| Plan Review Stops For Permit 05091151 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-08-11 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-08-11 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-22 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-22 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2006-06-22 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | FROM FIRST REVIEW - | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | | | | THIS WAS ADDRESSED IN THE SECOND REVIEW. | | | THIRD REVIEW, THE ANCHORING INFORMATION | | | HAS BEEN VOIDED.PROVIDE A NEW DETAIL. | | 2006-06-18 00:00:00 | NEW SHEET/DETAIL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-01-23 |
Time |
15:16 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2006-01-23 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-23 |
Time |
16:45 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2005-11-23 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2005-11-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-14 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-14 |
Time |
16:51 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-21 |
Time |
19:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-21 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | **** UNSAT 5TH REVIEW **** | | | | | | | | | 1) NOTE: PLEASE SEE LOAD CALCUATIONS ARE | | | STILL NOT BEING SUBMITTED. | | | THE INFORMATION ON THE UPPER LEFT HAND | | | CORNER OF PLANS ARE NOT SUFFICIENT. | | | 220, 215.5, 106.1.2 FBC ADMIN SECT | | | | | | 2) NOTE: PLEASE SEE NO SPEC/MANUFACTURES | | | CUT SHEETS WERE SUBMITTED FOR THE | | | GENERATOR AND WP ENCLOSURE. | | | FBC 106.1.2 90.7 | | | | | | 3) NOTE: PLEASE SEE POSSIBLE BLDG REVIEW | | | NOTES AS THE ATTACHMENT OF THE GEN TO | | | SLAB WAS NOT SPECIFIED? | | | | | | 4) NOTE: PLEASE SEE THAT THE FOLLOWING | | | CODES ARE REFLECTED, AT A MIN 2002 | | | NFPA-70, | | | | | | ** IMPORTANT** | | | | | | PLEASE SEE ZONING NOTE AS SCREENING | | | WALLS ARE REQUIRED PER ZONING CODE. | | | PLEASE KEEP IN MIND THE MIN CLEARENCES | | | REQUIRED BY THE MANUFACTURE. PLEASE SEE | | | THAT THE SPECS SHOULD INDICATE THE MIN | | | CLEARENCES. LTRS OBTAINED BY THIS OFFICE | | | FROM SOME MANUFACTURES REQUIRE A MIN OF | | | 3FT FOR LIQUID COOLED UNITS. | | | THE BRAND IS NOT KNOWN AT THIS TIME. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-18 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-18 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2006-06-18 00:00:00 | ********* UNSAT 4TH REVIEW ******** | | | | | | | | | 1) NOTE: PLEASE SEE ALL NOTES FROM ALL | | | PREVIOUS REVIEWS AND ADDRESS COMMENTS. | | | PLEASE SEE PLANS SHALL MEET NEC. | | | ALL CODES FOR RISER, DISCONNECTING | | | MEANS, GROUPED, DETACHED STRUCTURES, | | | LOAD CALCULATIONS, SITE PLAN ETC WERE | | | GIVEN IN THE PREVIOUS THREE REVIEWS. