRE
 RATING OF THE WALL & SUBMIT A DETAIL SHOWING HOW THE
 STRUCTURAL INTEGRITY OF THE COLUMN IS MAINTAINED WHERE
 THE LAV ARE IS ROUTED THRU THE COLUMN. SECTION 106.1.2.
  
 13. SHT P2.28 SHOW REVISION 11 IN TRIANGLE FOR REVISION
 NUMBER 11 ON THE FLOOR PLAN. SECTION 106.1.3. (TRIANGLE
 BLANK).
  
 14. SHT P2.31 REVISION INDEX REVISION NUMBERS 1 & 2
 WERE DELETED, REVISION NUMBER 2 WAS CHANGED TO REVISION
 NUMBER 4, ADDENDUM NUMBER 5 WAS ADDED TO REVISION
 NUMBER 5, KEY NOTES NUMBER 3 CHANGED WITH REVISION
 NUMBER 6 WAS NOT FOUND ON THE FLOOR PLAN, REVISON
 NUMBER 7 WAS FOUND ON THE FLOOR PLAN BUT NOT IN THE
 REVISION INDEX, AND KEY NOTES 4 & 5 ADDED BUT NO CLOUD
 OR REVISION NUMBER INDICATING THE REVISION. PLEASE
 CORRELATE, MAINTAIN THE REVISION HISTORY, SHOW ALL
 REVISIONS WITH CLOUDS & REVISION NUMBERS ETC. SECTIONS
 106.1.1, 106.1.2 & 106.1.3.
  
 15. SHT P2.33 REVISION INDEX ON THE SHEET STAMPED AND
 REVIEWED BY THE CITY WPB ON SEPT. 08, 2006 SHOWS
 REVISIONS 2, 3 & 4. THE NEW REVISIED SHEET SUBMITTED
 HAS REVISIONS 3, 4, 5, 6 & 11. REVISION 2 HAS BEEN
 DELETED, REVISION 3 HAS A DIFFERENT DATE, REVISION 4
 HAS A DIFFERENT DATE, & REVISION 5 WAS NOT FOUND ON THE
 FLOOR PLAN. THE REVISION HISTORY SHALL BE MAINTAINED
 THRU THE LIFE THE THE PLANS. CORRELATE NEW REVISION
 NUMBERS WITH THE FLOOR PLAN. SECTION 106.1.3.
  
 16. SHT P3.01 RISERS FOR 2, 3, 10, 11, 12 & 13 AND 36,
 37, 42 & 44 SHOW A 3" DRAINAGE LINE FROM THE COLLECTOR
 TANK OVERFLOWS. THE OVERFLOW SHALL DRAIN TO THE STORM
 SYSTEM. MUNICIPAL CODE ARTICLE III SECTION
 90-125(B)(5).
  
 17. SHT P3.10 SHOWS REVISION NUMBER 4 ON THE FLOOR PLAN
 BUT IS NOT INDICATED ON THE REVISION INDEX. THE
 REVISIONS IN KEY NOTES ARE NOT INDICATED WITH CLOUDS OR
 REVISION NUMBER. SECTION 106.1.3.
  
 18. SHT P3.11 KEY NOTES NUMBER 4 DOES NOT REFLECT
 CHANGES ON THE WATER UNIT DETAILS. PLEASE
 CLARIFY/CORRELATE. SECTIONS 106.1.1 & 106.1.2.
  
 19. SHT P3.14 REVISION NUMBER 6 HAS BEEN DELETED FROM
 THE REVISION HISTORY. PLEASE MAINTAIN THE REVISION
 HISTORY THRU THE LIFE TO THE PLANS. SECTION 106.1.3.
  
 20. SHT P4.01 REVISION NUMBER 2 HAS BEEN DELETED FROM
 THE REVISION HISTORY. PLEASE MAINTAIN THE REVISION
 HISTORY THRU THE LIFE TO THE PLANS. THE FUEL PIPING
 DETAIL FOR FOR THE MECHANICAL PLAN REVIEWER. PLEASE
 DELETE FROM PLUMBING AND SUBMIT REVISION UNDER THE
 MECHANICAL PLANS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 34 Status P Date 2008-11-26 Cont ID  
Sent By kstevens Date 2008-11-26 Time 16:15 Rev Time 0.00
Received By kstevens Date 2008-11-26 Time 16:15 Sent To  
Notes
2008-11-26 16:18:11REVISIONS OK -- SHT P2.01, P2.02, P2.08, P2.11, P2.13,
 P2.14, P2.16, P2.34, P3.04, P3.06, P3.07 & P3.13. ---
 RESTAMP OK -- SHT P2.29.

Review Stop P PLUMBING
Rev No 33 Status F Date 2008-10-23 Cont ID  
Sent By kstevens Date 2008-10-23 Time 14:05 Rev Time 0.00
Received By kstevens Date 2008-10-23 Time 14:05 Sent To  
Notes
2008-10-23 14:18:06RESTAMP DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 THE FOLLOWING SHEETS HAVE BEEN DENIED FOR RESTAMP AS
 THERE HAVE BEEN REVISIONS ADDED TO OR DELETED FROM
 PREVIOUSLY REVIEWED REVISIONS.
  
 SHTS P2.01 REV. 20, P2.02 REV. 17, P2.05 REV'S 12 - 13
 - 14, P2.06 REV'S 7 - 8 - 9, P2.08 REV 14, P2.11 REV
 14, P2.13 REV 14, P2.14 REV 14, P2.16 REV 17, P2.18 REV
 6 DELETED, P2.21 REV 6 DELETED, REV 2.22 REV 13, P2.25
 REV 13, P2.28 REV 11, P2.29 REV "X" ON FLOOR PLAN
 ADDED, P2.31 REV'S 1 & 2 DELETED & REV'S 4 - 6 - 11
 ADDED, P2.33 REV 2 DELETED & REV'S 5 - 6 - 11 ADDED,
 P2.34 REV 4, P2.35 REV 4, P3.01 REV'S 8 - 9 - 10, P3.03
 REV'S 11- 12, P3.04 REV 11, P3.06 REV 7, P3.07 REV 7,
 P3.10 REV 4, P3.11 REV 4 INFORMATION DELETED AND
 INFORMATION NOT LEGIBLE, P3.14 REV 6 DELETED & REV 11
 ADDED, P3.15 REV 17 & P4.01 REV 2 DELETED & REV'S 3 & 4
 ADDED.
  
 SUBMIT THE ABOVE SHEETS FOR REVISION, MINIMUM 2 SETS OF
 PLANS REQUIRED FOR REVISIONS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 32 Status P Date 2008-10-23 Cont ID  
Sent By kstevens Date 2008-10-23 Time 14:02 Rev Time 0.00
Received By kstevens Date 2008-10-23 Time 14:02 Sent To  
Notes
2008-10-23 14:05:03RESTAMP APPROVED FOR THE FOLLOWING SHEETS. -- P2.03,
 P2.04, P2.07, P2.09, P2.10, P2.12, P2.15, P2.19, P2.20,
 P2.23, P2.24, P2.26, P2.27, P2.30, P2.32. P2.36, P3.05,
 P3.08, P3.09, P3.12, P3.13 & P4.02

Review Stop P PLUMBING
Rev No 31 Status P Date 2008-09-02 Cont ID  
Sent By kstevens Date 2008-09-02 Time 11:08 Rev Time 0.00
Received By kstevens Date 2008-09-02 Time 11:08 Sent To  
Notes
2008-09-02 11:09:55SUBMITTAL APPROVED. -- PIPE GUARDS FOR THE GARAGE. --
 CUT OUT FOR CLEANOUT ACCESS AS REQUIRED FOR FIELD
 CONDITIONS.

Review Stop P PLUMBING
Rev No 30 Status F Date 2008-08-08 Cont ID  
Sent By kstevens Date 2008-08-08 Time 14:19 Rev Time 0.00
Received By kstevens Date 2008-08-08 Time 14:19 Sent To  
Notes
2008-08-08 14:24:20DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SUBMITTAL FOR PIPE GUARDS NOT APPROVED. PLEASE
 INDICATE HOW ACCESS TO CLEANOUTS REQUIRED BY SECTIONS
 708.3.4 & 1101.8 WILL BE ADDRESSED. SECTION 708.9.
 SUBMIT AN ELEVATION VIEW OF THE GUARD SHOWING HOW
 ACCESS WILL BE ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 29 Status N Date 2008-04-21 Cont ID  
Sent By mperson Date 2008-04-21 Time 14:33 Rev Time 0.00
Received By mperson Date 2008-04-21 Time 14:33 Sent To B
Notes
2008-04-21 14:36:04REVISION SHEET L1 THRU L4 AND SHEET I1 AND I2: NO
 REVISION NUMBER INDICATED AND NO CHANGES FROM ORIGINAL
 SHEETS.

Review Stop P PLUMBING
Rev No 28 Status P Date 2008-03-29 Cont ID  
Sent By kstevens Date 2008-03-29 Time 15:15 Rev Time 0.00
Received By kstevens Date 2008-03-29 Time 15:15 Sent To  
Notes
2008-03-29 15:17:34REVISIONS APPROVED--SHT P2.01 REVISION 19 OK -
 REVISIONS 17 & 18 NOT FOUND OR APPROVED.--SHT P3.12
 REVISIONS 16 & 18 OK -REVISIONS 14 & 17 NOT FOUND OR
 APPROVED.

Review Stop P PLUMBING
Rev No 27 Status F Date 2008-02-26 Cont ID  
Sent By kstevens Date 2008-02-26 Time 10:03 Rev Time 0.00
Received By kstevens Date 2008-02-25 Time 10:03 Sent To  
Notes
2008-02-26 10:17:01DENIED
 REFERENCE: CITY WPB MUNICIPAL CODE
 FBC-2001 CHAPTER 1
  
 1. SHT P2.01 THE LINE DRAINING INTO CATCH BASIN #4 FROM
 THE FAN ROOM DOES NOT INDICATE WHAT WILL BE DRAINING
 THROUGH IT. IS THIS STORM WATER? PLEASE CLARIFY. ONLY
 STORM WATER SHALL DRAIN INTO THE STORM SYSTEM PER
 ARTICLE III SECTION 90-203(A).--THERE IS NO
 REVISION NUMBER FOR THIS REVISION CORRELATING WITH THE
 REVISION NUMBERS OF THIS SUBMITTAL. (17 & 18).
  
 2. SHT P3.12INDICATE THE SQUARE FOOTAGE ON RISER PAD
 2 FOR THE NEW DECK DRAINS AND TRENCH DRAINS ON THE
 RISER DIAGRAM. TABLE 1106.3.--SURGE TANK ADDED TO
 RISER DP 4 IS INDICATED WITH A REVISION NUMBER 15.
 NUMBER 15 IS NOT INDICATED ON THE REVISION INDEX, AS
 ONLY REVISIONS 14, 16 & 17 WERE SUBMITTED FOR REVIEW
 THIS SUBMITTAL. PLEASE CLARIFY. SECTION 104.2.1.3.--
 THE LINE DRAINING INTO CATCH BASIN #4 FROM THE FAN ROOM
 DOES NOT INDICATE WHAT WILL BE DRAINING THROUGH IT. IS
 THIS STORM WATER? PLEASE CLARIFY. ONLY STORM WATER
 SHALL DRAIN INTO THE STORM SYSTEM PER ARTICLE III
 SECTION 90-203(A).
  
