Plan Review Details - Permit 05090644
Plan Review Stops For Permit 05090644
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-05 Cont ID  
Sent By alange Date 2005-10-05 Time 09:43 Rev Time 0.50
Received By alange Date 2005-10-05 Time 09:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-09-30 Cont ID  
Sent By mjacobs Date 2005-09-30 Time 08:59 Rev Time 2.00
Received By mjacobs Date 2005-09-30 Time 07:04 Sent To PC
Notes
2005-09-30 00:00:001) THE PRODUCT APPROVAL SUBMITTED FOR
 THE MODIFIED BITUMEN ROOF SYSTEM IS NOT
 APPROVED ON THE STATE WEBSITE AT THIS
 PRESENT MOMENT. SUBMIT AN APPROVED
 PRODUCT FOR PLAN REVIEW. IS THE DECK
 INSULATED OR NOT.
 NOTE:
 FBC 1606.2.5THE SYSTEM SELECTED FROM
 THE SUBMITTED FLAT ROOF PRODUCT APPROVAL
 NOA HAS A MAXIMUM DESIGN PRESSURE OF
 LESS THAN -89 PSF AND CITES GENERAL
 LIMITATION #9 (SEE PAGE 14/33 OF 38).
 GENERAL LIMITATION #9 PROHIBITS RATIONAL
 ANALYSIS OR EXTRAPOLATION TO ENHANCE THE
 UPLIFT PRESSURE AT PERIMETER AND CORNER
 AREAS BY REDUCING THE FASTENER SPACING
 IN THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 2) THE STATE COVER SHEET IS REQUIRED FOR
 ALL PRODUCT APPROVALS OR YOU MAY APPLY
 FOR LOCAL PRODUCT APPROVAL. THE BARREL
 ROOF TILE REPORT NEEDS THE STATE COVER
 SHEET.
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 BUILDING PLAN REVIEW
 MYRON JACOBS
 TEL: (561)805-6726
 FAX: (561)659-8026
 [email protected].
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-14 Cont ID  
Sent By rmcdouga Date 2005-09-14 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2005-09-14 Time 17:32 Sent To  
Notes
2005-09-14 00:00:00DENIED
  
 1) SPECIFY THE MEAN ROOF HEIGHT IN FEET.
  
 2) THE EVALUATION REPORT LISTED ON THE
 WEBSITE FOR FL3505-R1 FOR HASON BARREL
 TILE IS ICC/ES REPORT # 2203. SUBMIT THE
 CORRECT REPORT.
  
 3) SPECIFY HOW THE TILE WILL BE
 ATTACHED. MORTAR OR ADHESIVE.
  
 4) THE NOA THAT WAS SUBMITTED FOR THE
 POLYGLASS MODIFIED WITH # FL985-R1 HAS
 BEEN REVISED THE NEW NOA IS NUMBER
 03-0130.08.
  
 5) SUBMIT STATE PRODUCT APPROVAL FOR THE
 FLAT ROOF COVERING AND SPECIFY WHICH ONE
 OF THE APPROVED ASSEMBLIES WILL BE
 INSTALLED.
  
 6)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2005-09-14 00:00:00OK PER W ADAMS 9-14-05

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-04 Cont ID  
Sent By adarroug Date 2005-10-04 Time 16:42 Rev Time 0.00
Received By adarroug Date 2005-10-04 Time 16:42 Sent To B
Notes
2005-10-04 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-29 Cont ID  
Sent By mjacobs Date 2005-09-29 Time 16:43 Rev Time 0.00
Received By mjacobs Date 2005-09-29 Time 16:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By adarroug Date 2005-09-29 Time 13:03 Rev Time 0.00
Received By adarroug Date 2005-09-29 Time 13:03 Sent To B
Notes
2005-09-29 00:00:00TO 'MJACOBS" DESK/RESUB