Plan Review Details - Permit 05090939
| Plan Review Stops For Permit 05090939 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-10-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-10-05 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-10-05 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-09-28 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-09-28 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2005-09-28 00:00:00 | DENIED | | | | | | 1) CONCRETE WALL DOES NOT HAVE ADEQUATE | | | VERTICAL REINFORCEMENT TO RESIST 140 MPH | | | WINDLOADS. SUBMIT CALCULATIONS.FBC | | | 104.2.1.2 | | | | | | 2) A CONTINOUS TIE BEAM OR BOND BEAM | | | WITH CONTINOUS HORIZONTAL REINFORCEMENT | | | IS REQUIRED. FBC 2101. | | | | | | 3) PROVIDE DETAIL OF THE TIE BEAM AT THE | | | CHANGE OF ELEVATION FROM 6' TO 4'. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-04 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-04 |
Time |
09:20 |
Sent To |
B |
|
| Notes |
| 2005-10-04 00:00:00 | TO "RMCDOUGAL" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-27 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-27 |
Time |
14:46 |
Sent To |
B |
|
| Notes |
| 2005-09-27 00:00:00 | TO "MISC" BOX#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-21 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-21 |
Time |
17:00 |
Sent To |
Z |
|
| Notes |
| 2005-09-21 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-26 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-26 |
Time |
18:05 |
Sent To |
I |
|
| Notes |
| 2005-09-26 00:00:00 | NOTE: AT ANY ROAD INTERSECTION, | | | VISIBILITY SHALL NOT BE OBSCURED BY THE | | | CONSTRUCTION, PLACEMENT OR MAINTENANCE | | | OF A STRUCTURE WALL, FENCE, BERM, PLANT | | | MATERIAL, SHRUBS OR ANY SIMILAR ITEM. |
|
|
|