Plan Review Stops For Permit 05090663
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2006-02-14 Cont ID  
Sent By rmcdouga Date 2006-02-14 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2006-02-14 Time 10:39 Sent To  
Notes
2006-02-14 00:00:00PROCESS REVISED SHEETS. DATE STAMP, FILE
 PLANS AND CALL CONT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-02-06 Cont ID  
Sent By rmcdouga Date 2006-02-07 Time 8:51 Rev Time 0.00
Received By rmcdouga Date 2006-02-07 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-01-25 Cont ID  
Sent By rmcdouga Date 2006-01-25 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2006-01-25 Time 10:42 Sent To  
Notes
2006-01-25 00:00:00BUILDING PLAN REVIEW
 REVISED DRAWINGS DATED 11/28/05
  
 DENIED
  
 1) THE DOOR TO THE COPY/FAX ROOM DOES
 NOT PROVIDE THE REQUIRED 18" MINIMUM
 MANEUVERING CLEARANCE ON THE PULL SIDE.
 SEE FBC 11-4.13.6. SEE SAME COMMENT ON
 FIRST REVIEW, ITEM #1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-01-10 Cont ID  
Sent By rmcdouga Date 2006-01-10 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2006-01-10 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2005-12-28 Cont ID  
Sent By rmcdouga Date 2005-12-28 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2005-12-28 Time 11:36 Sent To  
Notes
2005-12-28 00:00:00DENIED
  
 1) RECEIPT OF YOUR LETTER DATED 12/6/05
 IS NOTED. PROVIDE A BREAKDOWN OF COSTS
 SPECIFYING THE PORTION THAT WILL BE
 SPENT SPECIFICALLY ON ACCESSIBILITY.
 THIS AMOUNT MUST TOTAL 20 PER CENT OF
 THE TOTAL PROJECT COST
 (20% DISPROPORTIONATE COST) OR THE ITEMS
 REQUIRED BY FBC 11-4.1.6 MUST BE
 COMPLIED WITH.
  
 THE VALUE OF THE PROJECT IS LISTED AS
 $95,000.00 ON THE PERMIT APPLICATION.
 THE 20% DISPROPORTIONATE COST IS
 $19,000.00.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-20 Cont ID  
Sent By rmcdouga Date 2005-10-20 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2005-10-20 Time 07:23 Sent To  
Notes
2005-10-20 00:00:00BUILDING PROVISO
  
 SUBMIT A COST BREAKDOWN INDICATING THAT
 THE 20 PERCENT DISPROPORTIONATE COST HAS
 BEEN COMPLIED WITH AS REQUIRED BY FBC
 11-4.1.6.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By rmcdouga Date 2005-09-26 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2005-09-26 Time 15:34 Sent To  
Notes
2005-09-26 00:00:00BUILDING PLAN REVIEW
  
  
 DENIED
  
 1) THE DOOR TO THE COPY/FAX ROOM DOES
 NOT PROVIDE THE REQUIRED 18" MINIMUM
 MANEUVERING CLEARANCE ON THE PULL SIDE.
 SEE FBC 11-4.13.6.
  
 2) ADDRESS COMMENTS OF OTHER PLAN
 REVIEWERS.
  
 3) SPECIFY THE LOCATION OF THE
 ACCESSIBLE DRINKING FOUNTAIN. SEE FBC
 PLUMBING 403.1, 404.2 AND 410.
  
 4) FBC 11-4.1.6(2) ALTERATIONS TO AN
 AREA CONTAINING A PRIMARY FUNCTION.
 DUTY TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO ALTERED AREAS SHALL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20 % OF
 THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA.
  
 (I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-02-10 Cont ID  
Sent By jleahy Date 2006-02-10 Time 19:43 Rev Time 0.45
Received By jleahy Date 2006-02-10 Time 19:42 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-01-19 Cont ID  
Sent By dpalmer Date 2006-01-19 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2006-01-19 Time 15:14 Sent To  
Notes
2006-01-19 00:00:00REV OK.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-12-21 Cont ID  
Sent By jleahy Date 2005-12-21 Time 09:07 Rev Time 0.45
Received By jleahy Date 2005-12-21 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By dpalmer Date 2005-10-14 Time 08:31 Rev Time 0.33
Received By dpalmer Date 2005-10-14 Time 08:29 Sent To  
Notes
2005-10-14 00:00:00*** UNSAT ***
  
 1)NOTE: PLEASE SEE THAT IS DOES NOT
 APPEAR COMMENTS FROM PREVIOUS REVIEW BY
 FIRE MARSHAL'S OFFICE HAVE BEEN
 ADDRESSED.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE THE REQUUIRED EITHER NEW OR
 EXISTING EMERGENCY OR EXIT LTS AS
 REQUESTED.
 PLEASE SEE NFPA 101 7.8,7.9 AND NFAP 70
 700.12E FOR CIRCUITING.
  