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE "SITE PLANS" ARE NOW | | | BACK WITH PNECILED IN DETAILS ETC WHICH | | | AS PREVIOUSLY MENTIONED IN PREVIOUS | | | REVIEWS ARE "NOT" PERMITTED. | | | ANY DRAWN DETAILS SHALL BE PHOTO-COPIED | | | AND SUBMITTED. | | | | | | 3) NOTE: PLEASE SEE THAT ALL | | | PLANS/DESIGNS ETC SUBMITTED SHALL | | | CONTAIN THE PRINTED NAME AND SIGNATURE | | | OF THE DESIGN ETC. | | | 104.2.1 ADMIN SECT FBC. | | | | | | 4) NOTE: AS REQUESTED ON ALL PREVIOUS | | | REVIEWS, SUBMIT TWO COMPLETE SETS OF ALL | | | PLANS, SPECS. MANUFACTURES CUT SHEETS. | | | PLEASE SEE ONLY PARTIAL AND ONLY ONE SET | | | OF SPECS ETC WERE SUBMITTED. | | | PLEASE KNOW, ONCE ALL AARE OK, ONE SET | | | OF THESE SPECS ARE STAMPED AND SHALL BE | | | ON JOBSITE AND ONE SET IS STAMPED AND | | | SHALL REMAIN PUBLIC RECORD. | | | 215.5,104 | | | | | | 5) NOTE: PLEASE SEE A NOTICE TO DESIGN | | | PROFESSIONAL INCLUDING CONTRACTOR WAS | | | GIVEN ON PREVIOUS NOTES WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. | | | PLEASE SEE NOTE WAS FOR FS 553.80(2)(B) | | | AND A 4X FEE FOR THE PLAN REVIEW PORTION | | | OF THE PERMIT FEE HAS NOW BEEN ASSESSED. | | | THE AMOUNT OF $1356 MUST BE PAID BEFORE | | | PLANS ARE RESUBMITTED FOR THE FOLLOWING | | | REVIEW. | | | PLEASE ALSO KNOW, ONE SET OF THE PLANS | | | SUBMITTED ARE NOW BEING RETAINED FOR | | | FILE FOR REVIEW BY THE BUILDING OFFICAL/ | | | ASST BUILDING OFFICAL AS REQUIRED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-04-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-27 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-26 |
Time |
20:20 |
Sent To |
|
|
| Notes |
| 2006-04-27 00:00:00 | ********* UNSAT 3RD REVIEW ********** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEWAND | | | 2ND REVIEW WHICH STILL NEED TO BE | | | ADDRESSED, ALONG WITH NEW COMMENTS DUE | | | TO PLANS AND INFORMAITON SUBMITTED.. | | | PLEASE SEE THE LAST NEW COMMENT. | | | | | | | | | 1)NOTE: NOTE #1 OK, HOWEVER PLEASE SEE | | | NEW COMMENTS. | | | | | | 2)NOTE: NOTE #2 NO, STILL ONLY | | | SUBMITTING ONE SET, NOTHING FOR THE | | | GENERATOR AND NOTHING FOR NEW PROPOSEED | | | PROPANE TANK. TANK. | | | | | | ** PREVIOUS NOTE ** | | | HOWEVER MUST SUBMIT TWO COPIES OF ALL. | | | PLEASE SEE SPECS FOR FUEL TANK SHALL BE | | | SUBMITTED TO VERIFY LISTING. PLEASE | | | KNOW, IT WILL ALSO BE REQUIRED UNDER THE | | | SEPARATE PERMIT AS NOTED BY OTHERS. | | | | | | 3)NOTE: NOTE #3NO, PLEASE SEE NEW | | | PLANS AND RISER IS NOW SUBMITTED, YET | | | PLANS DO NOT SHOW THE LOCATION OF THE | | | NEW ATS'S, NOR DOES IT INDICAT ANY | | | DISCONNECTING MEANS FOR THE FEEDERS | | | COMING FROM GEN.? | | | PLEASE SEE 225.31-225.39,110.27. | | | | | | **PREVIOUS NOTE ** | | | RISER SUBMITTED, HOWEVER PLEASE SEE NOTE | | | #1 AND PLEASE ALSO SEE MAINS WILL BE | | | REQUIRED AT THE BLDG GROUPED IN CLOSE | | | PROXIMITY OF EXISTING MAINS AND SHALL BE | | | LABELD AS REQUIRED IN 702.8, 230.2 ETC. | | | PLEASE KNOW, THE BRKRS LOCATED INSIDE | | | THE GENERATOR WILL NOT BE ACCEPTED AS | | | THE MEANS OF DISCONNECT FOR THESE | | | FEEDERS COMING UP INTO BLDG. | | | 225.31-225.39 | | | | | | 4)NOTE: NOTE #4 NO, PLEASE SEE THE SAME | | | LOAD CALCULATIONS WERE SUBMITTED WHICH | | | ARE FOR RESIDENTIAL. PLEASE HAVE THE NEW | | | ENGINEER OF RECORD SUPPLY. | | | | | | ** PREVIOUS NOTE ** | | | NO, THIS WAS NOT DONE. | | | PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR COMMERCIAL OCCUPANCY, | | | PLEASE INCLUDE ALL