 3. AS INDICATED NUMEROUS TIMES, PLEASE TURN OFF ALL
 CLOUDS & REVISION NUMBERS FOR REVISIONS THAT HAVE BEEN
 PREVIOUSLY APPROVED. THIS ADDS MUCH MORE TIME TO EACH
 REVISION REVIEW AS THE WHOLE SHEET HAS TO BE REVIEWED
 BECAUSE OF ALL THE CLOUDING. AS THE REVISIONS COME IN
 EACH REVISION TAKES LONGER TO PROCESS AND THUS SLOWS
 THE PLAN REVIEW PROCESS MAKING DELAYS IN PERMITTING OF
 JOBS. PLEASE TURN OFF ALL REVISION CLOUDS AND REVISIONS
 PREVIOUSLY APPROVED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 26 Status P Date 2008-02-26 Cont ID  
Sent By kstevens Date 2008-02-26 Time 10:01 Rev Time 0.00
Received By kstevens Date 2008-02-25 Time 15:34 Sent To  
Notes
2008-02-26 10:03:37REVISIONS OK--SHTS P2.03, P2.19, P2.20, P3.02 &
 P4.02

Review Stop P PLUMBING
Rev No 25 Status F Date 2007-12-17 Cont ID  
Sent By kstevens Date 2007-12-17 Time 12:44 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 12:44 Sent To  
Notes
2007-12-17 12:56:49REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.03 REVISIONS 7, 8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.03 WAS DATED 10-06-2006 AND
 HAD REVISIONS 3, 4 & 5. PLEASE CLOUD ALL REVISIONS NOT
 PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH A
 NUMBERED TRIANGLE. SECTION 106.1.3.
  
 2. SHT P2.19 REVISIONS11 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.19 WAS DATED 10-06-2006 AND
 HAD REVISIONS 3, 4, 5 & 6. PLEASE CLOUD ALL REVISIONS
 NOT PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH
 A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 3. SHT P2.20 REVISIONS 7, 8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P2.20 WAS DATED 11-20-2007 AND
 HAD REVISIONS 3, 4, 5 & 6. PLEASE CLOUD ALL REVISIONS
 NOT PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH
 A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 4. SHT P3.02 REVISIONS8 & 13 WERE NOT FOUND. THE
 PREVIOUS APPROVED SHEET P3.02 WAS DATED 11-20-2007 AND
 HAD REVISIONS 3, 4, 5, 6 & 7. PLEASE CLOUD ALL
 REVISIONS NOT PREVIOUSLY APPROVED AND INDICATE ALL
 REVISIONS WITH A NUMBERED TRIANGLE. SECTION 106.1.3.
  
 5. SHT P3.12 REVISION 14 WAS NOT FOUND. THE PREVIOUS
 APPROVED SHEET P3.12 WAS DATED 11-20-2007 AND HAD
 REVISIONS 3, 4 & 5. PLEASE CLOUD ALL REVISIONS NOT
 PREVIOUSLY APPROVED AND INDICATE ALL REVISIONS WITH A
 NUMBERED TRIANGLE. SECTION 106.1.3.
  
 6. SHT P4.02 REVISION IS INDICATED AS AN ADDITION OF
 THE GENERATOR WITH DIESEL INFORMATION ONLY. THE DIESEL
 PERMIT IS A MECHANICAL PERMIT AND AS SUCH ALL REVISIONS
 FOR DIESEL SHALL BE SUBMITTED ON THE MECHANICAL SHEETS,
 NOT THE PLUMBING SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 24 Status P Date 2007-12-17 Cont ID  
Sent By kstevens Date 2007-12-17 Time 12:42 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 12:42 Sent To  
Notes
2007-12-17 12:44:01REVISIONS APPROVED. SHEETS P2.01, P2.02, P2.16 & P3.15

Review Stop P PLUMBING
Rev No 23 Status P Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 18:57 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 18:13 Sent To  
Notes
2007-12-05 18:58:01REVISIONS OK FOR SHTS A1.31, A1.32 & A1.33 FOR THE
 SCUPPERS AND SCUPPER RELATED REVISIONS ONLY.

Review Stop P PLUMBING
Rev No 22 Status P Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 18:12 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 18:12 Sent To  
Notes
2007-12-05 18:13:13REVISION OK - SHTS P3.12 & P3.16.

Review Stop P PLUMBING
Rev No 21 Status F Date 2007-11-01 Cont ID  
Sent By kstevens Date 2007-11-01 Time 14:56 Rev Time 0.00
Received By kstevens Date 2007-11-01 Time 14:56 Sent To  
Notes
2007-11-01 15:22:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.01 REVISION SUBMITTED SHOWS THE LATEST
 REVISION AS #13. REVISIONS 13 & 14 WERE APPROVED ON
 10-15-07. REVISION RETURNED.
  
 2. SHT P2.05 KEY NOTE #13 NOT FOUND ON THE FLOOR PLAN.
 SOME REVISIONS WERE FOUND THAT HAD NO CLOUDS OR DELTA
 REVISION NUMBERS. PLEASE INDICATE ALL REVISIONS WITH
 CLOUDS AND REVISION NUMBERS. SECTION 106.1.3.
  
 3. SHT P2.17 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.
  
 4. SHT P2.19 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.--
 ALSO SEE THE FOLLOWING COMMENTS FROM THE PREVIOUS
 REVISION REVIEWS: --AS INDICATED IN THE REVISION
 DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL
 NOT ADDRESSED:
 ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV
 TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2.
 ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #6 INDICATED AS COORD. REV.
 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG
 DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS,
 ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.****
  
 5. SHT P2.20 PLANS AT THE TIME OF PERMIT SHOW REVISION
 #6 DATED 8-7-06. SHEET SUBMITTED SHOWS A NEW REVISION
 #6 DATED 4-27-07. FOR RECORD KEEPING A REVISION NUMBER
 IS ONLY USED ONCE AND A PROGRESSIVE SEQUENCE WILL BE
 USED. THE REVISION DATED 4-27-07 WAS NOT PREVIOUSLY
 SUBMITTED AND IS NOT APPROVED. SECTION 106.1.3.--
 ALSO THIS REVISION THE SANITARY PIPING IS NOT SHOWN AT
 THE FIXTURES IN THE MEN'S AND WOMEN'S TOILET ROOMS AS
 WELL AS AT THE DRINKING FOUNTAINS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 ***********NOTE: THE PREVIOUSLY APPROVED REVISIONS ON
 EACH SHEET SHALL BE TURNED OFF WHEN SUBMITTING
 REVISIONS FOR REVIEW. THIS HAS BEEN REQUESTED QUITE A
 FEW TIMES IN THE PAST BUT TO NO AVAIL. AS INDICATED
 PREVIOUSLY THE REVIEW TURN AROUND TIME AND THE PROCESS
 FOR REVISIONS IS SLOWED DOWN WHEN ONE HAS TO LOOK
 THROUGH ALL CLOUDS AND ALL REVISION NUMBERS FOR ALL
 REVISIONS, EVEN THOUGH MOST REVISIONS HAVE BEEN
 PREVIOUSLY BEEN APPROVED. THE PREVIOUSLY APPROVED
 REVISIONS ARE PART OF THE PLANS AND ARE NOT REVISIONS
 AFTER THAT. --- P L E A S E TURN OFF ALL PREVIOUSLY
 APPROVED REVISIONS WHEN SUBMITTING REVISIONS FOR
 REVIEW. THANKING YOU IN ADVANCE FOR YOUR COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 20 Status P Date 2007-11-01 Cont ID  
Sent By kstevens Date 2007-11-01 Time 14:54 Rev Time 0.00
Received By kstevens Date 2007-10-30 Time 11:56 Sent To  
Notes
2007-11-01 14:56:01REVISIONS APPROVED. SHEETS P2.02, P2.04, P2.07, P2.08,
 P2.10, P2.11, P2.13, P2.14, P2.16, P3.15.

Review Stop P PLUMBING
Rev No 19 Status F Date 2007-10-16 Cont ID  
Sent By kstevens Date 2007-10-16 Time 08:49 Rev Time 0.00
Received By kstevens Date 2007-10-16 Time 08:49 Sent To  
Notes
2007-10-16 09:17:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.16 NOT ALL REVISIONS HAVE BEEN CLOUDED, NOR
 DO ALL REVISIONS HAVE A REVISION NUMBER ATTACHED.
 PLEASE INDICATE ALL CHANGES/REVISIONS WITH A CLOUD AND
 A REVISION NUMBER. -- THE STORM LINE INDICATED BY KEY
 NOTE NUMBER 17 HAS BEEN DELETED, BUT THE KEY NOTE IS
 STILL SHOWN ON THE PLANS WHERE THE STORM LINE WAS
 LOCATED. PLEASE CLARIFY. SECTION 106.1.1.**NOTE: THE
 REVISION TURN AROUND TIME IS GREATLY INCREASED BECAUSE
 OF THE FACT THAT PREVIOUS REVISION CLOUDS AND REVISION
 NUMBER ARE STILL SHOWN ON THE PLANS. I HAVE ASKED
 REPEATEDLY FOR ALL REVISIONS THAT HAVE BEEN PREVIOUSLY
 APPROVED TO BE TURNED OFF. PLEASE COMPLY OR EXPLAIN WHY
 THIS CAN NOT BE DONE.
  
 2. SHT P2.19THE 4" ED, (1180SF). PLEASE IDENTIFY
 WHICH ROOF DRAINS WILL ADD UP TO 1180SF.--THE 6"
 ED, (1730SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL
 ADD UP TO 1730SF.--6" ED, (3240SF). PLEASE IDENTIFY
 WHICH ROOF DRAINS WILL ADD UP TO 3240SF.--4"ED,
 (1300SF). PLEASE IDENTIFY WHICH ROOF DRAINS WILL ADD UP
 TO 1300SF.--IF EACH DECK DRAIN HAS TO BE NUMBERED,
 (DD-1, DD-2 ETC), AND THEN TIED TO A NUMBERED EMERGENCY
 DRAIN, (ED-1, ED-2 ETC) TO CLARIFY WHICH DECK DRAINS
 SQUARE FOOTAGE ADDS UP TO WHICH EMERGENCY DRAIN, THIS
 WOULD HELP IN SHOWING ALL SQUARE FOOTAGE OF THE DECK
 DRAINS IS ACCOUNTED FOR IN THE EMERGENCY DRAINS. -- KEY
 NOTES #10 STATES "SEE SHT P2.20 FOR CONTINUATION". SHT
 P2.20 DOES NOT SHOW THE CONTINUATION. PLEASE CLARIFY.
 SECTION 106.1.1.--AS INDICATED IN THE REVISION
 DENIAL DATED 07/07/07, SEE THE FOLLOWING COMMENTS STILL
 NOT ADDRESSED:
 ***2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV
 TO THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2.
 ALSO A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #6 INDICATED AS COORD. REV.
 01-17-07. PLANS WERE ISSUED WITH A REVISION #6 "BLDG
 DEPT COMM" 08-07-06. IN ORDER TO TRACK ALL REVISIONS,
 ONLY ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.****
  
