| Plan Review Stops For Permit 05090770 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-03-27 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-27 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-03-27 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2006-03-27 00:00:00 | USE NEW ADDR 785 W EXECUTIVE CENTER DR | | | (EXT #0003 FOR 751 W EXECUTIVE CENTER | | | DR) FOR GOLFSMITH. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-05-10 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-05-10 |
Time |
09:10 |
Sent To |
PC |
|
| Notes |
| 2007-05-10 09:16:09 | ENGINEERS LETTER, PAVING, DRAINAGE WATER, SEWER. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2007-05-08 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2007-05-08 |
Time |
09:17 |
Sent To |
PC |
|
| Notes |
| 2007-05-08 09:20:32 | SUBMITTAL DATED 5-2-07 ENGINEERS CERTIFICATIOIN | | | DENIED | | | ASBUILT SEAL REQUIRED IN TITLE BLOCK. | | | ALL DOUCMENTS TO BE SIGNED AND SEALED BY ENGINEER OF | | | RECORD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2006-11-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-11-22 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-11-22 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2006-11-22 15:43:14 | REVISION, VARIOUS DATES, T1, A0.1, A1.1, A2.0, A2.1, | | | A2.4, A4.0, S304 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-19 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-19 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)FBC1006.3.8, EXIT SIGNS SHOWN | | | PREVIOUSLY ON THE LIFE SAFETY PLAN. | | | | | | 2.)A2.0, PARKING IS TO COMPLY WITH | | | CITY OF WEST PALM BEACH STANDARD, SEE | | | ATTACHED. | | | | | | 3.)LOCATION OF PUSH BUTTON FOR THE | | | AUTO DOOR OPENER APPEARS HAZARDOUS. | | | ONCE ACTIVATED, HOW MUCH TIME DOES THE | | | USER HAVE TO GET OUT OF THE WAY OF THE | | | MOVING DOOR?SEE SHEET A2.1, ENLARGED | | | ENTRANCE PLAN. | | | | | | 4.)ENERGY CALCS ARE TO BE REVISED TO | | | REFLECT NEW UNDER AIR AREA. | | | | | | 5.)REVISE PROJECT VALUATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-06-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-27 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-23 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2006-06-27 00:00:00 | ***PROVISO*** | | | PARKING TO COMPLY WITH CITY OF WPB | | | STANDARD | | | | | | SUBMIT 3RD SET TO BE STAMPED (AFTER | | | PERMIT ISSUANCE) | | | | | | CIVIL SHEETS TO BE SUBMITTED AS A | | | REVISION TO #06030742 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-06-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-06-21 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-06-21 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2006-06-21 00:00:00 | ****CORRECTIONS**** | | | ****THIRD REVIEW (SECOND PERMIT | | | REVIEW)**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | FROM PREVIOUS REVIEWS, NUMBERING | | | REMAINING THE SAME. | | | | | | 1.)ADDRESSED.PLEASE KEEP THE NOC IN | | | THE PACKAGE. | | | | | | 2.)ADDRESSED.PLEASE KEEP IMPACT FEE | | | STAMPED PAGE AND RECEIPT IN THE PACKAGE. | | | | | | 3.-5.)ADDRESSED. | | | | | | 6.)THIRD REQUEST FOR THREE SETS OF | | | PLANS.ONLY TWO SUBMITTED. | | | | | | 7.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS, FBC13-103.1. | | | | | | (2ND REVIEW) THIS WAS SIGNED.HOWEVER, | | | SEE OTHER | | | CORRECTIONS REGARDING ENERGY CALCS.IF | | | NEW ENERGY CALCS ARE PRODUCED PLEASE | | | SIGN THE NEW CALCS.THREE COPIES ARE | | | REQUIRED. | | | | | | (3RD REVIEW) SEE OTHER COMMENTS | | | REGARDING ENERGY CALCS.SUBMIT THREE | | | COPIES, ONLY ONE NEW AND TWO OLD ENERGY | | | CALCS SUBMITTED. | | | | | | 8-11.)ADDRESSED. | | | | | | 12.)IT APPEARS THAT ALL REFERENCES | | | HAVE BEEN REVISEDEXCEPT THAT S-001 | | | STILL REFERS TO ACI347R-94.IT IS | | | CLOUDED BUT NOT REVISED. | | | | | | 13-23.)ADDRESSED. | | | | | | COMMENTS FROM 2ND REVIEW, NOT ADDRESSED: | | | | | | 24.)ADDRESSED. | | | | | | 25.)THE ENERGY CALCS, CIVILS, AND | | | ARCHITECTURALS CONFLICT AS TO THE | | | BUILDING SIZE.NOTE THAT IMPACT FEE | | | ASSESSMENT REVISION MAY BE REQUIRED WHEN | | | THE ACTUAL BUILDING SIZE IS DETERMINED. | | | | | | 3RD REVIEW ? THE LETTER FROM THE | | | ARCHITECT REGARDING THE DISCREPANCY IN | | | SQUARE FOOTAGE ON THE ENERGY CALC IS | | | ACKNOWLEDGED.PLEASE SEE FBC13-2, | | | DEFINITIONS, CONDITIONED FLOOR AREA, TO | | | BE MEASURED EXTERIOR FACES OF EXTERIOR | | | WALLS.REVISE THE ENERGY CALCS; SQUARE | | | FOOT AREA TO MATCH ARCHITECTURAL PLAN. | | | | | | 26.)ADDRESSED | | | | | | 27.)NOTHING ON THE SHEET 5 OF THE | | | ENERGY CALCS IS MARKED AS BEING CHECKED. | | | THIS IS REQUIRED TO SHOW CODE COMPLIANCE | | | FBC13-103.1.1.1. | | | | | | 3RD REVIEW ? NOT ADDRESSED.HOWEVER, | | | THIS WAS ON PAGE 5 OF THE OLD ENERGY | | | CALC, NOW APPEARS ON PAGE 6.EITHER | | | CHECK OR MARK N/A TO SHOW CODE | | | COMPLIANCE, CANNOT BE LEFT BLANK. | | | | | | 28-33.)ADDRESSED | | | | | | 33.)PARKING IS TO COMPLY WITH CITY OF | | | WEST PALM BEACH STANDARD, SEE ATTACHED. | | | | | | THE NOTE STATING THAT THEY WILL CONFORM | | | TO THE STANDARD IS ACKNOWLEDGED. | | | HOWEVER, THE DETAILS ON THE | | | ARCHITECTURAL AND CIVIL SHEETS DO NOT | | | COMPLY.REVISE. | | | | | | 34.)ADDRESSED. | | | | | | 35.)S103, CLARIFY AS TO WHY TWO OF THE | | | CORNERS ARE ZONE 2 RATHER THAN ZONE 3. | | | FBC16. | | | | | | THE RESPONSE FROM THE ARCHITECT THAT | | | THOSE CORNERS ARE PROTECTED BY A PARAPET | | | WALL IS ACKNOWLEDGED.HOWEVER, SEE | | | ASCE7-02, SECTION 6.5.12.4.4 REGARDING | | | PARAPETS.SHOW ZONE 3 ON ALL CORNERS AS | | | REQUIRED BY ASCE7-02 DESIGN STANDARDS. | | | | | | THE SHEET WAS REVISED TO STATE FBC2001. | | | GOVERNING CODE IS FBC2004.REVISE. | | | | | | 36.)ADDRESSED. | | | | | | 37.)PROVIDE A FIRE SPRINKLER PLAN | | | FBC*106.3.5.1.1(5). | | | | | | THE ARCHITECT?S RESPONSE THAT THE | | | SPRINKLER PLANS WERE PROVIDED IS | | | ACKNOWLEDGED.HOWEVER, I AM UNABLE TO | | | FIND THEM IN THE PACKAGE SUBMITTED. | | | | | | NEW COMMENTS, THIRD REVIEW | | | | | | 38.)ROOF PRESSURES ON THE RAS117 | | | CALCULATIONS PREPARED BY ACRC ARE LOWER | | | FOR ZONE 3 THAN THE PLAN.THIS MAY BE | | | SUBMITTED LATER; NOT REQUIRED. | | | | | | 39.)THE FIRE SPRINKLER ENGINEERING IS | | | TO COMPLY WITH ALL REQUIREMENTS OF | | | FAC61G15-23.002 (TITLE BLOCK, INDEX | | | SHEET).THIS MAY BE SUBMITTED LATER | | | WITH THE FIRE SPRINKLER PERMIT | | | APPLICATION. | | | | | | 40.) THE CERTIFICATE OF FLAME RESISTANCE | | | SUBMITTED FOR THE AWNING FABRIC DOES NOT | | | SHOW COMPLIANCE WITH FBC3105.3.1. | | | PLEASE NOTE THAT THIS INFORMATION IS NOT | | | REQUIRED AT THIS TIME; THIS CAN BE | | | PROVIDED WITH THE AWNING PERMIT | | | APPLICATION. | | | | | | 41.) PLEASE REVISE THE ADDRESS ON THE | | | PLANS.THIS MAY BE DONE BY HAND.I | | | APOLOGIZE THAT I AGREED THAT THIS MAY BE | | | DONE BY LETTER; HOWEVER, I DID NOT | | | REALIZE AT THAT TIME THAT THE ADDRESS ON | | | THE PLAN WAS NOT THE ADDRESS FOR THE | | | PARCEL.THE ADDRESS SHOWN ON THE PLAN, | | | 201 EXECUTIVE CENTER DRIVE, DOES NOT | | | EXIST.I THOUGHT THAT THE ADDRESS ON | | | THE PLAN WAS 715 W EXECUTIVE CENTER | | | DRIVE, WHICH IS THE SAME PARCEL AS 785 W | | | EXECUTIVE CENTER DRIVE.MY APOLOGIES | | | FOR ANY INCONVENIENCE. | | | | | | 42.)SEE ATTACHED FS553.80(2)(B).A 4X | | | PLAN REVIEW FEE IS REQUIRED TO BE | | | CHARGED IF THE CORRECTIONS ARE NOT | | | ADDRESSED A THIRD TIME. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-03-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-03-24 |
Time |
19:01 |
Rev Time |
8.00 |
| Received By |
shill |
Date |
2006-03-24 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2006-03-24 00:00:00 | ****CORRECTIONS**** | | | ****SECOND REVIEW (FIRST PERMIT | | | REVIEW)**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | FROM PREVIOUS REVIEW, NUMBERING | | | REMAINING THE SAME.ITEMS IN CAPITAL | | | LETTERS ARE COMMENTS FROM THE SECOND | | | REVIEW, WITH THE EXCEPTION OF THE LAST | | | ITEMS WHICH ARE NEW COMMENTS. | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | THIS HAS BEEN DONE.PLEASE KEEP THE | | | STAMPED SHEET AND THE RECEIPT IN THE | | | PACKAGE WHEN RESUBMITTING. | | | | | | 3.)ADDRESSED. | | | | | | 4.-5.)ADDRESSED. | | | | | | 6.)THREE SETS OF PLANS AND ALL | | | DOCUMENTS REQUIRED; RESIDENT INSPECTOR | | | REQUIRED, FBC*109.3.7.PLEASE CONTACT | | | HAROLD PISKURA, 561-805-6711. | | | | | | NOT ADDRESSED; ONLY TWO COPIES SUBMITTED | | | ALTHOUGH THE RESPONSE LETTER STATES THAT | | | THREE WERE SUBMITTED. | | | | | | THE RESPONSE THAT THIS WILL BE DONE | | | PRIOR TO CONSTRUCTION IS ACKNOWLEDGED. | | | NOTE THAT THIS IS REQUIRED PRIOR TO | | | PERMIT ISSUANCE.TO AVOID FURTHER | | | DELAYS, CONTACT HAROLD PISKURA AS | | | REQUESTED.THE PRECONSTRUCTION MEETING | | | AND INSPECTION PLAN APPROVED BY THE CITY | | | ARE REQUIRED PRIOR TO PERMIT ISSUANCE. | | | | | | 7.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS, FBC13-103.1. | | | | | | THIS WAS SIGNED.HOWEVER, SEE OTHER | | | CORRECTIONS REGARDING ENERGY CALCS.IF | | | NEW ENERGY CALCS ARE PRODUCED PLEASE | | | SIGN THE NEW CALCS.THREE COPIES ARE | | | REQUIRED. | | | | | | 8.)ADDRESSED. | | | | | | 9.)SUBMIT PRODUCT APPROVALS, FAC9B72: | | | | | | ROOF | | | STOREFRONT SYSTEM | | | HOLLOW METAL DOOR | | | ROLL UP DOOR | | | GLASS BLOCK | | | | | | IF THE PRODUCTS SELECTED DO NOT MEET | | | WORST CASE WIND PRESSURES AS SPECIFIED | | | ON S-501, SUBMIT A SCHEDULE SPECIFYING | | | PRESSURES FOR EACH OPENING. | | | | | | FOR THE ROOF PRODUCT APPROVAL, INDICATE | | | WHICH APPROVED ASSEMBLY YOU ARE USING. | | | SEE S-103 FOR ROOF PRESSURES. | | | | | | THREE COPIES OF ALL DOCUMENTS REQUIRED. | | | ONLY TWO WERE SUBMITTED. | | | | | | FLORIDA STATE OR LOCAL PRODUCT APPROVALS | | | REQUIRED IN ADDITION TO THE NOAS | | | PROVIDED, WWW.FLORIDABUILDING.ORG. | | | PLEASE ADVISE IF IT IS NOT AVAILABLE FOR | | | ANY OF THE PRODUCTS. | | | | | | PRODUCT APPROVALS ARE TO BE REVIEWED BY | | | DESIGNER OF RECORD FBC*106.3.3. | | | | | | SEE ABOVE REQUEST IN REGARDS TO THE WIND | | | PRESSURES.PROVIDE THE DESIGN PRESSURES | | | FOR EACH OPENING ON THE ELEVATIONS | | | SHOWN.THE STOREFRONT SYSTEM, AS WELL | | | AS OTHER PRODUCTS SUBMITTED, ARE NOT | | | COMPLIANT FOR ?WORST CASE?.WORST CASE | | | IS 10SF ZONE 5, +50.1/-66.8.SEVERAL OF | | | THE PRODUCTS ARE NOT COMPLIANT. | | | | | | FOR THE GAF BUILT UP ROOF, THE | | | ARCHITECT?S RESPONSE LETTER THAT YOU ARE | | | USING SYSTEM B2 IS ACKNOWLEDGED. | | | | | | THE KAWNEER COMPANY SERIES 350-MS DOORS | | | ARE NOT TO BE USED WHERE WATER | | | INFILTRATION REQUIREMENT IS NEEDED. | | | ADDRESS.IF YOU ARE GOING TO USE THIS | | | DOOR, WRITE THE DOOR NUMBER DIRECTLY ON | | | THE PRODUCT APPROVAL PRIOR TO REVIEW BY | | | DESIGNER OF RECORD.DOR IS TO NOTE THAT | | | THIS HAS BEEN ADDRESSED. | | | | | | YKK AP AMERICA YHS-50 DOOR, INDICATE ON | | | SHEET 2 OF 6 OF THE PRODUCT APPROVAL | | | WHICH CONFIGURATION AND SIZE YOU ARE | | | INSTALLING.NOT ALL ARE COMPLIANT FOR | | | WIND PRESSURES. | | | | | | YKK AP AMERICA 35H DOOR, INDICATE WHICH | | | SPECIFIC OPTION YOU ARE INSTALLING.NOT | | | ALL ARE COMPLIANT FOR WIND PRESSURES. | | | | | | STEELCRAFT MANUFACTURING STEEL DOOR IS | | | NOT APPROVED FOR USE WHERE WATER | | | INFILTRATION REQUIREMENTS ARE NEEDED. | | | | | | CECO DOOR PRODUCTS IMPERIAL STEEL DOOR | | | IS NOT APPROVED FOR USE WHERE WATER | | | INFILTRATION REQUIREMENTS ARE NEEDED. | | | | | | OVERHEAD DOOR 16FT ROLLING INSULATED | | | STEEL DOOR APPEARS COMPLIANT.SEE OTHER | | | COMMENTS IN REGARDS TO DOR REVIEW AND | | | STATE PRODUCT APPROVAL. | | | | | | PITTSBURGH CORNING GLASS BLOCK IS NOT | | | COMPLIANT FOR ?WORST CASE? DESIGN | | | PRESSURES. | | | | | | 10.)SEE FBC*106.3.5.1.1.INFORMATION | | | SUCH AS MINIMUM BUILDING TYPE FBC602.1, | | | FBC503, FULLY SPRINKLED OR UNSPRINKLED, | | | OCCUPANCY FBC3, OCCUPANT LOAD FBC1004 | | | AND EGRESS REQUIREMENTS, LIFE SAFETY | | | PLAN FBC10 ARE NOT ON THE PLAN.PLEASE | | | PROVIDE ALL REQUIRED INFORMATION.CODE | | | COMPLIANCE CANNOT BE DETERMINED DUE TO | | | INSUFFICIENT INFORMATION. | | | | | | FBC11-4.1.2(9), ACCESSIBLE MEANS OF | | | EGRESS SHALL BE PROVIDED IN THE SAME | | | NUMBER AS REQUIRED FOR EXITS BY LOCAL | | | BUILDING/LIFE SAFETY REGULATIONS.ONLY | | | TWO ACCESSIBLE MEANS OF EGRESS SHOWN; | | | DOOR 7 SHOWS A STEP.THE OTHER TWO | | | MEANS OF EGRESS DOES NOT COMPLY WITH | | | FBC1005.1 (LOSS OF DOOR 1). | | | | | | 11.)THE BOUNDARY SURVEY PREPARED BY | | | WALLACE SURVEYORS IS TO BE SIGNED AND | | | SEALED. | | | | | | 12.)S-002, 03200, GENERAL NOTES, NOTE | | | 2 REFERS TO ACI318-95, FBC35.03300 | | | REFERS TO ACI301-96; 03200 REFERS TO | | | ACI301-99.PLEASE REVIEW ALL | | | REFERENCES. | | | | | | S-001 