| 2005-10-17 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- NEED FLORIDA PRODUCT APPROVAL OR |
| | LOCAL PRODUCT APPROVAL AS REQUIRED BY |
| | RULE 9B-72 OF DCA. SEE |
| | WWW.FLORIDABUILDING.ORG. |
| | DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATEWIDE PRODUCT |
| | APPROVAL. IF THERE IS NOT FLORIDA |
| | PRODUCT APPROVAL, THEN MANUFACTURER MAY |
| | APPLY FOR LOCAL PRODUCT APPROVAL USING |
| | THE DADE COUNTY NOA AND COMPLETING THE |
| | LOCAL PRODUCT APPROVAL FORM DOWNLOADED |
| | FROM WWW.FLORIDABUILDING.ORG. |
| | |
| | 3- CLEARLY SPECIFY WHERE IS THE EGRESS |
| | OPENING THAT COMPLIES WITH SEC. 1005.4.5 |
| | FBC 2001. |
| | |
| | 4- PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. |
| | |
| | 5- CLEARLY MARK ON DRAWINGS SPECIFIC |
| | ANCHOR TYPE AND SPACING TO BE USED |
| | ACCORDING TO THE DESIGN PRESSURES, EDGE |
| | DISTANCE, PANEL SPAN, CONNECTION TYPE |
| | AND STRUCTURE TO BE ATTACHED TO |
| | (CONCRETE, CONCRETE BLOCK OR WOOD). SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 6- ENGINEER WIND LOAD CHART CANN'T BE |
| | MARKED UP. SEE GENERAL NOTE #7. CHART |
| | WAS MARKED UP. PROVIDE CLEAN ONE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |