Plan Review Details - Permit 05091151
Plan Review Stops For Permit 05091151
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-11 Cont ID  
Sent By shill Date 2006-08-11 Time 10:32 Rev Time 0.00
Received By shill Date 2006-08-11 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-22 Cont ID  
Sent By shill Date 2006-06-22 Time 10:57 Rev Time 0.00
Received By shill Date 2006-06-22 Time 10:57 Sent To  
Notes
2006-06-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM FIRST REVIEW -
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
  
 THIS WAS ADDRESSED IN THE SECOND REVIEW.
 THIRD REVIEW, THE ANCHORING INFORMATION
 HAS BEEN VOIDED.PROVIDE A NEW DETAIL.
2006-06-18 00:00:00NEW SHEET/DETAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By shill Date 2006-01-23 Time 15:16 Rev Time 0.50
Received By shill Date 2006-01-23 Time 15:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-23 Cont ID  
Sent By shill Date 2005-11-23 Time 16:45 Rev Time 0.50
Received By shill Date 2005-11-23 Time 16:42 Sent To  
Notes
2005-11-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 17:43 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 16:51 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 19:01 Sent To  
Notes
2006-07-21 00:00:00**** UNSAT 5TH REVIEW ****
  
  
 1) NOTE: PLEASE SEE LOAD CALCUATIONS ARE
 STILL NOT BEING SUBMITTED.
 THE INFORMATION ON THE UPPER LEFT HAND
 CORNER OF PLANS ARE NOT SUFFICIENT.
 220, 215.5, 106.1.2 FBC ADMIN SECT
  
 2) NOTE: PLEASE SEE NO SPEC/MANUFACTURES
 CUT SHEETS WERE SUBMITTED FOR THE
 GENERATOR AND WP ENCLOSURE.
 FBC 106.1.2 90.7
  
 3) NOTE: PLEASE SEE POSSIBLE BLDG REVIEW
 NOTES AS THE ATTACHMENT OF THE GEN TO
 SLAB WAS NOT SPECIFIED?
  
 4) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES ARE REFLECTED, AT A MIN 2002
 NFPA-70,
  
 ** IMPORTANT**
  
 PLEASE SEE ZONING NOTE AS SCREENING
 WALLS ARE REQUIRED PER ZONING CODE.
 PLEASE KEEP IN MIND THE MIN CLEARENCES
 REQUIRED BY THE MANUFACTURE. PLEASE SEE
 THAT THE SPECS SHOULD INDICATE THE MIN
 CLEARENCES. LTRS OBTAINED BY THIS OFFICE
 FROM SOME MANUFACTURES REQUIRE A MIN OF
 3FT FOR LIQUID COOLED UNITS.
 THE BRAND IS NOT KNOWN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-18 Cont ID  
Sent By dpalmer Date 2006-06-18 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2006-06-18 Time 10:36 Sent To  
Notes
2006-06-18 00:00:00********* UNSAT 4TH REVIEW ********
  
  
 1) NOTE: PLEASE SEE ALL NOTES FROM ALL
 PREVIOUS REVIEWS AND ADDRESS COMMENTS.
 PLEASE SEE PLANS SHALL MEET NEC.
 ALL CODES FOR RISER, DISCONNECTING
 MEANS, GROUPED, DETACHED STRUCTURES,
 LOAD CALCULATIONS, SITE PLAN ETC WERE
 GIVEN IN THE PREVIOUS THREE REVIEWS.
 215.5
  
 2)NOTE: PLEASE SEE "SITE PLANS" ARE NOW
 BACK WITH PNECILED IN DETAILS ETC WHICH
 AS PREVIOUSLY MENTIONED IN PREVIOUS
 REVIEWS ARE "NOT" PERMITTED.
 ANY DRAWN DETAILS SHALL BE PHOTO-COPIED
 AND SUBMITTED.
  
 3) NOTE: PLEASE SEE THAT ALL
 PLANS/DESIGNS ETC SUBMITTED SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE DESIGN ETC.
 104.2.1 ADMIN SECT FBC.
  
 4) NOTE: AS REQUESTED ON ALL PREVIOUS
 REVIEWS, SUBMIT TWO COMPLETE SETS OF ALL
 PLANS, SPECS. MANUFACTURES CUT SHEETS.
 PLEASE SEE ONLY PARTIAL AND ONLY ONE SET
 OF SPECS ETC WERE SUBMITTED.
 PLEASE KNOW, ONCE ALL AARE OK, ONE SET
 OF THESE SPECS ARE STAMPED AND SHALL BE
 ON JOBSITE AND ONE SET IS STAMPED AND
 SHALL REMAIN PUBLIC RECORD.
 215.5,104
  
 5) NOTE: PLEASE SEE A NOTICE TO DESIGN
 PROFESSIONAL INCLUDING CONTRACTOR WAS
 GIVEN ON PREVIOUS NOTES WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE NOTE WAS FOR FS 553.80(2)(B)
 AND A 4X FEE FOR THE PLAN REVIEW PORTION
 OF THE PERMIT FEE HAS NOW BEEN ASSESSED.
 THE AMOUNT OF $1356 MUST BE PAID BEFORE
 PLANS ARE RESUBMITTED FOR THE FOLLOWING
 REVIEW.
 PLEASE ALSO KNOW, ONE SET OF THE PLANS
 SUBMITTED ARE NOW BEING RETAINED FOR
 FILE FOR REVIEW BY THE BUILDING OFFICAL/
 ASST BUILDING OFFICAL AS REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-27 Cont ID  
Sent By dpalmer Date 2006-04-27 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 20:20 Sent To  
Notes
2006-04-27 00:00:00********* UNSAT 3RD REVIEW **********
  
 PLEASE SEE NOTES FROM FIRST REVIEWAND
 2ND REVIEW WHICH STILL NEED TO BE
 ADDRESSED, ALONG WITH NEW COMMENTS DUE
 TO PLANS AND INFORMAITON SUBMITTED..
 PLEASE SEE THE LAST NEW COMMENT.
  
  
 1)NOTE: NOTE #1 OK, HOWEVER PLEASE SEE
 NEW COMMENTS.
  
 2)NOTE: NOTE #2 NO, STILL ONLY
 SUBMITTING ONE SET, NOTHING FOR THE
 GENERATOR AND NOTHING FOR NEW PROPOSEED
 PROPANE TANK. TANK.
  
 ** PREVIOUS NOTE **
 HOWEVER MUST SUBMIT TWO COPIES OF ALL.
 PLEASE SEE SPECS FOR FUEL TANK SHALL BE
 SUBMITTED TO VERIFY LISTING. PLEASE
 KNOW, IT WILL ALSO BE REQUIRED UNDER THE
 SEPARATE PERMIT AS NOTED BY OTHERS.
  
 3)NOTE: NOTE #3NO, PLEASE SEE NEW
 PLANS AND RISER IS NOW SUBMITTED, YET
 PLANS DO NOT SHOW THE LOCATION OF THE
 NEW ATS'S, NOR DOES IT INDICAT ANY
 DISCONNECTING MEANS FOR THE FEEDERS
 COMING FROM GEN.?
 PLEASE SEE 225.31-225.39,110.27.
  
 **PREVIOUS NOTE **
 RISER SUBMITTED, HOWEVER PLEASE SEE NOTE
 #1 AND PLEASE ALSO SEE MAINS WILL BE
 REQUIRED AT THE BLDG GROUPED IN CLOSE
 PROXIMITY OF EXISTING MAINS AND SHALL BE
 LABELD AS REQUIRED IN 702.8, 230.2 ETC.
 PLEASE KNOW, THE BRKRS LOCATED INSIDE
 THE GENERATOR WILL NOT BE ACCEPTED AS
 THE MEANS OF DISCONNECT FOR THESE
 FEEDERS COMING UP INTO BLDG.
 225.31-225.39
  
 4)NOTE: NOTE #4 NO, PLEASE SEE THE SAME
 LOAD CALCULATIONS WERE SUBMITTED WHICH
 ARE FOR RESIDENTIAL. PLEASE HAVE THE NEW
 ENGINEER OF RECORD SUPPLY.
  
 ** PREVIOUS NOTE **
 NO, THIS WAS NOT DONE.
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR COMMERCIAL OCCUPANCY,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 A/C LOADS ALREADY SHOWN.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 5)NOTE: NOTE #5 OK, HOWEVER SEE SLAB
 DETAIL COMMENT BELOW.
  
 **PREVIOUS NOTE **
 OK, NOT AN ELECTRICAL
 COMMENT. PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN AND SLAB DETAIL.
  
 6)NOTE: NOTE #6 OK, HOWEVER, SEE NEW
 PLAN NOTES.
  