CONTINUOUS LOADS AT | | | 125%. | | | A/C LOADS ALREADY SHOWN. | | | 220.3,220.10,220.11,220.13,215.3,230.42 | | | ETC | | | | | | 5)NOTE: NOTE #5 OK, HOWEVER SEE SLAB | | | DETAIL COMMENT BELOW. | | | | | | **PREVIOUS NOTE ** | | | OK, NOT AN ELECTRICAL | | | COMMENT. PLEASE SEE BLDG REVIEW COMMENTS | | | FOR TIE DOWN AND SLAB DETAIL. | | | | | | 6)NOTE: NOTE #6 OK, HOWEVER, SEE NEW | | | PLAN NOTES. | | | | | | ** PREVIOUS NOTE ** | | | OK. MIANS INDICATED | | | OUTSIDE. | | | | | | 7)NOTE:NOTE #7 OK, CORRECTED TO PVC. | | | | | | | | | 8)NOTE: NOTE #8 NO, PLEASE THIS WAS NOT | | | DONE, IN FACT PLEASE SEE ONLY ONE NEW | | | COPYOF THE SURVEY/SITE PLANS WAS | | | SUBMITTED, AND IT DID NOT CONTAIN THE | | | ORIG REVIEW BY THE ZONING TECH. | | | PLEASE ALSO SEE THE NEW SURVEY SHEET NOW | | | DOES NOT CONTAINTHE GEN, ATS, SETBACK, | | | LOCATIONS ETC OF THE PROPOSED WORK.?? | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE THE BELOW COMMENT FOR | | | SURVEY WAS NOTED ON PREVIOUS REVIEW , | | | HOWEVER THIS WAS NOT ADDRESSED. | | | *************************************** | | | PLEASE BE SURE TO PROVIDE A 2ND COPY OF | | | SURVEY WHICH IS NOT "PENCILED". | | | *************************************** | | | | | | NEW NOTES. | | | | | | 1)NOTE:OK. | | | | | | 2)NOTE: OK, HOWEVER LEAVE THIS IS SETS | | | WHEN RE-SUBMITTING. | | | | | | 3)NOTE: NOTE #3 OK, NEW RECORDED NOC WAS | | | SUBMITTED. PLEASE KNOW, THIS NOC IS ONLY | | | VALID FOR 90 DAYS FROM RECORDING DATE, | | | UNLESS WORK COMMENCES. PLEASE KNOW, IT | | | WAS 2+ MONTHS BEFORE PLANS WERE | | | RE-SUBMITTED. SINCE PLANS ARE COMING | | | BACK ONCE MORE, PLEASE BE SURE TO | | | RESUBMIT PLANS IN A TIMELY FASHION TO | | | AVOID THE NOC BECOMING VOID. | | | | | | | | | 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE. | | | PLEASE SEE NOTE BELOW. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE SEE BLDG COMMENTS, ALL DETAILS | | | SHALL CONTAIN THE PRINTED NAME AND | | | SIGNATURE OF ALL PERSON RESPONESIBLE | | | FOR SUCH PLANS/DESIGN. | | | FBC ADMIN SECTION, 104.2.1 | | | | | | ************************************ | | | NEW NOTE(S). | | | | | | 1) NOTE: PLEASE SEE NEW PLANS SUBMITTED | | | WHICH ARE PHOTO-COPIES OF PLANS WHICH | | | ARE SIGNED, DATED AND SEALED BY AN | | | ENGINEER. PLEASE KNOW, ALL COPIES | | | SUBMITTED SHALL BE ORIGINAL WITH RAISED | | | SEAL, WET SIGNATURE AND DATE. FAC | | | 61G15-23.002, FS 471.025 | | | | | | 2) NOTE: PLEASE SEE NEW PLAN SUBMITTED | | | NOW APPEAR TO SHOW THE "GRAND BANK" | | | DETACHED FROM THE MAIN BLGD? | | | PLEASE CLARIFY THIS SHOWN ON PLANS. | | | PLEASE VERIFY IF THIS IS INDEED THE | | | CASE, PLEASE INDICATE THE DISCONNECTING | | | MEANS REQUIRED OR IF THE EXISTING | | | PANEL(NOT LABLED) AND EXIST A/C PANEL | | | CONTAIN MCB'S. | | | THIS NOTE IS ONLY BASED ON NEW PLANS | | | SUBMITTED AS THE SURVEY/SITE PLANS DO | | | NOT CORRELATE WITH THIS PLAN AND | | | INDICATES ONLY ONE BLDG AND NOT BEING | | | DETACHED. | | | PLEASE VERIFY. | | | | | | 3) NOTE: PLEASE KNOW, PER FS | | | 553.80(2)(B), WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE. PLEASE | | | KNOW, IF PLANS COME BACK WITH OUT "ANY" | | | OF THE SAME CODE COMPLIANT