 3. SHT P3.01 THE OVERFLOW FROM THE COLLECTOR TANKS FOR
 THE POOL AND SPA SHALL DRAIN TO STORM, NOT SANITARY AS
 SHOWN.
  
 4. SHT P3.12 PD 310SF IS NOT SHOWN ON THE RISER DIAGRAM
 FOR THAT AREA. (DP/3). PLEASE INDICATE WHAT RISER THE
 PD CONNECTS TO. SECTION 106.1.2.--RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN FOR DP/4 WHERE THE
 TRENCH DRAINS CONNECT TO THE BRANCH DRAIN. DD'S ON
 STRUCTURAL SLAB CONNECT DOWNSTREAM OF THE TRENCH DRAINS
 ON THE FLOOR PLAN.--2 DECK DRAINS INDICATED AS
 BEING ON THE STRUCTURAL SLAB, BUT ALL 3 DECK DRAINS ARE
 SHOWN ON THE SAME ELEVATION PER THE RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. 8-1/2" BY 11" REVISIONS SUBMITTED MIRROR THE
 REVISIONS SUBMITTED ON SHEETS P2.01, P3.01,
 P3.05,P2.16, P2.19 & P3.12 SO THESE ARE NOT REQUIRED.
 THE AMOUNT OF SPACE REQUIRED FOR THE STORAGE OF PLANS
 SUBMITTED FOR PUBLIC RECORD IS LIMITED AND DUPLICATE
 INFORMATION NOT REQUIRED WILL NOT BE APPROVED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 18 Status P Date 2007-10-16 Cont ID  
Sent By kstevens Date 2007-10-16 Time 08:47 Rev Time 0.00
Received By kstevens Date 2007-10-15 Time 18:59 Sent To  
Notes
2007-10-16 08:49:16REVISION OK--SHT P2.01 & P3.05 (WATER HAMMER
 ARRESTOR REQUIRED AT THE D/W PER SECTION 604.9)

Review Stop P PLUMBING
Rev No 17 Status P Date 2007-10-11 Cont ID  
Sent By kstevens Date 2007-10-11 Time 08:44 Rev Time 0.00
Received By kstevens Date 2007-10-11 Time 08:44 Sent To  
Notes
2007-10-11 08:45:17SUBMITTAL FOR PRO-SLOPE APPROVED WITH REINFORCED 2"
 ABOVE THE SHOWER PAN.

Review Stop P PLUMBING
Rev No 16 Status F Date 2007-09-13 Cont ID  
Sent By kstevens Date 2007-09-13 Time 14:27 Rev Time 0.00
Received By kstevens Date 2007-09-13 Time 14:27 Sent To B
Notes
2007-09-13 14:33:12DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. PRO-SLOPE SUBMITTAL DENIED. NO APPROVAL BY A
 RECOGNIZED TESTING SHOWING COMPLIANCE WITH ALL CODES
 FOR BUILDING MATERIALS.INDICATE REFERENCE STANDARD
 PRODUCT BUILT TO AND SHOWAPPROVAL PER SECTIONS 303.2
 & 303.4.
  
 2. SHOW COMPLIANCE WITH SECTION 417.5 REQUIREMENTS FOR
 BEING IMPERVIOUS. IF THE PRO-SLOPE IS SHOWN TO COMPRESS
 UNDER WEIGHT THIS WILL AFFECT THE REQUIREMENT. PLEASE
 SHOW TESTING.
  
 3. FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL
 BE LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY
 SOUND BASE. SECTION 417.5.1. PLEASE SUBMIT TESTING
 SHOWING HOW THE ADVERTISED RATING OF 500LB PER SQUARE
 FOOT WAS PROVEN. THE PRODUCT DOES NOT MEET THE INTENT
 OF THE CODE THAT REQUIRES A UNIFORM SLOPE AT 1/4"/FT
 BECAUSE NO TESTING HAS BEEN SHOWN TO INDICATE THAT THE
 PRO-SLOPE WILL NOT COMPRESS AND LEAVE DIPS IN THE
 PRODUCT AND ULTIMATELY CRACKING IN THE TILE.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 15 Status F Date 2007-07-20 Cont ID  
Sent By kstevens Date 2007-07-20 Time 11:09 Rev Time 0.00
Received By kstevens Date 2007-07-20 Time 11:09 Sent To  
Notes
2007-07-20 11:13:59DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. PRO-SLOPE SUBMITTAL DENIED. NO APPROVAL OR
 INSTALLATION REQUIREMENTS INDICATED ON MANUF.
 SPECIFICATION SHEETS. INDICATE REFERENCE STANDARD
 PRODUCT BUILT TO AND APPROVAL PER SECTIONS 303.2 &
 303.4
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 14 Status P Date 2007-07-20 Cont ID  
Sent By kstevens Date 2007-07-20 Time 11:08 Rev Time 0.00
Received By kstevens Date 2007-07-20 Time 11:08 Sent To  
Notes
2007-07-20 11:09:05SUBMITTAL OK FOR THE SHOWER CURB AND THE SHOWER PAN
 MATERIAL

Review Stop P PLUMBING
Rev No 13 Status P Date 2007-07-07 Cont ID  
Sent By kstevens Date 2007-07-07 Time 16:37 Rev Time 0.00
Received By kstevens Date 2007-07-07 Time 16:37 Sent To  
Notes
2007-07-07 16:40:48REVISION APPROVED.SHTS P2.01, P2.02, P2.04, P2.07,
 P2.08, P2.08. P2.11, P2.14, P2.16, P2.32.
  
  
  
  
 PASSED PROVISO: REVISION REQUIRED FOR CONDENSATE RISER
 TO REFLECT THE CHANGES.
  
  
  
  
  
  
 PASSED PROVISO: REVISIONS REQUIRED TO CONDENSATE,
 SANITARY & WATER RISERS TO REFLECT THE CHANGES.
  
  
  

Review Stop P PLUMBING
Rev No 12 Status F Date 2007-07-07 Cont ID  
Sent By kstevens Date 2007-07-07 Time 14:53 Rev Time 0.00
Received By kstevens Date 2007-07-06 Time 18:50 Sent To  
Notes
2007-07-07 16:14:18REVISIONDENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.17 INDICATES REVISION #6 "OWNER REQ.
 REVISION" DATED 4-25-07. PLANS WERE ISSUED WITH A
 REVISION #6 "BLDG DEPT COMM" DATED 8-07-06. IN ORDER TO
 TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION
 NUMBER WILL BE ALLOWED. SECTION 106.1.3.--(NOTE THE
 REVIEW TIME IS INCREASED GREATLY WHEN ALL PREVIOUS
 APPROVED REVISION CLOUDS & REVISION TRIANGLE NUMBERS
 ARE STILL SHOWN ON EACH REVISION. ALSO IF THE
 BACKGROUND INFORMATION SUCH AS WALLS, CORRIDORS, DOORS,
 FIXTURES ETC. COULD BE LIGHTENED AS WELL AS PREVIOUS
 PIPING AND WITH THE APPLIED REVISION IN BOLD THE
 REVISIONS CAN BE EXPEDITED QUICKER).
  
 2. SHT P2.19 A RELIEF VENT IS REQUIRED FOR THE AAV TO
 THE SINK AT THE POOL DECK LEVEL. SECTION 917.3.2. ALSO
 A REVISION WILL BE REQUIRED FOR THE SANITARY RISER
 DIAGRAM TO REFLECT THE CHANGE TO THE SANT. SYSTEM.
 SECTION 106.1.1.---KEY NOTES #12 THE OVERFLOW
 FROM THE COLLECTOR TANKS SHALL DRAIN TO STORM, NOT
 SANITARY.---REVISION #8 IS SHOWN ON THE FLOOR
 PLAN, BUT NOT INDICATED ON THE REVISION INDEX. PLEASE
 CLARIFY. SECTION 106.1.3.---REVISION #6 INDICATED
 AS COORD. REV. 01-17-07. PLANS WERE ISSUED WITH A
 REVISION #6 "BLDG DEPT COMM" 08-07-06. IN ORDER TO
 TRACK ALL REVISIONS, ONLY ONE REVISION PER REVISION
 NUMBER WILL BE ALLOWED. SECTION 106.1.3.---DECK
 DRAINS ARE ALSO IDENTIFIED AS FD. PLEASE CLARIFY AS
 FLOOR DRAINS ARE NOT APPROVED STORM DRAINS. SECTION
 106.1.1.--- THE EMERGENCY (SECONDARY) ROOF DRAINS
 HAVE BEEN REDUCED IN CAPACITY & ARE NOT SIZED TO DRAIN
 ALL SQUARE FOOTAGE OF ALL AREAS OF THE DECK. SECONDARY
 ROOF DRAINS ARE REQUIRED FOR ALL SECTIONS OF THE DECK,
 INCLUDING THE PATIO AREAS PER SECTION 1107.3. SHOW THE
 SIZE OF EACH SECONDARY ROOF DRAINAND INDICATE SQUARE
 FOOTAGE DRAINED BY EACH SECONDARY ROOF DRAIN.
  
 3. SHT P2.20 REVISION #6 "OWNER REQD. REV 4-27-07.
 PLANS WERE ISSUED WITH A REVISION #6 "BLDG DEPT COMM"
 DATED 8-07-06. IN ORDER TO TRACK ALL REVISIONS, ONLY
 ONE REVISION PER REVISION NUMBER WILL BE ALLOWED.
 SECTION 106.1.3.---DECK DRAINS ARE ALSO
 IDENTIFIED AS FD. PLEASE CLARIFY AS FLOOR DRAINS ARE
 NOT APPROVED STORM DRAINS. SECTION 106.1.1.--- THE
 EMERGENCY (SECONDARY) ROOF DRAINS HAVE BEEN REDUCED IN
 CAPACITY & ARE NOT SIZED TO DRAIN ALL SQUARE FOOTAGE OF
 ALL AREAS OF THE DECK. SECONDARY ROOF DRAINS ARE
 REQUIRED FOR ALL SECTIONS OF THE DECK, INCLUDING THE
 PATIO AREAS PER SECTION 1107.3. SHOW THE SIZE OF EACH
 SECONDARY ROOF DRAINAND INDICATE SQUARE FOOTAGE
 DRAINED BY EACH SECONDARY ROOF DRAIN.
  
 4. SHT P2.31 REVISION #1 HAS BEEN DELETED FROM THE
 REVISION INDEX. PLEASE CLARIFY.---REVISIONS #2
 HAS BEEN CHANGED TO REVISION #4 ON THE REVISION INDEX.
 PLEASE CLARIFY. REVISION NUMBERS SHALL REMAIN THE SAME
 THROUGHOUT THE LIFE OF THE PLANS IN ORDER TO BE ABLE TO
 TRACK ALL CHANGES TO THE STAMPED SET OF REVIEWED PLANS.
 SECTION 106.1.3.---REVISION #7 SHOWN ON THE ROOF
 PLAN, BUT NOT SHOWN ON THE REVISION INDEX. PLEASE
 CLARIFY.---KEY NOTES 4 & 5 ARE NOT CLOUDED OR
 INDICATED AS REVISIONS WITH A REVISION NUMBER. PLEASE
 CLOUD AND NUMBER ALL REVISIONS.---REVISION #6 &
 KEY NOTE #3 STATES CONDENSATE PIPING TO TURN DOWN TO
 FLOOR BELOW, BUT IS SHOWN TURNED DOWN ON THE ROOF.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SHT P2.33A 3" VTR IS SHOWN UNDER RTU-5. THIS WILL
 NEED TO BE OFFSET 10' PAST AIR INTAKE. SECTION 904.5.
 ---VTR OFFSET & CONDENSATE LINE FROM RTU-5 IS NOT
 CLOUDED NOR INDICATED AS A REVISIONS WITH A REVISION
 NUMBER. PLEASE CLARIFY. ---REVISION #2 HAS BEEN
 DELETED FROM THE REVISION PLEASE CLAIFY.--- REVISION
 #2 HAS BEEN CHANGED TO REVISION #3 AT COL. LINE 23/I-G.
 ---REVISION #3 HAS BEEN CHANGED TO REVISION #4 AT
 COL. LINE 22/I.---REVISION #4 HAS BEEN CHANGED TO
 REVISION #5 AT COL. LINE 23/G-D.-TO TRACK REVISIONS
 AND TO KEEP PUBLIC RECORDS, THE REVISION NUMBERS SHALL
 STAY THE SAME THROUGH THE LIFE OF THE JOB/PLANS.
 SECTION 106.1.3.
  