 ** PREVIOUS NOTE **
 OK. MIANS INDICATED
 OUTSIDE.
  
 7)NOTE:NOTE #7 OK, CORRECTED TO PVC.
  
  
 8)NOTE: NOTE #8 NO, PLEASE THIS WAS NOT
 DONE, IN FACT PLEASE SEE ONLY ONE NEW
 COPYOF THE SURVEY/SITE PLANS WAS
 SUBMITTED, AND IT DID NOT CONTAIN THE
 ORIG REVIEW BY THE ZONING TECH.
 PLEASE ALSO SEE THE NEW SURVEY SHEET NOW
 DOES NOT CONTAINTHE GEN, ATS, SETBACK,
 LOCATIONS ETC OF THE PROPOSED WORK.??
  
 ** PREVIOUS NOTE **
 PLEASE SEE THE BELOW COMMENT FOR
 SURVEY WAS NOTED ON PREVIOUS REVIEW ,
 HOWEVER THIS WAS NOT ADDRESSED.
 ***************************************
 PLEASE BE SURE TO PROVIDE A 2ND COPY OF
 SURVEY WHICH IS NOT "PENCILED".
 ***************************************
  
 NEW NOTES.
  
 1)NOTE:OK.
  
 2)NOTE: OK, HOWEVER LEAVE THIS IS SETS
 WHEN RE-SUBMITTING.
  
 3)NOTE: NOTE #3 OK, NEW RECORDED NOC WAS
 SUBMITTED. PLEASE KNOW, THIS NOC IS ONLY
 VALID FOR 90 DAYS FROM RECORDING DATE,
 UNLESS WORK COMMENCES. PLEASE KNOW, IT
 WAS 2+ MONTHS BEFORE PLANS WERE
 RE-SUBMITTED. SINCE PLANS ARE COMING
 BACK ONCE MORE, PLEASE BE SURE TO
 RESUBMIT PLANS IN A TIMELY FASHION TO
 AVOID THE NOC BECOMING VOID.
  
  
 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE.
 PLEASE SEE NOTE BELOW.
  
 ** PREVIOUS NOTE **
 PLEASE SEE BLDG COMMENTS, ALL DETAILS
 SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF ALL PERSON RESPONESIBLE
 FOR SUCH PLANS/DESIGN.
 FBC ADMIN SECTION, 104.2.1
  
 ************************************
 NEW NOTE(S).
  
 1) NOTE: PLEASE SEE NEW PLANS SUBMITTED
 WHICH ARE PHOTO-COPIES OF PLANS WHICH
 ARE SIGNED, DATED AND SEALED BY AN
 ENGINEER. PLEASE KNOW, ALL COPIES
 SUBMITTED SHALL BE ORIGINAL WITH RAISED
 SEAL, WET SIGNATURE AND DATE. FAC
 61G15-23.002, FS 471.025
  
 2) NOTE: PLEASE SEE NEW PLAN SUBMITTED
 NOW APPEAR TO SHOW THE "GRAND BANK"
 DETACHED FROM THE MAIN BLGD?
 PLEASE CLARIFY THIS SHOWN ON PLANS.
 PLEASE VERIFY IF THIS IS INDEED THE
 CASE, PLEASE INDICATE THE DISCONNECTING
 MEANS REQUIRED OR IF THE EXISTING
 PANEL(NOT LABLED) AND EXIST A/C PANEL
 CONTAIN MCB'S.
 THIS NOTE IS ONLY BASED ON NEW PLANS
 SUBMITTED AS THE SURVEY/SITE PLANS DO
 NOT CORRELATE WITH THIS PLAN AND
 INDICATES ONLY ONE BLDG AND NOT BEING
 DETACHED.
 PLEASE VERIFY.
  
 3) NOTE: PLEASE KNOW, PER FS
 553.80(2)(B), WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW, IF PLANS COME BACK WITH OUT "ANY"
 OF THE SAME CODE COMPLIANT COMMENTS
 BEING ADDRESSED, A 4X FEE SHALL BE
 ACCESSED FOR THE PLAN REVIEW PORTION
 (30%X4) OF THE BASE PERMIT FEE.
 IT IS RECOMMENDED A MEETING BE HELD OR
 AT A MININUM A PHONE CONVERSTAION BE
 HELD TO GO OVER ANY QUESTIONS, OR
 COMMENTS.
  
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REIVEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-26 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 11:04 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 10:56 Sent To  
Notes
2006-01-20 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE NOTES FROM FIRST REVIEW WHICH
 STILL NEED TO BE ADDRESSED.
  
