Plan Review Details - Permit 05090954
Plan Review Stops For Permit 05090954
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-09 Cont ID  
Sent By kstevens Date 2006-01-09 Time 18:18 Rev Time 0.00
Received By kstevens Date 2006-01-09 Time 18:18 Sent To  
Notes
2006-01-09 00:00:00SIGNED OFF AND APPROVED BY JLEECH 1/4/6
 - KSTEVENS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By kstevens Date 2005-11-14 Time 18:03 Rev Time 1.25
Received By kstevens Date 2005-11-14 Time 18:03 Sent To  
Notes
2005-11-14 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. - ALL CUT SECTIONS FOR
 NEW SYSTEM SHALL BE SHOWN ON RISER
 DIAGRAM.
 2. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 3. SHOW LOCATION OF REGULATORS, AND
 SUBMIT MANUF. SPECIFICATION SHEETS FOR
 REGULATORS.
 4. MANUF. SHTTE INDICATES 54 CU/FT HR,
 BUT GAS RISER DIAGRAM INDICATES45K.
 PLEASE CLARIFY.
 5. GAS CHARTS FROM FBC-2001 TO BE USED.
 PLEASE INDICATE WHICH CHARTS FROM
 FBC-2001 FUEL GAS SHALL ARE USED FOR THE
 DESIGN. SECTION 402.
 6. ALL INFORMATION, DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-11-15 Cont ID  
Sent By tgordon Date 2005-11-15 Time 09:55 Rev Time 0.10
Received By tgordon Date 2005-11-15 Time 09:55 Sent To  
Notes
2005-11-15 00:00:00WITH PERMIT # 0509-951.