 6. SHT P3.12 RISER DP/4 THE SHOWER DECK DRAIN IS NOT
 SHOWN, THE SQUARE FOOTAGE FOR TWO DECK DRAINS DOES NOT
 REFLECT THE FLOOR PLAN, AND THE PIPING TO DECK DRAIN
 (140SF) DOES NOT REFLECT THE FLOOR PLAN NOR DOES THE
 BRANCH PIPING AT THE OFFSET UPSTREAM OF SAID DD.---
 DOWNSTREAM OF THE BASE OF RISER DP/5 DECREASES TO 4"
 FROM 6" RISER. THIS IS NOT APPROVED. SECTION 704.2.
  
 7. SHT P3.14 DETAIL 2 (EMERGENCY DRAINS) IS NOT
 APPROVED. THE SECONDARY ROOF SYSTEM DRAINS SHALL DRAIN
 THE TOTAL AREA EQUIVALENT TO THE AREA DRAINED GY THE
 TOTAL OF ALL PRIMARY ROOF DRAINS. SECTION 1107.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 11 Status P Date 2007-06-12 Cont ID  
Sent By kstevens Date 2007-06-12 Time 11:13 Rev Time 0.00
Received By kstevens Date 2007-06-12 Time 11:13 Sent To  
Notes
2007-06-12 11:15:02SUBMITTAL APPROVED PRO-PRESS SYSTEM FOR COPPER PIPE
 SYSTEMS

Review Stop P PLUMBING
Rev No 10 Status P Date 2007-04-26 Cont ID  
Sent By kstevens Date 2007-04-26 Time 13:28 Rev Time 0.00
Received By kstevens Date 2007-04-26 Time 13:28 Sent To  
Notes
2007-04-26 13:29:21REVISION OK--SHT P2.04

Review Stop P PLUMBING
Rev No 9 Status F Date 2007-02-26 Cont ID  
Sent By kstevens Date 2007-02-26 Time 18:51 Rev Time 0.00
Received By kstevens Date 2007-02-26 Time 18:51 Sent To  
Notes
2007-02-26 18:56:23REVISION DENIED
 REFERENCE: FBC-2001 PLUBMING
 FBC-2001 CHAPTER 1
  
 SHT P2.04 REVISION NUMBER 10 IS NOT INDICATED ON THE
 REVISION SCHEDULE.- -SOME CHANGES ARE NOT CLOUDED
 OR NUMBERED.- -KEY NOTES NUMBER 10 IS NOT FOUND.-
 -KEY NOTE NUMBER 9 INDICATES REVISION NUMBER 5. THIS
 IS A PREVIOUS REVISION NUMBER FROM A PAST REVIEW.- -
 TO HELP EXPEDITE FUTURE REVISIONS, PLEASE TURN OFF ALL
 PREVIOUSLY APPROVED REVISION NUMBERS AND CLOUDS.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2007-02-26 Cont ID  
Sent By kstevens Date 2007-02-26 Time 18:49 Rev Time 0.00
Received By kstevens Date 2007-02-26 Time 18:49 Sent To  
Notes
2007-02-26 18:51:23REVISION OK SHTS P2.01 REV 11, SHT P3.01 REV 7, SHT
 P3.02 REV 7, SHT P3.08 REV 11, SHT P3.09 REV 11

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-01-09 Cont ID  
Sent By kstevens Date 2007-01-09 Time 11:05 Rev Time 0.00
Received By kstevens Date 2007-01-09 Time 11:05 Sent To  
Notes
2007-01-09 11:11:23REVISION FAILED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT P2.04 INDICATES REVISION #5 FOR KEY NOTES #9
 ADDED. REVISION #5 WAS INDICATED ON SHEETS APPROVED
 DATED 9-8-06. NEW REVISION NUMBERS ARE REQUIRED FOR NEW
 REVISIONS. - REVISION #10 IS NOT INDICATED ON THE LIST
 OF REVISIONS.PLEASE CLARIFY. - KEY NOTE #10 NOT
 LOCATED. PLEASE CLARIFY. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-01-09 Cont ID  
Sent By kstevens Date 2007-01-09 Time 10:53 Rev Time 0.00
Received By kstevens Date 2007-01-08 Time 16:32 Sent To  
Notes
2007-01-09 11:02:10REVISION OK -
 SHT P2.01 OK - REVISIONS REQUIRED FOR THE SANITARY
 COLLECTION ISOMETRIC TO REFLECT THE REVISIONS
 APPROVED.
 SHT P2.02 OK - REVISIONS REQUIRED FOR THE SANT. & STORM
 COLLECTION ISOMETRICS TO REFLECT THE REVISIONS
 APPROVED.
 SHT P2.05 OK, SHT P2.28 OK, SHT P2.29 OK, SHT P3.03 OK,
 SHT P3.04 OK, SHT P3.08 OK, SHT P3.09 OK, SHT P3.16 OK
 UNIONS REQUIRED BY REGULATORS.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-08-28 Cont ID  
Sent By kstevens Date 2006-08-28 Time 16:47 Rev Time 0.00
Received By kstevens Date 2006-08-26 Time 17:28 Sent To  
Notes
2006-08-28 00:00:00SEE PROVISO ON GAS STOP

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-08-22 Cont ID  
Sent By kstevens Date 2006-08-22 Time 16:21 Rev Time 0.00
Received By kstevens Date 2006-08-22 Time 16:20 Sent To  
Notes
2006-08-22 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 ** **FROM PREVIOUS REVIEWS: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS THE
 PREVIOUS REVIEWS:
  
 FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS FIRST
 REVIEW: - NO COMMENT RESPONSES SUBMITTED
 FOR THE FIRST REVIEW.
  
 2. OK
  
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ***COMMENT CONCERNING 11-4.1.3(10)(A)
 NOT ADDRESSED. CLEAR FLOOR SPACE SHALL
 ALLOW FORWARD APPROACH. 11-4.15.5(1).
 ****RESPONSE NOTED, BUT PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS ON DIFFERENT SHEETS.
 ** **RESPONSE NOTED, BUT A PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS FOR SHEETS A0.3, A0.9, AND A1.21.
  
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER 2 FOR INFORMATION STILL REQUIRED
 FOR W/C'S AND LAVS.
 FOR SHOWERS
 A. 11-4.21.3 SEAT (FOLD-UP TYPE)
 B. 11-4.21.5 CONTROLS (FIG. 11-37)
 C. 11-4.21.6 SHOWER UNIT
 D. 11-4.21.7 CURBS
 SUBMIT ELEVATIONS FOR THE SHOWER SHOWING
 COMPLIANCE FOR THE PRIOR REQUIREMENTS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT
 REQUIRED BY 11-4.21.6 IS NOT SHOWN, AND
 CURBS ARE INDICATED, WHERE AS SECTION
 11-4.21.7 INDICATES CURBS ARE NOT TO BE
 INSTALLED. - NO BREAK ROOM SINK DETAIL
 OR ELEVATION IS FOUND. -
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 THE SHOWER SHALL SHOW A CLEAR FLOOR
 SPACE PER 11-4.21.2. SECTION
 11-4.22.2(1).
 ** **RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE BREAK
 ROOM SINK:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 5.OK
 6.OK
 11. OK
  
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 ***COMMENT NOT ADDRESSED.
 ****THIS ISSUE HAS NOT BEEN ADDRESSED.
 CLEAR FLOOR SPACE FOR THE LAV & TUB ARE
 SHOWN BUT NOT THE W/C.
 ** **RESPONSE NOTED, BUT A 30"X48" CLEAR
 FLOOR SPACE HAS BEEN SUPERIMPOSED ON THE
 PLANS WHICH DOES NOT REFLECT THE CLEAR
 FLOOR SPACES REQUIRED ON PAGE 7.43.
  
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 ***COMMENT NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE CLEARANCE
 SHOWN IS NOT THE MINIMUM CLEARANCE. (SEE
 ATTACHED SHEET FROM FHA DESIGN MANUAL).
 ** **RESPONSE NOTED, BUT THIS DOES NOT
 COMPLY WITH THE REQUIREMENT FOR THE
 MINIMUM CLEARANCE.
  
 14. OK
 15. OK
 19. OK
 23. OK
 26. OK
 30. SOK
 31. OK
 32. OK - TO BE A SUBMITTAL
 33. OK
 35. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. OK
 6B. OK
 7B. OK
 8B. OK
 9B. OK
 10B. OK
 11B. OK
 12B. OK
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
 18B. OK
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
 24B. OK
 25B. OK
 26B. OK
 27B. OK
 28B. OK
 29B. OK
 30B. OK
 31B. OK
 32B. OK
 33B. OK
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. OK
 B. OK
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
 ** **RESPONSE NOTED, THE GAS WILL NOT BE
 APPROVED ON THESE PLANS UNTIL ALL
 REQUIREMENTS ARE MET. GAS PLANS CAN BE
 DELETED AND RESUBMITTED AT TIME OF GAS
 APPLICATION.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
 ** **RESPONSE NOTED, THE GAS WILL NOT BE
 APPROVED ON THESE PLANS UNTIL ALL
 REQUIREMENTS ARE MET. GAS PLANS CAN BE
 DELETED AND RESUBMITTED AT TIME OF GAS
 APPLICATION.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
 ** **RESPONSE NOTED, THIS ISSUE CAN BE
 TAKEN CARE OF AT THE TIME OF GAS
 APPLICATION.
  
 G. AT TIME OF KITCHEN BUILD OUT
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
 ****COMMENT NOT ADDRESSED.
  
 **************NEW COMMENTS**************
  
 1C. OK
 2C. OK
 3C. OK
  
 4C. EMERGENCY DRAINS FOR THE DECK SHALL
 DRAIN THE TOTAL AREA OF THE DRAIN. SOME
 AREAS HAVE NO EMERGENCY DRAINS, AND ITS
 UNDERSTOOD THAT THOSE AREAS WILL DRAIN
 TO THE EMERGENCY DRAINS SHOWN. THE
 EMERGENCY DRAINS SHALL BE SIZED FOR THE
 TOTAL AREA THAT WILL BE DRAINED FOR EACH
 AREA. PLEASE INDICATE THE TOTAL AREA
 BEING DRAINED FOR EACH EMERGENCY DRAIN
 AND SIZE ED'S ACCORDINGLY. SECTION
 1107.3.
 ** **RESPONSE NOTED, BUT THE AREAS FOR
 MOST EMERGENCY ROOF DRAINS DOES NOT ADD
 UP TO THE SURRONDING AREAS. PLEASE
 RECHECK THE AREAS AND CHECK THE TOTAL
 SQUARE FOOTAGE FOR EACH EMERGNECY DRAIN
 AREA. PLEASE NUMBER EACH EMERGENCY DRAIN
 AND NUMBER AND OUTLINE EACH AREA
 DRAINING TO EACH EMERGENCY DRAIN FOR
 CLARITY. - ALSO RECHECK ALL PIPE SIZES
 AND ROOF DRAIN SIZES AS NOT ALL ARE
 CORRECT. SEE TABLE 1106.3 @ 4.5"/HR
 RAINFALL FOR SECONDARY ROOF DRAINS.
 (EXAMPLE ED 2914 SF ADDS UP TO 2804SF,
 4"RD SHOWN, 5"RD REQUIRED, 6" HORIZONTAL
 PIPE SHOWN, 8" HORIZONTAL PIPE
 REQUIRED).
  
