Plan Review Details - Permit 05090647
Plan Review Stops For Permit 05090647
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-24 Cont ID  
Sent By shill Date 2006-01-24 Time 14:08 Rev Time 0.00
Received By shill Date 2006-01-24 Time 14:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By shill Date 2005-11-08 Time 12:27 Rev Time 0.00
Received By shill Date 2005-11-08 Time 12:27 Sent To  
Notes
2005-11-08 00:00:00****CORRECTIONS****
 05090646 AND 05090647
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)UNDER WHICH CODE HAS THIS PROJECT
 BEEN DESIGNED?FBC2001 OR FBC2004?
 SPECIFY ON THE PLAN.THIS COMMENT LIST
 CANNOT REFER TO SPECIFIC CODE SECTIONS
 AS THIS HAS NOT YET BEEN DETERMINED.
  
 3.)THE FIRE PROTECTION SYSTEM IS TO BE
 DESIGNED BY A FIRE PROTECTION SYSTEM
 DESIGNER, FS553.79(6)(C), FAC61G15-32.
 SOMEONE HAS WRITTEN ?PRE ENGINEERED? ON
 THE SPECIFICATION SHEETS, AND MADE
 REFERENCE TO UL1245.THIS IS A TEST
 STANDARD, NOT A LISTING.ONE SET HAS
 BEEN RETAINED.
  
 4.)THE SITE PLAN IS NOT CLEAR.IS
 THE PAINT SPRAY BOOTH INSIDE OF THE
 BUILDING?THE ORIGINAL SITE PLAN HAS
 BEEN ALTERED.IF IT IS OUTSIDE, PROVIDE
 WIND DESIGN AND ANCHORING INFORMATION
 FBC16.
  
 5.)PROVIDE INFORMATION IN REGARDS TO
 THE BOOTH.CONSTRUCTION MATERIALS,
 CONNECTIONS, ETC.
  
 6.)DECLARE OCCUPANCY FOR THE EXISTING
 STRUCTURES, THE PREP STATION AND THE
 PAINT BOOTH.FBC3.SHOW OCCUPANCY
 SEPARATION IF APPLICABLE.
  
 7.)WHERE IS THE PAINT STORED?PROVIDE
 GALLONS, TYPE, ETC. TO ASSIST IN
 DETERMINING OCCUPANCY, SEE H AND S
 OCCUPANCIES.
  
 8.)ARE YOU USING LP OR NATURAL GAS?
 BOTH ARE SHOWN ON THE PLAN.WHAT IS
 THIS FOR?
  
 9.)SHEET 2 OF 6, PLAN VIEW, REFERS TO
 CLASSES AND DIVISIONS.WHAT IS THE CODE
 REFERENCE FOR THIS?INFORMATION ON THE
 PLAN IS TO BE SPECIFIC, AND CANNOT REFER
 TO CODE ONLY, ESPECIALLY CODES WHICH ARE
 NOT GOVERNING CODE FOR THIS PROJECT, FBC
 CHAPTER 1.
  
 10.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN IS
 TO BE ON THE DOCUMENT, FAC61G15-23.002.
  
 11.)PROVIDE A PENETRATION DETAIL FOR
 THE EXHAUST AND INTAKE.
  
 12.)THE CONNECTIONS FOR THE PLENUM,
 SHEET 3, IS TO BE DONE ?BY OTHERS?.
 PROVIDE A DETAIL.
  
 13.)SHOW THE DOOR DIMENSION, FBC10.
  
 14.)A PLAN WAS SHOWN FOR THE PAINT
 BOOTH, BUT NOT FOR THE PREP STATION.IT
 APPEARS THAT ONE SIDE OF THE PREP
 STATION IS OPEN, IS THAT CORRECT?IF
 NOT, SHOW EXIT DOOR ON THE PLAN.
  
 15.)SHOW EXITING INFORMATION, SEE
 FBC10.
  
 NOTE ? NOT ENOUGH INFORMATION ON THE
 PLAN TO DETERMINE CODE COMPLIANCE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 07:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By dpalmer Date 2005-10-05 Time 15:10 Rev Time 0.00
Received By dpalmer Date 2005-10-05 Time 14:52 Sent To  
Notes
2005-10-05 00:00:00****** UNSAT *****
  
 1)NOTE: PLEASE SEE FBC 104.21,
 ADMINISTRATIVE SECTION, CITY WIDE
 AMENDMENTS WHICH REQUIRES THE PRNINED
 NAME AND SIGNATUR OF THE PERSON
 RESPONSIBLE FOR PLANS TO PRINT NAME AND
 PROVIDE SIGNATURE.
  
 2)NOTE: PLEASE CORRELATE MOTORS AND
 CONNECTIONS POINTS ON ELECTRICAL PLANS
 SUBMITTED BY THE ENGINEER AND PLANS
 SUBMITTED BY THE ELECTRICAL CONTRACTOR.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-12 Cont ID  
Sent By mwennerg Date 2005-10-12 Time 14:54 Rev Time 0.00
Received By mwennerg Date 2005-10-12 Time 14:54 Sent To  
Notes
2005-10-12 00:00:00******PROVISO******
  
 SEPARATE PERMIT IS REQUIRED FOR FIRE
 SUPPRESSION SYSTEM
  
  
 SPRAY BOOTH AND PREP STATION TO BE TIED
 INTO THE BUILDING FIRE ALARM SYSTEM.
  
 PLANS WILL BE STAMPED WHEN RETURNED FOR
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By shill Date 2005-12-21 Time 12:22 Rev Time 0.00
Received By shill Date 2005-09-14 Time 08:46 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#13

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By pkrauss Date 2006-01-24 Time 12:29 Rev Time 0.00
Received By pkrauss Date 2006-01-24 Time 12:29 Sent To  
Notes
2006-01-24 00:00:00SEE PERMIT 05090646

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-01-24 Cont ID  
Sent By jleech Date 2006-01-24 Time 12:58 Rev Time 0.00
Received By jleech Date 2006-01-24 Time 12:58 Sent To  
Notes
2006-01-24 00:00:00NO PLUMBING ON THIS PLAN.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By kstevens Date 2005-11-14 Time 07:48 Rev Time 0.00
Received By kstevens Date 2005-11-14 Time 07:48 Sent To  
Notes
2005-11-14 00:00:00NO NOTES THIS PERMIT. SEE PLAN REVIEW
 NOTES PERMIT NUMBER 05090646

Review Stop Z ZONING
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By shill Date 2006-01-24 Time 14:07 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2006-01-24 00:00:00SEE MASTER 05090646