Plan Review Details - Permit 05090646
Plan Review Stops For Permit 05090646
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By shill Date 2006-01-24 Time 12:22 Rev Time 0.00
Received By shill Date 2006-01-24 Time 12:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-22 Cont ID  
Sent By shill Date 2005-12-22 Time 20:21 Rev Time 2.00
Received By shill Date 2005-12-22 Time 20:21 Sent To  
Notes
2005-12-22 00:00:00****CORRECTIONS****
 05090646 AND 05090647
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 PREVIOUS CORRECTION LIST; NUMBERING TO
 REMAIN THE SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 REQUIRED BEFORE THE PERMIT CAN BE
 ISSUED.
  
 2.)UNDER WHICH CODE HAS THIS PROJECT
 BEEN DESIGNED?FBC2001 OR FBC2004?
 SPECIFY ON THE PLAN.THIS COMMENT LIST
 CANNOT REFER TO SPECIFIC CODE SECTIONS
 AS THIS HAS NOT YET BEEN DETERMINED.
  
 FBC2000 WAS HAND WRITTEN ON THE PLAN,
 SHEET 2. THIS IS NOT A VALID GOVERNING
 CODE. SHEET 5 HAS FBC2004 HAND WRITTEN.
 ANY CHANGES TO THE PLAN ARE TO BE DONE
 BY THE ENGINEER.IF CHANGES ARE
 HANDWRITTEN, THEY ARE TO BE INITIALED.
 AS IT APPEARS THAT CHANGES MAY HAVE BEEN
 DONE BY SOMEONE OTHER THAN MR. MOLYET,
 PE, I WOULD LIKE CONFIRMATION EITHER BY
 SIGNED AND SEALED LETTER THAT HAND
 WRITTEN CHANGES WERE DONE BY HIM, OR
 HAVE THE CHANGES IMPLEMENTED INTO THE
 PLAN AND NEW SHEETS PRINTED.
  
 IT IS STILL UNCLEAR AS TO WHICH CODE THE
 ENGINEER HAS DESIGNED TO.
  
 3.)THE FIRE PROTECTION SYSTEM IS TO BE
 DESIGNED BY A FIRE PROTECTION SYSTEM
 DESIGNER, FS553.79(6)(C), FAC61G15-32.
 SOMEONE HAS WRITTEN "PRE ENGINEERED" ON
 THE SPECIFICATION SHEETS, AND MADE
 REFERENCE TO UL1245.THIS IS A TEST
 STANDARD, NOT A LISTING.ONE SET HAS
 BEEN RETAINED.
  
 NOT ADDRESSED.SAME PLANS SUBMITTED.
 THE WORDS "PYRO-CHEM IS THE DESIGNER FOR
 A PRE-ENGINEERED FIRE SYSTEM - UL 1254
 IS THE LISTING" WAS WRITTEN ON THE SAME
 UNSEALED PLAN.IF PYRO-CHEM IS LICENSED
 TO BE A FIRE PROTECTION SYSTEM DESIGNER,
 PROVIDE PLANS IN COMPLIANCE - SIGNED,
 SEALED, TITLE BLOCK.SEE FAC61G15-23,
 FAC615-32.PLEASE CONTACT FBPE IF THE
 DESIGN PROFESSIONAL IS UNCLEAR AS TO HIS
 OR HER RESPONSIBILITIES.
  
 4.)THE SITE PLAN IS NOT CLEAR.IS
 THE PAINT SPRAY BOOTH INSIDE OF THE
 BUILDING?THE ORIGINAL SITE PLAN HAS
 BEEN ALTERED.IF IT IS OUTSIDE, PROVIDE
 WIND DESIGN AND ANCHORING INFORMATION
 FBC16.
  
 PROVIDE A SITE PLAN PREPARED BY DESIGNER
 OF RECORD AS THE SITE PLAN ADDRESSES
 CODE COMPLIANCE ISSUES.
  
 5.)PROVIDE INFORMATION IN REGARDS TO
 THE BOOTH.CONSTRUCTION MATERIALS,
 CONNECTIONS, ETC.
  
 DESIGNER OF RECORD IS TO PROVIDE DESIGN
 CRITERIA ON THE PLAN.THE ASSEMBLY
 INSTRUCTIONS ARE NOT REQUIRED TO BE A
 PART OF THE PERMIT PACKAGE.HAVE THE
 ENGINEER PROVIDE INFORMATION REQUESTED.
  
