Plan Review Details - Permit 05091091
Plan Review Stops For Permit 05091091
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 09:01 Rev Time 0.50
Received By alange Date 2005-12-05 Time 08:55 Sent To  
Notes
2005-12-05 00:00:00DENIED
  
 1.SUBMIT A PLANS SHOWING FASTENING
 METHOD OF GENERATOR TO SLAB.
  
 NOTE: SEE ELECTRICAL COMMENTS REGARDING
 SIGNING PAGES.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 14:32 Rev Time 0.50
Received By alange Date 2005-10-04 Time 14:32 Sent To  
Notes
2005-10-04 00:00:00DENIED
  
 1.SUBMIT A PLANS SHOWING SLAB DETAIL
 AND FASTENING METHOD OF GENERATOR TO
 SLAB.
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-01 Cont ID  
Sent By btrobaug Date 2005-12-01 Time 07:17 Rev Time 0.50
Received By btrobaug Date 2005-12-01 Time 06:50 Sent To P
Notes
2005-12-01 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
 1} PLEASE GIVE LOAD CALCS FOR THE BRANCH
 CIRCUITS BEING SERVED BY THE GENERATOR.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF THE SERVICE EQUIPMENT AND
 THE PROPOSED LOCATION OF THE GENERATOR
 AND RELATED EQUIPMENT SO THAT COMPLIANCE
 FOR 225.31 THROUGH 225.37 INCLUSIVE MAY
 BE REVIEWED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO SAME PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 OR WE COULD SET UP A MEETING TO CLARIFY
 THESE ISSUES. YOU MUST ALSO INDICATE THE
 TYPE OF FUEL AS THE PRIME MOVER AS IT
 HAS A BEARING ON THE GENERATOR OUTPUT.
  
 THERE MAY BE OTHER COMMENTS WHEN THESE
 ITEMS ARE SUBMITTED.BE AWARE THAT ALL
 DISCONNECTS MUST BE SERVICE RATED PER
 225.36.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-30 Cont ID  
Sent By btrobaug Date 2005-09-30 Time 15:15 Rev Time 0.50
Received By btrobaug Date 2005-09-30 Time 14:59 Sent To M
Notes
2005-09-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW
  
 1} TWO COPIIES OF THE MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF THE SERVICE EQUIPMENT AND
 THE PROPOSED LOCATION OF THE GENERATOR
 AND RELATED EQUIPMENT SO THAT COMPLIANCE
 FOR 225.31 THROUGH 225.37 INCLUSIVE MAY
 BE REVIEWED.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT AND SIGN THEIR NAME
 TO SAME PER 104.2.1 FBC.
  
 4} THE VALUE ON THE PERMIT APPLICATION
 MUST REFLECT THE COST OF ALL LABOR AND
 MATERIAL (EQUIPMENT) FOR THIS PROJECT
 UNDER THE GEN RES PERMIT TYPE. SEE
 104.6.5.CWPB AMMENDMENTS.
  
 THERE MAY BE OTHER COMMENTS WHEN THESE
 ITEMS ARE SUBMITTED.BE AWARE THAT ALL
 DISCONNECTS MUST BE SERVICE RATED PER
 225.36.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2005-12-05 Cont ID  
Sent By jleech Date 2005-12-05 Time 08:42 Rev Time 0.25
Received By jleech Date 2005-12-05 Time 08:42 Sent To B
Notes
2005-12-05 00:00:00GAS PERMIT REQUIRED. GAS CONTRACTOR
 REQUIRED TO SUBMIT PLANS WITH
 APPLICATION. FINAL GAS INSPECTION TO BE
 DONE BEFORE FINAL INSPECTION ON
 GENERATOR.
 GAS REVIEW BY
 JOHN LEECH
 805-6695

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 07:36 Rev Time 0.25
Received By jleech Date 2005-10-04 Time 07:36 Sent To B
Notes
2005-10-04 00:00:00DENIED;
 FUEL TYPE NOT LISTED. PERMIT REQUIRED
 FOR FUEL. APPLICATION BY LICENSED
 CONTRACTOR PLANS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-29 Cont ID  
Sent By adarroug Date 2005-11-29 Time 08:07 Rev Time 0.00
Received By adarroug Date 2005-11-29 Time 08:07 Sent To E
Notes
2005-11-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-23 Cont ID  
Sent By adarroug Date 2005-11-23 Time 14:16 Rev Time 0.00
Received By adarroug Date 2005-11-23 Time 14:16 Sent To Z
Notes
2005-11-23 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 08:18 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 08:18 Sent To E
Notes
2005-09-30 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 08:56 Rev Time 0.00
Received By alange Date 2005-09-23 Time 13:30 Sent To  
Notes
2005-09-23 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By tgordon Date 2005-09-30 Time 15:59 Rev Time 0.15
Received By tgordon Date 2005-09-30 Time 15:59 Sent To P
Notes
2005-09-30 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. PER 2001 FBC/M 804.3.3 .
 2) MANUFACTURE'S INSTALLATION
 INSTRUCTIONS MUST BE SUBMITTED WITH
 PERMIT APPLICATION SHOWING MODEL AND GAS
 TYPE BEING INSTALLED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 07:35 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-11-29 Cont ID  
Sent By sgraham Date 2005-11-29 Time 07:08 Rev Time 0.00
Received By sgraham Date 2005-11-29 Time 07:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By mmclean Date 2005-09-29 Time 16:54 Rev Time 0.00
Received By mmclean Date 2005-09-29 Time 16:54 Sent To I
Notes
2005-09-29 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF THE
 GENERATOR AND SETBACKS. (DISTANCE FROM
 THE STRUCTURE & PROPERTY LINE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720