| Plan Review Stops For Permit 05090897 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-22 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-22 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2006-03-22 00:00:00 | SEPARATE PERMITS - ROOF REPAIR, | | | HARDIBOARD, DOORS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-03-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-20 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-03-20 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2006-03-20 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PREVIOUS CORRECTION LISTS HAD | | | REQUESTED THAT SCOPE OF WORK REGARDING | | | THE ROOF BE CLARIFIED.NOW SHEET 1 | | | STATES THAT THE ROOF IS TO BE PAINTED | | | RATHER THAN REPLACED.S1.2 SPECIFIES | | | REPLACEMENT OF SHEATHING WHICH IMPLIES | | | THAT ROOF WORK WILL BE DONE.THIS | | | COMMENT DOES NOT HAVE TO BE ADDRESSED ON | | | THE PLAN BUT BE ADVISED THAT PRODUCT | | | APPROVALS FOR THE METAL ROOF WILL BE | | | REQUIRED UNDER SEPARATE PERMIT. | | | | | | 2.)THE NEW SHEETS T1 AND A9.1 ARE TO | | | BE SIGNED, SEALED, AND DATED. | | | FAC61G1-16.STATUTORY REQUIREMENTS | | | CANNOT BE WAIVED PER BUILDING OFFICIAL. | | | | | | 3.)REMOVE THE REDUCED ARCHITECTURAL | | | SHEETS, EXCEPT FOR THE FOOD SERVICE PLAN | | | APPROVAL AND ANY OTHER SHEETS WHICH MAY | | | HAVE APPROVALS FROM OTHER GOVERNMENTAL | | | ENTITIES. | | | | | | 4.)ON ONE OF THE SETS, SOMEONE HAS | | | CHANGED THE 2001 FBC TO 2003 FBC.THE | | | OTHER PLAN IS STILL 2001 FBC.THIS | | | PROJECT COULD BE PERMITTED UNDER EITHER | | | FBC2001 OR FBC2004.IT WAS REVIEWED | | | UNDER FBC2001.DECLARE GOVERNING CODE. | | | CHANGING THE CODE AT THIS POINT WILL | | | RESULT IN ADDITIONAL DELAYS. | | | | | | 5.)PRODUCT APPROVALS HAVE BEEN | | | REQUESTED TWICE.ONLY WINDOW PRODUCT | | | APPROVALS WERE PROVIDED.ALSO REQUIRED | | | ARE PRODUCT APPROVALS FOR SIDING, DOORS, | | | AND THE METAL ROOF.SEE ALSO COMMENT #1 | | | ABOVE. | | | | | | NEW COMMENTS: | | | | | | 6.)A1.1 DECLARES THIS BUILDING AS TYPE | | | II CONSTRUCTION, WHICH REQUIRES THAT ALL | | | STRUCTURAL ELEMENTS ARE NONCOMBUSTIBLE | | | AND MEET THE FIRE RESISTANCE | | | REQUIREMENTS OF FBC TABLE 600, FBC604. | | | THIS IS IN CONFLICT WITH THE STRUCTURAL | | | DETAILS. IN ADDITION TO REQUIRING | | | NONCOMBUSTIBLE CONSTRUCTION AND FIRE | | | RATING IN COMPLIANCE WITH TABLE 600, | | | COMBUSTIBLES IN CONCEALED SPACES ARE NOT | | | ALLOWED AND THIS MUST BE NOTED ON THE | | | PLAN IF THE BUILDING IS TO BE A TYPE II. | | | NOTE THAT THE NEW STRUCTURAL SHOW | | | EXTERIOR COMBUSTIBLE NONBEARING WALLS AS | | | WELL AS AN EXISTING COMBUSTIBLE ROOF. | | | ADDRESS. | | | | | | 7.)WHEN RESUBMITTING, INCLUDE A | | | RESPONSE LETTER INDICATING HOW EACH ITEM | | | WAS ADDRESSED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-01-23 |
Time |
14:48 |
Rev Time |
2.00 |
| Received By |
shill |
Date |
2006-01-23 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | **NEW COMMENT 2/7/06** | | | | | | PLEASE PROVIDE A SURVEY FOR THIS JOB. | | | | | 2006-01-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | FROM PREVIOUS LIST, ITEMS NOT ADDRESSED, | | | NUMBERING TO REMAIN THE SAME FOR | | | CONSISTENCY | | | | | | 1.) A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED.THE NOC PROVIDED: | | | A. IS LACKING THE LEGAL DESCRIPTION, | | | FS713.13, | | | B. OWNER INFORMATION CONFLICTS WITH OUR | | | RECORDS AND THE PERMIT