Plan Review Details - Permit 05090897
Plan Review Stops For Permit 05090897
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-22 Cont ID  
Sent By shill Date 2006-03-22 Time 14:25 Rev Time 0.00
Received By shill Date 2006-03-22 Time 14:25 Sent To  
Notes
2006-03-22 00:00:00SEPARATE PERMITS - ROOF REPAIR,
 HARDIBOARD, DOORS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-20 Cont ID  
Sent By shill Date 2006-03-20 Time 16:49 Rev Time 0.00
Received By shill Date 2006-03-20 Time 16:39 Sent To  
Notes
2006-03-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PREVIOUS CORRECTION LISTS HAD
 REQUESTED THAT SCOPE OF WORK REGARDING
 THE ROOF BE CLARIFIED.NOW SHEET 1
 STATES THAT THE ROOF IS TO BE PAINTED
 RATHER THAN REPLACED.S1.2 SPECIFIES
 REPLACEMENT OF SHEATHING WHICH IMPLIES
 THAT ROOF WORK WILL BE DONE.THIS
 COMMENT DOES NOT HAVE TO BE ADDRESSED ON
 THE PLAN BUT BE ADVISED THAT PRODUCT
 APPROVALS FOR THE METAL ROOF WILL BE
 REQUIRED UNDER SEPARATE PERMIT.
  
 2.)THE NEW SHEETS T1 AND A9.1 ARE TO
 BE SIGNED, SEALED, AND DATED.
 FAC61G1-16.STATUTORY REQUIREMENTS
 CANNOT BE WAIVED PER BUILDING OFFICIAL.
  
 3.)REMOVE THE REDUCED ARCHITECTURAL
 SHEETS, EXCEPT FOR THE FOOD SERVICE PLAN
 APPROVAL AND ANY OTHER SHEETS WHICH MAY
 HAVE APPROVALS FROM OTHER GOVERNMENTAL
 ENTITIES.
  
 4.)ON ONE OF THE SETS, SOMEONE HAS
 CHANGED THE 2001 FBC TO 2003 FBC.THE
 OTHER PLAN IS STILL 2001 FBC.THIS
 PROJECT COULD BE PERMITTED UNDER EITHER
 FBC2001 OR FBC2004.IT WAS REVIEWED
 UNDER FBC2001.DECLARE GOVERNING CODE.
 CHANGING THE CODE AT THIS POINT WILL
 RESULT IN ADDITIONAL DELAYS.
  
 5.)PRODUCT APPROVALS HAVE BEEN
 REQUESTED TWICE.ONLY WINDOW PRODUCT
 APPROVALS WERE PROVIDED.ALSO REQUIRED
 ARE PRODUCT APPROVALS FOR SIDING, DOORS,
 AND THE METAL ROOF.SEE ALSO COMMENT #1
 ABOVE.
  
 NEW COMMENTS:
  
 6.)A1.1 DECLARES THIS BUILDING AS TYPE
 II CONSTRUCTION, WHICH REQUIRES THAT ALL
 STRUCTURAL ELEMENTS ARE NONCOMBUSTIBLE
 AND MEET THE FIRE RESISTANCE
 REQUIREMENTS OF FBC TABLE 600, FBC604.
 THIS IS IN CONFLICT WITH THE STRUCTURAL
 DETAILS. IN ADDITION TO REQUIRING
 NONCOMBUSTIBLE CONSTRUCTION AND FIRE
 RATING IN COMPLIANCE WITH TABLE 600,
 COMBUSTIBLES IN CONCEALED SPACES ARE NOT
 ALLOWED AND THIS MUST BE NOTED ON THE
 PLAN IF THE BUILDING IS TO BE A TYPE II.
 NOTE THAT THE NEW STRUCTURAL SHOW
 EXTERIOR COMBUSTIBLE NONBEARING WALLS AS
 WELL AS AN EXISTING COMBUSTIBLE ROOF.
 ADDRESS.
  
 7.)WHEN RESUBMITTING, INCLUDE A
 RESPONSE LETTER INDICATING HOW EACH ITEM
 WAS ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By shill Date 2006-01-23 Time 14:48 Rev Time 2.00
Received By shill Date 2006-01-23 Time 12:34 Sent To  
Notes
2006-02-07 00:00:00**NEW COMMENT 2/7/06**
  
 PLEASE PROVIDE A SURVEY FOR THIS JOB.
  
2006-01-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST, ITEMS NOT ADDRESSED,
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED:
 A. IS LACKING THE LEGAL DESCRIPTION,
 FS713.13,
 B. OWNER INFORMATION CONFLICTS WITH OUR
 RECORDS AND THE PERMIT APPLICATION, AND
 C. HAS BEEN SIGNED BY THE CONTRACTOR.
 IS THE CONTRACTOR THE OWNER OF THIS
 PROPERTY? PROVIDE DOCUMENTATION TO SHOW
 THAT THE INDIVIDUAL SIGNING THE NOC IS
 THE OWNER.
  
 2.) ADDRESSED.
  
 3.)THE DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION STATES THAT THIS IS
 HURRICANE REPAIR WORK.THIS IS AN
 ALTERATION.PLEASE REVISE THE
 APPLICATION TO CORRECTLY REFLECT THE
 SCOPE OF WORK.
  
 4.)THE SCOPE OF WORK IS NOT CLEAR.
 A4.1 STATES THAT THE EXISTING STANDING
 SEAM ROOF IS TO BE PAINTED, T1 STATES
 THAT THIS IS A NEW ROOF.
  
 5.)ADDRESSED.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.
 STANDING SEAM METAL ROOF
 HARDIBOARD SIDING
 SCREW ANCHORS
  
 NO PRODUCT APPROVALS SUBMITTED.ALSO
 REQUIRED ARE PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS.
  
 WHEN RESUBMITTING, REPLACE ONLY SHEETS
 WHICH HAVE CHANGED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-23 Cont ID  
Sent By shill Date 2005-11-23 Time 09:25 Rev Time 3.00
Received By shill Date 2005-11-22 Time 17:35 Sent To  
Notes
2005-11-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED:
 A. IS LACKING THE LEGAL DESCRIPTION,
 FS713.13,
 B. OWNER INFORMATION CONFLICTS WITH OUR
 RECORDS AND THE PERMIT APPLICATION, AND
 C. HAS BEEN SIGNED BY THE CONTRACTOR.
 IS THE CONTRACTOR THE OWNER OF THIS
 PROPERTY? PROVIDE DOCUMENTATION TO SHOW
 THAT THE INDIVIDUAL SIGNING THE NOC IS
 THE OWNER.
  
 2.)THE CA NUMBER FOR VILLA &
 ASSOCIATES IS TO BE ON THE PLAN,
 FAC61G1-16.
  
 3.)THE DESCRIPTION OF WORK ON THE
 PERMIT APPLICATION STATES THAT THIS IS
 HURRICANE REPAIR WORK.THIS IS AN
 ALTERATION.PLEASE REVISE THE
 APPLICATION TO CORRECTLY REFLECT THE
 SCOPE OF WORK.
  
 4.)THE SCOPE OF WORK IS NOT CLEAR.
 A4.1 STATES THAT THE EXISTING STANDING
 SEAM ROOF IS TO BE PAINTED, T1 STATES
 THAT THIS IS A NEW ROOF.
  
 5.)THE DEMO PLAN, A1.0, CONFLICTS WITH
 THE OTHER SHEETS AS TO THE ORIENTATION
 OF THE BUILDING.
  
 6.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FAC9B72.
 STANDING SEAM METAL ROOF
 HARDIBOARD SIDING
 SCREW ANCHORS
  
 7.)THIS IS AN OVER 50% IMPROVEMENT,
 SEE FBC3401.7.2.6.
  
 8.)PROVIDE ROOM DESIGNATIONS ON THE
 FLOOR PLAN, A1.1.
  
 9.)FBC11-4.1(3), WORK AREAS ARE TO BE
 CONSTRUCTED SO THAT INDIVIDUALS WITH
 DISABILITIES CAN APPROACH, ENTER, AND
 EXIT THE AREAS.SHOW COMPLIANCE.SHEET
 A1.2.
  
 10.)THE DOOR TO THE KITCHEN LACKS THE
 CLEARANCE REQUIRED, PULL SIDE, FBC11
 FIGURE 25, FBC11-4.13.6.
  
 11.)THE MENS' BATHROOM DOOR AND THE
 OFFICE DOOR LACK THE CLEARANCE REQUIRED,
 PUSH SIDE, IF THE DOOR HAS A CLOSER AND
 A LATCH, FBC11 FIGURE 25, FBC11-4.13.6.
  
  
 12.)PROVIDE THE DIMENSION ON THE PLAN
 TO SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 26 TWO HINGED DOORS IN A
 SERIES (BATHROOM).
  
 13.)SHOW ACCESSIBLE SEATING,
 FBC11-5.1.
  
 14.)SHOW ACCESS AISLE, FBC11-5.3.
  
 15.)PROVIDE A DETAIL FOR THE FOOD
 SERVICE AREAS, FBC11-5.5.
  
 16.)IS THERE A TABLEWARE/CONDIMENT
 AREA?PROVIDE A DETAIL, FBC11-5.6.
  
 17.)WHAT IS THE HEIGHT OF THE TABLES
 919, SHEET A1.2?SEE FBC11-5.2.
  
 18.)SHEET A2.1 SHOWS EXIT LIGHTS ON
 THE LEGEND BUT NONE ON THE PLAN.PLEASE
 MAKE CONSISTENT WITH E1.1.
  
 19.)INCLUDE THE DOOR DIMENSION ON THE
 PLAN FOR ALL EGRESS DOORS AND DOORS
 REQUIRED TO BE ACCESSIBLE.
  
 20.)SPECIFY INTERIOR FINISH
 CLASSIFICATION, FBC TABLE 803.3.
  
 21.)WHEN RESUBMITTING, PLEASE REPLACE
 ONLY SHEETS WHICH HAVE CHANGED.TO
 EXPEDITE PLAN REVIEW, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2007-01-31 Cont ID  
Sent By dpalmer Date 2007-01-31 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2007-01-31 Time 14:50 Sent To PC
Notes
2007-01-31 14:50:33REV'S FOR FINAL.

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-01-28 Cont ID  
Sent By dpalmer Date 2007-01-28 Time 16:43 Rev Time 0.00
Received By dpalmer Date 2007-01-28 Time 16:14 Sent To PC
Notes
2007-01-28 16:46:14** UNSAT **
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF SIGNED,
 DATED AND SEALED PLANS. PLEASE KNOW THAT ONE COPY WILL
 STAMPED ONCE REVIEWED FOR CODE COMPLIANCE AND BE
 RETAINED FOR PERMANENT RECORD SET OF PLANS FOR JOB AND
 ONE WILL STAMPED FOR CONTRACTOR'S COPY ON JOB SITE
 RECORD SET OF PLANS. PLEASE SEE ONLY ONE SET WAS
 SUBMITTED FOR REVIEW AND STAMPING. PLEASE SUBMIT.
  
 *PLEASE SEE COVER SHEET WHICH WAS FILLED OUT BY
 CONTRACTOR STATES ONLY ONE SET SUBMITTED.
  
 FBC 104.1 ADMIN SECTION. FAC 61G15-23.002, FS 471.025
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 08:32 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 08:23 Sent To PC
Notes
2006-11-14 08:34:19***** UNSAT *****
  
 1) NOTE: PLEASE SEE ADDITIONAL CIRCUITING, TRACK
 LIGHTING ETC WILL REQUIRE PANEL SCHEDULES AND LOADS TO
 BE REVISED ON OTHER SHEETS NOT SUBMITTED.
 220, 220.12 , ALSO CONTINUOUS LOADS PER 215.3, 230.42
 ETC.
  
 2) NOTE: PLEASE BE SURE ALL PLANS ARE SIGNED, DATED AND
 SEALED BY THE DESIGNER OF RECORD AS REQUIRED UNDER THE
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND FLORIDA
 STATUTES 471.025
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-16 Cont ID  
Sent By dpalmer Date 2006-09-16 Time 19:29 Rev Time 0.00
Received By dpalmer Date 2006-09-16 Time 19:18 Sent To PC
Notes
2006-09-16 00:00:00REV OK , REVISED SERVICE MAIN AND
 GROUNDING ELECTRODE/SYSTEM.
  