COMMENTS | | | BEING ADDRESSED, A 4X FEE SHALL BE | | | ACCESSED FOR THE PLAN REVIEW PORTION | | | (30%X4) OF THE BASE PERMIT FEE. | | | IT IS RECOMMENDED A MEETING BE HELD OR | | | AT A MININUM A PHONE CONVERSTAION BE | | | HELD TO GO OVER ANY QUESTIONS, OR | | | COMMENTS. | | | | | | | | | PLEASE SEE POSSIBLE NOTES FROM OTHER | | | REIVEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-04-26 00:00:00 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-20 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-20 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | ********* UNSAT 2ND REVIEW ********** | | | | | | PLEASE SEE NOTES FROM FIRST REVIEW WHICH | | | STILL NEED TO BE ADDRESSED. | | | | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SUBMIT PLANS | | | DESIGNED, | | | SIGNED DATED AND SEALED BY AN ENGINEER | | | LICENSED UNDER THE STATE OF FLORIDA. | | | 471.003(H). | | | | | | 2)NOTE: NOTE #2 OK, HOWEVER MUST SUBMIT | | | TWO COPIES OF ALL. | | | PLEASE SEE SPECS FOR FUEL TANK SHALL BE | | | SUBMITTED TO VERIFY LISTING. PLEASE | | | KNOW, IT WILL ALSO BE REQUIRED UNDER THE | | | SEPARATE PERMIT AS NOTED BY OTHERS. | | | | | | 3)NOTE: NOTE #3 RISER SUBMITTED, HOWEVER | | | PLEASE SEE NOTE #1 AND PLEASE ALSO SEE | | | MAINS WILL BE REQUIRED AT THE BLDG | | | GROUPED IN CLOSE PROXIMITY OF EXISTING | | | MAINS AND SHALL BE LABELD AS REQUIRED IN | | | 702.8, 230.2 ETC. | | | PLEASE KNOW, THE BRKRS LOCATED INSIDE | | | THE GENERATOR WILL NOT BE ACCEPTED AS | | | THE MEANS OF DISCONNECT FOR THESE | | | FEEDERS COMING UP INTO BLDG. | | | 225.31-225.39 | | | | | | 4)NOTE: NOTE #4 NO, THIS WAS NOT DONE. | | | PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR COMMERCIAL OCCUPANCY, | | | PLEASE INCLUDE ALL CONTINUOUS LOADS AT | | | 125%. | | | A/C LOADS ALREADY SHOWN. | | | 220.3,220.10,220.11,220.13,215.3,230.42 | | | ETC | | | | | | 5)NOTE: NOTE #5 OK, NOT AN ELECTRICAL | | | COMMENT. PLEASE SEE BLDG REVIEW COMMENTS | | | FOR TIE DOWN AND SLAB DETAIL. | | | | | | 6)NOTE: NOTE #6 OK. MIANS INDICATED | | | OUTSIDE. | | | | | | 7)NOTE:NOTE #7 OK, CORRECTED TO PVC. | | | | | | | | | 8)NOTE: PLEASE SEE THE BELOW COMMENT FOR | | | SURVEY WAS NOTED ON PREVIOUS REVIEW , | | | HOWEVER THIS WAS NOT ADDRESSED. | | | *************************************** | | | PLEASE BE SURE TO PROVIDE A 2ND COPY OF | | | SURVEY WHICH IS NOT "PENCILED". | | | *************************************** | | | | | | NEW NOTES. | | | | | | 1)NOTE: PLEASE SEE MAINS FOR THESE TWO | | | PANELS ARE NOTED AS BEING LOCATED IN | | | EXISTING 600A METER BANK, HOWEVER THE | | | OCP IS NOT INDICATED. | | | | | | 2)NOTE: PLEASE PROVIDE A COPY OF THE | | | SIGNED WRITTEN PROPOSAL FOR PROPOSED | | | WORK. PLEASE KNOW, VALUE SHALL INCLUDE | | | ALL LABOR AND MATERIALS EVEN IF ANY | | | EQUIPMENT IS OWNER SUPLIED. THIS WOULD | | | INCLUDE GEN/ ATS ETC. | | | PLEASE SEE MATERIALS LIST HAS VALUE | | | CROSSED OUT FOR EQUIPMENT? | | | FBC ADMINISTRATIVE SECTION104.6.5 | | | | | | 3)NOTE: PLEASESEE THE NOC SUBMITTED HAS | | | SINCE EXPIRED AND WILL NEED TO BE | | | RE-RECORDED. | | | PLEASE SEE FS 713.13(2), IF WORK HAS NOT | | | COMMENCED WITHIN 90 DAYS OF RECORDING | | | NOC, SUCH NOC SHALL BECOME VOID. | | | | | | 4)NOTE: PLEASE SEE BLDG COMMENTS, ALL | | | DETAILS SHALL CONTAIN THE PRINTED NAME | | | AND SIGNATURE OF ALL PERSON RESPONESIBLE | | | FOR SUCH PLANS/DESIGN. | | | FBC ADMIN SECTION, 104.2.1 | | | | | | PLEASE SEE POSSIBLE NOTES FROM OTHER | | | REIVEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-16 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-11-16 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | ******** UNSAT ********* | | | | | | 1)NOTE: PLEASE SUBMIT PLANS DESIGNED, | | | SIGNED DATED AND SEALED BY AN ENGINEER | | | LICENSED UNDER THE STATE OF FLORIDA. | | | 471.003(H). | | | | | | 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES | | | CUT/SPEC SHEETS FOR GENERATOR, ATS | | | SWITCHES, AND PROPANE TANK,(REVIEWED BY | | | OTHERS). | | | GEN, ATS TO BE REVIEWED BY FIRE , | | | ELECTRICA ETC. | | | | | | 3)NOTE: PLEASE SUBMIT A RISER DIAGRMA ON | | | ALL EXISTING AND NEW EELCTRICAL WHICH | | | WILL INCLUDE ANY EXISTING MAINS AND | | | LOCATIONS. | | | PLEASE SEE RISER SHOWS PANELS AS MLO? | | | PLEASE CLARIFY WHERE MAINS ARE? | | | PLEASE VERIFY GROUPING OF MAINS AND | | | DISCONNECTING MEANS REQUIRED FOR | | | GENERATOR. | | | PLEASE SEE 230.72,230.76.230.79, | | | 225.31-225.39. | | | | | | 4)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR COMMERCIAL OCCUPANCY, | | | PLEASE INCLUDE ALL CONTINUOUS LOADS AT | | | 125%. | | | A/C LOADS ALREADY SHOWN. | | | 220.3,220.10,220.11,220.13,215.3,230.42 | | | ETC | | | | | | 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | FOR TIE DOWN AND SLAB DETAIL. | | | | | | 6)NOTE: PLEASE SEE 250.6,250.24, | | | "EQUIPMENT GROUNDING CONDUCTORS" ARE | | | ONLY INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | | | | 7)NOTE: PLEASE SEE "EMT" IS INDICATED AS | | | DIRECT BURIED , PLEASE SEE USES | | | PERMITTED, AS EMT MAY NOT BE USED.358.12 | | | | | | *************************************** | | | PLEASE BE SURE TO PROVIDE A 2ND COPY OF | | | SURVEY WHICH IS NOT "PENCILED". | | | *************************************** | | | | | | | | | PLEASE SEE POSSIBLE NOTES FROM OTHER | | | REIVEWERS WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-11 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-11 |
Time |
15:19 |
Sent To |
|
|
| Notes |
| 2006-08-11 00:00:00 | ***PROVISO*** | | | | | | 1) PLANS STILL DON'T ILLUSTRATE WHAT | | | PROTECTION SAFEGUARDS ARE IN PLACE FOR | | | PROPANE TANK. PLEASE REFER TO FIRST FIRE | | | REVIEW COMMENT (6). | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2006-06-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-06-19 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-06-19 |
Time |
11:31 |
Sent To |
|
|
| Notes |
