Plan Review Details - Permit 05090984
Plan Review Stops For Permit 05090984
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 09:04 Rev Time 0.66
Received By alange Date 2006-06-27 Time 09:04 Sent To  
Notes
2006-06-27 00:00:00REVISION DENIED
  
 1.REVISIONS TO ORIGONAL PERMIT SHALL
 BE DESIGNED BY THE DESIGNER OF RECORD.
  
 2.SHOW LOCATION OF BEDROOMS ON PLANS
 SUBMITTED SO THAT EMERGENCY ESCAPE
 RESCUE OPENING SIZES CAN BE VERIFIED.
  
 3.SHOW SQUARE FOOTAGE AND ROOF SLOPE
 OF EXISTING ROOF.
  
 4.TRUSS DRAWINGS HAV NOT BEEN APPROVED
 YET AND STILL NEED TO BE RESUBMITTED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-05-31 Cont ID  
Sent By alange Date 2006-05-31 Time 14:31 Rev Time 0.50
Received By alange Date 2006-05-31 Time 14:31 Sent To  
Notes
2006-05-31 00:00:00TRUSS DRAWING REVIEW DENIED:
  
 SEE ATTACH SECTIONS FROM THE FLORIDA
 ADMINISTRATIVE CODE.
 61G15-23.001AND61G15-23.002
  
 ORIGONAL SIGNED AND SEALED DOCUMENTS
 WITH THE CORRECT SEALS REQUIRED
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-23 Cont ID  
Sent By alange Date 2006-05-23 Time 12:03 Rev Time 0.33
Received By alange Date 2006-05-23 Time 12:03 Sent To M
Notes
2006-05-23 00:00:00DENIED
  
 ENGINEERS SEAL USED SHOULD READ
 "LICENSED" NOT CERTIFICATE61G1-16.001
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-27 Cont ID  
Sent By alange Date 2005-12-27 Time 07:49 Rev Time 1.25
Received By alange Date 2005-12-23 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By alange Date 2005-10-05 Time 07:09 Rev Time 1.25
Received By alange Date 2005-10-04 Time 16:39 Sent To Z
Notes
2005-10-05 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION HAS BEEN
 REVISED TO
 76.96 PER SQ. FT. X 710 = $54,641.00
 ADDITIONAL PERMIT FEES ARE DUE.
  
 4.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS.FBC 2309.7.1
  
 5.SUBMIT PRODUCT APPROVALS WITH
 QUALITY ASSURANCE FOR THE FOLLOWING:
 WINDOWS, EXTERIOR DOORS, IMPACT
 PROTECTION, STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-13 Cont ID  
Sent By jleahy Date 2005-12-13 Time 17:09 Rev Time 0.45
Received By jleahy Date 2005-12-13 Time 17:09 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-25 Cont ID  
Sent By jleahy Date 2005-09-23 Time 22:08 Rev Time 0.45
Received By jleahy Date 2005-09-23 Time 22:05 Sent To M
Notes
2005-09-25 00:00:00THE TWO SMALL BATHROOMS NEED GFI OUTLETS
 210.8A1
  
 MASTER BATH NEEDS ADDITIONAL GFI WITHIN
 3' OF THE SINKS BOTH SINKS 210.52D
  
 NEED AN OUTLET ON BACK OF HOUSE
 210.8A3, 210.52E
  
 OUTLET SPACING NOT TO CODE IN MASTER
 BDROOM AND BDROOM TO THE LEFT
 210.52A1,2
  
 OUTLETS IN BDROOMS TO BE ARC FAULT
 PROTECTED210.12B
  
 NEED A PANEL SCHEDULE SHOWING BREAKER
 SIZES AND WIRE SIZES PER CODE.

