Plan Review Details - Permit 05090668
Plan Review Stops For Permit 05090668
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-27 Cont ID  
Sent By lmartine Date 2006-02-27 Time 12:36 Rev Time 0.00
Received By lmartine Date 2006-02-25 Time 14:20 Sent To  
Notes
2006-02-25 00:00:00 
 BUILDING REVIEW
 -------- ------
  
  
  
 INSTALLATION OF PLYWOOD BACKING IS NOT
 PERMITTED AS AN EXTERIOR COMPONENT FOR
 TYPE IV CONSTRUCTION.
  
  
 PROVIDE COMPONENTS AND CLADDING
 PRESSURES.
  
  
  
  
 REVIEW NOT COMPLETE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By lmartine Date 2005-11-22 Time 17:10 Rev Time 0.00
Received By lmartine Date 2005-11-22 Time 17:10 Sent To  
Notes
2005-11-22 00:00:00 
  
 BUILDING REVIEW
 -------- ------
  
  
  
  
 SHEET A-3 CALLS FOR SYSTEM 1
 ENGINEERING, PRODUCT APPROVAL SUBMITTTED
 IS FOR SYSTEM 2, SUBMIT COMPLETE PRODUCT
 APPROVAL AND SPECIFY APPLICATION TO BE
 INSTALLED.
  
  
 PROVIDE BUILDING CLASSIFICATION,
 OCCUPANCY AND CONSTRUCTION TYPE.
  
  
 SPECIFY ALL FASTENERS.
  
  
  
  
  
  
 L. MARTINEZ
 805-6710

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 09:30 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 09:30 Sent To B
Notes
2006-01-19 00:00:00TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-22 Cont ID  
Sent By lmartine Date 2005-11-22 Time 17:26 Rev Time 0.00
Received By lmartine Date 2005-09-16 Time 13:35 Sent To  
Notes
2005-09-16 00:00:00TO "MISC" BOX#1