Plan Review Details - Permit 05090701
Plan Review Stops For Permit 05090701
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-05-26 Cont ID  
Sent By alange Date 2006-05-26 Time 12:50 Rev Time 0.50
Received By alange Date 2006-05-26 Time 12:50 Sent To  
Notes
2006-05-26 00:00:00SPIRAL STAIR SUBMITTAL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 15:45 Rev Time 0.66
Received By alange Date 2006-05-09 Time 15:45 Sent To  
Notes
2006-05-09 00:00:00STRUCTURAL REV. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-19 Cont ID  
Sent By alange Date 2006-04-19 Time 16:08 Rev Time 0.25
Received By alange Date 2006-04-19 Time 16:08 Sent To  
Notes
2006-04-19 00:00:00ENERGY CALC REV OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-19 Cont ID  
Sent By alange Date 2006-01-19 Time 15:48 Rev Time 3.00
Received By alange Date 2006-01-19 Time 10:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-22 Cont ID  
Sent By alange Date 2005-12-22 Time 13:02 Rev Time 2.00
Received By alange Date 2005-12-22 Time 12:58 Sent To  
Notes
2005-12-22 00:00:00DENIED
  
  
 3.FBC TABLE 500 R-3 BUILDINGS OF TYPE
 VI CONSTRUCTION ARE LIMITED TO TWO
 STORIES.
  
 4.PLEASE SUBMIT DETAILS FOR SPRIRAL
 STAIRCASE.SHEET SUBMITTED CONTAINS
 INSUFFICIENT INFORMATION.SHOW STAIR
 DETAIL ON PLANS,FBC 1007.8.2.3
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By alange Date 2005-10-11 Time 08:21 Rev Time 4.25
Received By alange Date 2005-10-11 Time 08:21 Sent To  
Notes
2005-10-11 00:00:00DENIED
  
 1.PLEASE SIGN OWNER/AGENT ON ENERGY
 CALCS.
  
 2.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR LINTELS AND STRAPS AND
 TIEDOWNS.
 ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.FBC TABLE 500 R-3 BUILDINGS OF TYPE
 VI CONSTRUCTION ARE LIMITED TO TWO
 STORIES.
  
 4.PLEASE SUBMIT DETAILS FOR SPRIRAL
 STAIRCASE.
  
 5.CHANGE REFERENCE TO THE FBC 2004
 CODE TO THE 2001 FBC.
  
 6.FBC2305.2.2 FLOOR/CEILING
 ASSEMBLIES
 SINGLE FAMILY DWELLINGS.IN
 FLOOR/CEILING ASSEMBLIES SEPARATING
 USEABLE SPACES INTO TWO OR MORE
 APPROXIMATE AREAS WITH NO AREA
 GREATER THAN 500 SQ FT DRAFTSTOPPING
 SHALL BE PROVIDED PARALLEL TO THE MAIN
 FRAMING MEMBERS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 18:24 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 18:16 Sent To P
Notes
2006-05-02 00:00:00*********UNSAT *********
  
 1) NOTE: PLEASE SEE 230.7, SEC'S AND
 FEEDER IN DISCONNECT "A" IS NOT
 PERMITTED.
 PLEASE SEE THAT THE SEC'S TO DISC "B"
 SHALL BE IN A SEPARATE RACEWAY AND NOT
 THROUGH DISC "A".
  
 2) NOTE: PLEASE SEE ALL LV SOUND/ SPKR
 AND LV ITEMS NOT ON ORIGINAL PLANS SHALL
 BE UNDER A SEPARATE PERMIT WITH SEPARATE
 LV PLANS.
 PLEASE KNOW, ALL VALUE FOR TAHT SCOPE OF
 WORK SHALL ALSO APPLY.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 ONE ON A REVISION AND ONEUNDER A
 SEPARATE PERMIT.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-11 Cont ID  
Sent By dpalmer Date 2006-01-11 Time 16:30 Rev Time 0.00
Received By dpalmer Date 2006-01-11 Time 16:15 Sent To M
Notes
2006-01-11 00:00:00REDLINED RECEPT 2ND FLR 210.52
 REDLINED, NO ELECTRICAL WIRING OR
 CONDUITS FOR OTHER THAN LT AND SD ON
 THIRD FLR.
 3RD FLR IS TO BE NON-A/C ATTIC STORAGE.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 12:50 Rev Time 0.00
Received By dpalmer Date 2005-12-09 Time 12:33 Sent To M
Notes
2005-12-09 00:00:00*** UNSAT ***
  
 PLEASE SEE TWO NOTES FROM PREVIOUS
 REVIEW AND NOTE DUE TO BLD REVIEW.
  
  
 1)NOTE: PLEASE SEE PLANS STILL INDICATE
 ONLY ONE DISCONNECT OUTSIDE NEXT TO
 METER, WHERE-AS RISER SHOWS TWO?
 PLEASE SHOW THIS LOCATION IN ORDER TO
 VERIFY GROUPING OF MAINS.
 215.5,230.72 , 230.70
  
 2)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN
 BEFORE THE FIRST MEANS OF DISCONNECT
 LOCATED AHEAD OF MAIN "B".
 PLEASE SEE 250.6,250.24, ONLY AFTER THE
 FIRST MEANS OF DISCONNETC.
  
 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 WITH RESPECT TO 3-STORY, AND HABITABLE
 ROOM AT 3RD LEVEL.
 PLEASE SEE ELECTRICAL PLANS MAY ONLY
 INDICATE, SD, MEANS OF EGRESS LTS.
 TV, PHONE, SINK, GFI'S, AND OTHER
 ELECTRICAL RECEPTS ARE TO BE REMOVED.
 A NOTE ON ELECTRICAL, WILL BE REQUIRED
 TO STATE, " NON-HABITABLE ROOM" NOT FOR
 HUMAN OCCUPANCY".
  
 FBC TABLE 500
  
 4)NOTE: PLEASE SEE REDLINED MIN
 CLEARENCES FOR AHU DISC IN GARAGE.
 110.26
  
 PLEASE MAKE THE ABOVE CORRECTIONS, AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By dpalmer Date 2005-09-23 Time 12:10 Rev Time 1.00
Received By dpalmer Date 2005-09-23 Time 10:41 Sent To  
Notes
2005-09-23 00:00:00*********** UNSAT *********
  
 1)NOTE: PLEASE SEE 250.66,310.15B6 FOR
 MIN GROUNDING ELECTRODE CONDUCTOR FOR
 400A SERVICE AS SHOWN. 1/0 MIN.
  
 2)NOTE: PLEASE SEE 250.6,250.24, AN
 "EQUIPMENT GROUNDING CONDUCTOR" IS ONLY
 INSTALLED AFTER THE FIRST MEASN OF
 DISCONNECT(S).
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52. PLEASE SEE MANY OF THESE ARE
 REDLINED ON ONE SET OF REVIEWED PLANS
 FOR LOCATIONS.
  
 4)NOTE: PLEASE SEE MISSING BATH GFI PER
 210.52D, 210.11C3, BATH #5.
  
 PLEASE ALSO VERIFY ONLY ONE CIRCUIT
 SHOWN FOR BATH GFI CIRCUIT.?
 210.11C3. THIS IS ONLY A NOTE:
  
 5)NOTE: PLEASE SEE A RECEPT IS SHOWN ON
 ELECTRICAL PLANS FOR WHIRLPOOLTUB,
 HOWEVER THIS DEDICATED CIRCUIT IS NOT
 INDICATED ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS.
 PLEASE ALSO SEE MISSING INDICATION OF
 GFI PROTECTION PER 680.71
 215.5, 220
  
 6)NOTE: PLEASE SEE 210.8A2, WHICH
 REQUIRES ALL RECEPTS IN GARAGE NOT USED
 FOR A DEDICATED CIRCUIT, SHALL BE GFI.
 PLEASE ALSO SEE 210.8A7 FOR ALL RECEPTS
 OF WET BARS/ SINKS (NOT KITCHEN) TO BE
 GFI OR GFI PROTECTED.
 PLEASE SEE RECEPT W/IN 6' OF SINK IN
 OBSERVATION ROOM, THIRD LEVEL.
  
 7)NOTE: PLEASE SEE PLANS INDICATE ONLY
 ONE MAIN DISCONNECT AT METER LOCATIION
 ON OUTSIDE OF HOUSE, WHERE-AS RISER
 INDICATES , TWO MAINS.
 PLEAS ADJUST.
  
 8)NOTE: PLEASE INDICATE CONTINUOUS LOADS
 IN LOAD CALCUALTIONS ON PANEL "B" FOR
 POOL PUMP AND POOL HEATER. 215.3,230.42.
 THESE LOADS SHOULD BE 125% MIN.
 PLEASE ADJUST LOAD CALCS.
  