 **************NEW COMMENT**************
  
 1D. SHT A1.18 AREA FROM COL. LINE M TO
 AREA BETWEEN COL'S P & Q FROM COL. 11
 THRU COL. 19 FLOOR PLAN IS MISSING.
 PLEASE RESUBMIT SHEET WILL ALL REQUIRED
 INFORMATION. CHECK TO SEE IF ALL
 INFORMATION IS CORRECT IN THIS AREA.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-08-04 Cont ID  
Sent By kstevens Date 2006-08-04 Time 18:30 Rev Time 0.00
Received By kstevens Date 2006-08-02 Time 18:58 Sent To  
Notes
2006-08-04 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS FIRST
 REVIEW: - NO COMMENT RESPONSES SUBMITTED
 FOR THE FIRST REVIEW.
  
 2. OK
  
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ***COMMENT CONCERNING 11-4.1.3(10)(A)
 NOT ADDRESSED. CLEAR FLOOR SPACE SHALL
 ALLOW FORWARD APPROACH. 11-4.15.5(1).
 ****RESPONSE NOTED, BUT PARALLEL
 APPROACH IS STILL SHOWN ON THE FLOOR
 PLANS ON DIFFERENT SHEETS.
  
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER 2 FOR INFORMATION STILL REQUIRED
 FOR W/C'S AND LAVS.
 FOR SHOWERS
 A. 11-4.21.3 SEAT (FOLD-UP TYPE)
 B. 11-4.21.5 CONTROLS (FIG. 11-37)
 C. 11-4.21.6 SHOWER UNIT
 D. 11-4.21.7 CURBS
 SUBMIT ELEVATIONS FOR THE SHOWER SHOWING
 COMPLIANCE FOR THE PRIOR REQUIREMENTS.
 ****RESPONSE NOTED, BUT THE SHOWER UNIT
 REQUIRED BY 11-4.21.6 IS NOT SHOWN, AND
 CURBS ARE INDICATED, WHERE AS SECTION
 11-4.21.7 INDICATES CURBS ARE NOT TO BE
 INSTALLED. - NO BREAK ROOM SINK DETAIL
 OR ELEVATION IS FOUND. -
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE REQUIRED FOR ANY FIXTURE.
 THE SHOWER SHALL SHOW A CLEAR FLOOR
 SPACE PER 11-4.21.2. SECTION
 11-4.22.2(1).
  
 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER
 ROOMS TO BE ACCESSABLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTION 11-4.16,
 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND
 ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER TWO FOR INFORMATION STILL
 REQUIRED. ALSO THE INFORMATION FOR THE
 URINAL STILL REQUIRED:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT NO COMPLIANCE
 FOR THE FLUSH CONTROLS IS INDICATED.
  
 6.OK
 11. OK
  
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 ***COMMENT NOT ADDRESSED.
 ****THIS ISSUE HAS NOT BEEN ADDRESSED.
 CLEAR FLOOR SPACE FOR THE LAV & TUB ARE
 SHOWN BUT NOT THE W/C.
  
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 ***COMMENT NOT ADDRESSED.
 ****RESPONSE NOTED, BUT THE CLEARANCE
 SHOWN IS NOT THE MINIMUM CLEARANCE. (SEE
 ATTACHED SHEET FROM FHA DESIGN MANUAL)
  
 14. OK
 15. OK
 19. OK
 23. OK
 26. OK
 30. SOK
 31. OK
 32. OK - TO BE A SUBMITTAL
  
 33. GREASE INTECEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 PLEASE CONTACT LYNN MASSON (561)
 822-2271 OR BY FAX (561) 822-2279 OR BY
 E-MAIL [email protected].
 ***NOT ADDRESSED.
 ****WAITING FOR APPROVAL FROM L. MASSON
  
  
 35. PLANS SHOW A VENT IN THE WALL AND AN
 OPEN 2" DRAIN IN THE PLENUM. MORE
 INFORMATION IS REQUIRED. WILL THE ROOM
 AS A PLENUM PULL THE AIR FROM THE 2"
 OPEN DRAIN AND INTRODUCE THE HUMID, WARM
 AIR INTO THE AIR CONDITIONED AIR OF THE
 UNIT? IS THIS PRACTICE ACCEPTABLE TO THE
 MECHNAICAL ENGINEER? - ALSO THE VENT
 TERMINATION SHALL EITHER VENT THRU THE
 ROOF OR TERMINATE ABOVE THE CEILING 6"
 ABOVE THE INSULATION.
 ***NOT ADDRESSED.
 ****RESPONSE NOTED, BUT VENT IS STILL
 SHOWN IN THE WALL, AND THE DRAIN IS
 STILL SHOWN ALSO.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO COMMENT RESPONSE WAS SUBMITTED AND
 BECAUSE OF THAT AND PLAN DEVELOPMENT
 BETWEEN REVIEWS, THE RESUBMITTAL WAS
 TREATED AS A COMPLETE REVIEW OF THE
 PLAN. THIS CONTRIBUTES TO A LONGER TURN
 AROUND TIME FOR PLAN REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B.OK
 5B. OK
  
 6B. SHT P2.06 SHOWS RWL/35 BETWEEN COLS.
 28.1 AND 29. PLEASE CLARIFY. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT RWL 35 STILL
 SHOWN.
  
 7B. OK
 8B. OK
  
 9B. SHT P2.20 3"PD(68SF) & 3"PD(92SF)
 ARE NOT SHOWN ON ANY RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT NOW 68SF IS NOT
 SHOWN ON THE PLUMBING PLAN, & 92SF IS
 NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE.
  
 10B. OK
 11B. OK
  
 12B. SHTS P2.23 & P2.24 MATCH LINE DOES
 NOT MATCH FLOOR PLAN AT COL. LINE "22".
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THERE IS MISSING
 INFORMATION FOR THE FLOOR PLAN ON SHT
 P2.23.
  
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
  
 18B. SHT P3.01 RECHECK ADDITION OF DFU'S
 AS THEY ACCUMULATE IN THE SANT. SYSTEM.
 TABLE 710.1(1).
 ****RESPONSE NOTED, BUT ADDITION OF
 DFU'S INCORRECT IN SOME AREAS.
  
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
  
 24B. SHT P3.06 2 W/4 RISERS SHOWN, 2
 W/11 RISERS SHOWN, 2 W/8 RISERS SHOWN &
 2 W/28 RISERS SHOWN. PLEASE CORRELATE
 RISER DIAGRAM WITH FLOOR PLAN.
 ****RESPONSE NOTED, BUT SHT P3.07 STILL
 SHOWS 2 W/28 RISERS.
  
 25B. OK
 26B. OK
 27B. OK
  
 28B. SHT P3.13 3" PAD (136SF) NOT
 INDICATED ON DECK PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT 3" PAD (136SF)
 STILL NOT FOUND. - NEW COMMENT NEW 2ND
 4" DD (378SF) SHOWN ON RISER NOT FOUND
 ON DECK PLAN.
  
 29B. SHT P3.14 6" REQUIRED AT SD
 (1657SF). TABLE 1106.3.
 ****RESPONSE NOTED, BUT PIPES ARE
 UNDERSIZED DOWNSTREAM OF 4" DD (763SF)
 RISER DP7, DOWNSTREAM OF 3" PD (134SF)
 RISER DP8, & DOWNSTREAM OF 3" PD (81SF)
 SHOWS 8" THEN REDUCING TO 6" IN THE
 DIRECTION OF FLOW. SECTION 704.2.
  
 30B. OK
 31B. OK
 32B. OK
 33B. OK
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THE GAS LINE TO
 THE POOL HEATER APPEARS TO BE RUN IN THE
 5TH FLOOR CEILING. WILL THE POOL HEATER
 BE LOCATED IN THE CEILING, OR WILL THERE
 BE A DROP TO THE HEATER. PLEASE CLARIFY.
  
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 ****RESPONSE NOTED, BUT THE TABLE SHOWN
 IS FROM FBC-2001 FUEL GAS CODE. PLEASE
 DESIGN AND INDICATE TABLE FROM FBC-2004
 FUEL GAS CODE.
 C. OK
  
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 ****NOT ADDRESSED.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 ****NOT ADDRESSED. ITS UNDERSTOOD THE
 KITCHEN GAS EQUIPMENT WILL BE SUBMITTED
 AT KITCHEN BUILD-OUT, BUT THE POOL
 HEATER SPECIFICATIONS SHEETS WILL BE
 REQUIRED.
  
 G. AT KITCHEN BUILD-0UT
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
 ****COMMENT NOT ADDRESSED.
  
 **************NEW COMMENTS**************
  
 1C. CONDENSATE/PAN DRAIN LINE TO BE
 SEPARATE. CONDENSATE LINES CAN BACK UP
 BECAUSE OF THE BUILD-UP AND THE EXHAUST
 FROM THE PARKING GARAGE CAN ENTER THE
 A/C CLOSETS. PAN DRAIN LINES SHOULD
 TERMINATE OUTSIDE THE BUILDING, OR BE
 PIPED INDIRECTLY TO THE SANITARY SYSTEM.
 SECTION 504.7.2.
  
 2C. SHT P3.04 RISER 139 WASH MACHINE TO
 DISCHARGE DOWNSTREAM OF BATHROOM
 FIXTURES. VENT REQUIRED FOR W/C &
 SHOWER. SECTIONS 901.2 & 909.1
  
 3C. SHT P3.04 RISER 98 FITTING TO BE
 INSTALLED TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3.
  
 4C. EMERGENCY DRAINS FOR THE DECK SHALL
 DRAIN THE TOTAL AREA OF THE DRAIN. SOME
 AREAS HAVE NO EMERGENCY DRAINS, AND ITS
 UNDERSTOOD THAT THOSE AREAS WILL DRAIN
 TO THE EMERGENCY DRAINS SHOWN. THE
 EMERGENCY DRAINS SHALL BE SIZED FOR THE
 TOTAL AREA THAT WILL BE DRAINED FOR EACH
 AREA. PLEASE INDICATE THE TOTAL AREA
 BEING DRAINED FOR EACH EMERGENCY DRAIN
 AND SIZE ED'S ACCORDINGLY. SECTION
 1107.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-26 Cont ID  
Sent By kstevens Date 2006-05-26 Time 15:33 Rev Time 0.00
Received By kstevens Date 2006-05-13 Time 18:19 Sent To  
Notes
2006-05-26 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 FROM PREVIOUS REVIEW: THE COMMENT
 NUMBERS SHALL REMAIN THE SAME AS FIRST
 REVIEW: - NO COMMENT RESPONSES SUBMITTED
 FOR THE FIRST REVIEW.
  
 2. SHT A1.0 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS.
 *** COMMENT NOT ADDRESSED. SHOW THE
 FOLLOWING: FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.2 CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
  
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 ***COMMENT CONCERNING 11-4.1.3(10)(A)
 NOT ADDRESSED. CLEAR FLOOR SPACE SHALL
 ALLOW FORWARD APPROACH. 11-4.15.5(1).
  