REFERS TO ACI347R-94 AND ASCE7-98. | | | S-002 REFERS TO ACI315-94 AND | | | ACI439-3R-83.REVISE IN ACCORDANCE WITH | | | FBC35 AND CHECK ALL REFERENCES. | | | | | | 13.)ADDRESSED. | | | | | | 14.)FOR THE ONE HOUR WALL A2.0, | | | PROVIDE EITHER AN APPROVED ASSEMBLY | | | LISTING OR SHOW CALCULATED FIRE | | | RESISTANCE FBC7.PROVIDE AN ASSEMBLY | | | LISTING AND DETAIL FOR THE TOP OF THE | | | WALL WHERE THE WALL MEETS THE DECK. | | | | | | THE WRITTEN DESCRIPTION ON A2.0 | | | CONFLICTS WITH THE DETAIL ON A2.2 AND | | | CONFLICTS WITH THE UL ASSEMBLY | | | REFERENCED.SEE ALSO UL U466 AS THE | | | DETAIL YOU PROVIDED ON A2.2 MORE CLOSELY | | | RESEMBLES THAT ASSEMBLY.DETAILS ARE TO | | | BE CONSISTENT AND TO MEET THE | | | SPECIFICATIONS OF THE ASSEMBLY YOU WISH | | | TO USE. | | | | | | SHOW FIRE RESISTANCE OF THE ROOF DECK. | | | THIS IS REQUIRED FOR THE UL HW DETAIL | | | YOU SPECIFY AS WELL AS SHOWING | | | COMPLIANCE WITH FBC708.4, CONTINUITY. | | | | | | 15.)PROVIDE A GUARD DETAIL WITH | | | INCLUDING DESIGN STRENGTH FBC1607.7, | | | FBC1012.INCLUDE ALL DIMENSIONS. | | | | | | SHOW OPENING MAXIMUM DIMENSION | | | FBC1012.3.ADD THE CONCENTRATED LOAD | | | REQUIREMENT OF FBC1607.7.1.1 TO THE | | | DESIGN SPECIFICATION. | | | | | | 16-22.) ADDRESSED. | | | | | | 23.)SHOW ACCESSIBLE SALES COUNTER, | | | FBC11-7.2. | | | | | | PROVIDE DESIGN CRITERIA.REFERRING TO A | | | CODE NUMBER IS NOT SUFFICIENT. | | | | | | NEW COMMENTS: | | | | | | 24.)S-001 STRUCTURAL LOADING REFERS TO | | | ASCE7-98; SHOULD BE ASCE7-02 FBC35. | | | | | | 25.)THE ENERGY CALCS, CIVILS, AND | | | ARCHITECTURALS CONFLICT AS TO THE | | | BUILDING SIZE.NOTE THAT IMPACT FEE | | | ASSESSMENT REVISION MAY BE REQUIRED WHEN | | | THE ACTUAL BUILDING SIZE IS DETERMINED. | | | | | | 26.)THE ENERGY CALCS REFER TO THE | | | WRONG JURISDICTION.THE JURISDICTION | | | NUMBER FOR THE CITY OF WEST PALM BEACH | | | IS 604700, FBC APPENDIX 13A.INCLUDE | | | ALL PERTINENT INFORMATION; OWNER, PERMIT | | | NUMBER. | | | | | | 27.)NOTHING ON THE SHEET 5 OF THE | | | ENERGY CALCS IS MARKED AS BEING CHECKED. | | | THIS IS REQUIRED TO SHOW CODE COMPLIANCE | | | FBC13-103.1.1.1. | | | | | | 28.)SOME ITEMS WERE NOT ENTERED FOR | | | THE ENERGY CALCS; FOR INSTANCE, WATER | | | HEATING SYSTEMS.INCLUDE ALL REQUIRED | | | INFORMATION FBC13-103. | | | | | | 29.)BE ADVISED THAT I ?SPOT CHECK? THE | | | ENERGY CALCS.THE ABOVE CORRECTIONS MAY | | | NOT INCLUDE ALL ITEMS.CONFIRM THAT ALL | | | INFORMATION ON THE ENERGY CALC IS | | | CORRECT PRIOR TO RESUBMITTAL. | | | | | | 30.)ENERGY CALCS REQUIRED FOR THE | | | FUTURE TENANT SPACE, FBC13-101.1.6. | | | | | | 31.)SEPARATE PERMIT REQUIRED FOR THE | | | DUMPSTER ENCLOSURE.PROVIDE A COMPLETED | | | APPLICATION. | | | | | | 32.)DOOR 17, SHOW MANEUVERING | | | CLEARANCE, PULL SIDE FBC11-4.13, FBC | | | FIGURE 25. | | | | | | 33.)PARKING IS TO COMPLY WITH CITY OF | | | WEST PALM BEACH STANDARD, SEE ATTACHED. | | | | | | 34.)THE LANDSCAPE SHEETS PREPARED BY | | | THE LANDSCAPE ARCHITECT ARE TO BE DATED | | | AS WELL AS SIGNED AND SEALED, FS481.321. | | | | | | 35.)S103, CLARIFY AS TO WHY TWO OF THE | | | CORNERS ARE ZONE 2 RATHER THAN ZONE 3. | | | FBC16. | | | | | | 36.)E0.0 GENERAL NOTES REFERS TO THE | | | WRONG BUILDING CODE, FBC2001 RATHER THAN | | | FBC2004. | | | | | | 37.)PROVIDE A FIRE SPRINKLER PLAN | | | FBC*106.3.5.1.1(5). | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-11-09 |
Time |
15:14 |
Rev Time |
6.00 |
| Received By |
shill |
Date |
2005-11-08 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2005-11-09 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE STAMPED | | | AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. | | | | | | 3.)A PERMIT APPLICATION MUST BE | | | SUBMITTED PRIOR TO PERMIT ISSUANCE. | | | THIS IS A PLAN CHECK ONLY. | | | | | | 4.)PERMITS APPLIED FOR ON OR AFTER | | | OCTOBER 1, 2005 ARE TO BE DESIGNED UNDER | | | FBC2004.SOME PAGES REFER TO FBC2001, | | | INCLUDING S-001, S-103. CHECK ALL | | | SHEETS. ARCHITECT AND ENGINEER BOTH ARE | | | TO INDICATE THAT THE PLANS HAVE BEEN | | | DESIGNED TO FBC2004. | | | | | | 5.)SOME OF THE SHEETS WERE BOUND | | | UPSIDE DOWN.THIS DELAYS PLAN REVIEW. | | | PLEASE SUBMIT PROPERLY. | | | | | | 6.)THREE SETS OF PLANS AND ALL | | | DOCUMENTS REQUIRED; RESIDENT INSPECTOR | | | REQUIRED, FBC*109.3.7.PLEASE CONTACT | | | HAROLD PISKURA, 561-805-6711. | | | | | | 7.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALCS, FBC13-103.1. | | | | | | 8.)FOR THE ARCHITECT TITLE BLOCK, THE | | | PRINTED NAME OF THE PERSON SEALING THE | | | DOCUMENT IS TO BE ON THE PLAN, | | | FAC61G1-16.003, 004. | | | | | | 9.)SUBMIT PRODUCT APPROVALS, FAC9B72: | | | | | | ROOF | | | STOREFRONT SYSTEM | | | HOLLOW METAL DOOR | | | ROLL UP DOOR | | | | | | IF THE PRODUCTS SELECTED DO NOT MEET | | | WORST CASE WIND PRESSURES AS SPECIFIED | | | ON S-501, SUBMIT A SCHEDULE SPECIFYING | | | PRESSURES FOR EACH OPENING. | | | | | | FOR THE ROOF PRODUCT APPROVAL, INDICATE | | | WHICH APPROVED ASSEMBLY YOU ARE USING. | | | SEE S-103 FOR ROOF PRESSURES. | | | | | | 10.)SEE FBC*106.3.5.1.1.INFORMATION | | | SUCH AS MINIMUM BUILDING TYPE FBC602.1, | | | FBC503, FULLY SPRINKLED OR UNSPRINKLED, | | | OCCUPANCY FBC3, OCCUPANT LOAD FBC1004 | | | AND EGRESS REQUIREMENTS, LIFE SAFETY | | | PLAN FBC10 ARE NOT ON THE PLAN.PLEASE | | | PROVIDE ALL REQUIRED INFORMATION.CODE | | | COMPLIANCE CANNOT BE DETERMINED DUE TO | | | INSUFFICIENT INFORMATION. | | | | | | 11.)THE BOUNDARY SURVEY PREPARED BY | | | WALLACE SURVEYORS IS TO BE SIGNED AND | | | SEALED. | | | | | | 12.)S-002, 03200, GENERAL NOTES, NOTE | | | 2 REFERS TO ACI318-95, FBC35.03300 | | | REFERS TO ACI301-96; 03200 REFERS TO | | | ACI301-99.PLEASE REVIEW ALL | | | REFERENCES. | | | | | | 13.)11-201 STATES THAT THE RETAINING | | | WALL WILL BE DESIGNED BY THE CIVIL | | | ENGINEER.PROVIDE A DETAIL. | | | | | | 14.)FOR THE ONE HOUR WALL A2.0, | | | PROVIDE EITHER AN APPROVED ASSEMBLY | | | LISTING OR SHOW CALCULATED FIRE | | | RESISTANCE FBC7.PROVIDE AN ASSEMBLY | | | LISTING AND DETAIL FOR THE TOP OF THE | | | WALL WHERE THE WALL MEETS THE DECK. | | | | | | 15.)PROVIDE A GUARD DETAIL WITH | | | INCLUDING DESIGN STRENGTH FBC1607.7, | | | FBC1012.INCLUDE ALL DIMENSIONS. | | | | | | 16.)PROVIDE A DETAIL FOR THE RAMP | | | HANDRAILS, FBC1010, FBC11-4.8, | | | FBC11-4.26. | | | | | | 