  
 1)NOTE: NOTE #1 NO, PLEASE SUBMIT PLANS
 DESIGNED,
 SIGNED DATED AND SEALED BY AN ENGINEER
 LICENSED UNDER THE STATE OF FLORIDA.
 471.003(H).
  
 2)NOTE: NOTE #2 OK, HOWEVER MUST SUBMIT
 TWO COPIES OF ALL.
 PLEASE SEE SPECS FOR FUEL TANK SHALL BE
 SUBMITTED TO VERIFY LISTING. PLEASE
 KNOW, IT WILL ALSO BE REQUIRED UNDER THE
 SEPARATE PERMIT AS NOTED BY OTHERS.
  
 3)NOTE: NOTE #3 RISER SUBMITTED, HOWEVER
 PLEASE SEE NOTE #1 AND PLEASE ALSO SEE
 MAINS WILL BE REQUIRED AT THE BLDG
 GROUPED IN CLOSE PROXIMITY OF EXISTING
 MAINS AND SHALL BE LABELD AS REQUIRED IN
 702.8, 230.2 ETC.
 PLEASE KNOW, THE BRKRS LOCATED INSIDE
 THE GENERATOR WILL NOT BE ACCEPTED AS
 THE MEANS OF DISCONNECT FOR THESE
 FEEDERS COMING UP INTO BLDG.
 225.31-225.39
  
 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE.
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR COMMERCIAL OCCUPANCY,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 A/C LOADS ALREADY SHOWN.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 5)NOTE: NOTE #5 OK, NOT AN ELECTRICAL
 COMMENT. PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN AND SLAB DETAIL.
  
 6)NOTE: NOTE #6 OK. MIANS INDICATED
 OUTSIDE.
  
 7)NOTE:NOTE #7 OK, CORRECTED TO PVC.
  
  
 8)NOTE: PLEASE SEE THE BELOW COMMENT FOR
 SURVEY WAS NOTED ON PREVIOUS REVIEW ,
 HOWEVER THIS WAS NOT ADDRESSED.
 ***************************************
 PLEASE BE SURE TO PROVIDE A 2ND COPY OF
 SURVEY WHICH IS NOT "PENCILED".
 ***************************************
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE MAINS FOR THESE TWO
 PANELS ARE NOTED AS BEING LOCATED IN
 EXISTING 600A METER BANK, HOWEVER THE
 OCP IS NOT INDICATED.
  
 2)NOTE: PLEASE PROVIDE A COPY OF THE
 SIGNED WRITTEN PROPOSAL FOR PROPOSED
 WORK. PLEASE KNOW, VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SUPLIED. THIS WOULD
 INCLUDE GEN/ ATS ETC.
 PLEASE SEE MATERIALS LIST HAS VALUE
 CROSSED OUT FOR EQUIPMENT?
 FBC ADMINISTRATIVE SECTION104.6.5
  
 3)NOTE: PLEASESEE THE NOC SUBMITTED HAS
 SINCE EXPIRED AND WILL NEED TO BE
 RE-RECORDED.
 PLEASE SEE FS 713.13(2), IF WORK HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING
 NOC, SUCH NOC SHALL BECOME VOID.
  
 4)NOTE: PLEASE SEE BLDG COMMENTS, ALL
 DETAILS SHALL CONTAIN THE PRINTED NAME
 AND SIGNATURE OF ALL PERSON RESPONESIBLE
 FOR SUCH PLANS/DESIGN.
 FBC ADMIN SECTION, 104.2.1
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REIVEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By dpalmer Date 2005-11-16 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2005-11-16 Time 12:07 Sent To  
Notes
2005-11-16 00:00:00******** UNSAT *********
  
 1)NOTE: PLEASE SUBMIT PLANS DESIGNED,
 SIGNED DATED AND SEALED BY AN ENGINEER
 LICENSED UNDER THE STATE OF FLORIDA.
 471.003(H).
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GENERATOR, ATS
 SWITCHES, AND PROPANE TANK,(REVIEWED BY
 OTHERS).
 GEN, ATS TO BE REVIEWED BY FIRE ,
 ELECTRICA ETC.
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRMA ON
 ALL EXISTING AND NEW EELCTRICAL WHICH
 WILL INCLUDE ANY EXISTING MAINS AND
 LOCATIONS.
 PLEASE SEE RISER SHOWS PANELS AS MLO?
 PLEASE CLARIFY WHERE MAINS ARE?
 PLEASE VERIFY GROUPING OF MAINS AND
 DISCONNECTING MEANS REQUIRED FOR
 GENERATOR.
 PLEASE SEE 230.72,230.76.230.79,
 225.31-225.39.
  
