Plan Review Details - Permit 05090555
Plan Review Stops For Permit 05090555
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-10 Cont ID  
Sent By lmartine Date 2006-01-10 Time 12:45 Rev Time 0.00
Received By lmartine Date 2006-01-10 Time 12:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-06 Cont ID  
Sent By shill Date 2005-11-06 Time 14:49 Rev Time 0.00
Received By shill Date 2005-11-06 Time 14:37 Sent To  
Notes
2005-11-06 00:00:00FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE NOTICE OF COMMENCEMENT IS TO
 INCLUDE THE LEGAL DESCRIPTION, FS713.13.
  
 2.)THE APPLICATION INDICATES THAT A
 ROLL UP DOOR IS TO BE INSTALLED.
 PRODUCT APPROVALS REQUIRED.INCLUDE
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING ? AREA, HEIGHT,
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 NOT, BUILDING TYPE FBC6.
  
 4.)PROVIDE AREA CALCULATIONS ON THE
 PLAN (AREA OF NEW STORAGE, TOTAL AREA)
 TO SHOW COMPLIANCE WITH FBC704.1.2.2(4).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By dpalmer Date 2005-12-21 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2005-12-21 Time 17:28 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By dpalmer Date 2005-09-27 Time 20:43 Rev Time 0.75
Received By dpalmer Date 2005-09-27 Time 20:32 Sent To  
Notes
2005-09-27 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES.
 PLEASE SEE RISER SHOWS THREE PANELS
 BEING FED FROM EXISTING MDP, HOWEVER MDP
 ONLY SHOWS FEEDS TO PANEL "A" AND PANEL
 "B"? PLEASE CLARIFY WHERE FED TO PANEL
 "C" IS LOCATED.
 PLEASE IDENTIFY ALL PANELS ON RISER
 DIAGRAM.
 PLEASE SEE RISER SHOWS ONE "NEW" PANEL
 BEING FED FROM MDP , HOWEVER PLANS
 INDICATE ALL PANELS AN "EXISTING " AND
 PANEL SCHEDULES ALSO INDICATE ALL PANEL
 SCHEDULES AS EXISTING.??
 215.5
  
 2)NOTE: PLEASE INDICATE OF NEW OR
 EXISTING ROOF-TOP GFI IS PROVIDED.
 210.63
  
 3)NOTE; PLEASE INDICATE NEW OR EXISTING
 REQUIRED SIGN CIRCUIT PER 600.5
  
 4)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 "SHOW WINDOW" RECEPTS.
 PLEASE SEE OCCUPANCY NOW INDICATES AN
 NEW "SHOWROOM".
 NEW RECEPTS LOCATED ABOVE WINDOWS WILL
 BE REQUIRED.
 PLEASE SEE 220.12 FOR LOAD CALCUALTIONS
 AND CIRCUITING.220.3B7
  
 5)NOTE: PLEASE SEE SOME ITEMS INDICATED
 AS "E" (EXISTING ) ON PLANS AND SOME
 NEW, AND SOME ??
  
 6)NOTE: PLEASE NOTE/ CIRCUIT EM/ EXT LTS
 PER 700.12E.
 PLEASE SEE THAT ALL EM/EXT LTS SHALL BE
 CIRCUITED TO THE LOCAL BRANCH CIRCUIT
 FEEDING AREA.
  
  
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED PLANS AND
 ONLY INSERT NEW REVISED PLANS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-10 Cont ID  
Sent By mwennerg Date 2006-01-10 Time 15:10 Rev Time 0.00
Received By mwennerg Date 2006-01-10 Time 15:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mwennerg Date 2005-10-04 Time 14:13 Rev Time 0.00
Received By mwennerg Date 2005-10-04 Time 14:12 Sent To  
Notes
2005-10-04 00:00:00******OK******
  
 AN EXIT SIGN WILL BE REQUIRED AT THE
 SIDE HINGED DOOR LOCATED NEXT TO THE
 ROLL UP DOOR IN THE STORAGE ROOM.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 09:25 Sent To  
Notes
2005-12-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 12:59 Rev Time 0.00
Received By kstevens Date 2005-09-13 Time 15:33 Sent To  
Notes
2005-09-13 00:00:00TO "COMM" BD#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-08 Cont ID  
Sent By hmoser Date 2005-11-08 Time 17:58 Rev Time 0.00
Received By hmoser Date 2005-11-08 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 12:58 Rev Time 0.33
Received By kstevens Date 2005-11-12 Time 12:58 Sent To  
Notes
2005-11-12 00:00:00PLUMBING DEMO PERMIT REQUIRED. NO DEAD
 ENDS ALLOWED. SECTION 704.5