17.)LANDING AT THE BOTTOM OF A RAMP | | | SHALL BE NOT LESS THAN 72IN,FBC11-4.8.4. | | | | | | 18.)PROVIDE DETAILS FOR THE HANDRAILS, | | | FBC11-4.26.SHOW THE EXTENSION AT THE | | | BOTTOM, SEE FBC11 FIGURE 19(C). | | | | | | 19.)IS THE DETAIL FOR THE GOLFSMITH | | | ENTRANCE TO BE USED FOR THE FUTURE | | | TENANT ENTRANCE?A RAMP IS SHOWN ON THE | | | CROSS SECTION DETAIL 1-301, SHEET S-301, | | | BUT NOT ON THE CIVILS, ARCHITECTURALS, | | | OR OTHER STRUCTURAL SHEETS.THIS | | | ENTRANCE IS TO BE ACCESSIBLE; CANNOT | | | HAVE A .25 FOOT STEP AS SHOWN ON THE | | | CIVILS. | | | | | | 20.)THE SECTION INDICATED FOR THE | | | ENTRANCE TO GOLFSMITH, 11-201, IS THE | | | DETAIL FOR THE DUMPSTER ENCLOSURE. | | | | | | 21.)SEE A3.0 AND A2.3.THE ELEVATION | | | FOR THE ENTRANCE CONFLICTS WITH THE PLAN | | | VIEW (PLANTER NOT SHOWN ON THE | | | ELEVATION). | | | | | | 22.)THE WALKWAY BETWEEN THE BUILDING | | | AND THE LOADING AREA APPEARS TO SLOPE. | | | SPECIFY THE DEGREE OF SLOPE.IF THIS | | | AREA IS NOT SLOPED, HOW DOES IT | | | TRANSITION FROM THE 18' FFE TO THE | | | SIDEWALK IN THE FRONT? | | | | | | 23.)SHOW ACCESSIBLE SALES COUNTER, | | | FBC11-7.2. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-28 |
Time |
12:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-28 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2006-10-28 12:33:58 | REDLINED NOTE FOR OVER RIDE DEVICES. | | | IF OCC SENSOR TYPE, IT IS A MAX OF 30MINS NOT 4HRS. | | | | | | ELECTRICAL SHEET CONTAINING LT POLE DETAIL, REVIEWED | | | FOR ELDCTRICAL ONLY. NEEDS BLDG REVIEW SEPARATELY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-09-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-17 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-17 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2006-09-17 00:00:00 | ***UNSAT *** | | | | | | 1) NOTE: PLEASE SEE PLANS NOW INDICATE | | | THE BUILDINGOUT OF WHAT WAS TO BE THE | | | "FUTURE TENANT" AND IS BEING | | | INCORPORATED INTO THE SCOPE OF WORK. | | | PLEASE SEE AN ADJUSTMENT IN BUILDING | | | VALUATION IS REQUIRED PER FBC 108.3 | | | | | | 2) NOTE: PLEASE PROVIDE CLEAR FLOOR | | | SPACE LAYOUT FOR ALL ELECTRICAL | | | EQUIPMENT. PLEASE ALSO NOTE , NO | | | STORAGE. | | | PLEASE SEE FIRE REVIEW AS THE NEW BACK | | | DOOR LOCATION WILL BE THE LIKELY | | | LOCATION OF THE KNOX BOX WHICH WILL BE | | | REQUIRED. PLEASE KNOW THIS IS GOING TO | | | BE THE FIRE MARSHAL'S OFFICE REVIEW NOTE | | | AND CONSIDERATION SHOULD BE TAKEN FOR | | | DISTANCE OF TRAVEL INTO BUILDING FOR | | | SAFETY OF FIRE DEPT PERSONNEL TO TURN | | | OFF POWER AT THE MAIN. | | | 230.70 | | | | | | 3) NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REDLINES WHICH REQUESTED THE TIMES FOR | | | ALL OVER-RIDE(S) DEVICES. | | | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2, | | | .1.3 | | | | | | 4) NOTE: PLEASE SUBMIT COMPLETE REVISED | | | FLORIDA ENERGY CALCULATIONS FOR | | | INCREASED SPACE FOR BUILD OUT. | | | FBC 13-101.1.1,13-415.1.AB.1. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-06-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-18 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-18 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2006-06-18 00:00:00 | ***** PROVISO/REVISION********** | | | | | | 1) NOTE: PLEASE SEE FUTURE TENANT SPACES | | | SHALL CONTAIN AUTO SHUT OF OF LIGHTING | | | WITH OVER-RIDES DEVICES OF SOME TYPE | | | LOCATED IN AN ACCESSIBLE LOCATION AT | | | ENTRANCE TO SPACE. | | | EITHER A TIMED OVER-RIDE (MAX 4HRS OR | | | OCC SENSOR TYPE OVER-RIDE DEVICE (MAX | | | 30MINS) SHALL BE INDICATED. | | | | | | 2) NOTE: PLEASE LIST TIMES FOR | | | OVER-RIDES DEVICES. | | | PLEASE SEE UNITS AT FRONT DOOR AND OCC | | | SENSORS. | | | | | | ** FBC CHAPTER 13, 13-415.1.ABC.1.1, | | | .1.2,.1.3 ETC. | | | | | | *** IMPORTANT** | | | THIS REVISION ALONG WITH ANY OTHER | | | REVISIONS ARE TO BE SUBMITTED TO THE | | | CITY FOR REVIEW AND STAMPING "BEFORE | | | ROUGH" ELECTRICAL INSPECTION IS CALLED | | | IN. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | ******* NOTE ALSO ADDED TO FRONT SCREEN* | | | | | | | | | PLEASE SEE NOTICE OF COMMENCMENT | | | SUBMITTED WHICH WAS RECORDED ON FEB 10, | | | 2006 HAS EXPIRED AS WORK HAS NOT | | | COMMENCED WITHIN 90 DAYS OF RECORD NOC | | | AND NOC HAS NOW BECOME "VOID". | | | PLEASE SEE FS 7.13.13(2). | | | | | | A NEW NOC WILL BE REQUIRED BEFORE | | | PICKING UP PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-03-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-16 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-16 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2006-03-16 00:00:00 | GOLF SMITH | | | | | | ********* UNSAT 2ND REVIEW *********** | | | | | | PLEASE SEE PLANS ARE NOW BEING SUBMITTED | | | FOR PERMIT. PLEASE SEE SOME COMMENTS ARE | | | EXISTING FROM PREVIOUS REVIEW AND SOME | | | NEW COMMENTS FOR 2004 FBC. | | | | | | | | | 1)NOTE:NOTE # 1 NO, PLEASE SEE SHEET | | | A.01 WHICH STILL REFERENCES THE 1999 | | | NEC. | | | PLEASE SEE E0.0 WHICH STILL REFLECTS THE | | | "2001 FBC"?? | | | PLEASE SEE COMMENTS BELOW AS PERMIT | | | APPLICATION IS NOW BEING MADE UNDER THE | | | 2004 FBC. | | | | | | **PLEASE SEE DUE TO PLANS BEING | | | SUBMITTED FOR "PLAN REVIEW" ONLY, PLEASE | | | BE AWARE AS OF OCT 1ST, 2005 THE NEW FBC | | | 2004 HAS BEEN ADOPTED AND IS NOW IN | | | EFFECT. | | | PLEASE SEE PLANS REFERENCE 2001 FBC | | | WHICH CAN NO LONGER BE USED FOR DESIGN | | | AND USE FOR THIS PROJECT. | | | PLEASE KNOW WHEN SUBMITTING FOR PERMIT A | | | , NEW PERMIT NUMBER WILL BE REQUIRED TO | | | BE GENERATED FOR PROCESSING AFTER OCT | | | 1ST, 2005. | | | PLEASE SEE WRONG CODE REFERENCED FOR | | | LS101. NFPA-101 IS THE 2003 EDITION. | | | PLEASE SEE OTHER COMMENTS FROM OTHER | | | REVIEWERS WHICH WILL APPLY TO CODE | | | CHANGE. | | | | | | 2)NOTE:NOTE #2, OK, TITLE BLOCKS ARE | | | NOW ADDED FOR ENGINEER'S, HOWEVER | | | RESPONSE LTR MENTIONS THAT "EACH SHEET | | | HAS THE CERTIFICATE OF AUTHORIZATION | | | NUMBER." PLEASE VERIFY AS THE INDIVIDUAL | | | ENGINEER'S WITH THE TITLE BLOCKS AS | | | SHOWN DO NOT REQUIRE ANY CA # AND ONLY | | | THE PE'S REGISTRATION # IS SHOWN. | | | THE PREVIOUS REVIEW WAS NOT A COMMENT | | | FOR ARCHITECTURAL FIRM. THE COMMENT ONLY | | | MENTIONED THAT A CA # WOULD BE REQUIRED | | | FOR ENGINEER'S/FIRM, "IF AAPLICABLE". | | | | | | | | | | | | **PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCKS FOR ALL ENGINEER'S OF | | | RECORD AS REQUIRED UNDER FAC | | | 61G15-23.002. | | | PLEASE SEE M, E, P, PLANS ARE SIGNED, | | | DATED AND SEALED BY ENGINEER'S, HOWEVER | | | NO TITLE BLOCKS ARE SHOWN?? | | | PLEASE ALSO SEE FS 471.023 IF APPLICABLE | | | FOR CERTIFICATE OF AUTHORIZATION NUMBER. | | | THIS IS REQUIRED OF ALL SHEETS AND FOR | | | ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 3)NOTE: NOTE #3 NO, IT IS NOTED THAT A | | | DETAIL AND NOTE WAS ADDED FOR POLES AND | | | LTS TO BE ABLE TO WINDSTAND 140 MPH, | | | HOWEVER PLEASE SEE WIND LOAD | | | CALCUALTIONS WERE NOT SUBMITTED. THESE | | | ARE REQUIRED TO BE SIGNED, DATED AND | | | SEALED BY A FLORIDA LICENSED PE. | | | | | | ** PLEASE SUBMIT COMPLETE | | | WIND-LOADING CALCULATIONS FOR | | | SITE-LIGHTING POLES AND FIXTURES. | | | PLEASE SUBMIT A DETAIL FOR POLE/FIXTURE | | | AND FOUNDATION FOR POLE(S). | | | PLEASE KNOW THE WIND LOADS ARE FER FBC | | | 140 MPH. | | | PLEASE KNOW THAT THE STRUCTUAL | | | CALCULATIONS WILL BE REVIEWED BY THE | | | BUILDING REVIEWER. | | | | | | 4)NOTE:NOTE #4 OK. | | | | | | 5)NOTE: NOTE #5 OK | | | | | | 6)NOTE: NOTE #6 OK. | | | | | | 7)NOTE: NOTE #7 NO/YES. PLEASE SEE | | | CALCUALTIONS WERE SUBMITTED FOR THE | | | SAPCE THAT IS BEING BUILT OUT, HOWEVER, | | | WATTS/PER FT, # OF RECEPTS @180VA PER | | | EACH, ETC WAS NOT SHOWN. HOW WERE THESE | | | LOADS DERIVED.? | | | | | | **PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR REVIEW. PLEASE ALSO | | | INDICATE ALL CONTINUOUS LOADS AND | | | LARGEST MOTOR LOADS AT 125%. | | | 220.3,220.10,220.13,220.11,215.3,230.42 | | | ETC. | | | | | | 8)NOTE: NOTE #8 NO, PLEASE SEE PLANS | | | STILL SHOW THIS PANEL BEING INSTALLED IN | | | AN AREA FOR FUTURE TOILET?? | | | | | | ** PLEASE VERIFY LOCATION OF NEW | | | PANEL T-1 WHICH IS BEING SHOWN IN | | | "FUTURE TOILET RM" IN FUTURE TENANT | | | SPACE. | | | 240.24,215.5 | | | | | | 9)NOTE: NOTE #9 OK | | | | | | 10)NOTE: NOTE #10 OK. | | | | | | 11)NOTE: NOTE #11 OK. | | | | | | 12)NOTE: NOTE #12 OK. | | | | | | 13)NOTE: NOTE #13 ?PLEASE SEE | | | GROUNDING ELECTRODE RISER WAS REVISED | | | OK, HOWEVER SYSTEM SHOWN TO BLDG STEEL | | | AND NOT FOOTER STEEL. PLEASE SEE THE | | | BLDG STEEL IS OK AND IS REQUIRED , | | | HOWEVER FOOTER STEEL IS ALSO REQUIRED. | | | 250.50,250.52 | | | | | | **PLEASE SEE NEC WHICH REQUIRES | | | THE GROUNDING ELECTRODE TO BE | | | CONTINUOUS, WHICH WOULD REQUIRE THE 3/0 | | | TO GROUND ROD ALSO. SHOWN AS #6.250.50 | | | | | | NEW NOTE: | | | **************************************** | | | | | | 14) NOTE: PLEASE SEE 2004 FBC CHAPTER | | | 13-413.1ABC.1 PROVIDE VOLTAGE DROP | | | ANALYSIS. | | | PLEASE SEE 13-415.1.ABC.1.1 AND .2, SOME | | | SORT OF DAY CONTROL WAS SUBMITTED, | | | HOWEVER PLEASE SUBMIT MORE DETAILS FOR | | | SYSTEM BEING INSTALLED. | | | PLEASE SEE INDICATE ALL OVER-RIDE | | | LOCATION CLEARLY ON PLANS. | | | PLEASE SEE .2, FOR SPACE CONTROLL FOR | | | ALL INDIVIDUAL SPACES CONTAINING WALLS. | | | PLEASE PROVIDE CALCS PER 13-415.1.AB.1 | | | | | | | | | 15) NOTE: PLEASE SEE NOTE BELOW WHICH | | | REQUESTED ON FIRST REVIEW TO SUBMIT | | | OLD/VOIDED SHEETS SEPARATELY. PLEASE SEE | | | THESE SHEET ARE ATTACHED TO NEW SETS. | | | PLEASE SUBMIT NEW SETS AND OLD SET | | | SEPARATELY. | | | | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | EELCTRICAL PLANS. | | | | | | ** PLEASE COMPLETELY REMOVE ANY | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COMPLETE SET OF ALL | | | OLD/VOIDED SHEETS FOR REFERENCE ONLY. | | | THESE SHALL BE SEPARATE FROM COMPLETE | | | SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-11 |
Time |
18:46 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-10-11 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2005-10-11 00:00:00 | IN ELEC FOR REVIEW. | | | GOLF SMITH | | | | | | ********* UNSAT *********** | | | | | | PLEASE KNOW, PLANS WERE ONLY SUBMITTED | | | FOR "PLAN REVIEW" AND WERE NOT | | | SUBMITTED FOR PERMIT. | | | PLEASE SEE THE FOLLOWING COMMENTS. | | | | | | | | | 1)NOTE: PLEASE SEE DUE TO PLANS BEING | | | SUBMITTED FOR "PLAN REVIEW" ONLY, PLEASE | | | BE AWARE AS OF OCT 1ST, 2005 THE NEW FBC | | | 2004 HAS BEEN ADOPTED AND IS NOW IN | | | EFFECT. | | | PLEASE SEE PLANS REFERENCE 2001 FBC | | | WHICH CAN NO LONGER BE USED FOR DESIGN | | | AND USE FOR THIS PROJECT. | | | PLEASE KNOW WHEN SUBMITTING FOR PERMIT A | | | , NEW PERMIT NUMBER WILL BE REQUIRED TO | | | BE GENERATED FOR PROCESSING AFTER OCT | | | 1ST, 2005. | | | PLEASE SEE WRONG CODE REFERENCED FOR | | | LS101. NFPA-101 IS THE 2003 EDITION. | | | PLEASE SEE OTHER COMMENTS FROM OTHER | | | REVIEWERS WHICH WILL APPLY TO CODE | | | CHANGE. | | | | | | 2)NOTE: PLEASE SEE MISSING INFORMATION | | | ON TITLE BLOCKS FOR ALL ENGINEER'S OF | | | RECORD AS REQUIRED UNDER FAC | | | 61G15-23.002. | | | PLEASE SEE M, E, P, PLANS ARE SIGNED, | | | DATED AND SEALED BY ENGINEER'S, HOWEVER | | | NO TITLE BLOCKS ARE SHOWN?? | | | PLEASE ALSO SEE FS 471.023 IF APPLICABLE | | | FOR CERTIFICATE OF AUTHORIZATION NUMBER. | | | THIS IS REQUIRED OF ALL SHEETS AND FOR | | | ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 3)NOTE: PLEASE SUBMIT COMPLETE | | | WIND-LOADING CALCULATIONS FOR | | | SITE-LIGHTING POLES AND FIXTURES. | | | PLEASE SUBMIT A DETAIL FOR POLE/FIXTURE | | | AND FOUNDATION FOR POLE(S). | | | PLEASE KNOW THE WIND LOADS ARE FER FBC | | | 140 MPH. | | | PLEASE KNOW THAT THE STRUCTUAL | | | CALCULATIONS WILL BE REVIEWED BY THE | | | BUILDING REVIEWER. | | | | | | 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | IT IT NOTED THAT THE AIC RATINGS ARE | | | SHOWN FOR MDP AND SUB PANELS, HOWEVER | | | PLEASE INDICATE FOR MAIN DISCONNECTS. | | | | | | 5)NOTE: PLEASE SEE PANEL "LB" IS BEING | | | FED FROM MDP WITH 100A OCPWITH 3/0'S?? | | | PLEASE KNOW THIS IS OK AND MEETS CODE, | | | HOWEVER IF SHOWN WITH 3/0'S THEN 3/0'S | | | WILL BE REQUIRED TO BE INSTALLED. | | | VERIFY OF 3/0S CONNECT INTO A 100A BRKR | | | LUGS WITH OUT ANY ADAPTER(S). | | | 215.5 | | | | | | 6)NOTE: PLEASE SEE PANEL "CR" WHICH | | | INDICATES A 60A SUB FEED OCP FROM MDP, | | | HOWEVER RISER NOTES SHOWS #10'S AWG? | | | PLEASE SEE 240.310.16 FOR MIN AWG | | | REQUIRED FOR 60A OCP. | | | PLEASE ALSO SEE PANEL "CR" IS ALSO SHOWN | | | AS A 20CIRCUIT 30A PANEL? PLEASE VERIFY | | | BUS RATING, PANEL RATING