APPLICATION, AND | | | C. HAS BEEN SIGNED BY THE CONTRACTOR. | | | IS THE CONTRACTOR THE OWNER OF THIS | | | PROPERTY? PROVIDE DOCUMENTATION TO SHOW | | | THAT THE INDIVIDUAL SIGNING THE NOC IS | | | THE OWNER. | | | | | | 2.) ADDRESSED. | | | | | | 3.)THE DESCRIPTION OF WORK ON THE | | | PERMIT APPLICATION STATES THAT THIS IS | | | HURRICANE REPAIR WORK.THIS IS AN | | | ALTERATION.PLEASE REVISE THE | | | APPLICATION TO CORRECTLY REFLECT THE | | | SCOPE OF WORK. | | | | | | 4.)THE SCOPE OF WORK IS NOT CLEAR. | | | A4.1 STATES THAT THE EXISTING STANDING | | | SEAM ROOF IS TO BE PAINTED, T1 STATES | | | THAT THIS IS A NEW ROOF. | | | | | | 5.)ADDRESSED. | | | | | | 6.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED FAC9B72. | | | STANDING SEAM METAL ROOF | | | HARDIBOARD SIDING | | | SCREW ANCHORS | | | | | | NO PRODUCT APPROVALS SUBMITTED.ALSO | | | REQUIRED ARE PRODUCT APPROVALS FOR THE | | | EXTERIOR DOORS. | | | | | | WHEN RESUBMITTING, REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-23 |
Time |
09:25 |
Rev Time |
3.00 |
| Received By |
shill |
Date |
2005-11-22 |
Time |
17:35 |
Sent To |
|
|
| Notes |
| 2005-11-23 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED.THE NOC PROVIDED: | | | A. IS LACKING THE LEGAL DESCRIPTION, | | | FS713.13, | | | B. OWNER INFORMATION CONFLICTS WITH OUR | | | RECORDS AND THE PERMIT APPLICATION, AND | | | C. HAS BEEN SIGNED BY THE CONTRACTOR. | | | IS THE CONTRACTOR THE OWNER OF THIS | | | PROPERTY? PROVIDE DOCUMENTATION TO SHOW | | | THAT THE INDIVIDUAL SIGNING THE NOC IS | | | THE OWNER. | | | | | | 2.)THE CA NUMBER FOR VILLA & | | | ASSOCIATES IS TO BE ON THE PLAN, | | | FAC61G1-16. | | | | | | 3.)THE DESCRIPTION OF WORK ON THE | | | PERMIT APPLICATION STATES THAT THIS IS | | | HURRICANE REPAIR WORK.THIS IS AN | | | ALTERATION.PLEASE REVISE THE | | | APPLICATION TO CORRECTLY REFLECT THE | | | SCOPE OF WORK. | | | | | | 4.)THE SCOPE OF WORK IS NOT CLEAR. | | | A4.1 STATES THAT THE EXISTING STANDING | | | SEAM ROOF IS TO BE PAINTED, T1 STATES | | | THAT THIS IS A NEW ROOF. | | | | | | 5.)THE DEMO PLAN, A1.0, CONFLICTS WITH | | | THE OTHER SHEETS AS TO THE ORIENTATION | | | OF THE BUILDING. | | | | | | 6.)FLORIDA STATE OR LOCAL PRODUCT | | | APPROVAL REQUIRED FAC9B72. | | | STANDING SEAM METAL ROOF | | | HARDIBOARD SIDING | | | SCREW ANCHORS | | | | | | 7.)THIS IS AN OVER 50% IMPROVEMENT, | | | SEE FBC3401.7.2.6. | | | | | | 8.)PROVIDE ROOM DESIGNATIONS ON THE | | | FLOOR PLAN, A1.1. | | | | | | 9.)FBC11-4.1(3), WORK AREAS ARE TO BE | | | CONSTRUCTED SO THAT INDIVIDUALS WITH | | | DISABILITIES CAN APPROACH, ENTER, AND | | | EXIT THE AREAS.SHOW COMPLIANCE.SHEET | | | A1.2. | | | | | | 10.)THE DOOR TO THE KITCHEN LACKS THE | | | CLEARANCE REQUIRED, PULL SIDE, FBC11 | | | FIGURE 25, FBC11-4.13.6. | | | | | | 11.)THE MENS' BATHROOM DOOR AND THE | | | OFFICE DOOR LACK THE CLEARANCE REQUIRED, | | | PUSH SIDE, IF THE DOOR HAS A CLOSER AND | | | A LATCH, FBC11 FIGURE 25, FBC11-4.13.6. | | | | | | | | | 12.)PROVIDE THE DIMENSION ON THE PLAN | | | TO SHOW COMPLIANCE WITH FBC11-4.13.7, | | | FBC FIGURE 26 TWO HINGED DOORS IN A | | | SERIES (BATHROOM). | | | | | | 13.)SHOW ACCESSIBLE SEATING, | | | FBC11-5.1. | | | | | | 14.)SHOW ACCESS AISLE, FBC11-5.3. | | | | | | 15.)PROVIDE A DETAIL FOR THE FOOD | | | SERVICE AREAS, FBC11-5.5. | | | | | | 16.)IS THERE A TABLEWARE/CONDIMENT | | | AREA?PROVIDE A DETAIL, FBC11-5.6. | | | | | | 17.)WHAT IS THE HEIGHT OF THE