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER 2 FOR INFORMATION STILL REQUIRED
 FOR W/C'S AND LAVS.
 FOR SHOWERS
 A. 11-4.21.3 SEAT (FOLD-UP TYPE)
 B. 11-4.21.5 CONTROLS (FIG. 11-37)
 C. 11-4.21.6 SHOWER UNIT
 D. 11-4.21.7 CURBS
 SUBMIT ELEVATIONS FOR THE SHOWER SHOWING
 COMPLIANCE FOR THE PRIOR REQUIREMENTS.
  
 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER
 ROOMS TO BE ACCESSABLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTION 11-4.16,
 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND
 ALL SUBSECTIONS.
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER TWO FOR INFORMATION STILL
 REQUIRED. ALSO THE INFORMATION FOR THE
 URINAL STILL REQUIRED:
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.4 FLUSH CONTROLS
  
 6. SHT A1.21 MEN'S & WOMEN'S TOILET
 ROOMS AND DRINKING FOUNTAIN SHALL BE
 ACCESSIBLE. (SEE COMMENTS 2, 3 & 5).
 ***COMMENT NOT ADDRESSED. SEE COMMENT
 NUMBER TWO FOR INFORMATION STILL
 REQUIRED.
  
 11. SHT A9.24 UNITS C1.1, C1.2, & C1
 OPENING FOR WATER CLOSET IN BATH #2
 SHALL BE MINIMUM 33" . PLEASE INDICATE
 ON PLANS. PAGE 7.44.
 ***COMMENT NOT ADDRESSED.
  
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 ***COMMENT NOT ADDRESSED.
  
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 ***COMMENT NOT ADDRESSED.
  
 14. SHT P2.01 NO PIPING SHOWN TO 3 PAD'S
 PLEASE CLARIFY. SECTION 106.1.1. SHOW
 ALL PIPE SIZES FOR ALL PIPE SYSTEMS ON
 THE THE FLOOR PLAN. TABLES 710.1 &
 1106.3.
 ***PAD'S STILL SHOWN, BUT NOT
 IDENTIFIED. PLEASE CLARIFY. - PIPE
 SIZING NOT SHOWN ON FLOOR PLAN PIPING.
  
 15. SHT P2.02NO PIPING SHOWN TO 2
 PAD'S. SECTION 106.1.1. - SHOW ALL PIPE
 SIZING FOR U/G BUILDING SANT. , STORM,
 COND., AND DRAIN PIPING. SECTION
 106.1.1. TABLES 710.1 & 1106.3.
 ***PAD'S STILL SHOWN, BUT NOT
 IDENTIFIED, PLEASE CLARIFY. SECTION
 106.1.1.
  
 19. SHTS P2.19 & P2.20 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 STORM DRAINS. SHOW SQUARE FEET, 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND AREA OF ROOFS DRAINING TO
 DECK AREA FROM ABOVE IN THE CALCULATIONS
 PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECITONS. - SHOW THE LOCATION OF ALL
 SECONDARY DRAINS.
 ***COMMENT NOT ADDRESSED. NO CALC'S
 FOUND. SECONDARY DRAIN LOCATIONS NOT
 SHOWN. CONTRIBUTION FROM THE PRIVACY
 WALLS TO BOTH SIDES AT THE DECK AREAS
 WERE NOT INDICATED.
  
 23. SHT P3.02 2-WAY CLEANOUTS ARE
 REQUIRED ON BOTH THE ENTRANCE AND EXIT
 OF THE GREASE INTERCEPTOR PER UTILITY
 STANDARDS. - FIXTURE UNIT VALUE NOT
 SHOWN FOR 3 FUTURE STUB UPS. TABLE
 710.1(1).
 ***2-WAY CLEANOUT NOT SHOWN ON THE INLET
 SIDE OF THE GREASE INTERCEPTOR. -
 FIXTURE UNIT VALUE STILL NOT SHOWN FOR
 ALL FUTURE STUB UPS.
  
 26. SHT P3.08 KEY NOTES INFORMATION IS
 REVERSED FROM RISERS. PLEASE CORRELATE
 KEY NOTES AND RISERS. SECTION 106.1.1.
 ***THIS IS STILL NOT CHANGED ON ALL
 RISERS.
  
  
 30. SHT P3.14 6PLEASE NUMBER
 OR PLACE A DESIGNATION ON THE LIFT
 STATIONS BOTH ON THE RISER DIAGRAMS AND
 THE FLOOR PLANS TO HELP EXPEDITE THE
 PLAN REVIEW.
 ***NOT ADDRESSED.
  
 31. SHT P3.15 RISER DOES NOT REFLECT THE
 FLOOR PLAN. RISERS CD/37 & DR/37 ARE NOT
 SHOWN ON THE RISER DIAGRAM.
 ***NOT ADDRESSED.
 32. DOMESTIC BOOSTER PUMPS, STORM LIFT
 STATION PUMPS SHALL BE LISTED. PLEASE
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 EACH. SECTION 303.
 ***NOT ADDRESSED.
  
 33. GREASE INTECEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 PLEASE CONTACT LYNN MASSON (561)
 822-2271 OR BY FAX (561) 822-2279 OR BY
 E-MAIL [email protected].
 ***NOT ADDRESSED.
  
  
 35. PLANS SHOW A VENT IN THE WALL AND AN
 OPEN 2" DRAIN IN THE PLENUM. MORE
 INFORMATION IS REQUIRED. WILL THE ROOM
 AS A PLENUM PULL THE AIR FROM THE 2"
 OPEN DRAIN AND INTRODUCE THE HUMID, WARM
 AIR INTO THE AIR CONDITIONED AIR OF THE
 UNIT? IS THIS PRACTICE ACCEPTABLE TO THE
 MECHNAICAL ENGINEER? - ALSO THE VENT
 TERMINATION SHALL EITHER VENT THRU THE
 ROOF OR TERMINATE ABOVE THE CEILING 6"
 ABOVE THE INSULATION.
 ***NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ***NO COMMENT RESPONSE WAS SUBMITTED AND
 BECAUSE OF THAT AND PLAN DEVELOPMENT
 BETWEEN REVIEWS, THE RESUBMITTAL WAS
 TREATED AS A COMPLETE REVIEW OF THE
 PLAN. THIS CONTRIBUTES TO A LONGER TURN
 AROUND TIME FOR PLAN REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. SHT A9.27 DETAIL ELEVATIONS 3 & 5 NO
 DISPENSER SHOWN. STALL DOES NOT REFLECT
 FIG. 30E. LAV TO BE A MINIMUM 60" OFF
 THE W/C WALL. (MIN. 15" OFF WALL TO
 CENTERLINE OF LAV). WATER CLOSET TO BE
 17" TO 19" OFF FLOOR TO SEAT. INDICATE
 ON PLANS. SHOW CLEARANCE FOR LAVS TO BE
 2'3". SECTIONS 11-4.16.3, 11-4.16.6,
 11-4.19.2,
  
 2B. SHTS P2.01 THRU P2.0-5, P2.07,
 P2.08, P2.10, P2.11, P2.13, P2.14,
 P2.16, & P2.17 IDENTIFY ALL RISERS FOR
 ALL SYSTEMS. SECTION 106.1.1.
  
 3B. SHT P2.02 8" FD TO STORM IN MAINT.
 ROOM. PLEASE INDICATE WHAT IS BEING
 DRAINED. IF NOT STORM WATER, DRAIN TO BE
 CONNECTED TO SANITARY. MUNICIPAL CODE
 SECTION 90-203.
  
 4B. SHT P2.03 FITTING CONNECTING 2"
 DRAIN BETWEEN COLS. 28 & 29 TO BUILDING
 SANT. FITTING IS NOT INSTALLED TO GUIDE
 SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW AS REQUIRED IN SECTION 706.3.
  
 5B. SHT P2.05 SHOWS 2 W/26 RISERS.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 6B. SHT P2.06 SHOWS RWL/35 BETWEEN COLS.
 28.1 AND 29. PLEASE CLARIFY. SECTION
 106.1.1.
  
 7B. SHTS P2.07, P2.10, & P2.13 SHOWS
 RWL/18 BETWEEN COLS. 5 & 6. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 8B. SHT P2.19 4"DD (1,525SF) & 3"PD
 (92SF) NOT SHOWN ON ANY RISER DIAGRAM. -
 EXTRA FD SHOWN @ COL LINE 7 BETWEEN
 COLS. O & N. PLEASE CLARIFY. SECTION
 106.1.1.
  
 9B. SHT P2.20 3"PD(68SF) & 3"PD(92SF)
 ARE NOT SHOWN ON ANY RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 10B. SHTS P2.22, P2.23, P2.24 INDICATES
 "TYPICAL FLOOR". PLEASE INDICATE WHAT
 ITS TYPICAL OF. SECTION 106.1.1.
  
 11B. SHTS P2.22 & P2.23 MATCH LINE DOES
 NOT MATCH FLOOR PLAN AT COL. LINE "N".
 PLEASE CLARIFY. SECTION 106.1.1.
  
 12B. SHTS P2.23 & P2.24 MATCH LINE DOES
 NOT MATCH FLOOR PLAN AT COL. LINE "22".
 PLEASE CLARIFY. SECTION 106.1.1.
  
 13B. SHTS P2.22 & P2.25 RISER
 DESIGNATION FOR S/46 COVERED UP BY RISER
 RWL/12 DESIGNATION. PLEASE INDICATE
 CLEARLY RISER DESIGNATION S/46. SECTION
 106.1.1.
  
 14B. SHT P2.26 WATER LINE FROM M/B TO
 KITCHEN IN UNIT 'A 5.2' NOT ON PLANS.
 SECTION 106.1.1.
  
 15B. SHT P2.31 2 VTR'S IN EGRESS
 STAIRWELL ARE NOT APPROVED. NFPA 101
 SECTION 7.1.3.2.1(6).
  
 16B. SHTS P2.31, P2.32, P2.33 PLEASE
 IDENTIFY ROOF DRAINS WITH A NUMBER
 DESIGNATION THAT CORRELATES WITH A RWL
 DESIGNATION. (EXAMPLE RD-1 WITH RWL-1)
  
 17B. SHT P2.33 NO SF SHOWN FOR AREA NEXT
 TO 6"RD(1560SF).
  
 18B. SHT P3.01 RECHECK ADDITION OF DFU'S
 AS THEY ACCUMULATE IN THE SANT. SYSTEM.
 TABLE 710.1(1).
  
 19B. P3.01 LINE TO (A)(47FU), WHERE IS
 THE CONTINUATION TO THIS LINE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 20B. SHT P3.01 TOILET ROOM ISOMETRIC,
 PLEASE INDICATE WHICH RISER THE SANT.
 BRANCH LINE CONNECTS TO. SECTION
 106.1.1.
  
 21B. SHT P3.01 AAV FOR 2" STACK TO SINK
 NOT APPROVED. SECTION 917.3.
  
 22B. SHTS P3.03 & P3.04 CHECK RED LINE
 CORRECTION FOR FIXTURE UNITS AT EACH
 STACK INCICATED. FLOOR DRAINS OVER 2",
 FIXTURE UNITS PER TABLE 709.2.
  
 23B. P3.05 FUTURE WATER SUPPLY SHOWN AS
 KEY NOTE #1, (6" WATER SERVICE) & SUB
 METERS ARE SHOWN AS #2 (BACKFLOWS).
 PLEASE CORRELATE KEY NOTES AND FLOOR
 PLAN. SECTION 106.1.1.
  