 6.)DECLARE OCCUPANCY FOR THE EXISTING
 STRUCTURES, THE PREP STATION AND THE
 PAINT BOOTH.FBC3.SHOW OCCUPANCY
 SEPARATION IF APPLICABLE.
  
 NOT ADDRESSED."ONE MAN IN PAINT BOOTH"
 IS NOT AN OCCUPANCY.IF THE ENGINEER IS
 UNCLEAR AS TO HOW TO DECLARE AN
 OCCUPANCY AND SHOW SEPARATIONS AS
 REQUESTED, PLEASE HAVE HIM CONTACT ME.
  
 7.)WHERE IS THE PAINT STORED?PROVIDE
 GALLONS, TYPE, ETC. TO ASSIST IN
 DETERMINING OCCUPANCY, SEE H AND S
 OCCUPANCIES.
  
 NOT ADDRESSED.
  
 8.)ARE YOU USING LP OR NATURAL GAS?
 BOTH ARE SHOWN ON THE PLAN.WHAT IS
 THIS FOR?
  
 THERE IS A NOTE (WHICH IS NOT INITIALED
 AS REQUIRED) WHICH INDICATES THAT THIS
 WILL BE NATURAL GAS.WHAT IS THIS FOR?
  
 9.)SHEET 2 OF 6, PLAN VIEW, REFERS TO
 CLASSES AND DIVISIONS.WHAT IS THE CODE
 REFERENCE FOR THIS?INFORMATION ON THE
 PLAN IS TO BE SPECIFIC, AND CANNOT REFER
 TO CODE ONLY, ESPECIALLY CODES WHICH ARE
 NOT GOVERNING CODE FOR THIS PROJECT, FBC
 CHAPTER 1.
  
 NOT ADDRESSED.
  
 10.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN IS
 TO BE ON THE DOCUMENT, FAC61G15-23.002.
  
 PROVIDE A TITLE BLOCK WITH ALL
 INFORMATION REQUIRED BY FAC61G15-23.002.
  
 11.)PROVIDE A PENETRATION DETAIL FOR
 THE EXHAUST AND INTAKE.
  
 NOT ADDRESSED.
  
 12.)THE CONNECTIONS FOR THE PLENUM,
 SHEET 3, IS TO BE DONE "BY OTHERS".
 PROVIDE A DETAIL.
  
 ENGINEER CANNOT ADDRESS THIS STRUCTURAL
 ITEM WITH A SHOP DRAWING.INCORPORATE
 INTO THE PLAN OR PROVIDE A TITLE BLOCK,
 SIGN AND SEAL THE DRAWING WHICH WAS
 STAPLED TO THE PLAN.
  
 13.)SHOW THE DOOR DIMENSION, FBC10.
  
 CHANGES TO THE PLAN ARE TO BE INITIALED
 OR INCORPORATED INTO THE PLAN.
  
 14.)A PLAN WAS SHOWN FOR THE PAINT
 BOOTH, BUT NOT FOR THE PREP STATION.IT
 APPEARS THAT ONE SIDE OF THE PREP
 STATION IS OPEN, IS THAT CORRECT?IF
 NOT, SHOW EXIT DOOR ON THE PLAN.
  
 SHEET 2 SHOWS DOORS WHICH DO NOT APPEAR
 TO BE COMPLIANT WITH FBC11-4.13.PLAN
 VIEW HAS AN ACCESS DOOR HAND DRAWN.IT
 APPEARS THAT THERE ARE FOLDING DOORS IN
 THE FRONT, BUT THE PLAN VIEW DOES NOT
 CORRELAT WITH THE FRONT VIEW.THERE ARE
 TWO PLAN VIEWS, BOTH REFER TO THE SPRAY
 BOOTH.PROVIDE FLOOR PLANS FOR THE PREP
 STATION AND THE PAINT BOOTH, CLEARLY
 SHOW DOORS, SO THAT CODE COMPLIANCE (FBC
 CHAPTER 10 AND FBC CHAPTER 11) CAN BE
 DETERMINED.
  
 15.)SHOW EXITING INFORMATION, SEE
 FBC10.
  
 NOT ADDRESSED.ENGINEER IS TO PROVIDE A
 CLEAR SITE PLAN, A FLOOR PLAN OF THE
 EXISTING, SHOW THE PROPOSED
 IMPROVEMENTS, AND A LIFE SAFETY PLAN.
  
 NOTE - NOT ENOUGH INFORMATION ON THE
 PLAN TO DETERMINE CODE COMPLIANCE.
  
