Plan Review Details - Permit 05090667
Plan Review Stops For Permit 05090667
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-22 Cont ID  
Sent By mjacobs Date 2005-10-22 Time 09:24 Rev Time 0.50
Received By mjacobs Date 2005-10-22 Time 08:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By mjacobs Date 2005-09-26 Time 14:06 Rev Time 1.50
Received By mjacobs Date 2005-09-26 Time 10:46 Sent To  
Notes
2005-09-26 00:00:001) THE FIRE RATED WALL HAS TO EXTEND TO
 THE EXTERIOR STRUCTURE OF THE BUILDING
 AND FORM THE FLOOR TO THE STRUCTURE
 ABOVE.
  
 2) IN THE AREA OF THE ELECTRICAL PANEL
 'A', PLEASE SHOW IF THAT EXISTING WALL
 IS A FIRE RATED WALL. IF IT IS NOT, THE
 NEW FIRE WALL WILL HAVE TO CONTINUE TO
 THE EXTERIOR WALL OF THE BUILDING ALSO.
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-10-20 Cont ID  
Sent By dpalmer Date 2005-10-20 Time 11:41 Rev Time 0.40
Received By dpalmer Date 2005-10-20 Time 11:34 Sent To  
Notes
2005-10-20 00:00:00RED LINED 700.12E
  
 PLANS ARE TO BE REVISED TO INDICAT EALL
 NEW CIRCUITING AND CORRELATE WITH PANEL
 SCHEDULE BEFORE FINAL ELECTRICAL
 INSPECTION.
  
  
 ** NOTE**
 ALL OTHER REVISIONS ARE TO BE SUBMITTED
 BEFORE ROUGH ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By dpalmer Date 2005-09-19 Time 09:41 Rev Time 0.50
Received By dpalmer Date 2005-09-19 Time 09:41 Sent To  
Notes
2005-09-19 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES FOR NEW ELECTRICAL.
 PLEASE SEE PANEL "A" STILL APPEARS TO BE
 SHOWN FACING INTO OTHER TENANT SPACE?
 PLEASE SEE 240.24 (A)(B).
  
 2)NOTE: PLEASE CORRELATE ELECTRICAL
 FLOOR PLAN WITH A-SHEETS, PLEASE SEE
 AREA WITH WHAT APPEARS TO CONTAIN EXIT
 LTS WITH-OUT GOING TO ANYWHERE?
 PLEASE SEE
 PLEASE SEE FIRE REVIEW COMMENTS FOR EXT
 LTS AND EM LTS TO BE ADJUSTED OR MOVED.
 NFPA-101. 7.8,7.9, PLEASE ALSO INDICATE
 CIRCUITING PER 700.12E TO LOCAL BRANCH
 CIRCUIT IN AREA
  
 3)NOTE: PLEASE VERIFY NEW OR EXISTING
 SIGN CIRCUIT REQUIRED FOR EACH. 600.5
 PLEASE INDICATEWHERE ENTRANCED IS
 LOCATED , INTERIOR HALL? EXTERIOR?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-10-18 Cont ID  
Sent By nmccray Date 2005-10-18 Time 15:41 Rev Time 0.00
Received By nmccray Date 2005-10-18 Time 15:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By mcarsill Date 2005-09-26 Time 13:03 Rev Time 0.00
Received By mcarsill Date 2005-09-26 Time 13:02 Sent To  
Notes
2005-09-26 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3. PLEASE EXPLAIN SINGLE MEANS OF EGRESS
 FROM TENANT SPACE "A". PLEASE PROVIDE
 DETAILS FOR WHAT EXCEPTION IS PLANNED
 TO BE USED.
  
 4. PLEASE EXPLAIN COMMON PATH OF TRAVEL
 IN SPACE A AND PROVIDE OCCUPANT LOADS
 FOR BOTH SPACES.
  
 5. ARE ANY EXISTING FIRE ALARM EQUIPMENT
 PRESENT IN SPACE A OR B. IS THE BUILDING
 FIRE SPRINKLER PROTECTED.
  
 IS THE RELOCATED DOOR CURRENTLY FIRE
 RATED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
  
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 14:50 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 14:50 Sent To  
Notes
2005-10-18 00:00:00TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 07:50 Rev Time 0.00
Received By pkrauss Date 2005-09-16 Time 13:49 Sent To  
Notes
2005-09-16 00:00:00TO "BOB"#7

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-11-16 Cont ID  
Sent By pkrauss Date 2005-11-16 Time 15:23 Rev Time 0.40
Received By pkrauss Date 2005-11-16 Time 15:23 Sent To  
Notes
2005-11-16 00:00:00PROVISO:
 NEW RETURN AIR TO NEW OFFICE AREAS TO BE
 SIZED EQUAL TO THE EXISTING SUPPLY INTO
 THAT OFFICE AREA - 2001 FBC(M)601.4
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-10-19 Cont ID  
Sent By hmoser Date 2005-10-19 Time 09:03 Rev Time 0.00
Received By hmoser Date 2005-10-19 Time 09:02 Sent To  
Notes
2005-10-19 00:00:00PLAN DENIED
 ALL NEW DUCT MUST HAVE DUCT SIZE AND
 CFM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By prafter Date 2005-09-27 Time 12:00 Rev Time 1.00
Received By prafter Date 2005-09-27 Time 12:00 Sent To P
Notes
2005-09-27 00:00:00MECH. PLAN REVIEW:
  
 1.THREE OFFICE/ROONS TO NORTH SIDE OF
 TENATE REMODEL REQUIRE R/A OUT OF AREA.
 2003 FBC/M 601.4 .
  
 2. DUCT SMOKE DETECTORS MUST BE TESTED
 AT FINAL INSPECTION TIME.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By pkrauss Date 2005-09-30 Time 07:48 Rev Time 0.15
Received By pkrauss Date 2005-09-30 Time 07:48 Sent To  
Notes
2005-09-30 00:00:00NO PLUMBING PLANS OR CONTRACTOR
 INDICATED WITH BUILDING PLANS &
 APPLICATION.PLAN SHEET A1 'SCOPE OF
 WORK' ITEM #4 INDICATES NO PLUMBING
 WORK.