 24B. SHT P3.06 2 W/4 RISERS SHOWN, 2
 W/11 RISERS SHOWN, 2 W/8 RISERS SHOWN &
 2 W/28 RISERS SHOWN. PLEASE CORRELATE
 RISER DIAGRAM WITH FLOOR PLAN..
  
 25B. SHT P3.06 3/4" WATER SUPPLY TO
 URINAL IS CONNECTING TO 1/2" WATER
 SUPPLY. PLEASE CLARIFY. SECTION 106.1.1.
  
 26B. SHTS P3.12, P3.13, P3.14, & P3.15
 INDICATE RISER NUMBER FOR ALL "PAD"
 RISERS, AND 5TH FLOOR DECK DRAIN/PLANTER
 DRAIN RISERS TO BE ABLE TO TRACK RISERS
 FROM THE BUILDING DRAIN THRU TO THE
 DRAINS. SECTION 106.1.1.
  
 27B. P3.12 CHECK ADDITION ON SF FOR SOME
 RISERS. ALSO RWL/2 SF AT ROOF DRAIN
 SHOWS (1866SF), BUT (1849SF) ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 28B. SHT P3.13 3" PAD (136SF) NOT
 INDICATED ON DECK PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 29B. SHT P3.14 6" REQUIRED AT SD
 (1657SF). TABLE 1106.3
  
 30B. SHT P3.14 RISER DOES NOT REFLECT
 THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 31B. SHT P3.14 RISER SHOWS 2 2ND FLOORS
 AND 2 4TH FLOORS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 32B. SHT P3.14 CHECK ADDITION OF STORM
 DRAIN PRIOR TO DRAINAGE WELL. TABLE
 1106.3.
  
 33B. SHT P3.15 PAD RISER DOES NOT
 REFLECT FLOOR PLAN AT THE MEZZ. LEVEL.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 34B. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (EACH SYSTEM).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (EACH
 SYSTEM).
 D. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304. (EACH SYSTEM).
 E. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (EACH SYSTEM).
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (EACH
 SYSTEM).
 G. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (FOR
 KITCHEN SYSTEM ONLY).
  
 35B. THERE IS ONE SET OF "RED LINED"
 PLANS. PLEASE RETURN THIS SET AND
 COMMENT RESPONSES TO HELP EXPEDITE THE
 NEXT PLAN REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By kstevens Date 2005-12-05 Time 16:57 Rev Time 37.50
Received By kstevens Date 2005-12-01 Time 19:08 Sent To  
Notes
2005-12-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. IF THE DESIGN PROFESSIONAL IS AN
 ARCHITECT OR ENGINEER LEGALLY REGISTERED
 UNDER THE LAWS OF THIS STATE REGULATING
 THE PRACTICE OF ARCHITECTURE AS PROVIDED
 FOR IN CHAPTER 481, FLORIDA STATUTES, OR
 ENGINEERING AS PROVIDED FOR IN CHAPTER
 471, FLORIDA STATUTES, THEN HE OR SHE
 SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE, AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS
 REQUIRED BY FLORIDA STATUTE. SECTION
 106.1, FAC 61G15-23.002(2)/61G1-16.003
 AND FS 471.2055/481.025.
 2. SHT A1.0 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS.
 3. SHT A1.0 THE DRINKING FOUNTAIN SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH SECTIONS 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
 4. SHT A1.2 MEN'S & WOMEN'S TOILET ROOMS
 SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, 11-4.21, 11-4.22 AND
 ALL SUBSECTIONS. ALSO FOR THE BREAK ROOM
 SINK, 11-4.24 AND ALL SUBSECTIONS.
 5. SHT A1.18 MEN'S AND WOMEN'S LOCKER
 ROOMS TO BE ACCESSABLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTION 11-4.16,
 11-4.18, 11-4.19, 11-4.21, & 11-4.22 AND
 ALL SUBSECTIONS.
 6. SHT A1.21 MEN'S & WOMEN'S TOILET
 ROOMS AND DRINKING FOUNTAIN SHALL BE
 ACCESSIBLE. (SEE COMMENTS 2 AND 5).
 7. SHT A9.10 UNITS A5.2, A5 & A5.1 CLEAR
 FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO THE FIXTURE AND FLUSH WITH
 THE CONTROLS. PAGE 7.56 PARAGRAPH TWO. -
 UNITS A5, & A5.1 INDICATE SIZE OF
 OPENING FOR W/C'S. (MINIMUM 33" REQD.).
 8. SHT A9.11 UNITS A5A.2, A5A. & A5A.1
 CLEAR FLOOR SPACE FOR SHOWERS SHALL BE
 PARALLEL TO THE FIXTURE AND FLUSH WITH
 THE CONTROL WALL. PAGE 7.56.
 9. SHT A9.13 UNITS A7 & A7.1 CLEAR FLOOR
 SPACE FOR SHOWERS SHALL BE PARALLEL TO
 THE FIXTURE AND FLUSH WITH THE CONTROL
 WALL. PAGE 7.56.
 10. UNITS B1D.2, & B1D.1 W/C IN MASTER
 BATH SHALL BE 18" OFF THE WALL TO THE
 CENTER OF THE FIXTURE. PLEASE SHOW ON
 THE PLANS. PAGES 7.43 THRU 7.46.
 11. SHT A9.24 UNITS C1.1, C1.2, & C1
 OPENING FOR WATER CLOSET IN BATH #2
 SHALL BE MINIMUM 33" . PLEASE INDICATE
 ON PLANS. PAGE 7.44
 12. SHTS A9.2 THRU A9.24 ALL UNITS.
 CLEAR FLOOR SPACE FOR THE WATER CLOSETS
 SHALL BE APPLIED OR SUPERIMPOSED OVER A
 PLAN PER PAGE 7.43 PARAGRAPH ONE.
 13. SHTS A9.2 THRU A9.24 PER PAGE 7.7
 MINIMUM CLEARANCES BETWEEN COUNTERS AND
 ALL OPPOSING ELEMENTS IS 40". PLEASE
 INDICATE ON THE PLANS THE MINIMUM
 CLEARANCE FOR ALL KITCHENS.
 14. SHT P2.01 NO PIPING SHOWN TO 3 PAD'S
 PLEASE CLARIFY. SECTION 106.1.1 - SHOW
 ALL PIPE SIZES FOR ALL PIPE SYSTEMS ON
 THE FLOOR PLAN. TABLES 710.1 & 1106.3. -
 TRAPS REQUIRED ON THE DRAIN LINES FOR
 THE FIRE DRAIN RISERS. SECTION 802.2. -
 FITTINGS SHALL BE INSTALLED TO GUIDE
 SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW. SECTION 706.3 (SEE CD & D LINES TO
 THE LEFT OF THE MANHOLE. - INDICATE
 WHERE SD LINE IS GOING AT COL. LINE 12
 BETWEEN COLS. P & Q. SECTION 106.1.1.
 15. SHT P2.02 RISERS 9 & 10 ARE
 MISLABLED AT COL. LINE 6-E. SECTION
 106.1.1. - NO PIPING SHOWN TO 2 PAD'S.
 SECTION 106.1.1. - SHOW ALL PIPE SIZING
 FO U/G BUILDING SANT. , STORM, COND.,
 AND DRAIN PIPING. SECTION 106.1.1.
 16. SHT P2.03 SANT. PIPING NOT APPROVED
 IN THE EGRESS STAIRWELL AT COL LINE 22-I
 PER NFPA-101 SECTION 7.1.3.2.1(6). - 2"
 DRAIN LINE TO THE RIGHT OF COL. LINE 28
 REQUIRES A VENT. SECTION 901.2.1. -
 FOUNTAIN WATER SUPPLY REQUIRES BACKFLOW
 PROTECTION PER SECTION 608.13. INDICATE
 METHOD OF PROTECTION. - KEY NOTES 4 & 7
 NOT FOUND. PLEASE CLARIFY. SECTION
 106.1.1.
 17. SHT P2.04 SANT. PIPING NOT ALLOWED
 IN THE STAIRWELL PER NFPA-101 SECTION
 7.1.3.2.1(6).
 18. SHTS P2.16 & P2.17 KEY NOTE 2
 INDICATES, AND PLAN SHOWS RISER THRU
 NEXT FLOOR, WHEN THEY SHOUD INDICATE
 "TURN DOWN". PLEASE CLARIFY. SECTION
 106.1.1.
 19. SHTS P2.19 & P2.20 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 STORM DRAINS. SHOW SQUARE FEET, 1/2 AREA
 OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, AND AREA OF ROOFS DRAINING TO
 DECK AREA FROM ABOVE IN THE CALCULATIONS
 PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECITONS. - SHOW THE LOCATION OF ALL
 SECONDARY DRAINS.
 20 SHTS P2.28, P2.29, & P2.30 ARE
 SHOWING ALL 37 RWL'S. PREVIOUS LEVELS
 SHOW JUST A FEW IF ANY RWL LOCATIONS.
 PLEASE SHOW ALL RWL'S ON EACH LEVEL.
 SECTION 106.1.1.
 21. SUBMIT A STORM DRAIN COLLECTION
 ISOMETRIC RISER DIAGRAM. (SHT P3.13
 SHOWN ON THE INDEX PAGE WAS NOT
 SUBMITTED). - SHOW ALL PIPE SIZES,
 SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM & LOCATION OF EACH RWL RISER.
 SECTION 106.1.1. - SUBMIT STORM RISER
 DIAGRAMS SHOWING ALL PIPE SIZES,
 OFFSETS, AND SQUARE FOOTAGE ECT. SECTION
 106.3.5.1.3(7)(13).
 22. SHT P3.01 RECALCULATE FU'S FOR RISER
 11 & DOWNSTREAM. (11 NOT ADDED IN FU'S.)
 SECTION 106.1.1 & TABLE 710.1(1). - ALL
 FIRE DRAIN LINES REQUIRE A TRAP PER
 SECTION 802.2. - RISERS 49 & 55 APPEAR
 TO RISE TO THE 7TH FLOOR. PLEASE CLARIFY
 SECTION 106.1.1. - PARTIAL SANITARY
 COLLECTION ISOMETRIC DOES NOT REFLECT
 THE FLOOR PLAN UPSTREAM OF THE TRASH
 ROOM FLOOR DRAIN, AND DOWNSTREAM OF THE
 MOP SINK. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
 23. SHT P3.02 2-WAY CLEANOUTS ARE
 REQUIRED ON BOTH THE ENTRANCE AND EXIT
 OF THE GREASE INTERCEPTOR PER UTILITY
 STANDARDS. - FIXTURE UNIT VALUE NOT
 SHOWN FOR 3 FURTURE STUB UPS. TABLE
 710.1(1). - 10" 2679FU REQUIRES 12" PIPE
 OR SHALL BE SHOWN AS 1/8"FT THE ENTIRE
 RUN. TABLE 710.1(1) AND SECTION 704.1. -
 10" 2689FU REQUIRES 12" PIPE OR SHALL BE
 SHOWN AS 1/8"FT THE ENTIRE RUN. TABLE
 710.1(1) & SECTION 704.1. - 12" 4402FU
 REQUIRES 15" PIPE OR SHALL BE SHOWN AS
 1/8"FT THE ENTIRE RUN. TABLE 710.1(1) &
 SECTION 704.1.
 24. SHT P3.03 RISERS S/27, S/36, S/78,
 S/94 & S/31, S/89, S/147, S/149 VENT
 STACK REQUIRED PER TABLE 903.2
 25. SHTS P3.05, P3.06, & P3.07 SHT PX
 INDICATED ON EACH SHEET WAS NOT LOCATED.
 PLEASE SUBMIT SHT PX. SECTION 106.1.1.
 26. SHT P3.08 KEY NOTES INFORMATION IS
 REVERSED FROM RISERS. PLEASE CORRELATE
 KEY NOTES AND RISERS. SECTION 106.1.1.
 27. SHT P3.10 WATER RISER FOR UNIT A3.1
 AND REV. A3.1 INDICATE 2 W/M'S. FLOOR
 PLAN ONLY INDICATES ONE. PLEASE
 CORRELATE FLOOR PLAN & RISER DIAGRAM.
 SECTION 106.1.1.
 28. SHT P3.12 PAD RISER TO THE LEFT OF
 LIFT STATION AND PIPING WHERE THE PIPING
 SPLITS LEFT & RIGHT PRIOR TO THE LIFT
 STATION DO NOT REFLECT THE FLOOR PLAN.
 ALSO 6 RISERS SHOW 2 FOURTH FLOORS.
 PLEASE CORRELATE RISERS & FLOOR PLANS.
 SECTION 106.1.1.
 29. SHT P3.13 NOT SUBMITTED. (SHOWN ON
 THE INDEX SHEET).
 30. SHT P3.14 6 STORM MANHOLES ARE SHOWN
 ON THE GROUND FLOOR PLUMBING PLANS.
 THESE ARE NOW REFERED TO AS STORM DRAIN
 LIFT STATIONS, AND ONLY 4 ARE SHOWN.
 PLEASE CORRELATE THE TERMINOLOGY AND
 INDICATE WHERE THE OTHER LIFT STATIONS
 ARE LOCATED. NONE OF THE RISERS DIAGRAMS
 REFLECT THE FLOOR PLANS. - PLEASE NUMBER
 OR PLACE A DESIGNATION ON THE LIFT
 STATIONS BOTH ON THE RISER DIAGRAMS AND
 THE FLOOR PLANS TO HELP EXPEDITE THE
 PLAN REVIEW. - RISER (4" 2830SF) DOES
 NOT APPEAR TO PICK UP ANY DRAINS. PLEASE
 CLARIFY. - 2" DRAIN UPSTREAM OF 4" HD IS
 SHOWN TO BE ON THE SANT. SYSTEM ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 106.1.1.
 31. SHT P3.15 FITTINGS SHALL BE
 INSTALLED TO GUIDE SEWAGE AND WASTE IN
 THE DIRECTION OF FLOW. SECTION 706.3.
 SEE FITTING UPSTREAM OF MANHOLE (OR LIFT
 STATION). - DOES NOT REFLECT THE FLOOR
 PLAN. RISERS CD/37 & DR/37 NOT SHOWN ON
 RISER DIAGRAM.
 32. DOMESTIC BOOSTER PUMPS, STORM LIFT
 STATION PUMPS SHALL BE LISTED. PLEASE
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 EACH. SECTION 303.
 33. GREASE INTECEPTOR SHALL BE SIZED BY
 THE ENVIRONMENTAL COMPLIANCE MANAGER.
 PLEASE CONTACT LYNN MASSON (561)
 822-2271 OR BY FAX (561) 822-2279 OR BY
 E-MAIL [email protected].
 34. SHT P309 KEY NOTES 7 - A/C CLOSET IS
 A PLENUM AND AS SUCH SHALL HAVE NO
 COMBUSTABLE MATERIAL. PLEASE INDICATE
 THE MATERIAL BEING USED FOR THE THERMAL
 EXPANSION VALVE DRAIN, THE P&T RELIEF
 VALVE DISCHARGE DRAIN, AND THE EMERGENCY
 PAN DRAIN FOR THE WATER HEATER.
 35. PLANS SHOW A VENT IN THE WALL AND AN
 OPEN 2" DRAIN IN THE PLENUM. MORE
 INFORMATION IS REQUIRED. WILL THE ROOM
 AS A PLENUM PULL THE AIR FROM THE 2"
 OPEN DRAIN AND INTRODUCE THE HUMID, WARM
 AIR INTO THE AIR CONDITIONED AIR OF THE
 UNIT? IS THIS PRACTICE ACCEPTABLE TO THE
 MECHNAICAL ENGINEER? - ALSO THE VENT
 TERMINATION SHALL EITHER VENT THRU THE
 ROOF OR TERMINATE ABOVE THE CEILING 6"
 ABOVE THE INSULATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 15 Status P Date 2008-09-09 Cont ID  
Sent By mflis Date 2008-09-09 Time 08:34 Rev Time 0.00
Received By mflis Date 2008-09-09 Time 08:34 Sent To  
Notes
2008-09-09 08:35:43ZONING REVIEW: PASS
  