  
 NEW COMMENT -
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT PROPERLY ADDRESSED IN
 THE THIRD REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By shill Date 2005-11-08 Time 12:25 Rev Time 2.00
Received By shill Date 2005-11-08 Time 12:25 Sent To  
Notes
2005-11-08 00:00:00****CORRECTIONS****
 05090646 AND 05090647
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)UNDER WHICH CODE HAS THIS PROJECT
 BEEN DESIGNED?FBC2001 OR FBC2004?
 SPECIFY ON THE PLAN.THIS COMMENT LIST
 CANNOT REFER TO SPECIFIC CODE SECTIONS
 AS THIS HAS NOT YET BEEN DETERMINED.
  
 3.)THE FIRE PROTECTION SYSTEM IS TO BE
 DESIGNED BY A FIRE PROTECTION SYSTEM
 DESIGNER, FS553.79(6)(C), FAC61G15-32.
 SOMEONE HAS WRITTEN ?PRE ENGINEERED? ON
 THE SPECIFICATION SHEETS, AND MADE
 REFERENCE TO UL1245.THIS IS A TEST
 STANDARD, NOT A LISTING.ONE SET HAS
 BEEN RETAINED.
  
 4.)THE SITE PLAN IS NOT CLEAR.IS
 THE PAINT SPRAY BOOTH INSIDE OF THE
 BUILDING?THE ORIGINAL SITE PLAN HAS
 BEEN ALTERED.IF IT IS OUTSIDE, PROVIDE
 WIND DESIGN AND ANCHORING INFORMATION
 FBC16.
  
 5.)PROVIDE INFORMATION IN REGARDS TO
 THE BOOTH.CONSTRUCTION MATERIALS,
 CONNECTIONS, ETC.
  
 6.)DECLARE OCCUPANCY FOR THE EXISTING
 STRUCTURES, THE PREP STATION AND THE
 PAINT BOOTH.FBC3.SHOW OCCUPANCY
 SEPARATION IF APPLICABLE.
  
 7.)WHERE IS THE PAINT STORED?PROVIDE
 GALLONS, TYPE, ETC. TO ASSIST IN
 DETERMINING OCCUPANCY, SEE H AND S
 OCCUPANCIES.
  
 8.)ARE YOU USING LP OR NATURAL GAS?
 BOTH ARE SHOWN ON THE PLAN.WHAT IS
 THIS FOR?
  
 9.)SHEET 2 OF 6, PLAN VIEW, REFERS TO
 CLASSES AND DIVISIONS.WHAT IS THE CODE
 REFERENCE FOR THIS?INFORMATION ON THE
 PLAN IS TO BE SPECIFIC, AND CANNOT REFER
 TO CODE ONLY, ESPECIALLY CODES WHICH ARE
 NOT GOVERNING CODE FOR THIS PROJECT, FBC
 CHAPTER 1.
  
 10.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN IS
 TO BE ON THE DOCUMENT, FAC61G15-23.002.
  
 11.)PROVIDE A PENETRATION DETAIL FOR
 THE EXHAUST AND INTAKE.
  
 12.)THE CONNECTIONS FOR THE PLENUM,
 SHEET 3, IS TO BE DONE ?BY OTHERS?.
 PROVIDE A DETAIL.
  
 13.)SHOW THE DOOR DIMENSION, FBC10.
  
 14.)A PLAN WAS SHOWN FOR THE PAINT
 BOOTH, BUT NOT FOR THE PREP STATION.IT
 APPEARS THAT ONE SIDE OF THE PREP
 STATION IS OPEN, IS THAT CORRECT?IF
 NOT, SHOW EXIT DOOR ON THE PLAN.
  
 15.)SHOW EXITING INFORMATION, SEE
 FBC10.
  
 NOTE ? NOT ENOUGH INFORMATION ON THE
 PLAN TO DETERMINE CODE COMPLIANCE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 07:54 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 10:42 Sent To  
Notes
2005-12-21 00:00:00SEE REVIEW UNDER 05070647

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By dpalmer Date 2005-10-05 Time 15:24 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2005-10-05 00:00:00SEE NOTES UNDER 05090647

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-19 Cont ID  
Sent By mcarsill Date 2005-12-19 Time 10:40 Rev Time 0.00
Received By mcarsill Date 2005-12-19 Time 10:32 Sent To  
Notes
2005-12-19 00:00:001. NEW SPRAY BOOTH IS SUBJECT TO FIELD
 INSPECTION.
  