TABLES | | | 919, SHEET A1.2?SEE FBC11-5.2. | | | | | | 18.)SHEET A2.1 SHOWS EXIT LIGHTS ON | | | THE LEGEND BUT NONE ON THE PLAN.PLEASE | | | MAKE CONSISTENT WITH E1.1. | | | | | | 19.)INCLUDE THE DOOR DIMENSION ON THE | | | PLAN FOR ALL EGRESS DOORS AND DOORS | | | REQUIRED TO BE ACCESSIBLE. | | | | | | 20.)SPECIFY INTERIOR FINISH | | | CLASSIFICATION, FBC TABLE 803.3. | | | | | | 21.)WHEN RESUBMITTING, PLEASE REPLACE | | | ONLY SHEETS WHICH HAVE CHANGED.TO | | | EXPEDITE PLAN REVIEW, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-31 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-31 |
Time |
14:50 |
Sent To |
PC |
|
| Notes |
| 2007-01-31 14:50:33 | REV'S FOR FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2007-01-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-28 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-28 |
Time |
16:14 |
Sent To |
PC |
|
| Notes |
| 2007-01-28 16:46:14 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF SIGNED, | | | DATED AND SEALED PLANS. PLEASE KNOW THAT ONE COPY WILL | | | STAMPED ONCE REVIEWED FOR CODE COMPLIANCE AND BE | | | RETAINED FOR PERMANENT RECORD SET OF PLANS FOR JOB AND | | | ONE WILL STAMPED FOR CONTRACTOR'S COPY ON JOB SITE | | | RECORD SET OF PLANS. PLEASE SEE ONLY ONE SET WAS | | | SUBMITTED FOR REVIEW AND STAMPING. PLEASE SUBMIT. | | | | | | *PLEASE SEE COVER SHEET WHICH WAS FILLED OUT BY | | | CONTRACTOR STATES ONLY ONE SET SUBMITTED. | | | | | | FBC 104.1 ADMIN SECTION. FAC 61G15-23.002, FS 471.025 | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-14 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-14 |
Time |
08:23 |
Sent To |
PC |
|
| Notes |
| 2006-11-14 08:34:19 | ***** UNSAT ***** | | | | | | 1) NOTE: PLEASE SEE ADDITIONAL CIRCUITING, TRACK | | | LIGHTING ETC WILL REQUIRE PANEL SCHEDULES AND LOADS TO | | | BE REVISED ON OTHER SHEETS NOT SUBMITTED. | | | 220, 220.12 , ALSO CONTINUOUS LOADS PER 215.3, 230.42 | | | ETC. | | | | | | 2) NOTE: PLEASE BE SURE ALL PLANS ARE SIGNED, DATED AND | | | SEALED BY THE DESIGNER OF RECORD AS REQUIRED UNDER THE | | | FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND FLORIDA | | | STATUTES 471.025 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-16 |
Time |
19:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-16 |
Time |
19:18 |
Sent To |
PC |
|
| Notes |
| 2006-09-16 00:00:00 | REV OK , REVISED SERVICE MAIN AND | | | GROUNDING ELECTRODE/SYSTEM. | | | | | | | | | GFI'S IN KITCHEN AREA ARE TO BE VERIFIED | | | IN FIELD AS NO REVSION WAS SUBMITTED FOR | | | REDLINED NOTES.210.8B3 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-01-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-23 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-23 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2006-01-23 00:00:00 | PERMIT EXPEDITOR CAME IN AND CORRECTED | | | SETS. | | | SEE THE FOLLOWING FOR REDLINED ITEMS. | | | | | | | | | | | | | | | | | | 1)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED | | | PER FS 713.13(2). | | | IF WORK HAS NOT COMMENCED WITHIN 90 DAYS | | | OF RECORDING OF SAID NOC. THE NOC SHALL | | | BECOME VOID AND WILL BE REQUIRED TO BE | | | RE-RECORDED BEFORE PICKING UP OF PERMIT. | | | | | | | | | ** REDLINED, | | | | | | 2002NEC210.8B3 AS SOME KITCHEN AREA | | | RECEPTS DO NOT APPEAR TO BE NOTED OR | | | CONTAIN GFI RECEPTS/PROTECTION AS | | | REQUIRED. | | | PLEASE SEE AREAS CONTAING EQUIPMENT FOR | | | KITCHEN, FOOD PREP ETC SHALL BE | | | CONSIDERED PART OF THE KITCHEN AREA. | | | | | | ** REDLINED , | | | 250.6,250.24 FOR THE "BOND" SHOWN FROM | | | METER CT CAN. | | | THE GROUNDING OF ELECTRICAL SYSTEMS, | | | CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND | | | CONDUCTIVE NON?CURRENT-CARRYING | | | MATERIALS AND EQUIPMENT SHALL BE | | | INSTALLED AND ARRANGED IN A MANNER THAT | | | WILL PREVENT OBJECTIONABLE CURRENT OVER | | | THE GROUNDING CONDUCTORS OR GROUNDING | | | PATHS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-20 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-20 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2006-01-20 00:00:00 | ****** NOTES, | | | PLANS TO REMAIN IN "F" STATUS UNTIL NOTE | | | #1 BELOW IS ADDRESSED. | | | | | | | | | 1)NOTE: AS REQUESTED ON PREVIOUS REVIEW; | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM | | | SETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO THE COMPLETE SETS FOR REVIEW AND | | | STAMPING. ONLY ONE COPY OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE ONLY . | | | **THIS WAS NOT DONE AND A REPRESENTIVE | | | FOR PROJECT SHOULD SET UP A TIME WITH | | | PLAN REVIEW STAFF TO COME INTO OFFICE TO | | | REMOVE SHEETS AND MAKE TWO CLEAN SETS. | | | | | | 2)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED | | | PER FS 713.13(2). | | | IF WORK HAS NOT COMMENCED WITHIN 90 DAYS | | | OF RECORDING OF SAID NOC. THE NOC SHALL | | | BECOME VOID AND WILL BE REQUIRED TO BE | | | RE-RECORDED BEFORE PICKING UP OF PERMIT. | | | | | | | | | ** REDLINED, | | | | | | 2002NEC210.8B3 AS SOME KITCHEN AREA | | | RECEPTS DO NOT APPEAR TO BE NOTED OR | | | CONTAIN GFI RECEPTS/PROTECTION AS | | | REQUIRED. | | | PLEASE SEE AREAS CONTAING EQUIPMENT FOR | | | KITCHEN, FOOD PREP ETC SHALL BE | | | CONSIDERED PART OF THE KITCHEN AREA. | | | | | | ** REDLINED , | | | 250.6,250.24 FOR THE "BOND" SHOWN FROM | | | METER CT CAN. | | | THE GROUNDING OF ELECTRICAL SYSTEMS, | | | CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND | | | CONDUCTIVE NON?CURRENT-CARRYING | | | MATERIALS AND EQUIPMENT SHALL BE | | | INSTALLED AND ARRANGED IN A MANNER THAT | | | WILL PREVENT OBJECTIONABLE CURRENT OVER | | | THE GROUNDING CONDUCTORS OR GROUNDING | | | PATHS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-10-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-13 |
Time |
13:44 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-10-13 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2005-10-13 00:00:00 | ****** UNSAT ******* | | | | | | 1)NOTE: PLEASE INCLUDE RECEPTS REQUIRED | | | ABOVE ALL OUTSIDE WINDOWS.210.62 | | | THESE WILL BE REQUIRED TO DISCOURAGE | | | FLOOR RECEPTACLES AND UNSIGHTLY | | | EXTENSION CORDS LIKELY TO CAUSE PHYSICAL | | | INJURY, RECEPTACLES MUST BE INSTALLED | | | DIRECTLY ABOVE A SHOW WINDOW, AND ONE | | | RECEPTACLE IS REQUIRED FOR EVERY 12 | | | LINEAR FT OR ?MAJOR FRACTION THEREOF? (6 | | | FT OR MORE). SEE 220.3(B)(7) AND | | | 220.12(A) FOR INFORMATION REGARDING LOAD | | | COMPUTATIONS FOR SHOW WINDOWS. | | | THESE ARE MAINLY USED FOR SIGNAGE WHICH | | | IS TYPICALLY INSTALLED ABOVE WINDOWS. | | | | | | 2)NOTE: PLEASE SEE 600.5 FOR MIN SIGN | | | CIRCUIT REQUIRED AT FRONT ENTRANCE | | | LOCATION SUBJECT TO PEDESTRIAN TRAFFIC. | | | | | | 3)NOTE: PLEASE SEE AN "EQUIPMENT | | | GROUNDING" CONDUCTOR IS BEING SHOWN | | | BEFORE THE FIRST MEANS OF DISCONNECT. | | | PLEASE SEE 250.6,250.24, THE "EQUIPMENT | | | GROUNDING CONDUCTOR IS ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 4)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | SYSTEM SEEMS TO BE MISSING THE REQUIRED | | | CONNECTION TO THE COLD WATER PIPE. | | | 250.50 | | | | | | 5)NOTE: PLEASE SEE "DP" WILL BE REQUIRED | | | TO CONTAIN A MCB AS PANEL IS SHOWN AS | | | MLO WITH MORE THAN 6 SPACES. | | | PLEASE INDICATE THE AS MCB. | | | PLEASE KNOW THE MCB WILL ONLY BE | | | REQUIRED TO HAVE THE 65,000 AIC RATED | | | MAIN AND OTHER BREAKERS IN PANEL MAY BE | | | RATED FOR SERIES RATING. | | | 110.9, 230.70 | | | | | | 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR | | | KITCHENS IN OTHER THAN DWELLING UNITS | | | FOR GFI PROTECTION OF ALL 15/20A 120 V | | | RECEPTS. | | | | | | **PLEASE BE SURE TO SEE FIE REVIEW | | | COMMENTS AND ANY POSSIBLE COMMENT SFORM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD | | | BE SUBMITTED FOR REFERENCE ONLY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-10-11 00:00:00 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-01-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2006-01-20 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2006-01-20 |
Time |
14:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-10-11 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-10-11 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2005-10-11 00:00:00 | ******DENIED****** | | | | | | 1) AN ADDRESS ON BUILDING IS REQUIRED | | | AND SHALL BE A MINIMUM OF 6" IN HEIGHT | | | AND CONTRASTING TO BACKGROUND. | | | | | | 2) PLEASE INDICATE THE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | PLEASE ILLUSTRATE IN TERMS OF CLASS A,B, | | | OR C. | | | | | | 3) PLEASE INDICATE THE OCCUPANT LOAD. A | | | NEW OCCUPANT LOAD SIGN WILL BE ISSUED | | | PRIOR TO OR AT THE TIME OF THE FINAL | | | FIRE INSPECTION. | | | | | | 4) PLEASE EXPLAIN THE RELOCATION OF FIRE | | | SPRINKLER HEADS ABOVE DRAFT CURTAIN? | | | | | | 5) IN ADDITION TO A "K" TYPE FIRE | | | EXTINGUISHER IN THE KITCHEN, 2A-10B,C | | | RATED FIRE EXTINGUISHERS ARE REQUIRED. | | | | | | 6) VISUAL/AUDIBLE WARNING DEVICES SHALL | | | BE INSTALLED IN THE AREA OF DUCT SMOKE | | | DETECTORS. | | | | | | 7) PLANS MENTION HOOD/SUPPRESSION | | | SYSTEMS. SEPARATE SHOP DRAWINGS AND | | | PERMITS WILL BE REQUIRED. | | | | | | | | | MIKE WENNERGREN, CAPTAIN | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2006-09-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-16 |
Time |
06:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-16 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2006-09-16 00:00:00 | GAS REVISION OK - CHANGED PIPE SIZE TO | | | PIZZA OVEN TO 1-1/2". SHEETS P-1 & P-4 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2006-03-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-03-10 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-03-10 |
Time |
11:21 |
Sent To |
P |
|
| Notes |
| 2006-03-10 00:00:00 | RE-SUB | | | SEPRERATE PERMIT FOR GAS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-28 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-28 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2006-01-28 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | PREVIEW | | | GASDENIED | | | PREVIOUS COMMENTS DATED 11-26-05 NOT | | | ADDRESSED. | | | | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | | | | E. SUBMIT MANFACTURE SPECIFICATION | | | SHEETS FOR REGULATORS SHOWING LISTING | | | FOR REGULATORS, AND INDICATE VENTING | | | LINES & MATERIAL IF | | | REQUIRED. | | | NEW COMMENT: "SEPERATE GAS PERMIT" | | | END OF COMMENTS,QUESTIONS 561-805-6692 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
11:29 |
Sent To |
E |
|
| Notes |
| 2007-01-24 11:30:13 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-11-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-08 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-08 |
Time |
16:04 |
Sent To |
E |
|
| Notes |
| 2006-11-08 16:05:18 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-09 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-09 |
Time |
13:44 |
Sent To |
E |
|
| Notes |
| 2006-09-09 00:00:00 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-08 |
Time |
18:44 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-08 |
Time |
18:44 |
Sent To |
P |
|
| Notes |
| 2006-09-08 00:00:00 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-03-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-07 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-07 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2006-03-07 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-19 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-19 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2006-01-19 00:00:00 | TO "COMM" BD#29 | | 2005-12-19 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-26 |
Time |
11:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-22 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2005-09-23 00:00:00 | TO "COMM" BD#9 | | 2005-09-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-07-05 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-07-05 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-03-16 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-31 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-31 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | PROVISO: | | | ADDITIONAL PERMITS REQUIRED FOR HOODS & | | | WALK-IN COOLER.PLEASE PROVIDE THE | | | FOLLOWING INFORMATION WITH PERMIT | | | APPLICATION: | | | | | | 1. MANUFACTURER'S SUBMITTAL DATA | | | 2. TYPE AND GAUGE OF METAL FOR HOODS & | | | GREASE DUCT. | | | 3. AIR BALANCE SCHEDULE. | | | 4. TERMINATION OF GREASE DUCT IN | | | IN RELATION TO PROPERTY LINES, | | | | | | PARAPETS, ADJACENT BUILDINGS, FRESH | | | AIR INTAKES, ETC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-08 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2005-11-08 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2005-11-08 |
Time |
18:04 |
Sent To |
|
|
| Notes |
| 2005-11-08 00:00:00 | PLAN DENIED | | | 1) PLEASE PROVIDE FRESH AIR CALCULATIONS | | | PER TABLE 403.3 FBC(M) | | | 2) PLEASE REFER TO SECTION 606.2.1 | | | SUPPLY AIR SYSTEM AND 606.4.1 | | | SUPERVISION. | | | 3) ADDITIONAL PERMITS ARE REQUIRED FOR | | | HOODS AND WALK IN COOLERS. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-03-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-03-10 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-03-10 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2006-03-10 00:00:00 | ALL WORK SUBJECT TO FIELD INSPECTOR. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-01-28 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-01-28 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2006-01-28 00:00:00 | PAUL SCHMITZ | | | FBC2001 FUEL GAS CODEPLAN REVIEW | | | FBC 2001 PLUMBING CODEPLAN REVIEW | | | FBC 2001 FL ACESSIBILITY CODE PLAN | | | PREVIEW. | | | PLUMBINGDENIED | | | PREVIOUS COMMENTS DATED 11-26-05 NOT | | | ADDRESSED. | | | PLAN REVIEW COMMENTS SHALL BE RESPONDED | | | TO BY THE DESIGN PROFESSIONALS. REFERING | | | TO EACH OTHER OR CONTRACTOR, IS NOT | | | HELPFUL IN EXPEDITING YOUR PERMIT. | | | | | | 2. APPLICATION INDICATES "REPAIR STORM | | | DAMAGE", BUT NEW FLOOR PLAN INDICATES | | | ALTERATION OF SPACE. PLEASE DESCRIBE | | | PROJECT IN DETAIL AS REQUIRED ON | | | APPLICATION FOR PERMIT. | | | | | | 5. PLANS SHALL BE ROUTED TO STATE OF | | | FLORIDA DBPR HOTEL AND RESTURANT DIV. | | | FOR REVIEW PRIOR TO RESUBMITTING TO CITY | | | WPB FOR REVIEW. | | | MINIMUM 2 COPIES STAMPED | | | BY DBPR WITH 2 PAGE "WORKSHEETS" | | | ATTACHED TO EACH SET OF PLANS SUBMITTED | | | FOR REVIEW. SECTION 101.4.7. CONTACT | | | NUMBER FOR DBPR IS (850) 487-1395 | | | | | | 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO | | | GUTTER, DOWN SPOUTS | | | CONDENSATE SHALL DRAIN | | | SEPARATELY OUT OF THE BUILDING AND SHALL | | | TERMINATE TO A STORM CATCH BASIN, | | | PLANTED AREA OR A DRYWELL. IF CONNECTED | | | TO A CATCH BASIN, A RELIEF VENT IS | | | REQUIRED AS THE CONDENSATE EXITS THE | | | BUILDING. CITY CODE 90-125(B)(5). | | | | | | 12. SHT P1 WATER FILTER SHALL COMPLY | | | WITH NSF 42. SUBMIT MANUF. SPECIFICATION | | | SHOWING COMPLIANCE. SECTION 611.1 | | | | | | 16.SEPERATE GAS STOP FOR GAS. | | | END OF COMMNENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-11-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-11-26 |
Time |
10:01 |
Rev Time |
3.50 |
| Received By |
kstevens |
Date |
2005-11-26 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2005-11-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | WPB CITY CODE | | | | | | 1. SHTS T1 THRU A9.1 FIRM LICENSE NUMBER | | | IS REQUIRED IN THE TITLE BLOCK OF THE | | | ARCHITECT ON EACH SHEET. FAC | | | 61G1-16.004(2) & FS 481.219 FS 481.2055. | | | 2. APPLICATION INDICATES "REPAIR STORM | | | DAMAGE", BUT NEW FLOOR PLAN INDICATES | | | ALTERATION OF SPACE. PLEASE DESCRIBE | | | PROJECT IN DETAIL AS REQUIRED ON | | | APPLICATION FOR PERMIT. | | | 3. SHT A1.1 TOILET IN WOMEN'S TOILET | | | INDICATEED AS 11-1/8" OFF THE WALL TO | | | THE CENTER OF THE W/C. MINIMUM CLEARANCE | | | FOR W/C'S IS 15" OFF WALL TO CENTER OF | | | FIXTURE. MINIMUM 30" FINISH OPENING | | | REQUIRED FOR THIS TOILET. SECTION | | | 405.3.1. INDICATE ON FLOOR PLAN. | | | 4. SHT A1.1 TURNING AREA SHALL BE IN THE | | | TOILET ROOM, NOT IN THE STALL. PLEASE | | | SHOW AREA IN TOILET ROOM. SECTION | | | 11-4.22.3. | | | 5. PLANS SHALL BE ROUTED TO STATE OF | | | FLORIDA DBPR HOTEL AND RESTURANT DIV. | | | FOR REVIEW PRIOR TO RESUBMITTING TO CITY | | | WPB FOR REVIEW. MINIMUM 2 COPIES STAMPED | | | BY DBPR WITH 2 PAGE "WORKSHEETS" | | | ATTACHED TO EACH SET OF PLANS SUBMITTED | | | FOR REVIEW. SECTION 101.4.7. CONTACT | | | NUMBER FOR DBPR IS (850) 487-1395 | | | 6. SHTS A1.2 & A1.3 EQUIPMENT LAYOUT | | | PLAN DOES NOT REFLECT THE EQUIPMENT | | | SCHEDULE. AE #53, AE #410, & AE #416 NOT | | | FOUND ON LAYOUT PLAN. AE #426 FOUND ON | | | FLOOR PLAN DOES NOT INDICATE WATER | | | SUPPLY OR DRAIN ON EQUIPMENT SECHEDULE. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 7. SHTS A4.1 & A4.2 INDICATES "NEW | | | PARAPET SEE DETAIL SHEET S1 FOR DETAILS" | | | NO SHT S1 SUBMITTED, NO DETAIL FOUND. | | | PLEASE CLARIFY. SECTION 104.2.1. | | | 8. SHT A8.2 RESTROOM ELEVATIONS. PLEASE | | | SHOW THE FOLLOWING INFORMATION: | | | A. 11-4.16.3 HEIGHT | | | B. 11-4.18.3 CLEAR FLOOR SPACE | | | C. 11-4.18.4 FLUSH CONTROLS | | | D. 11-4.19.5 FAUCETS | | | 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO | | | SANITARY SYSTEM. CONDENSATE SHALL DRAIN | | | SEPARATELY OUT OF THE BUILDING AND SHALL | | | TERMINATE TO A STORM CATCH BASIN, | | | PLANTED AREA OR A DRYWELL. IF CONNECTED | | | TO A CATCH BASIN, A RELIEF VENT IS | | | REQUIRED AS THE CONDENSATE EXITS THE | | | BUILDING. CITY CODE 90-125(B)(5). | | | 10. SHT P1 ALL FLOOR DRAINS IN THE | | | KITCHEN AND DISHWASH AREAS AND THE MOP | | | SINK SHALL DRAIN INTO THE GREASE SYSTEM, | | | NOT THE SANT. SYSTEM. - ALSO SHOW THESE | | | CHANGES ON THE SANT./GREASE ISOMETRIC | | | RISER DIAGRAM. | | | 11. SHT P1 THE NEW GREASE INTERCEPTORS | | | SHALL BE SIZED BY LYNN MASSON, | | | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE | | | CONTACT HER AT (561) 822-2271, OR FAX | | | (561) 822-2279, OR E-MAIL | | | [email protected]. WASTE ORD. #3434. | | | 12. SHT P1 WATER FILTER SHALL COMPLY | | | WITH NSF 42. SUBMIT MANUF. SPECIFICATION | | | SHOWING COMPLIANCE. SECTION 611.1 | | | 13. SHT P2 DETAIL #1 GAS WATER HEATER | | | DRAIN LINE SHALL DRAIN TO A FLOOR SINK | | | OR HUB DRAIN. FLOOR DRAINS ARE NOT AN | | | APPROVED INDIRECT WASTE INTERCEPTOR. | | | SECTIONS 802.3 & 802.3.2. INDICATE WHERE | | | T & P RELIEF VALVE WILL TERMINATE. | | | SECTION 504.7.1 | | | 14. SHT P2 DETAIL #5 GREASE INTERCEPTORS | | | LIDS TO BE STAMPED "GREASE" NOT SANT. AS | | | INDICATED. - A 2-WAY CLEANOUT IS | | | REQUIRED UPSTREAM OF THE ENTERANCE OF | | | THE GREASE INTERCEPTORS AS WELL AS AT | | | THE EXITS. | | | 15. SUBMIT A WATER RISER ISOMETRIC | | | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, | | | AND WATER HAMMER ARRESTORS REQUIRED BY | | | SECTION 604.9. WATER HAMMER ARRESTORS | | | SHALL BE LOCTED NEAR THE FIXTURES IN AN | | | "EFFECTIVE RANGE" NOT IN THE CEILING. | | | PDI-WH 201 AND MANUF. INSTALLATION | | | INSTRUCTIONS. | | | 16. THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | A. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | B. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). | | | C. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). - ADDING CUT | | | SECTIONS PROVIDED CONFLICTS WITH THE | | | DEVELOPED LENGTH SHOWN ON SHT P1. PLEASE | | | CLARIFY. | | | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2001 FUEL GAS CODE SEC 402.2 | | | E. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - | | | PRESSURE ON SHT P-4 GAS RISER DIAGRAM | | | INDICATES 2PSI SYSTEM. PLEASE INDICATE | | | LOCATION OF REGULATORS REDUCING PRESSURE | | | FROM 2PSI TO 1/2PSI. SUBMIT MANUF. | | | SPECIFICATION SHEETS FOR REGULATORS | | | SHOWING LISTING FOR REGULATORS, AND | | | INDICATE VENTING LINES & MATERIAL IF | | | REQUIRED. | | | F. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-02-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-02-17 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-02-17 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2006-02-17 00:00:00 | PARCEL CREATED BY RECORDED MINOR | | | SUBDIVISION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-30 |
Time |
17:41 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-30 |
Time |
17:41 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | DENIED, | | | 1. NEED TO PROVIDE A UNITY OF TITLE FOR | | | PROPERTY. |
|
|