 ** PLAN REVISIONS A0.8, A1.15, A1.16
  
 **COMPACT CAR SPACES SHALL BE MARKED ON THE PAVEMENT AS
 COMPACT OR SMALL SPACES
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 14 Status P Date 2008-09-08 Cont ID  
Sent By mflis Date 2008-09-08 Time 09:38 Rev Time 0.00
Received By mflis Date 2008-09-08 Time 09:38 Sent To  
Notes
2008-09-08 09:42:06ZONING REVIEW: PASSED
  
 NOTE: CAT PALMS AT GROUND FLOOR IN PLANTER BOXES SHOULD
 BE COORDINATED AS PER DISCUSSION WITH CITY LANDSCAPE
 PLANNER.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 13 Status P Date 2008-07-14 Cont ID  
Sent By mflis Date 2008-07-14 Time 14:55 Rev Time 0.00
Received By mflis Date 2008-07-14 Time 14:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 12 Status P Date 2008-07-14 Cont ID  
Sent By mflis Date 2008-07-14 Time 14:55 Rev Time 0.00
Received By mflis Date 2008-07-14 Time 14:55 Sent To  
Notes
2008-07-14 14:59:02ZONING REVIEW: PASSED
  
 ** LANDSCAPE DRAWINGS ONLY- L1,L2,L3 AND L4
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 11 Status P Date 2008-05-14 Cont ID  
Sent By mflis Date 2008-05-14 Time 14:49 Rev Time 0.00
Received By mflis Date 2008-05-14 Time 14:49 Sent To  
Notes
2008-05-14 14:50:05ZONING REVIEW: PASSED
  
 ** REVISED SHEET A4.5
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 10 Status P Date 2008-04-08 Cont ID  
Sent By mflis Date 2008-04-08 Time 11:56 Rev Time 0.00
Received By mflis Date 2008-04-08 Time 11:56 Sent To P
Notes
2008-04-15 16:06:46LANDSCAPE REVISION

Review Stop Z ZONING
Rev No 9 Status N Date 2008-03-18 Cont ID  
Sent By mflis Date 2008-03-18 Time 08:55 Rev Time 0.00
Received By mflis Date 2008-03-18 Time 08:55 Sent To  
Notes
2008-03-18 08:55:59ZONING REVIEW: NOT REQUIRED
  
 * REVISIONS TO INTERIOR WORK, SECTIONS, AND RCP
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 8 Status P Date 2008-03-18 Cont ID  
Sent By mflis Date 2008-03-18 Time 08:53 Rev Time 0.00
Received By mflis Date 2008-03-18 Time 08:53 Sent To  
Notes
2008-03-18 08:54:26ZONING REVIEW: PASSED
  
 * REVISIONS TO CLOCK TOWER
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 7 Status P Date 2007-12-21 Cont ID  
Sent By mflis Date 2007-12-21 Time 10:05 Rev Time 0.00
Received By mflis Date 2007-12-21 Time 10:05 Sent To  
Notes
2007-12-21 10:05:56ZONING REVIEW: PASSED
  
 * ARCH REV 22 - PLANS & ELEVATIONS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 6 Status P Date 2007-10-26 Cont ID  
Sent By mflis Date 2007-10-26 Time 13:51 Rev Time 0.00
Received By mflis Date 2007-10-26 Time 14:09 Sent To  
Notes
2007-10-26 13:54:52ZONING REVIEW: PASSED
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 5 Status N Date 2007-07-31 Cont ID  
Sent By mflis Date 2007-07-31 Time 14:17 Rev Time 0.00
Received By mflis Date 2007-07-31 Time 14:17 Sent To B
Notes
2007-07-31 14:20:43ZONING REVIEW: NOT REQUIRED
  
 * GENERAL REVIEW OF SHOP DRAWING SUBMITTALS FOR
 AWNINGS, SHUTTERS, POOL FENCE/GATE, CLOCK TOWER
 LOUVERS, SITE FENCE, PROPERTY FENCE.
  
 * PLEASE CONFIRM SITE FENCING SHALL NOT EXCEED MAX
 ALLOWED BY CODE
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By mflis Date 2007-06-28 Time 11:15 Rev Time 0.00
Received By mflis Date 2007-06-28 Time 11:18 Sent To  
Notes
2007-06-28 11:19:34ZONING REVIEW: PASSED WITH PROVISO
  
 * PLEASE ADJUST REVISED DOOR AT COMMERICAL SPACE #15 SO
 THAT IT DOES NOT SWING INTO THE 10'-0" SIDEWALK. THE
 SIDEWALK MUST REMAIN CLEAR.
 (SEE COMM. SPACES #12 AND #14 FOR EXAMPLES OF DOORS
 THAT ARE INSET SO SWING DOES NOT IMPINGE UPON
 SIDEWALK).
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2006-07-28 Cont ID  
Sent By mflis Date 2006-07-28 Time 17:16 Rev Time 0.00
Received By mflis Date 2006-07-28 Time 17:16 Sent To  
Notes
2006-07-28 00:00:00TDR CERTIFICATES ADDED TO BUILDING
 PERMIT SUBMITTAL PACKAGE FOR RECORD
 ONLY.
 MJF

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-18 Cont ID  
Sent By mflis Date 2006-05-18 Time 08:29 Rev Time 0.00
Received By mflis Date 2006-05-16 Time 09:30 Sent To  
Notes
2006-05-18 00:00:001. PLEASE SUBMIT COPY OF TDR CERTIFICATE
 WITH BUILDING PERMIT FOR REVIEW AGAIN
 BLDG SQUARE FOOTAGES
 2. PROVIDE ELEVATION AND/OR
 MANUFACTURERS INFO REGARDING OH DOOR
 (#22) INTO "MAINTAINENCE" ROOM ALONG
 IRIS (MATERIAL ETC). AREA WILL NOT BE
 DIRECTLY ACCESSIBLE BY VEHICLES - IS
 LARGE OVERHEAD DOOR NECESSARY?

Review Stop Z ZONING
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By mflis Date 2005-11-14 Time 16:39 Rev Time 0.00
Received By mflis Date 2005-10-21 Time 11:58 Sent To  
Notes
2005-11-14 00:00:00VERIFY LANDSCAPING MEETS REQ'S AFTER
 COMPLIANCE WITH AFOREMENTIONED NOTES
2005-10-21 00:00:00SIDEWALKS MUST BE 10'-0" MINIMUM ALL
 FRONTAGES. NORTH AND SOUTH FRONTAGES DO
 NOT APPEAR TO BE IN COMPLIANCE.
  
 LOADING DOCK TO BE RELATED OFF EXTERIOR
 OF BUILDING AND INCORPORATED IN-SITE PER
 SEC 94-485.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved