Plan Review Details - Permit 05091244
Plan Review Stops For Permit 05091244
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 09:39 Rev Time 0.66
Received By alange Date 2005-10-17 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-06 Cont ID  
Sent By dpalmer Date 2005-12-06 Time 07:04 Rev Time 0.00
Received By dpalmer Date 2005-12-06 Time 06:50 Sent To  
Notes
2005-12-06 00:00:00*** REDLINED PLANS**
  
 RISER SHOWS HA AS 200A AND PANEL
 SCHEDULE INDICATES AS 250A?
 ALL AS EXISTING.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-11-10 Cont ID  
Sent By dpalmer Date 2005-11-10 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2005-11-10 Time 17:20 Sent To  
Notes
2005-11-10 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE PLANS ARE NOW COMING
 BACK SHOWING PANEL "HA AND LA" AS
 EXISTING. THIS OK, HOWEVER PLEASE SHOW
 ALL CIRCUITING ON PLANS AND CORRELATE
 WITH PANEL SCHEDULES AS PREVIOUSLY
 REQUESTED.
 *** PLEASE KNOW ***
 ALL ELECTRICAL ON PLANS ARE NOW SHOWN
 CIRCUITED TO THE HIGH VOLTAGE PANEL
 "HA". THIS IS NOT POSSIBLE AS , RECEPTS
 AND OTHER MISC LOADS ARE PROBABLY NOT
 277/480V.
 PLEASE VERIFY TRACK LIGHTING AND ALL
 ELECTRICAL. PLEASE ADJUST CIRCUITING AND
 SUBMIT LA PANEL SCHEDULE FOR 120/208 OR
 240V LOADS.
  
 2)NOTE: PLEASE SEE PANEL "HA" IS SHOWN
 AS 150A'S AND 225A'S.
 PLEASE SEE RISER SHOWS 150A'S
 PLEASE CORRELATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-03 Cont ID  
Sent By dpalmer Date 2005-10-03 Time 15:01 Rev Time 1.00
Received By dpalmer Date 2005-10-03 Time 15:01 Sent To  
Notes
2005-10-03 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE NOTES
 MENTIONS "TWO NEW PANELS", HOWEVER NO
 REVISED RISER DIAGRAM WAS SUBMITTED?
 PLANS ALSO MENTIONS, EXISTING RISER TO
 REMAIN??
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE PANEL HA IS SHOWN
 BEING 120/208, HOWEVER THIS PANEL ALSO
 INDICATES FEEDING A NEW PANEL "A' VIA
 TRANSFORMER. PLEASE VERIFY VOLTAGE OF
 PANEL "A" .
 PLEASE SUBMIT A PANEL SCHEDULE FOR NEW
 PANEL "A".
 PLEASE BE SURE ALL NEW CIRCUITING SHOWN
 ON PLANS, CORRELATES WIHT THE SUBMITTED
 PANELSCHEDULES.215.3
 PLEASE BE AWARE AN NEW EELCTRICAL
 SERVICE WORK FOR 277/480V SYSTEMS IS
 REQUIRED TO BE DONE BY A PE.
 FS 471.003H2
  
 3)NOTE: PLEASE SEE 700.12E WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 EM/EXT LTS IS THE SAME CIRCUIT FEEDING
 LOCAL LIGHTING.
  
 4)NOTE: LOADS FOR TRK LIGHTING TO BE
 INDICATED PER 220.12B
  
 PLEASE KNOW, A COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 PLEASE BE SURE TO REMOVED ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 ONE SET OF THE OLD VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANYQUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SUBMIT THE ABOVE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-09-27 Cont ID  
Sent By nmccray Date 2005-09-27 Time 10:41 Rev Time 0.00
Received By nmccray Date 2005-09-27 Time 10:41 Sent To  
Notes
2005-09-27 00:00:001) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER SYSTEM
 REMODEL.
  
 2) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE ALARM SYSTEM REMODEL.
  
 3) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 4) DEBRIS SHALL BE REMOVED FROM
 DEMOLITION ACTIVITIES DAILY.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
  
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 09:12 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 09:12 Sent To E
Notes
2005-11-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 11:32 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 11:32 Sent To E
Notes
2005-10-18 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 09:39 Rev Time 0.00
Received By alange Date 2005-09-26 Time 17:56 Sent To  
Notes
2005-09-26 00:00:00TO "BOB"#1

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-09-30 Cont ID  
Sent By prafter Date 2005-09-30 Time 09:11 Rev Time 1.00
Received By prafter Date 2005-09-30 Time 09:11 Sent To  
Notes
2005-09-30 00:00:00MECH. PLAN REVIEW:
  
 PROVISO:AUTO FAN SHUT DOWN TO BE
 TESTED AT A/C FINAL INSPECTION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 08:00 Rev Time 0.25
Received By jleech Date 2005-10-01 Time 08:00 Sent To  
Notes
2005-10-01 00:00:00NO PLUMBING WORK ON THIS RETAIL SPACE.