| 2005-09-30 00:00:00 | *******DENIED******* |
| | MYRON JACOBS(561) 805 6726 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | 1) FBC 1606.2.5THE SYSTEM SELECTED |
| | FROM THE SUBMITTED FLAT ROOF PRODUCT |
| | APPROVAL NOA HAS A MAXIMUM DESIGN |
| | PRESSURE OF LESS THAN -89 PSF AND CITES |
| | GENERAL LIMITATION #9 (SEE PAGE 39 OF |
| | 45).GENERAL LIMITATION #9 PROHIBITS |
| | RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| | ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| | AND CORNER AREAS BY REDUCING THE |
| | FASTENER SPACING IN THESE AREAS.EITHER |
| | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| | APPROVAL) THAT DOES NOT CITE GENERAL |
| | LIMITATION #9.ALTERNATIVELY IF THE |
| | SELECTED SYSTEM DOES CITE GENERAL |
| | LIMITATION #9, IT MUST HAVE A MAXIMUM |
| | DESIGN PRESSURE THAT EXCEEDS THE |
| | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| | LESS). |
| | |
| | 2) FL#560-R1 IS NOT APPROVED ON THE |
| | STATE WEB-SITE. CHOOSE AN APPROVED |
| | PRODUCT AND SUBMIT IT FOR PLAN REVIEW. |
| | THE REPORT ON THE WEB-SITE IS A SBCCI |
| | REPORT. |
| | |