 2. SPRAY BOOTH AND EXTINGUISHING SYSTEM
 TO COMPLY WITH NFPA APPROPRIATE
 STANDARDS.
  
 3. SEPERATE PLANS AND PERMITS REQUIRED
 FOR REQUIRED FIRE SUPPRESSION SYSTEM.
  
 4. SPRAY BOOTH INSTALLATION SHALL COMPLY
 WITH NFPA 33.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-12 Cont ID  
Sent By mwennerg Date 2005-10-12 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2005-10-12 Time 15:30 Sent To  
Notes
2005-10-12 00:00:00******PROVISO******
  
 SPRAY BOOTH AND PREP STATION TO BE TIED
 INTO BUILDING FIRE ALARM SYSTEM.
  
 SEE OTHER REVIEW REGARDING FIRE
 SUPPRESSION SYSTEM.
  
 PLANS WILL BE STAMPED WHEN RETURNED FOR
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-12-13 Cont ID  
Sent By jleech Date 2005-12-13 Time 13:44 Rev Time 0.00
Received By jleech Date 2005-12-13 Time 13:44 Sent To  
Notes
2005-12-13 00:00:00GAS PLANS TOBE SUBMITED BY GAS
 CONTRACTOR AT TIME OF PERMIT
 APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-24 Cont ID  
Sent By shill Date 2006-01-24 Time 11:12 Rev Time 0.00
Received By shill Date 2006-01-24 Time 11:12 Sent To  
Notes
2006-01-24 00:00:00TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 09:41 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 09:41 Sent To  
Notes
2005-12-16 00:00:00TO "COMM" BD#29
2005-11-30 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-23 Cont ID  
Sent By adarroug Date 2005-09-23 Time 09:44 Rev Time 0.00
Received By adarroug Date 2005-09-23 Time 09:44 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#13
2005-09-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-15 Cont ID  
Sent By adarroug Date 2005-09-15 Time 08:33 Rev Time 0.00
Received By adarroug Date 2005-09-15 Time 08:33 Sent To Z
Notes
2005-09-15 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-01-24 Cont ID  
Sent By pkrauss Date 2006-01-24 Time 12:28 Rev Time 0.00
Received By pkrauss Date 2006-01-24 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-09 Cont ID  
Sent By pkrauss Date 2006-01-09 Time 16:31 Rev Time 0.00
Received By pkrauss Date 2006-01-09 Time 14:23 Sent To  
Notes
2006-01-09 00:00:00DENIED:
 PLANS INDICATE 2000 FBC ON PLAN SHEET 2
 OF 2 (SHOULD READ 2001 OR 2004 FBC).
 PLEASE NOTE THE 2001 FBC WAS IN EFFECT
 UNTIL SEPTEMBER 30, 2005.2004 FBC WENT
 INTO EFFECT OCTOBER 1, 2005.PLEASE
 REVISE PLANS TO INDICATE WHICH CODE THIS
 IS DESIGNED TO.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By hmoser Date 2005-11-10 Time 10:23 Rev Time 0.00
Received By hmoser Date 2005-11-10 Time 10:23 Sent To  
Notes
2005-11-10 00:00:00PLAN DENIED
 1) NEED TWO SETS OF PLANS.
 2) PLEASE REFER TO SECTION 401.5 OPENING
 LOCATION.AND 401.5.1 INTAKE OPENINGS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status N Date 2005-12-13 Cont ID  
Sent By jleech Date 2005-12-13 Time 13:47 Rev Time 0.00
Received By jleech Date 2005-12-13 Time 13:47 Sent To  
Notes
2005-12-13 00:00:00NO PLUMBING ON THIS PLAN. GAS PLAN WILL
 BE PROVIDED BY GAS CONTRACTOR WHEN GAS
 APPLICATION IS SUBMITED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By kstevens Date 2005-11-14 Time 07:19 Rev Time 1.67
Received By kstevens Date 2005-11-12 Time 19:03 Sent To  
Notes
2005-11-14 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 B. 2 OR MORE SETS OF CONSTRUCTION
 DOCUMENTS SHALL BE SUBMITTED WITH EACH
 APPLICATION FOR A PERMIT. SECTION 106.1
 C. ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. - NO NAME ORADDRESS
 SHOWN ON TITLE BLOCK. FAC
 61G15-23-002(2) AND FS 471.025.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-22 Cont ID  
Sent By mmclean Date 2005-09-22 Time 14:45 Rev Time 0.00
Received By mmclean Date 2005-09-22 Time 14:45 Sent To I
Notes
***NONE***