  
 GFI'S IN KITCHEN AREA ARE TO BE VERIFIED
 IN FIELD AS NO REVSION WAS SUBMITTED FOR
 REDLINED NOTES.210.8B3

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-23 Cont ID  
Sent By dpalmer Date 2006-01-23 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2006-01-23 Time 10:44 Sent To  
Notes
2006-01-23 00:00:00PERMIT EXPEDITOR CAME IN AND CORRECTED
 SETS.
 SEE THE FOLLOWING FOR REDLINED ITEMS.
  
  
  
  
  
 1)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED
 PER FS 713.13(2).
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING OF SAID NOC. THE NOC SHALL
 BECOME VOID AND WILL BE REQUIRED TO BE
 RE-RECORDED BEFORE PICKING UP OF PERMIT.
  
  
 ** REDLINED,
  
 2002NEC210.8B3 AS SOME KITCHEN AREA
 RECEPTS DO NOT APPEAR TO BE NOTED OR
 CONTAIN GFI RECEPTS/PROTECTION AS
 REQUIRED.
 PLEASE SEE AREAS CONTAING EQUIPMENT FOR
 KITCHEN, FOOD PREP ETC SHALL BE
 CONSIDERED PART OF THE KITCHEN AREA.
  
 ** REDLINED ,
 250.6,250.24 FOR THE "BOND" SHOWN FROM
 METER CT CAN.
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 11:58 Sent To  
Notes
2006-01-20 00:00:00****** NOTES,
 PLANS TO REMAIN IN "F" STATUS UNTIL NOTE
 #1 BELOW IS ADDRESSED.
  
  
 1)NOTE: AS REQUESTED ON PREVIOUS REVIEW;
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO THE COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE ONLY .
 **THIS WAS NOT DONE AND A REPRESENTIVE
 FOR PROJECT SHOULD SET UP A TIME WITH
 PLAN REVIEW STAFF TO COME INTO OFFICE TO
 REMOVE SHEETS AND MAKE TWO CLEAN SETS.
  
 2)NOTE: PLEASE SEE NOC HAS SINCE EXPIRED
 PER FS 713.13(2).
 IF WORK HAS NOT COMMENCED WITHIN 90 DAYS
 OF RECORDING OF SAID NOC. THE NOC SHALL
 BECOME VOID AND WILL BE REQUIRED TO BE
 RE-RECORDED BEFORE PICKING UP OF PERMIT.
  
  
 ** REDLINED,
  
 2002NEC210.8B3 AS SOME KITCHEN AREA
 RECEPTS DO NOT APPEAR TO BE NOTED OR
 CONTAIN GFI RECEPTS/PROTECTION AS
 REQUIRED.
 PLEASE SEE AREAS CONTAING EQUIPMENT FOR
 KITCHEN, FOOD PREP ETC SHALL BE
 CONSIDERED PART OF THE KITCHEN AREA.
  
 ** REDLINED ,
 250.6,250.24 FOR THE "BOND" SHOWN FROM
 METER CT CAN.
 THE GROUNDING OF ELECTRICAL SYSTEMS,
 CIRCUIT CONDUCTORS, SURGE ARRESTERS, AND
 CONDUCTIVE NON?CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE
 INSTALLED AND ARRANGED IN A MANNER THAT
 WILL PREVENT OBJECTIONABLE CURRENT OVER
 THE GROUNDING CONDUCTORS OR GROUNDING
 PATHS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-13 Cont ID  
Sent By dpalmer Date 2005-10-13 Time 13:44 Rev Time 2.00
Received By dpalmer Date 2005-10-13 Time 13:30 Sent To  
Notes
2005-10-13 00:00:00****** UNSAT *******
  
 1)NOTE: PLEASE INCLUDE RECEPTS REQUIRED
 ABOVE ALL OUTSIDE WINDOWS.210.62
 THESE WILL BE REQUIRED TO DISCOURAGE
 FLOOR RECEPTACLES AND UNSIGHTLY
 EXTENSION CORDS LIKELY TO CAUSE PHYSICAL
 INJURY, RECEPTACLES MUST BE INSTALLED
 DIRECTLY ABOVE A SHOW WINDOW, AND ONE
 RECEPTACLE IS REQUIRED FOR EVERY 12
 LINEAR FT OR ?MAJOR FRACTION THEREOF? (6
 FT OR MORE). SEE 220.3(B)(7) AND
 220.12(A) FOR INFORMATION REGARDING LOAD
 COMPUTATIONS FOR SHOW WINDOWS.
 THESE ARE MAINLY USED FOR SIGNAGE WHICH
 IS TYPICALLY INSTALLED ABOVE WINDOWS.
  
 2)NOTE: PLEASE SEE 600.5 FOR MIN SIGN
 CIRCUIT REQUIRED AT FRONT ENTRANCE
 LOCATION SUBJECT TO PEDESTRIAN TRAFFIC.
  
 3)NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING" CONDUCTOR IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE 250.6,250.24, THE "EQUIPMENT
 GROUNDING CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 4)NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SEEMS TO BE MISSING THE REQUIRED
 CONNECTION TO THE COLD WATER PIPE.
 250.50
  
 5)NOTE: PLEASE SEE "DP" WILL BE REQUIRED
 TO CONTAIN A MCB AS PANEL IS SHOWN AS
 MLO WITH MORE THAN 6 SPACES.
 PLEASE INDICATE THE AS MCB.
 PLEASE KNOW THE MCB WILL ONLY BE
 REQUIRED TO HAVE THE 65,000 AIC RATED
 MAIN AND OTHER BREAKERS IN PANEL MAY BE
 RATED FOR SERIES RATING.
 110.9, 230.70
  
 6)NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLING UNITS
 FOR GFI PROTECTION OF ALL 15/20A 120 V
 RECEPTS.
  
 **PLEASE BE SURE TO SEE FIE REVIEW
 COMMENTS AND ANY POSSIBLE COMMENT SFORM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-10-11 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By mcarsill Date 2006-01-20 Time 14:03 Rev Time 0.00
Received By mcarsill Date 2006-01-20 Time 14:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By mwennerg Date 2005-10-11 Time 13:47 Rev Time 0.00
Received By mwennerg Date 2005-10-11 Time 13:47 Sent To  
Notes
2005-10-11 00:00:00******DENIED******
  
 1) AN ADDRESS ON BUILDING IS REQUIRED
 AND SHALL BE A MINIMUM OF 6" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 2) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
 PLEASE ILLUSTRATE IN TERMS OF CLASS A,B,
 OR C.
  
 3) PLEASE INDICATE THE OCCUPANT LOAD. A
 NEW OCCUPANT LOAD SIGN WILL BE ISSUED
 PRIOR TO OR AT THE TIME OF THE FINAL
 FIRE INSPECTION.
  
 4) PLEASE EXPLAIN THE RELOCATION OF FIRE
 SPRINKLER HEADS ABOVE DRAFT CURTAIN?
  
 5) IN ADDITION TO A "K" TYPE FIRE
 EXTINGUISHER IN THE KITCHEN, 2A-10B,C
 RATED FIRE EXTINGUISHERS ARE REQUIRED.
  
 6) VISUAL/AUDIBLE WARNING DEVICES SHALL
 BE INSTALLED IN THE AREA OF DUCT SMOKE
 DETECTORS.
  
 7) PLANS MENTION HOOD/SUPPRESSION
 SYSTEMS. SEPARATE SHOP DRAWINGS AND
 PERMITS WILL BE REQUIRED.
  
