Plan Review Details - Permit 05091189
Plan Review Stops For Permit 05091189
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-04 Cont ID  
Sent By alange Date 2006-01-04 Time 09:16 Rev Time 1.50
Received By alange Date 2006-01-04 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 07:34 Rev Time 2.25
Received By alange Date 2005-11-22 Time 07:14 Sent To  
Notes
2005-11-22 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS REQUIRED FOR THE
 FOLLOWING;HARDIPLANK SIDING, TRUSS
 ANCHORS, CSEMENT WINDOWS AND FIXED
 WINDOWS.
 ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.ENERGY CALCS SPEC R-30 IN ATTIC YET
 PLANS ARE R-19.PLEASE ADJUST PLANS TO
 MATCH ENERGY CALCS.
  
 5.SUBMIT DETAILS FOR SPIRAL STAIRS.
  
 6.PERMIT VALUE IS TOO LOW AND HAS BEEN
 REVISED TO $50,177.00 ACCORDING TO SBCCI
 BUILDING VALUATION DATA.ADDITIONAL
 PERMIT FEES ARE DUE.SEE ATTACHED
 INVOICE.
  
 7.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS FBC 2309.6
  
 8.SHOW THE USE OF THE LOFT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-30 Cont ID  
Sent By btrobaug Date 2006-06-30 Time 14:20 Rev Time 0.50
Received By btrobaug Date 2006-06-30 Time 12:49 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-23 Cont ID  
Sent By btrobaug Date 2005-12-23 Time 14:43 Rev Time 0.50
Received By btrobaug Date 2005-12-23 Time 14:15 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By btrobaug Date 2005-10-06 Time 10:55 Rev Time 0.50
Received By btrobaug Date 2005-10-06 Time 10:07 Sent To P
Notes
2005-10-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT A DISCONNECTING MEANS
 IS REQUIRED AT THE SEPERATE STRUCTURE ON
 THE EXTERIOR WHERE THE UNGROUNDED
 CONDUCTORS ENTER THE BUILDING PER
 225.31.
  
 2} THE ABOVE DESCRIBED DISCONNECTING
 MEANS MUST BE GROUNDED PER 250.32.
 PLEASE DRAW SAME ON RISER, INDICATE GEC
 SIZE.
  
 3} THE BRANCH CIRCUIT FOR THE BATHROOM
 MUST COMLY WITH 210.11(C)(3). PLEASE
 INDICATE SAME ON THE SCHEDULE AND WITH
 THE CIRCUIT NUMBER ON THE DRAWING.
  
 NOTE: AN ELECTRICAL PERMIT IS REQUIRED
 FOR THIS WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 13:37 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 13:37 Sent To E
Notes
2006-06-22 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-23 Cont ID  
Sent By adarroug Date 2005-12-23 Time 09:43 Rev Time 0.00
Received By adarroug Date 2005-12-23 Time 09:43 Sent To E
Notes
2005-12-23 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 16:20 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 16:20 Sent To E
Notes
2005-10-05 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 07:34 Rev Time 0.00
Received By alange Date 2005-09-23 Time 18:37 Sent To  
Notes
2005-09-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-30 Cont ID  
Sent By tgordon Date 2006-06-30 Time 14:42 Rev Time 0.20
Received By tgordon Date 2006-06-30 Time 14:42 Sent To  
Notes
2006-06-30 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By tgordon Date 2005-10-06 Time 15:10 Rev Time 0.20
Received By tgordon Date 2005-10-06 Time 15:10 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By btrobaug Date 2005-12-23 Time 14:48 Rev Time 0.33
Received By jleech Date 2005-10-06 Time 13:41 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mmclean Date 2005-10-04 Time 15:27 Rev Time 0.00
Received By mmclean Date 2005-10-04 Time 15:27 Sent To I
Notes
***NONE***