 PLEASE SEE FIRE REVIEWERS COMMENT IN
 REFERENCE TO PULL STATIONS ETC.
  
 PLEASE SEE THESE WILL DIRECTLY AFFECT
 ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-19 Cont ID  
Sent By dpalmer Date 2005-09-19 Time 08:39 Rev Time 0.30
Received By dpalmer Date 2005-09-19 Time 08:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2006-02-13 Cont ID  
Sent By nmccray Date 2006-02-13 Time 11:54 Rev Time 0.00
Received By nmccray Date 2006-02-13 Time 11:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-01-23 Cont ID  
Sent By nmccray Date 2006-01-23 Time 15:18 Rev Time 0.00
Received By nmccray Date 2006-01-23 Time 15:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-21 Cont ID  
Sent By mcarsill Date 2005-12-21 Time 11:21 Rev Time 0.00
Received By mcarsill Date 2005-12-21 Time 11:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2005-10-18 Cont ID  
Sent By nmccray Date 2005-10-18 Time 10:41 Rev Time 0.00
Received By nmccray Date 2005-10-18 Time 10:41 Sent To  
Notes
2005-10-18 00:00:00PLEASE SEE NOTES FROM CAPTAIN WENNERGREN
 FROM FIRST PLAN REVIEW BY FIRE AND MAKE
 NECESSARY CORRECTIONS.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-23 Cont ID  
Sent By mwennerg Date 2005-09-23 Time 10:41 Rev Time 0.00
Received By mwennerg Date 2005-09-23 Time 10:41 Sent To  
Notes
2005-09-23 00:00:00******DENIED******
  
 1) PLANTERS SHALL NOT BE ARRANGED WHERE
 INTERFERENCE WITH EXITING REQUIREMENTS
 MAY OCCUR.
  
 2) NO MENTION OF EXIT SIGNS/EMERGENCY
 LIGHTS. NEW OR EXISTING?
  
 3) PLANS SHOW THE RELOCATION OF A PULL
 BOX AND STROBE. IS THERE AN EXISTING
 FIRE ALARM SYSTEM? PLEASE EXPLAIN
 LOCATION OF PULL BOX AWAY FROM MAIN
 EXIT?
  
 4) PLANS MENTION FIRE EXTINGUISHERS.
 2A-10 B,C RATED EXTINGUISHERS ARE
 REQUIRED AND SHALL BE MOUNTED TO SATISFY
 THE 75' TRAVEL DISTANCE BASED ON LOW
 HAZARD.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 16:26 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 16:26 Sent To  
Notes
2006-02-03 00:00:00TO "BOB"#14

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-01-18 Cont ID  
Sent By adarroug Date 2006-01-18 Time 16:26 Rev Time 0.00
Received By adarroug Date 2006-01-18 Time 16:26 Sent To  
Notes
2006-01-18 00:00:00TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 16:15 Sent To B
Notes
2006-01-09 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-14 Time 17:04 Rev Time 0.00
Received By adarroug Date 2005-12-14 Time 17:04 Sent To  
Notes
2005-12-14 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 14:04 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 14:04 Sent To  
Notes
2005-10-12 00:00:00TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-26 Cont ID  
Sent By rmcdouga Date 2005-09-26 Time 16:35 Rev Time 0.00
Received By rmcdouga Date 2005-09-16 Time 11:39 Sent To  
Notes
2005-09-16 00:00:00TO "BOB"#6

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-10-20 Cont ID  
Sent By jleech Date 2005-10-20 Time 13:40 Rev Time 0.50
Received By jleech Date 2005-10-20 Time 13:40 Sent To  
Notes
2005-10-20 00:00:00PROVISO;
 NO DEAD ENDS IN DRAINAGE SYSTEM. SEE
 FBC-2001 PLUMBING SEC. 704.5.REMOVE
 DRAIN PIPES NOT BEING USED. INSPECTION
 OF DEMO. WORK REQUIRED.
 JOHN LEECH
 805-6695