  
 MIKE WENNERGREN, CAPTAIN
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-09-16 Cont ID  
Sent By kstevens Date 2006-09-16 Time 06:47 Rev Time 0.00
Received By kstevens Date 2006-09-16 Time 06:47 Sent To  
Notes
2006-09-16 00:00:00GAS REVISION OK - CHANGED PIPE SIZE TO
 PIZZA OVEN TO 1-1/2". SHEETS P-1 & P-4

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-03-10 Cont ID  
Sent By pschmitz Date 2006-03-10 Time 11:21 Rev Time 0.00
Received By pschmitz Date 2006-03-10 Time 11:21 Sent To P
Notes
2006-03-10 00:00:00RE-SUB
 SEPRERATE PERMIT FOR GAS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-28 Cont ID  
Sent By pschmitz Date 2006-01-28 Time 10:28 Rev Time 0.00
Received By pschmitz Date 2006-01-28 Time 10:28 Sent To  
Notes
2006-01-28 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 PREVIEW
 GASDENIED
 PREVIOUS COMMENTS DATED 11-26-05 NOT
 ADDRESSED.
  
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 E. SUBMIT MANFACTURE SPECIFICATION
 SHEETS FOR REGULATORS SHOWING LISTING
 FOR REGULATORS, AND INDICATE VENTING
 LINES & MATERIAL IF
 REQUIRED.
 NEW COMMENT: "SEPERATE GAS PERMIT"
 END OF COMMENTS,QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 11:29 Sent To E
Notes
2007-01-24 11:30:13TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-08 Cont ID  
Sent By adarroug Date 2006-11-08 Time 16:04 Rev Time 0.00
Received By adarroug Date 2006-11-08 Time 16:04 Sent To E
Notes
2006-11-08 16:05:18TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 13:44 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 13:44 Sent To E
Notes
2006-09-09 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 18:44 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 18:44 Sent To P
Notes
2006-09-08 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 16:54 Sent To  
Notes
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 11:37 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 11:37 Sent To  
Notes
2006-01-19 00:00:00TO "COMM" BD#29
2005-12-19 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-11-26 Time 11:36 Rev Time 0.00
Received By adarroug Date 2005-09-22 Time 16:33 Sent To  
Notes
2005-09-23 00:00:00TO "COMM" BD#9
2005-09-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-05 Cont ID  
Sent By hmoser Date 2006-07-05 Time 11:06 Rev Time 0.00
Received By hmoser Date 2006-07-05 Time 11:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-16 Cont ID  
Sent By pkrauss Date 2006-01-31 Time 16:03 Rev Time 0.00
Received By pkrauss Date 2006-01-31 Time 15:52 Sent To  
Notes
2006-01-31 00:00:00PROVISO:
 ADDITIONAL PERMITS REQUIRED FOR HOODS &
 WALK-IN COOLER.PLEASE PROVIDE THE
 FOLLOWING INFORMATION WITH PERMIT
 APPLICATION:
  
 1. MANUFACTURER'S SUBMITTAL DATA
 2. TYPE AND GAUGE OF METAL FOR HOODS &
 GREASE DUCT.
 3. AIR BALANCE SCHEDULE.
 4. TERMINATION OF GREASE DUCT IN
 IN RELATION TO PROPERTY LINES,
  
 PARAPETS, ADJACENT BUILDINGS, FRESH
 AIR INTAKES, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By hmoser Date 2005-11-08 Time 18:20 Rev Time 0.00
Received By hmoser Date 2005-11-08 Time 18:04 Sent To  
Notes
2005-11-08 00:00:00PLAN DENIED
 1) PLEASE PROVIDE FRESH AIR CALCULATIONS
 PER TABLE 403.3 FBC(M)
 2) PLEASE REFER TO SECTION 606.2.1
 SUPPLY AIR SYSTEM AND 606.4.1
 SUPERVISION.
 3) ADDITIONAL PERMITS ARE REQUIRED FOR
 HOODS AND WALK IN COOLERS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-10 Cont ID  
Sent By pschmitz Date 2006-03-10 Time 12:45 Rev Time 0.00
Received By pschmitz Date 2006-03-10 Time 12:45 Sent To  
Notes
2006-03-10 00:00:00ALL WORK SUBJECT TO FIELD INSPECTOR.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-28 Cont ID  
Sent By pschmitz Date 2006-01-28 Time 10:47 Rev Time 0.00
Received By pschmitz Date 2006-01-28 Time 10:47 Sent To  
Notes
2006-01-28 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 PREVIEW.
 PLUMBINGDENIED
 PREVIOUS COMMENTS DATED 11-26-05 NOT
 ADDRESSED.
 PLAN REVIEW COMMENTS SHALL BE RESPONDED
 TO BY THE DESIGN PROFESSIONALS. REFERING
 TO EACH OTHER OR CONTRACTOR, IS NOT
 HELPFUL IN EXPEDITING YOUR PERMIT.
  