ETC, AS THIS | | | DOES NOT SEEM TO BE A COMMON PANEL. | | | 215.5 | | | | | | 7)NOTE: PLEASE SUBMIT COMPLETE LOAD | | | CALCULATIONS FOR REVIEW. PLEASE ALSO | | | INDICATE ALL CONTINUOUS LOADS AND | | | LARGEST MOTOR LOADS AT 125%. | | | 220.3,220.10,220.13,220.11,215.3,230.42 | | | ETC. | | | | | | 8)NOTE: PLEASE VERIFY LOCATION OF NEW | | | PANEL T-1 WHICH IS BEING SHOWN IN | | | "FUTURE TOILET RM" IN FUTURE TENANT | | | SPACE. | | | 240.24,215.5 | | | | | | 9)NOTE: PLEASE INDICATE ALL ROOF-TOP | | | RECEPTS WHICH ARE SHOWN FOR RFTOP A/C | | | EQUIPMENT AS GFI/GFI PROTECTED. | | | 210.8B2 | | | | | | 10)NOTE: PLEASE SEE 210.62, 220.12 FOR | | | MISSING "SHOW WINDOW" RECEPTS WHICH ARE | | | AND WILL BE REQUIRED. | | | | | | 11)NOTE: PLEASE SEE PANEL SCHEDULE LA | | | INDICATES NUMEROUS "SIGN CIRCUITS" FOR | | | SIGNAGE, HOWEVER, 600.5 REQUIRES A MIN | | | OF ONE CIRCUIT AT THE LOCATION OF THE | | | FRONT DOOR OR IMMEDIATE VICINITY THERTO. | | | PLEASE CALRIFY WHERE THESE SIGN CIRCUITS | | | ARE ON PLANS. | | | | | | 12)NOTE: PLEASE SEE ELECTRICLA PLANS DO | | | NOT INDICATE ANY SINKS IN BREAK RM, | | | HOWEVER ALL RECEPTS LOCATED WITHIN 6' OF | | | A SINK SHALL BE GFI/GFI | | | PROTECTED.210.8B3, PLEASE CALL TO GO | | | OVER CHANGES TO THE 2002 NEC. | | | | | | 13)NOTE: PLEASE SEE NEC WHICH REQUIRES | | | THE GROUNDING ELECTRODE TO BE | | | CONTINUOUS, WHICH WOULD REQUIRE THE 3/0 | | | TO GROUND ROD ALSO. SHOWN AS #6.250.50 | | | | | | ** PLEASE SEE NOTE NUMBER ONE, PLANS DI | | | NOT COME IN FOR PERMIT UNDER THE 2001 | | | FBC. | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | EELCTRICAL PLANS. | | | | | | ** PLEASE COMPLETELY REMOVE ANY | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE SUBMIT ONE COMPLETE SET OF ALL | | | OLD/VOIDED SHEETS FOR REFERENCE ONLY. | | | THESE SHALL BE SEPARATE FROM COMPLETE | | | SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
6 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-11-02 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-11-02 |
Time |
16:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
F |
Date |
2006-09-22 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-09-22 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-09-22 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2006-09-22 00:00:00 | FAILED FOR FOLLOWING REASONS: | | | | | | 1. PLEASE DESCRIBE MORE DETAIL WHAT ARE | | | YOU CHANGING IN CIVIL DRAWINGS FROM | | | PREVIOUSLY PERMITTED DRAWINGS, FOR | | | EXAMPLE, PAVEMENT & DRAINAGE PLAN, STORM | | | WATER, CONTROL STRUCTURES, PERVIOUS, | | | IMPERVIOUS AREA,SIDEWALK,HANDICAP | | | PARKING ETC., WHAT CHANGES YOU ARE | | | MAKING? | | | | | | | | | PLEASE DESCRIBE EACH ITEM TO EXPEDITE | | | THE PERMITTING PROCESS. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
N |
Date |
2006-07-12 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2006-07-12 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2006-07-12 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2006-07-12 00:00:00 | ENG PERMIT ISSUED 06030742 | | | REVISED CIVIL TO BE SUBMITTED AS A | | | REVISION TO PERMIT # 06030742 | | 2006-06-18 00:00:00 | NEW REVIED "C" SHEETS SUBMIITED. | | | PREVIOUS CIVILS WERE STAMPED, HOWEVER | | | THESE HAVE BEEN REVISED. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-03-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2006-03-17 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2006-03-17 00:00:00 | N: | | | | | | 1. CONTRACTOR APPLIED FOR A SEPARATE | | | PERMIT FOR CIVIL/ UNDERGROUND UTILITIES, | | | SEE PERMIT # 06030742. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2006-03-03 |
Time |
10:30 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2006-03-03 |
Time |
10:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-09-23 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-09-23 |
Time |
14:55 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-09-23 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2005-09-23 00:00:00 | FAILED: | | | | | | 1. SHEET C-2, REFERS TO ARCHITECTURAL | | | PLANS FOR DUMPSTER ENCLOSURE, DETAILS AS | | | PROVIDED DO NOT COMPLY WITH CITY' | | | REQUIREMENTS FOR THE CITY PICK-UP, | | | PLEASER VERIFY WITH THE OWNER. | | | 2. POLUTION/ EROSION PLANS MUST BE | | | INCLUDED IN CIVIL PLANS, PLEASE PROVIDE | | | DETAILS OR NOTE TO THE GC, SILT FENCE, | | | ETC.. | | | 3. SHEET C-4 , PROPOSED 238 LF-4" WM AS | | | SHOWN, PASSES TROUGH CATCH BASIN, THIS | | | DOES NOT COMPLY WITH WATER SEPARATION | | | STATEMENT, PLEASE VERIFY. | | | 4. FIRE HYDS. LOCATION MUST BE APPROVED | | | BY THE CITY' FIRE DEPARTMENT, MIN. 40' | | | FROM THE BUILDINGS. | | | 5. PLEASE PROVIDE MIN. WATER CROSSING | | | CLEARANCES. | | | 6 PLEASE NOTE THAT CIVIL PLANS MUST BE | | | SUBMITED TO THE PUBLIC UTILITIES AND | | | ENGINEERING ATT; MANNY GONZALEZ, | | | 494-1085. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2006-12-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-21 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-21 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2006-12-21 09:40:05 | *****APPROVED***** | | | | | | | | | | | | | | | SPRINKLERSHOP DRAWINGS (FP-1 AND FP-2) ADDED TO | | | FILED PLAN. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-21 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-21 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2006-09-21 00:00:00 | ***DENIED*** | | | | | | 1) FIRE PROTECTION REVISIONS ARE SHOWN | | | ON P1.1. A FIRE SPRINKLER PERMIT HAS | | | BEEN ISSUED, AND ANY CHANGES OR | | | REVISIONS TO THE FIRE SPRINKLER SYSTEM | | | SHALL BE REFLECTED ON THE FIRE SPRINKLER | | | SHOP DRAWINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-07-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-07-07 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-07-07 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-03-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-03-29 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-03-29 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2006-03-29 00:00:00 | ******DENIED****** | | | | | | 1) THE REQUIRED FIRE EXTINGUISHERS SHALL | | | BE 2A-10B,C RATED AND MOUNTED AT | | | DISTANCES TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 2) FIRE SPRINKLER AND FIRE ALARM LAYOUTS | | | ARE NOT PROVIDED WITH SUBMITTAL. PLEASE | | | NOTE THAT SEPARATE SHOP DRAWINGS AND | | | PERMITS ARE REQUIRED FOR FIRE SPRINKLER | | | AND FIRE ALARM SYSTEMS. | | | | | | 3) FIRE ALARM SYSTEM SHALL BE UL | | | CERTIFIED FOR CENTRAL STATION SERVICE. | | | DOCUMENTATION OF THE CERTIFICATE | | | REQUIRED AT TIME OF FIRE ALARM FINAL | | | INSPECTION. | | | | | | 4) PLEASE PROVIDE SPECIFIC DETAILS | | | REGARDING MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILING. | | | | | | 5) PLEASE PROVIDE FURTHER INFORMATION IN | | | REFERENCE TO AUTOMATIC SHUT DOWN ON SHT | | | A0.1. | | | | | | 6) A KNOX BOX IS REQUIRED AND | | | APPLICATION CAN BE OBTAINED THROUGH THE | | | BUREAU OF FIRE PREVENTION. | | | | | | 7) SHT A0.1 REFERENCES FIRE ALARM DEVICE | | | LAYOUT ON ELECTRICAL SHEETS. IT DOES NOT | | | APPEAR THAT ALL DEVICES AND ASSOCIATED | | | EQUIPMENT, CONTROL PANEL ETC ARE | | | ILLUSTRATED. | | | | | | 8) DOOR #6 INDICATES 210 OCCUPANTS. A | | | MAXIMUM OF 180 PERSONS IS ALLOWABLE | | | BASED ON THE CALCULATION OF 0.2" PER | | | PERSON. | | | | | | 9) RAMPS SHALL HAVE HANDRAILS ON BOTH | | | SIDES. | | | | | | 10) PLEASE NOTE THAT THE WRONG EDITION | | | OF NFPA 101 HAS BEEN REFERENCED ON SHT | | | A8.0. | | | | | | 11) PLEASE PROVIDE FLAME RETARDANT | | | CERTIFICATION FOR AWNINGS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-11-15 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-11-15 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2005-11-15 00:00:00 | ******DENIED****** | | | | | | PLAN REVIEW ONLY | | | | | | 1) ALL ACCESS ROADS FOR EMERGENCY | | | TRAFFIC ARE TO BE MAINTAINED AT MINIMUM | | | CLEAR AND UNOBSTRUCTED WIDTH OF 20'. | | | | | | 2) AN ADDRESS IS REQUIRED ON THE | | | BUILDING AND SHALL BE A MINIMUM OF 6" IN | | | HEIGHT AND CONTRASTING TO THE | | | BACKGROUND. PLEASE PROVIDE ON ELEVATION | | | SHEET. | | | | | | 3) NFPA 101, 2003 EDITION TO BE | | | REFERENCED AFTER JAN. 1, 2005. | | | | | | 4) PLEASE SHOW LOCATION OF ALL HYDRANTS | | | THAT ARE TO BE WET AND OPERATIONAL PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | | | | 5) PLEASE SUBMIT A LIFE SAFETY PLAN TO | | | DETERMINE REQUIRED MEANS OF EGRESS WHEN | | | SUBMITTING FOR PERMIT. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-30 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-30 |
Time |
11:40 |
Sent To |
P |
|
| Notes |
| 2007-01-30 11:41:12 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-12-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-12 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-12 |
Time |
11:30 |
Sent To |
FIRE |
|
| Notes |
| 2006-12-12 11:31:03 | TO "F" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-26 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-26 |
Time |
09:39 |
Sent To |
|
|
| Notes |
| 2006-10-27 15:36:39 | TO "COMM" BD#63 | | 2006-10-26 09:40:41 | WAITING FOR "COMM" BD-REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-07 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-07 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-18 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-18 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2006-06-23 00:00:00 | 5/23/06--3RD SET WAS SUBMITTED TODAY. | | | PUT WITH OTHER PLANS IN REVIEW. "COMM" | | | BD#24 | | 2006-06-15 00:00:00 | TO "COMM" BD#24 | | 2006-05-18 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-14 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-14 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2006-03-13 00:00:00 | TO "COMM" BD#60 | | 2006-02-24 00:00:00 | ***NOTIFY R BROWN WHEN 2ND REVIEW IS | | | COMPLETE*** | | | | | | | | 2006-02-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-12-14 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-19 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2005-09-21 00:00:00 | TO "COMM" BD#44 | | 2005-09-19 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-11-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-11-04 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-11-04 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-10-12 |
Time |
19:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-10-12 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2006-10-12 19:29:23 | ---------------DENIED----------------- | | | 1. SUBMIT REVISED ENERGY CALCULATIONS TO INCLUDE NEW | | | EQUIPMENT AND EXPANDED CONDITIONED SPACE. | | | | | | 2. PG.M1.2 BREAK ROOM 110 SHOWS R/A GRILL IN CEILING | | | OPEN TO PLENUM SPACE ABOVE.HOW WILL R/A LEAVE PLENUM | | | SPACE? BALANCED R/A IS REQUIRED PER FBC,M 601.4 | | | | | | 3. PG.M1.2 GOLFTEC BAYS 1,2,3: DO THESE ROOMS HAVE | | | DOORS ON ENTRANCES? IF THERE ARE DOORS, THE R/A | | | OPENINGS IN WALLS (ABOVE CEILING) ARE TOO SMALL TO | | | ACHIEVE BALANCED RETURN PER FBC,M 601.4 EXCEPTION #2 IF | | | THERE ARE NO DOORS ON THESE ROOMS, THEN R/A GRILLS ARE | | | NOT REQUIRED IN CEILINGS OR WALLS. | | | | | | 4. PGM1.2 OFFICE 104: R/A TRANSFER GRILL IS TOO SMALL | | | PER FBC,M 601.4 EXCEPTION #2 | | | | | | 5. PG.M1.2 GENERAL NOTE #7: COMPLIANCE WITH WIND LOAD | | | REQUIREMENTS OF FBC CHAPTER 16 REQUIRES AN ENGINEERED | | | SYSTEM. PLEASE PROVIDE DETAILS FOR CURB-TO-ROOF AND | | | RTU-TO-CURB ATTACHMENTS. NOTE: THE CITY OF WEST PALM | | | BEACH IS IN THE 140MPH WIND ZONE PER FBC CHAPTER 16. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-03-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-03-17 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-03-17 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2006-03-17 00:00:00 | PROVISO: | | | RETURN AIR FROM THE BATHROOM AREAS SHALL | | | NOT BE RE-CIRCULATED PER 2004 FMC TABLE | | | 403.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-12-03 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-12-03 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2005-12-03 00:00:00 | *****PLAN SUBMITTED FOR REVIEW ONLY***** | | | | | | 1)MISSING INFORMATION ON TITLE BLOCK FOR | | | ENGINEER OF REGORD PER FAC 61G15-23.002 | | | | | | 2)INDICATE LOCATION FOR SUPPLY AND | | | RETURN DUCT SMOKE DETECTORS.DUCT | | | DETECTORS SHALL BE CONNECTED TO BUILDING | | | FIRE ALARM SYSTEM IF APPLICABLE OR BE | | | PROVIDED WITH VISIBLE/AUDIBLE | | | NOTIFICATION PER FBC,M 2004 606.4.1 | | | | | | 3)CONDENSATE DISPOSAL ON ROOF TO BE | | | PIPED TO APPROVED ROOF DRAIN OR 6" RAIN | | | LEADERS WHICH ARE SHOWN ON PLAN PROVIDED | | | THE RAIN LEADER DISCHARGE LOCATION IS IN | | | COMPLIANCE WITH FBC,M 2004 307.2.1 | | | | | | 4)AUXILIARY/SECONDARY DRAIN PROTECTION | | | IS REQUIRED FOR ROOFTOP PACKAGE UNITS | | | PER FBC,M 2004 307.2.3.THIS CAN BE | | | ACCOMPLISHED VIA A WATER-LEVEL DETECTION | | | DEVICE LOCATED IN EACH UNIT'S PRIMARY | | | DRAIN PAN. | | | | | | ANY QUESTIONS PLEASE CALL RONALD J. | | | REGUEIRO AT 561-805-6734 OR PATTY KRAUS | | | AT 561.805.6719 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-03-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-06 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-06 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2007-03-06 15:15:40 | REVISION OK - SHTS P0.1, P1.1, P1.2, P1.3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-18 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-18 |
Time |
10:07 |
Sent To |
|
|
| Notes |
| 2006-09-18 00:00:00 | REVISION OK - SHTS P1.0, P1.1, P1.2, AND | | | P1.3. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-07-05 |
Time |
07:21 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-07-05 |
Time |
07:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-03-25 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-03-25 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-03-25 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2006-03-25 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | DENIED | | | | | | 1) SHT 1.3 PLUMBING RISER DIAGRAM. | | | 606.1 LOCATION OF FULL-OPEN VALVES. | | | FULL-OPEN VALVES SHALL BE INSTALLED IN | | | THE FOLLOWING LOCATIONS: | | | (4). ON THE TOP OF EVERY WATER DOWN-FEED | | | PIPE IN OCCUPANCIES OTHER THAN ONE- AND | | | TWO-FAMILY RESIDENTIAL OCCUPANCIES. | | | 2) SHT.P1.0WATER HEATER DETAIL. | | | PROVIDE A VACUN RELIEF VALVE. | | | " NOT A VACUM BREAKER." | | | 504.2 VACUUM RELIEF VALVE. | | | BOTTOM FED WATER HEATERS AND BOTTOM FED | | | TANKS CONNECTED TO WATER HEATERS SHALL | | | HAVE A VACUUM RELIEF VALVE INSTALLED. | | | THE VACUUM RELIEF VALVE SHALL COMPLY | | | WITH ANSI Z21.22. | | | 3)SHT A2.0,A2.1 PREVIOUS COMMENT: | | | REMOVE THE TURNING CIRCLE FROM BOTH | | | STALLS. SEC.11-4.22.3 | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-11-14 |
Time |
14:40 |
Rev Time |
1.84 |
| Received By |
kstevens |
Date |
2005-11-14 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2005-11-14 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. PLANS ARE IN FOR FLAN REVIEW ONLY AT | | | THIS TIME. PLANS SUBMITTED FOR PERMIT | | | AFTER 10-01-05 SHALL BE DESIGNED FOR | | | COMPLIANCE WITH FBC-2004. | | | 2. SHTS A1.0 THRU A7.4 IMPRESSION SEAL | | | FOR ARCHITECT DOES NOT SHOW INFORMATION | | | REQUIRED BY FAC 61G1-16.002(1) AND FS | | | 481.2055. PLEASE RESEAL SHEETS WITH A | | | SEAL THAT IMPARTS INFORMATION REQUIRED. | | | 3. SHTS A1.0 THRU A7.4 AAC NUMBER IN | | | TITLE BLOCK OF ARCHITECT DOES NOT SHOW | | | UP ON DBPR WEBSITE IN SEARCH OF LICENSES | | | PLEASE VERIFY NUMBER. (SEE ATTACHED | | | SHEETS FROM DBPR WEBSITE, SHOWS LICENSE | | | NUMBER FOR ARCHITECT). | | | 4. SHTS A2.0 AND A2.1 SHOW 5' TURNING | | | AREA IN THE TOILET ROOM, NOT IN STALL. | | | SECTION 11-4.22.3. | | | 5. SUBMIT CALCULATIONS FOR MINIMUM | | | FIXTURE FACILITIES PER TABLES 1004.1.2 | | | AND 403.1. INDICATE SQUARE FOOTAGE FOR | | | EACH OCCUPANCY AND OCCUPANCY LOAD FOR | | | EACH AREA. | | | 6. SHT A2.1 ELEVATIONS 1 THRU 6 SHOW | | | COMPLIANCE WITH: | | | FOR W/C'S | | | A. 11-4.16.3 HEIGHT | | | B. 11-4.16.6 DISPENSERS | | | FOR URINALS | | | A. FLUSH CONTROLS | | | FOR LAVS | | | A. 11-4.24.2 HEIGHT & CLEARANCES | | | B. 11-4.19.4 EXPOSED PIPES & SURFACES | | | C. 11-4.19.5 FAUCETS | | | D. 11-4.19.6 MIRRORS | | | 7. SUBMIT A DETAIL FOR THE DRINKING | | | FOUNTAIN SHOWING COMPLIANCE WITH: | | | A. 11-4.15.2 SPOUT HEIGHT | | | B. 11-4.15.3 SPOUT LOCATION | | | C. 11-4.15.4 CONTROLS | | | D. 11-4.15.5 CLEARANCES | | | 8. SHT A2.2 ELEVATION 7A, SHOW | | | COMPLIANCE WITH: | | | A. 11-4.24.3 KNEE CLEARANCE | | | B. 11-4.24.4 SINK DEPTH | | | C. 11-4.24.5 CLEAR FLOOR SPACE - SHALL | | | BE FORWARD APPROACH AND SHALL EXTEND A | | | MAXIMUM OF 19" UNDERNEATH THE SINK. | | | D. 11-4.24.6 EXPOSED PIPES & SURFACES | | | E. 11-4.24.7 FAUCETS | | | 9. SUBMIT CALCULATIONS FOR ROOF | | | DRAINAGE. SHOW SQUARE FOOTAGE FOR THE | | | ROOF AND SQUARE FOOTAGE DRAINED BY EACH | | | DOWNSPOUT. SHOW 1/2 AREA OF ALL VERTICAL | | | WALLS, INCLUDING PARAPETS IN | | | CALCULATIONS. INDICATE THE GUTTER SIZE, | | | AS WELL AS THE SLOPE OF THE GUTTER. SHOW | | | THE HIGH & LOW POINTS OF THE GUTTER ON | | | THE PLANS. INDICATE THE SIZE OF ALL | | | DOWNSPOUTS. | | | 10. SHTS P1.0, P1.1, P1.2, & P1.3, | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR | | | NAME, ADDRESS, AND LICENSE NUMBER ON | | | EACH SHEET. FAC 61G15-23.002(2) AND FS | | | 471.025. | | | 11. SHT P1.2 GENERAL NOTES, AND KEYED | | | NOTES #2 REFERENCE GAS SYSTEM. NO GAS | | | SYSTEM LOCATED ON PLANS. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-11-17 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-11-17 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2006-11-17 15:05:27 | **FAILED** | | | | | | PLEASE PROVIDE AN UPDATED COPY OF THE LANDSCAPE PLAN | | | REFLECTING THE NEW CONFIGURATION OF THE PARKING AREA | | | NORTHEAST OF THE BUILDING. PLEASE NOTE THAT TERMINAL | | | ISLANDS ARE REQUIRED TO PROVIDE AT LEAST A 5 FOOT | | | UNINTERRUPTED LANDSCAPE BUFFER FOR THEIR FULL LENGTH. | | | AT LEAST ONE SHADE TREE SHALL BE PLANTED IN EACH | | | TERMINAL ISLAND. | | | | | | PLEASE SHOW HOW PLACEMENT OF THE BIKE RACK AT THE EAST | | | CORNER OF THE BUILDING WILL NOT OBSTRUCT THE SIDEWALK | | | WHEN BICYCLES ARE SECURED IN THE RACK. | | | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY | | | QUESTIONS. (561) 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2006-10-11 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2006-10-11 |
Time |
19:14 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-10-11 |
Time |
19:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
Gjoyce |
Date |
2005-12-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2006-10-11 |
Time |
19:12 |
Sent To |
R |
|
| Notes |
| 2006-06-18 00:00:00 | **** NOTE ALSO ADDED TO FRONT SCREEN, | | | THE NOTICE OF COMMENCEMENT SUBMITTED | | | DATED 2/10/06 HAS EXPIRED PER FS | | | 713.13(2). | | | THE NOC MUST BE RE-RECORDED AND | | | SUBMITTED BEFORE PICKING UP PERMIT. |
|
|