| 2006-06-19 00:00:00 | 1. NO CHANGES TO THE PLANS. SAME PLANS | | | THAT LACK SUFFICIENT DETAILS AND ARE | | | STILL CONFUSING. FOURTH FIRE PLAN REVIEW | | | PERFORMED FOR THIS PROJECT. | | | | | | FAILED DUE TO CAUSE AS PREVIOUSLY | | | STATED. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2006-05-23 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-23 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-23 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2006-05-23 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE NOTE THAT THE PLANS DO NOT | | | APPEAR TO HAVE BEEN UPDATED TO REFLECT | | | INFORMATION REQUESTED IN LAST FIRE | | | REVIEW. | | | | | | 2) PLEASE REFER TO ELECTRICAL NOTE | | | REQUIRING MINIMUM OF (2) COPIES OF | | | COMPLETE SUBMITTAL. (PLANS, SPEC SHEETS, | | | MANUALS, ETC). | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-01-20 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-01-20 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | 1. THE INFORMATION PROVIDED ON | | | SEVERAL SHEETS OF PAPER NEEDS TO BE | | | PLACED ON A PLAN TO FULLY ILLUSTRATE | | | THE PROPOSED WORK. THE ORGINAL | | | SUBMISSION APPEARED TO BE INACCURATE | | | AND CONFUSING. SOME OF THE INFORMATION | | | ON THE NEW SUBMITTAL NEEDS TO BE PLACED | | | ON A PLAN WITH THE OTHER INFOMATION. | | | PLEASE CORRECT THE PLANS AS NECESSARY. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-11-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2005-11-10 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2005-11-10 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2005-11-10 00:00:00 | 1. ALL ELECTRICAL INSTALLATIONS TO | | | COMPLY WITH THE NATIONAL ELECTRICAL | | | CODE, NFPA 70. | | | | | | 2. WHAT DEVICES OR EQUIPMENT IN THE | | | NEW GENERATOR SUPPLYING POWER TO. | | | | | | 3. ARE THERE ANY DOORS, OR WINDOW | | | OPENINGS LOCATED NEAR THE PROPOSED | | | GENERATOR LOCATION. | | | | | | 4. PAPERWORK DISPLAYS AN UNDERGROUND | | | GAS LIBE BUT DOES NOT INDICATE SIZE OR | | | ANY VALVES. | | | | | | 5. DRAWING INDICATES ABOVE GROUND | | | PROPANE TANK BUT THE DRAWINGS INDICATES | | | A BURIED PROPANE TANK. WHICH IS IT. | | | | | | 6. A 10,000 GALLON PROPANE TANK ABOVE | | | GROUND WILL NOT BE ALLOWED TO BE | | | INSTALLED. ALSO NO INFORMATION PROVIDED | | | WITH REGARDS TO SAFETY, SECURITY, OR | | | MECHANICAL PROTECTION PLANNED FOR ANY | | | TYPE OF PROPANE TANK. | | | | | | 7. NO CUT SHEETS PROVIDED FOR GENERATOR. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2005-11-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-11-26 |
Time |
14:50 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2005-11-26 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2005-11-26 00:00:00 | GAS PERMIT APPLIED FOR (05091466) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-14 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-14 |
Time |
10:20 |
Sent To |
E |
|
| Notes |
| 2006-08-14 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-05 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-05 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2006-07-19 00:00:00 | TO "COMM" BD#47 | | 2006-07-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-05-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-30 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-30 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2006-06-16 00:00:00 | TO "COMM" BD#28 | | 2006-05-30 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-05 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-05 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2006-04-19 00:00:00 | TO "COMM" BD#27 | | 