 9)NOTE: PLEASE SEE DISCONNECTING MEANS
 FOR AHU ON SECOND FLR TO MEET 110.26 OR
 IS PART OF UNIT?
 ** ONLY A NOTE**
 PLEASE SEE DISCONNECTING MEANS FOR AHU
 IN GARAGE TO MEET 110.26, IF INSTALLED.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABVOE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 08:30 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 08:30 Sent To B
Notes
2006-05-26 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 10:11 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 10:11 Sent To E
Notes
2006-05-12 00:00:00TO "DPALMER" DEK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 10:50 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 10:50 Sent To M
Notes
2006-05-04 00:00:00TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-04-28 Cont ID  
Sent By adarroug Date 2006-04-28 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-04-28 Time 11:45 Sent To E
Notes
2006-04-28 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-21 Cont ID  
Sent By adarroug Date 2006-04-21 Time 16:14 Rev Time 0.00
Received By adarroug Date 2006-04-21 Time 16:14 Sent To M
Notes
2006-04-21 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 12:45 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 12:45 Sent To B
Notes
2006-04-17 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 14:31 Sent To E
Notes
2006-01-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-09 Cont ID  
Sent By dpalmer Date 2005-12-09 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2005-12-09 Time 12:32 Sent To  
Notes
2005-12-09 00:00:00SENT TO ELEC.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-14 Cont ID  
Sent By adarroug Date 2005-11-14 Time 18:31 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 18:31 Sent To Z
Notes
2005-11-14 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 08:43 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 08:43 Sent To E
Notes
2005-09-23 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-11 Cont ID  
Sent By alange Date 2005-10-11 Time 08:32 Rev Time 0.00
Received By alange Date 2005-09-16 Time 14:09 Sent To  
Notes
2005-09-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 11:28 Rev Time 0.15
Received By tgordon Date 2006-09-28 Time 11:28 Sent To  
Notes
2006-09-28 00:00:00SUBMITTAL FOR AHU #2.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-05-04 Cont ID  
Sent By tgordon Date 2006-05-04 Time 11:14 Rev Time 0.30
Received By tgordon Date 2006-05-04 Time 11:14 Sent To  
Notes
2006-05-04 00:00:00REVISION TO MECH. PLANS.
 *** PROVISO ***
 1)DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R R309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-04-26 Cont ID  
Sent By tgordon Date 2006-04-26 Time 11:25 Rev Time 0.30
Received By tgordon Date 2006-04-26 Time 11:24 Sent To  
Notes
2006-04-26 00:00:00MECHANICAL REVISION TO PLANS.
 *** PROVISO ***
 1)DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R R309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-12 Cont ID  
Sent By tgordon Date 2006-01-12 Time 09:37 Rev Time 0.30
Received By tgordon Date 2006-01-12 Time 09:36 Sent To P
Notes
2006-01-12 00:00:00*** PROVISO ***
 1)DUCTS IN THE GARAGE AND DUCTS
 PENETRATING THE WALLS OR CEILINGS
 SEPARATING THE DWELLING FROM THE GARAGE
 SHALL BE CONSTRUCTED OF A MINIMUM NO. 26
 GAGE SHEET STEEL OR OTHER APPROVED
 MATERIAL AND SHALL HAVE NO OPENINGS INTO
 THE GARAGE. PER 2004 FBC/R R309.1.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-09 Cont ID  
Sent By tgordon Date 2005-12-09 Time 13:52 Rev Time 0.20
Received By tgordon Date 2005-12-09 Time 13:52 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By tgordon Date 2005-09-26 Time 10:45 Rev Time 0.35
Received By tgordon Date 2005-09-26 Time 10:45 Sent To P
Notes
2005-09-26 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE
 SIGNED.
 2) ENERGY CALCULATIONS CALLING FOR A 4
 TON A/C SYSTEM AND A 5 TON A/C SYSTEM,
 PLANS SHOWING TWO 5 TON A/C SYSTEMS.
 ENERGY CAL'S AND PLANS MUST COINCIDE.
 3) NEED MANUFACTURE'S INFO. REGUARDING
 MODEL NUMBER, TYPE OF GAS, AND BTU'S FOR
 VENTLESS FIREPLACE.
 4) NEED COMBUSTION AIC CALCULATIONS FOR
 VENTLESS FIREPLACE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-05-08 Cont ID  
Sent By jleech Date 2006-05-08 Time 09:17 Rev Time 0.00
Received By jleech Date 2006-05-08 Time 09:17 Sent To B
Notes
2006-05-08 00:00:00REVISION

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 14:56 Rev Time 0.50
Received By jleech Date 2006-01-13 Time 14:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-10 Cont ID  
Sent By pschmitz Date 2005-12-10 Time 12:40 Rev Time 0.00
Received By pschmitz Date 2005-12-10 Time 12:40 Sent To B
Notes
2005-12-10 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
  
 1.SHTA-3 SINK ON 3RD FLOOR.
 SEE NOTE #3 FROM BUILDING PLAN REVIEW ON
 3RD FLR.
  
 3.FBC TABLE 500 R-3 BUILDINGS OF TYPE
 VI CONSTRUCTION ARE LIMITED TO TWO
 STORIES.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-26 Cont ID  
Sent By jleech Date 2005-09-26 Time 13:47 Rev Time 0.33
Received By jleech Date 2005-09-26 Time 13:47 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-12-07 Cont ID  
Sent By mmclean Date 2005-12-07 Time 15:00 Rev Time 0.00
Received By mmclean Date 2005-12-07 Time 15:00 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-22 Cont ID  
Sent By mmclean Date 2005-09-22 Time 16:15 Rev Time 0.00
Received By mmclean Date 2005-09-22 Time 16:15 Sent To I
Notes
2005-09-22 00:00:00DENIED,
 1. BALCONY CAN ONLY ENCROACH 3FT INTO
 SETBACK. PLANS SHOWS 3' 6".
 2. MUST SHOW SECOND BALCONY ON THE SITE
 PLAN.
  
 NOTE:
 1. MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK.
 2. MUST PULL A SEPERATE PERMIT FOR FENCE
 WITH APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT, BELLSOUTH, FPL,
 FLORIDA PUBLIC UTILITIES, ADELPHIA FOR
 THE 2'6" UTILITY EASEMENT IN REAR OF
 PROPERTY.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720