Plan Review Details - Permit 05090557
Plan Review Stops For Permit 05090557
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-17 Cont ID  
Sent By jgomez Date 2005-10-17 Time 12:36 Rev Time 0.33
Received By jgomez Date 2005-10-17 Time 12:36 Sent To PC
Notes
2005-10-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- NEED FLORIDA PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL AS REQUIRED BY
 RULE 9B-72 OF DCA. SEE
 WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE PRODUCT
 APPROVAL. IF THERE IS NOT FLORIDA
 PRODUCT APPROVAL, THEN MANUFACTURER MAY
 APPLY FOR LOCAL PRODUCT APPROVAL USING
 THE DADE COUNTY NOA AND COMPLETING THE
 LOCAL PRODUCT APPROVAL FORM DOWNLOADED
 FROM WWW.FLORIDABUILDING.ORG.
  
 3- CLEARLY SPECIFY WHERE IS THE EGRESS
 OPENING THAT COMPLIES WITH SEC. 1005.4.5
 FBC 2001.
  
 4- PROVIDE A COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 5- CLEARLY MARK ON DRAWINGS SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE, CONCRETE BLOCK OR WOOD). SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 6- ENGINEER WIND LOAD CHART CANN'T BE
 MARKED UP. SEE GENERAL NOTE #7. CHART
 WAS MARKED UP. PROVIDE CLEAN ONE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 14:01 Sent To B
Notes
2005-09-13 00:00:00TO "JGOMEZ" DESK