Plan Review Details - Permit 05090962
Plan Review Stops For Permit 05090962
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-19 Cont ID  
Sent By alange Date 2006-04-19 Time 09:09 Rev Time 0.50
Received By alange Date 2006-04-19 Time 09:09 Sent To  
Notes
2006-04-19 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION IS TOO LOW.
 IT HAS BEEN REVISED AS FOLLOWS:
 468 A/C SQ. FT. X $70.72 = $33,096.00
 COVER AREA 277 X $38.48 = $10,428.00
 REVISED PERMIT VALUATION IS $43,524.00
 ADDITIONAL PERMIT FEES ARE DUE.
  
 5.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 07:52 Rev Time 1.00
Received By alange Date 2005-10-04 Time 07:52 Sent To  
Notes
2005-10-04 00:00:00DENIED
  
 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SHOW AREA CALCULATIONS ON PLANS,
 SHOW EXISTING AREAS AND SHOW NEW A?C
 AREA AND COVERED AREAS.
  
 3.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUATION IS TOO LOW.
 IT HAS BEEN REVISED AS FOLLOWS:
 468 A/C SQ. FT. X $70.72 = $33,096.00
 COVER AREA 277 X $38.48 = $10,428.00
 REVISED PERMIT VALUATION IS $43,524.00
 ADDITIONAL PERMIT FEES ARE DUE.
  
 4.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIEDOWNS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-13 Cont ID  
Sent By btrobaug Date 2006-04-13 Time 12:09 Rev Time 0.50
Received By btrobaug Date 2006-04-13 Time 11:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-30 Cont ID  
Sent By btrobaug Date 2005-09-30 Time 08:36 Rev Time 0.50
Received By btrobaug Date 2005-09-30 Time 07:43 Sent To P
Notes
2005-09-30 00:00:00 
 PLEASE INDICATE THE LOCATION OF THE OF
 "NEW PANEL "A" SHOWN ON SHEET "A2".
  
 PLEASE SUBMIT A RISER DIAGRAM SHOWING
 THE SERVICE EQUIPMENT AND GROUNDING,
 EXISTING AND NEW.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 17:14 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 17:14 Sent To E
Notes
2006-04-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-04 Cont ID  
Sent By adarroug Date 2006-04-04 Time 16:04 Rev Time 0.00
Received By adarroug Date 2006-04-04 Time 16:04 Sent To Z
Notes
2006-04-04 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-28 Cont ID  
Sent By adarroug Date 2005-09-28 Time 14:14 Rev Time 0.00
Received By adarroug Date 2005-09-28 Time 14:14 Sent To E
Notes
2005-09-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 08:00 Rev Time 0.00
Received By alange Date 2005-09-21 Time 16:25 Sent To  
Notes
2005-09-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-10-03 Cont ID  
Sent By tgordon Date 2005-10-03 Time 09:28 Rev Time 0.15
Received By tgordon Date 2005-10-03 Time 09:28 Sent To B
Notes
2005-10-03 00:00:00NO MECH. PLANS, OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-03 Cont ID  
Sent By jleech Date 2005-10-03 Time 08:53 Rev Time 0.25
Received By jleech Date 2005-10-03 Time 08:53 Sent To M
Notes
2005-10-03 00:00:00NO RISER DIAGRAM NOT ENOUGH INFORMATION
 TO DO A PLUMBING PLAN REVIEW.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-12 Cont ID  
Sent By mmclean Date 2006-04-12 Time 07:35 Rev Time 0.00
Received By mmclean Date 2006-04-12 Time 07:35 Sent To I
Notes
2006-04-12 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By mmclean Date 2005-09-27 Time 17:10 Rev Time 0.00
Received By mmclean Date 2005-09-27 Time 17:10 Sent To I
Notes
2005-09-27 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY (MAY SHOW THE PROPOSED ADDITION
 WITH SETBACKS)
 2. SITEPLAN PROVIDED DOES NOT PROVIDE
 ALL INFORMATION NEEDED FOR REVIEW, MUST
 PROVIE THE DIMENSION OF THE LOT WITH
 SEBACK OF THE EXISTING STRUCTURE AND
 PROPOSED ADDITION.ALL SITEPLAN OR
 SURVEY SHOULD SHOW THE PROPOSED WORK
 WITH SETBACKS.
 3. SITEPLAN SHOULD SHOW ONLY THE
 PROPOSED WORK FOR THE APPLIED PERMIT.
 4. NEED TO IDENTIFY THE ROOM THAT THE
 PROPOSED ADDITION WILL HAVE INTERIOR
 ACCESS FROM ON FLOOR PLANS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy