Plan Review Details - Permit 05090750
Plan Review Stops For Permit 05090750
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-03 Cont ID  
Sent By shill Date 2005-11-03 Time 13:51 Rev Time 2.00
Received By shill Date 2005-11-03 Time 13:51 Sent To  
Notes
2005-11-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SHOW ACCESSIBLE PARKING DIMENSIONS
 FOR THE SPACE AND THE ACCESS AISLE,
 FBC11-4.6.THIS IS SHOWN ON L-1.
  
 3.)PROVIDE FINISHED FLOOR ELEVATIONS
 OR SLOPE FOR THE ACCESSIBLE ROUTE
 (SIDEWALK TO ENTRANCE) AND A RAMP
 DETAIL, FBC11-4.8.SHEET ID-0.2.
  
 4.) PLEASE DECLARE OCCUPANCY FOR THE
 ADJACENT TENANT SPACE.
  
 5.) THE BLOCK WALL APPEARS TO BE A
 TENANT SEPARATION; PLEASE INDICATE AS
 SUCH. SHOW FIRE RATING OF THE EXISTING
 TENANT SEPARATION SHOWN; S4-ID4.0 REFERS
 TO U419 BUT SHOULD ALSO INDICATE RATING.
 INDICATE FIRE RATING OF THE BLOCK WALL.
 SHEET ID-2.0 REFERS TO A 1 HOUR
 OCCUPANCY SEPARATION OF AN HOUR IN THE
 FORM OF A NOTE, AND DOOR B IS SHOWN AS
 AN EXISTING FIRE RATED DOOR.SHOW THE
 FIRE RATING FOR THE DOOR.NO OCCUPANCY
 SEPARATION SHOWN ON THE PLAN.
  
 6.)PROVIDE A ROOM DESIGNATION FOR THE
 ROOM WHICH HAS ACCESS TO THE EXTERIOR
 BUT NOT ACCESS FROM THE OTHER SPACE
 (ADJACENT TO THE MODEL KITCHEN).
 DECLARE AN OCCUPANCY FOR THIS AREA.IF
 IT IS ACCESSORY STORAGE, PROVIDE
 INFORMATION AS TO WHAT WILL BE STORED.
 SHOW ANY REQUIRED TENANT OR OCCUPANCY
 SEPARATIONS.
  
 7.)THE MAXIMUM TRAVEL DISTANCE WHEN
 SCALED IS 73.5' RATHER THAN 70' AS
 INDICATED ON THE PLAN.THE PATH OF
 TRAVEL IS SHOWN GOING THROUGH FURNITURE,
 SEE ID2.1.ALSO THE PATH OF TRAVEL IN
 SOME PLACES IS AGAINST (OR VERY CLOSE
 TO) THE WALL; PLEASE SHOW A NATURAL PATH
 OF TRAVEL.IF THE TRAVEL DISTANCE
 EXCEEDS 75' A SECOND EGRESS DOOR IS
 REQUIRED, FBC1020.1(4).
  
 8.)IS THIS BUILDING SPRINKLED? PROVIDE
 FIRE SPRINKLER PLANS, FBC104.3.1.1.
  
 9.)SPECIFY MINIMUM INTERIOR FINISH
 CLASSIFICATION, FBC803.2.
  
 10.)SHOW EXIT SIGNS, FBC1016.3.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By btrobaug Date 2005-09-20 Time 09:33 Rev Time 0.75
Received By btrobaug Date 2005-09-19 Time 12:34 Sent To I
Notes
2005-09-19 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SEE 220.12(B) FOR CALCULATING TRACK
 LIGHTING LOADS, AND 215.3 FOR CONTINUOUS
 LOADS.
  
 2} SHOW REQUIRED EXIT AND EMERGENCY
 LIGHTING ON PLANS WITH CIRCUIT NUMBERS.
  
 3} PLEASE SEE 220.13 FOR RECEPTACLE
 CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By mwennerg Date 2005-10-06 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2005-10-06 Time 15:32 Sent To  
Notes
2005-10-06 00:00:00******DENIED******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
 2) PLEASE SHOW LOCATIONS OF ILLUMINATED
 EXIT SIGNS AND EMERGENCY LIGHTING
 FACILITIES.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED AT
 LOCATIONS TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-10 Cont ID  
Sent By adarroug Date 2006-01-10 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-01-10 Time 08:14 Sent To  
Notes
2006-01-10 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-22 Cont ID  
Sent By mmclean Date 2005-11-22 Time 17:34 Rev Time 0.00
Received By mmclean Date 2005-09-16 Time 16:36 Sent To  
Notes
2005-09-16 00:00:00TO "COMM" BD#15

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By hmoser Date 2005-11-14 Time 09:57 Rev Time 0.00
Received By hmoser Date 2005-11-14 Time 09:56 Sent To  
Notes
2005-11-14 00:00:00PLAN DENIED
 1) PLEASE SHOW DISTRIBUTION BOXES ON
 MAIN TRUNKLINE ON MECHANICAL PLANS
 2) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR 2001 FBC(M).
 3) PLEASE REFER TO 606.2.1 SUPPLY AIR
 SYSTEMS SMOKE DETECTORS,AND 606.4.1
 SUPERVISION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By kstevens Date 2005-11-14 Time 13:44 Rev Time 1.00
Received By kstevens Date 2005-11-14 Time 13:44 Sent To  
Notes
2005-11-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT ID-2.1 KITCHENETTE SINK SHALL
 COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SHOW ON DETAIL:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH REQUIRED
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 2. TOILET ROOM SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS. PLEASE PROVIDE A
 DETAIL. SECTION 104.2.1.
 3. THE DRINKING FOUNTAIN SHALL COMPLY
 WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS. PROVIDE A DETAIL. ALSO
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING IF THE DRINKING FOUNTAIN IS NOT
 A HIGH/LOW UNIT.
 4. A SEPARATE PLUMBING PERMIT IS
 REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By mmclean Date 2005-11-22 Time 17:31 Rev Time 0.00
Received By mmclean Date 2005-11-22 Time 17:31 Sent To  
Notes
2005-11-22 00:00:00DENIED,
 1. NEED TO PROVIDE THE PARKING PLANS FOR
 PARKING COUNT FOR LOCATION.
 (MAKING SURE THAT THE LOCATION
 MEETS/HAVE THE REQUIRED PARKING).
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720