2006-04-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-12-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-20 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-20 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2006-01-19 00:00:00 | TO "COMM" BD#52 | | 2005-12-20 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-30 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-30 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2005-09-30 00:00:00 | TO "COMM" BD#36 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-23 |
Time |
17:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-23 |
Time |
17:45 |
Sent To |
Z |
|
| Notes |
| 2005-09-23 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-12-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-12-03 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-12-03 |
Time |
12:15 |
Sent To |
|
|
| Notes |
| 2005-12-03 00:00:00 | INSTALLATION OF UNDERGROUND PROPANE TANK | | | AND RELATED FUEL LINES TO BE REVIEWED | | | UNDER GAS PERMIT (APPLIED FOR | | | SEPERATELY) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2005-11-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-11-26 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2005-11-26 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2006-07-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-19 |
Time |
18:19 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-19 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2006-07-20 00:00:00 | THE PROPOSED GENERATOR MUST BE SCREENED, | | | SEC 94-444(B) - SCREENING SHALL BE | | | CONSTRUCTED OF BRICK DECORATIVE | | | CONCRETE, OTHER DECORATIVE MASONRY AND | | | WALLS SHALL BE LANDSCAPE WITH SHRUBS AND | | | HEDGES PLANTED AT TWO-FOOT INTERVALS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-06-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-06-26 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-06-26 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2006-06-26 00:00:00 | DENIED, | | | 1. PLEASE SUBMIT TWO COPY OF SURVEY | | | SHOWING THE LOCATION OF THE PROPOSED | | | GENERATOR. (2ND REQUEST) ONLY 1 COPY WAS | | | SUBMITTED. | | | 2. INFORMATION SUBMITTED CANNOT BE SHOWN | | | IN PENCIL, BUT IN CLARITY AS WRITTEN IN | | | THE CITY OF WEST PALM AMENDMENTS TO THE | | | FLORIDA BUIDLING CODE, CHAPTER 1, | | | ADMINISTRATION 106.1.3 (QUALITY OF | | | BUILDING PLANS). | | | | | | NOTE: | | | SEC 94-303 MECHANICAL/POOL | | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-05-24 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-24 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-05-24 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2006-05-24 00:00:00 | DENIED, | | | 1. THE PROPOSED GENERATOR IS NOT SHOWN | | | ON THE SITEPLAN PROVIDED. | | | 2. PLEASE SHOW THE LOCATON OF THE | | | GENERATOR ON TWO COPY OF SITEPLAN WITH | | | SETBACKS FROM PROPERTY LINE. | | | 3. ONLY 1 SET OF SITEPLAN WAS SUBMITTED. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-29 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-29 |
Time |
16:44 |
Sent To |
I |
|
| Notes |
| 2005-09-29 00:00:00 | GENERATOR CAN ONLY ENCROACH 4FT INTO | | | SETBACK. |
|
|