 2. APPLICATION INDICATES "REPAIR STORM
 DAMAGE", BUT NEW FLOOR PLAN INDICATES
 ALTERATION OF SPACE. PLEASE DESCRIBE
 PROJECT IN DETAIL AS REQUIRED ON
 APPLICATION FOR PERMIT.
  
 5. PLANS SHALL BE ROUTED TO STATE OF
 FLORIDA DBPR HOTEL AND RESTURANT DIV.
 FOR REVIEW PRIOR TO RESUBMITTING TO CITY
 WPB FOR REVIEW.
 MINIMUM 2 COPIES STAMPED
 BY DBPR WITH 2 PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SECTION 101.4.7. CONTACT
 NUMBER FOR DBPR IS (850) 487-1395
  
 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO
 GUTTER, DOWN SPOUTS
 CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND SHALL
 TERMINATE TO A STORM CATCH BASIN,
 PLANTED AREA OR A DRYWELL. IF CONNECTED
 TO A CATCH BASIN, A RELIEF VENT IS
 REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. CITY CODE 90-125(B)(5).
  
 12. SHT P1 WATER FILTER SHALL COMPLY
 WITH NSF 42. SUBMIT MANUF. SPECIFICATION
 SHOWING COMPLIANCE. SECTION 611.1
  
 16.SEPERATE GAS STOP FOR GAS.
 END OF COMMNENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-26 Cont ID  
Sent By kstevens Date 2005-11-26 Time 10:01 Rev Time 3.50
Received By kstevens Date 2005-11-26 Time 10:01 Sent To  
Notes
2005-11-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WPB CITY CODE
  