 4)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR COMMERCIAL OCCUPANCY,
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125%.
 A/C LOADS ALREADY SHOWN.
 220.3,220.10,220.11,220.13,215.3,230.42
 ETC
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN AND SLAB DETAIL.
  
 6)NOTE: PLEASE SEE 250.6,250.24,
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 7)NOTE: PLEASE SEE "EMT" IS INDICATED AS
 DIRECT BURIED , PLEASE SEE USES
 PERMITTED, AS EMT MAY NOT BE USED.358.12
  
 ***************************************
 PLEASE BE SURE TO PROVIDE A 2ND COPY OF
 SURVEY WHICH IS NOT "PENCILED".
 ***************************************
  
  
 PLEASE SEE POSSIBLE NOTES FROM OTHER
 REIVEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2006-08-11 Cont ID  
Sent By mwennerg Date 2006-08-11 Time 15:19 Rev Time 0.00
Received By mwennerg Date 2006-08-11 Time 15:19 Sent To  
Notes
2006-08-11 00:00:00***PROVISO***
  
 1) PLANS STILL DON'T ILLUSTRATE WHAT
 PROTECTION SAFEGUARDS ARE IN PLACE FOR
 PROPANE TANK. PLEASE REFER TO FIRST FIRE
 REVIEW COMMENT (6).
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2006-06-19 Cont ID  
Sent By mcarsill Date 2006-06-19 Time 11:33 Rev Time 0.00
Received By mcarsill Date 2006-06-19 Time 11:31 Sent To  
Notes
2006-06-19 00:00:001. NO CHANGES TO THE PLANS. SAME PLANS
 THAT LACK SUFFICIENT DETAILS AND ARE
 STILL CONFUSING. FOURTH FIRE PLAN REVIEW
 PERFORMED FOR THIS PROJECT.
  
 FAILED DUE TO CAUSE AS PREVIOUSLY
 STATED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-05-23 Cont ID  
Sent By mwennerg Date 2006-05-23 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2006-05-23 Time 10:36 Sent To  
Notes
2006-05-23 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT THE PLANS DO NOT
 APPEAR TO HAVE BEEN UPDATED TO REFLECT
 INFORMATION REQUESTED IN LAST FIRE
 REVIEW.
  
 2) PLEASE REFER TO ELECTRICAL NOTE
 REQUIRING MINIMUM OF (2) COPIES OF
 COMPLETE SUBMITTAL. (PLANS, SPEC SHEETS,
 MANUALS, ETC).
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By mcarsill Date 2006-01-20 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2006-01-20 Time 14:08 Sent To  
Notes
2006-01-20 00:00:001. THE INFORMATION PROVIDED ON
 SEVERAL SHEETS OF PAPER NEEDS TO BE
 PLACED ON A PLAN TO FULLY ILLUSTRATE
 THE PROPOSED WORK. THE ORGINAL
 SUBMISSION APPEARED TO BE INACCURATE
 AND CONFUSING. SOME OF THE INFORMATION
 ON THE NEW SUBMITTAL NEEDS TO BE PLACED
 ON A PLAN WITH THE OTHER INFOMATION.
 PLEASE CORRECT THE PLANS AS NECESSARY.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By mcarsill Date 2005-11-10 Time 09:19 Rev Time 0.00
Received By mcarsill Date 2005-11-10 Time 09:10 Sent To  
Notes
2005-11-10 00:00:001. ALL ELECTRICAL INSTALLATIONS TO
 COMPLY WITH THE NATIONAL ELECTRICAL
 CODE, NFPA 70.
  
 2. WHAT DEVICES OR EQUIPMENT IN THE
 NEW GENERATOR SUPPLYING POWER TO.
  
 3. ARE THERE ANY DOORS, OR WINDOW
 OPENINGS LOCATED NEAR THE PROPOSED
 GENERATOR LOCATION.
  
 4. PAPERWORK DISPLAYS AN UNDERGROUND
 GAS LIBE BUT DOES NOT INDICATE SIZE OR
 ANY VALVES.
  
 5. DRAWING INDICATES ABOVE GROUND
 PROPANE TANK BUT THE DRAWINGS INDICATES
 A BURIED PROPANE TANK. WHICH IS IT.
  
 6. A 10,000 GALLON PROPANE TANK ABOVE
 GROUND WILL NOT BE ALLOWED TO BE
 INSTALLED. ALSO NO INFORMATION PROVIDED
 WITH REGARDS TO SAFETY, SECURITY, OR
 MECHANICAL PROTECTION PLANNED FOR ANY
 TYPE OF PROPANE TANK.
  
 7. NO CUT SHEETS PROVIDED FOR GENERATOR.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-11-26 Cont ID  
Sent By kstevens Date 2005-11-26 Time 14:50 Rev Time 0.50
Received By kstevens Date 2005-11-26 Time 14:47 Sent To  
Notes
2005-11-26 00:00:00GAS PERMIT APPLIED FOR (05091466)

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 10:20 Sent To E
Notes
2006-08-14 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 13:36 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 13:36 Sent To  
Notes
2006-07-19 00:00:00TO "COMM" BD#47
2006-07-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-30 Cont ID  
Sent By adarroug Date 2006-05-30 Time 16:09 Rev Time 0.00
Received By adarroug Date 2006-05-30 Time 16:09 Sent To  
Notes
2006-06-16 00:00:00TO "COMM" BD#28
2006-05-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 16:40 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 16:40 Sent To  
Notes
2006-04-19 00:00:00TO "COMM" BD#27
2006-04-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 16:06 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 16:06 Sent To  
Notes
2006-01-19 00:00:00TO "COMM" BD#52
2005-12-20 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 08:24 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 08:24 Sent To  
Notes
2005-09-30 00:00:00TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 17:46 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 17:45 Sent To Z
Notes
2005-09-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-03 Cont ID  
Sent By rregueir Date 2005-12-03 Time 12:18 Rev Time 0.00
Received By rregueir Date 2005-12-03 Time 12:15 Sent To  
Notes
2005-12-03 00:00:00INSTALLATION OF UNDERGROUND PROPANE TANK
 AND RELATED FUEL LINES TO BE REVIEWED
 UNDER GAS PERMIT (APPLIED FOR
 SEPERATELY)

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-11-26 Cont ID  
Sent By kstevens Date 2005-11-26 Time 14:47 Rev Time 0.00
Received By kstevens Date 2005-11-26 Time 14:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-19 Cont ID  
Sent By mmclean Date 2006-07-19 Time 18:19 Rev Time 0.00
Received By mmclean Date 2006-07-19 Time 18:19 Sent To  
Notes
2006-07-20 00:00:00THE PROPOSED GENERATOR MUST BE SCREENED,
 SEC 94-444(B) - SCREENING SHALL BE
 CONSTRUCTED OF BRICK DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY AND
 WALLS SHALL BE LANDSCAPE WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-06-26 Cont ID  
Sent By mmclean Date 2006-06-26 Time 10:56 Rev Time 0.00
Received By mmclean Date 2006-06-26 Time 10:56 Sent To  
Notes
2006-06-26 00:00:00DENIED,
 1. PLEASE SUBMIT TWO COPY OF SURVEY
 SHOWING THE LOCATION OF THE PROPOSED
 GENERATOR. (2ND REQUEST) ONLY 1 COPY WAS
 SUBMITTED.
 2. INFORMATION SUBMITTED CANNOT BE SHOWN
 IN PENCIL, BUT IN CLARITY AS WRITTEN IN
 THE CITY OF WEST PALM AMENDMENTS TO THE
 FLORIDA BUIDLING CODE, CHAPTER 1,
 ADMINISTRATION 106.1.3 (QUALITY OF
 BUILDING PLANS).
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-05-24 Cont ID  
Sent By mmclean Date 2006-05-24 Time 11:41 Rev Time 0.00
Received By mmclean Date 2006-05-24 Time 11:41 Sent To  
Notes
2006-05-24 00:00:00DENIED,
 1. THE PROPOSED GENERATOR IS NOT SHOWN
 ON THE SITEPLAN PROVIDED.
 2. PLEASE SHOW THE LOCATON OF THE
 GENERATOR ON TWO COPY OF SITEPLAN WITH
 SETBACKS FROM PROPERTY LINE.
 3. ONLY 1 SET OF SITEPLAN WAS SUBMITTED.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-29 Cont ID  
Sent By mmclean Date 2005-09-29 Time 16:44 Rev Time 0.00
Received By mmclean Date 2005-09-29 Time 16:44 Sent To I
Notes
2005-09-29 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.