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 16:03 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 16:03 Sent To M
Notes
2006-08-14 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 16:53 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 16:53 Sent To M
Notes
2006-08-10 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 10:29 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 10:29 Sent To B
Notes
2006-06-21 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-27 Cont ID  
Sent By adarroug Date 2006-05-27 Time 15:21 Rev Time 0.00
Received By adarroug Date 2006-05-27 Time 15:21 Sent To B
Notes
2006-05-27 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 16:35 Sent To B
Notes
2006-05-22 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 15:13 Sent To M
Notes
2006-05-06 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 09:30 Sent To E
Notes
2005-12-13 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-05 Cont ID  
Sent By alange Date 2005-10-05 Time 07:23 Rev Time 0.00
Received By alange Date 2005-09-22 Time 14:54 Sent To  
Notes
2005-09-22 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2007-01-02 Cont ID  
Sent By pkrauss Date 2007-01-02 Time 10:49 Rev Time 0.00
Received By pkrauss Date 2007-01-02 Time 10:49 Sent To  
Notes
2007-01-02 11:04:12A/C PLANS FOR THE EXISITNG HOME SYSTEM #2 (MANUAL J
 CALCS)

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-08-15 Cont ID  
Sent By tgordon Date 2006-08-15 Time 14:43 Rev Time 0.30
Received By tgordon Date 2006-08-15 Time 14:43 Sent To  
Notes
2006-08-15 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 09:33 Rev Time 0.30
Received By tgordon Date 2006-08-11 Time 09:33 Sent To  
Notes
2006-08-11 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL PLAN DETAIL ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 2) THE PLANS NEED TO BE SEALED BY THE
 ENGINEER AS HIS NAME AND INFORMATION IS
 IN THE TITLE BLOCK, PER FAC 61G15-23.002
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-05-24 Cont ID  
Sent By tgordon Date 2006-05-24 Time 14:51 Rev Time 0.25
Received By tgordon Date 2006-05-24 Time 14:51 Sent To  
Notes
2006-05-24 00:00:00REVISION TO ENERGY CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 12:10 Rev Time 0.20
Received By tgordon Date 2006-05-08 Time 12:10 Sent To B
Notes
2006-05-08 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) NEED TO SUBMIT 2 COPY'S OF ALL
 PAPER-WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-20 Cont ID  
Sent By pkrauss Date 2005-12-20 Time 11:10 Rev Time 0.40
Received By pkrauss Date 2005-12-20 Time 11:10 Sent To B
Notes
2005-12-20 00:00:00PROVISO:
 1.RETURN AIR SHALL BE EQUAL TO SUPPLY.
 ALL SUPPLY AIR INTO THE MASTER SUITE IS
 TO BE INCLUDED WHEN SIZING THE RETURN
 AIR.
  
 2.PLEASE PROVIDE AS BUILT DRAWINGS
 PRIOR TO INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-12-14 Cont ID  
Sent By tgordon Date 2005-12-14 Time 09:09 Rev Time 0.25
Received By tgordon Date 2005-12-14 Time 09:09 Sent To P
Notes
2005-12-14 00:00:00*** DENIED ***
 1)NEED TWO COPYS OF ENERGY CALCULATIONS.
 2) ENERGY CALCULATIONS NEED TO BE
 SIGNED.
 3) PLANS SHOW NO A/C DUCT WORK, AND NO
 AIR HANDLER LOCATION.
 4) PLANS SHOOW TWO A/C CONDENSER UNITS,
 PLEASE EXPLAIN WHY.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By jleahy Date 2005-09-25 Time 22:23 Rev Time 0.15
Received By tgordon Date 2005-09-27 Time 08:11 Sent To P
Notes
2005-09-27 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS SUBMITTED.
 2) NEED NOTICE OF COMMENCEMENT.
 3) NEED ENERGY CALCULATIONS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By jleech Date 2005-12-14 Time 13:51 Rev Time 0.25
Received By jleech Date 2005-12-14 Time 13:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 15:29 Rev Time 0.33
Received By jleech Date 2005-10-04 Time 15:29 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By mmclean Date 2005-10-06 Time 15:33 Rev Time 0.00
Received By mmclean Date 2005-10-06 Time 15:33 Sent To  
Notes
***NONE***