 1. SHTS T1 THRU A9.1 FIRM LICENSE NUMBER
 IS REQUIRED IN THE TITLE BLOCK OF THE
 ARCHITECT ON EACH SHEET. FAC
 61G1-16.004(2) & FS 481.219 FS 481.2055.
 2. APPLICATION INDICATES "REPAIR STORM
 DAMAGE", BUT NEW FLOOR PLAN INDICATES
 ALTERATION OF SPACE. PLEASE DESCRIBE
 PROJECT IN DETAIL AS REQUIRED ON
 APPLICATION FOR PERMIT.
 3. SHT A1.1 TOILET IN WOMEN'S TOILET
 INDICATEED AS 11-1/8" OFF THE WALL TO
 THE CENTER OF THE W/C. MINIMUM CLEARANCE
 FOR W/C'S IS 15" OFF WALL TO CENTER OF
 FIXTURE. MINIMUM 30" FINISH OPENING
 REQUIRED FOR THIS TOILET. SECTION
 405.3.1. INDICATE ON FLOOR PLAN.
 4. SHT A1.1 TURNING AREA SHALL BE IN THE
 TOILET ROOM, NOT IN THE STALL. PLEASE
 SHOW AREA IN TOILET ROOM. SECTION
 11-4.22.3.
 5. PLANS SHALL BE ROUTED TO STATE OF
 FLORIDA DBPR HOTEL AND RESTURANT DIV.
 FOR REVIEW PRIOR TO RESUBMITTING TO CITY
 WPB FOR REVIEW. MINIMUM 2 COPIES STAMPED
 BY DBPR WITH 2 PAGE "WORKSHEETS"
 ATTACHED TO EACH SET OF PLANS SUBMITTED
 FOR REVIEW. SECTION 101.4.7. CONTACT
 NUMBER FOR DBPR IS (850) 487-1395
 6. SHTS A1.2 & A1.3 EQUIPMENT LAYOUT
 PLAN DOES NOT REFLECT THE EQUIPMENT
 SCHEDULE. AE #53, AE #410, & AE #416 NOT
 FOUND ON LAYOUT PLAN. AE #426 FOUND ON
 FLOOR PLAN DOES NOT INDICATE WATER
 SUPPLY OR DRAIN ON EQUIPMENT SECHEDULE.
 PLEASE CLARIFY. SECTION 104.2.1.
 7. SHTS A4.1 & A4.2 INDICATES "NEW
 PARAPET SEE DETAIL SHEET S1 FOR DETAILS"
 NO SHT S1 SUBMITTED, NO DETAIL FOUND.
 PLEASE CLARIFY. SECTION 104.2.1.
 8. SHT A8.2 RESTROOM ELEVATIONS. PLEASE
 SHOW THE FOLLOWING INFORMATION:
 A. 11-4.16.3 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 D. 11-4.19.5 FAUCETS
 9. SHT P1 CONDENSATE SHALL NOT DRAIN TO
 SANITARY SYSTEM. CONDENSATE SHALL DRAIN
 SEPARATELY OUT OF THE BUILDING AND SHALL
 TERMINATE TO A STORM CATCH BASIN,
 PLANTED AREA OR A DRYWELL. IF CONNECTED
 TO A CATCH BASIN, A RELIEF VENT IS
 REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. CITY CODE 90-125(B)(5).
 10. SHT P1 ALL FLOOR DRAINS IN THE
 KITCHEN AND DISHWASH AREAS AND THE MOP
 SINK SHALL DRAIN INTO THE GREASE SYSTEM,
 NOT THE SANT. SYSTEM. - ALSO SHOW THESE
 CHANGES ON THE SANT./GREASE ISOMETRIC
 RISER DIAGRAM.
 11. SHT P1 THE NEW GREASE INTERCEPTORS
 SHALL BE SIZED BY LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE
 CONTACT HER AT (561) 822-2271, OR FAX
 (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. #3434.
 12. SHT P1 WATER FILTER SHALL COMPLY
 WITH NSF 42. SUBMIT MANUF. SPECIFICATION
 SHOWING COMPLIANCE. SECTION 611.1
 13. SHT P2 DETAIL #1 GAS WATER HEATER
 DRAIN LINE SHALL DRAIN TO A FLOOR SINK
 OR HUB DRAIN. FLOOR DRAINS ARE NOT AN
 APPROVED INDIRECT WASTE INTERCEPTOR.
 SECTIONS 802.3 & 802.3.2. INDICATE WHERE
 T & P RELIEF VALVE WILL TERMINATE.
 SECTION 504.7.1
 14. SHT P2 DETAIL #5 GREASE INTERCEPTORS
 LIDS TO BE STAMPED "GREASE" NOT SANT. AS
 INDICATED. - A 2-WAY CLEANOUT IS
 REQUIRED UPSTREAM OF THE ENTERANCE OF
 THE GREASE INTERCEPTORS AS WELL AS AT
 THE EXITS.
 15. SUBMIT A WATER RISER ISOMETRIC
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. WATER HAMMER ARRESTORS
 SHALL BE LOCTED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 16. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). - ADDING CUT
 SECTIONS PROVIDED CONFLICTS WITH THE
 DEVELOPED LENGTH SHOWN ON SHT P1. PLEASE
 CLARIFY.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -
 PRESSURE ON SHT P-4 GAS RISER DIAGRAM
 INDICATES 2PSI SYSTEM. PLEASE INDICATE
 LOCATION OF REGULATORS REDUCING PRESSURE
 FROM 2PSI TO 1/2PSI. SUBMIT MANUF.
 SPECIFICATION SHEETS FOR REGULATORS
 SHOWING LISTING FOR REGULATORS, AND
 INDICATE VENTING LINES & MATERIAL IF
 REQUIRED.
 F. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-17 Cont ID  
Sent By eschneid Date 2006-02-17 Time 13:46 Rev Time 0.00
Received By eschneid Date 2006-02-17 Time 13:46 Sent To  
Notes
2006-02-17 00:00:00PARCEL CREATED BY RECORDED MINOR
 SUBDIVISION.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By mmclean Date 2006-01-30 Time 17:41 Rev Time 0.00
Received By mmclean Date 2006-01-30 Time 17:41 Sent To  
Notes
2006-01-30 00:00:00DENIED,
 1. NEED TO PROVIDE A UNITY OF TITLE FOR
 PROPERTY.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved