| 2005-09-27 00:00:00 | ************ UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | AND PANEL SCHEDULES. |
| | PLEASE SEE RISER SHOWS THREE PANELS |
| | BEING FED FROM EXISTING MDP, HOWEVER MDP |
| | ONLY SHOWS FEEDS TO PANEL "A" AND PANEL |
| | "B"? PLEASE CLARIFY WHERE FED TO PANEL |
| | "C" IS LOCATED. |
| | PLEASE IDENTIFY ALL PANELS ON RISER |
| | DIAGRAM. |
| | PLEASE SEE RISER SHOWS ONE "NEW" PANEL |
| | BEING FED FROM MDP , HOWEVER PLANS |
| | INDICATE ALL PANELS AN "EXISTING " AND |
| | PANEL SCHEDULES ALSO INDICATE ALL PANEL |
| | SCHEDULES AS EXISTING.?? |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE INDICATE OF NEW OR |
| | EXISTING ROOF-TOP GFI IS PROVIDED. |
| | 210.63 |
| | |
| | 3)NOTE; PLEASE INDICATE NEW OR EXISTING |
| | REQUIRED SIGN CIRCUIT PER 600.5 |
| | |
| | 4)NOTE: PLEASE SEE 210.62 FOR REQUIRED |
| | "SHOW WINDOW" RECEPTS. |
| | PLEASE SEE OCCUPANCY NOW INDICATES AN |
| | NEW "SHOWROOM". |
| | NEW RECEPTS LOCATED ABOVE WINDOWS WILL |
| | BE REQUIRED. |
| | PLEASE SEE 220.12 FOR LOAD CALCUALTIONS |
| | AND CIRCUITING.220.3B7 |
| | |
| | 5)NOTE: PLEASE SEE SOME ITEMS INDICATED |
| | AS "E" (EXISTING ) ON PLANS AND SOME |
| | NEW, AND SOME ?? |
| | |
| | 6)NOTE: PLEASE NOTE/ CIRCUIT EM/ EXT LTS |
| | PER 700.12E. |
| | PLEASE SEE THAT ALL EM/EXT LTS SHALL BE |
| | CIRCUITED TO THE LOCAL BRANCH CIRCUIT |
| | FEEDING AREA. |
| | |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED PLANS AND |
| | ONLY INSERT NEW REVISED PLANS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |