| Plan Review Stops For Permit 05090521 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-01-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-01-03 |
Time |
15:32 |
Rev Time |
1.25 |
| Received By |
alange |
Date |
2006-01-03 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-12-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-12-01 |
Time |
11:17 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2005-12-01 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2005-12-01 00:00:00 | DENIED | | | | | | 3.PRODUCT APPROVALS STILL MISSING FOR | | | LINTELS. | | | | | | 4.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE PRODUCT APPROVALS | | | ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | 6.THE MINIMUM FOOTING DEPTH SHALL BE | | | NO LESS THAN 12 BELOW GRADE. FBC | | | 1804.1.3 | | | | | | 7.SUBMIT TWO COPIES OF ENERGY CALCS | | | PER FBC CH.13ENERGY CALS SUBMITTED NOT | | | SIGNED BY THE OWNER/AGENT.ENERGY CALCS | | | SPEC OUT "R" 5.0 ON WALL YET PLANS ARE | | | FOR "R" 4.2. | | | | | | NEW: | | | A.SUBMIT SPECS FOR REQUIRED HOOD | | | ASSEMBLY TO GO WITH BUILT IN BBQ. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-10-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-03 |
Time |
07:38 |
Rev Time |
2.25 |
| Received By |
alange |
Date |
2005-09-30 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2005-10-03 00:00:00 | DENIED | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3.PRODUCT APPROVALS WITH QUALITY | | | ASSURANCE REQUIRED FOR THE FOLLOWING: | | | EXTERIOR DOORS, WINDOWS, ROOFING, IMPACT | | | PROTECTION, STRAPS AND TIEDOWNS AND | | | LINTELS. | | | | | | 4.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE PRODUCT APPROVALS | | | ATTACHED. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5.SUBMIT TWO ORIGONAL SIGNED AND | | | SEALED SURVEYS. FS 472.025 | | | | | | 6.THE MINIMUM FOOTING DEPTH SHALL BE | | | NO LESS THAN 12 BELOW GRADE. FBC | | | 1804.1.3 | | | | | | 7.SUBMIT TWO COPIES OF ENERGY CALCS | | | PER FBC CH.13 | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-30 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-30 |
Time |
07:12 |
Sent To |
P |
|
| Notes |
| 2005-12-30 00:00:00 | NEW SHEETS | | | REDLINED 210.63, 210.70 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-09-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-09-22 |
Time |
22:34 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2005-09-22 |
Time |
22:34 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-16 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-16 |
Time |
14:22 |
Sent To |
M |
|
| Notes |
| 2006-10-16 14:22:53 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-13 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-13 |
Time |
16:45 |
Sent To |
M |
|
| Notes |
| 2006-09-13 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2005-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-27 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-27 |
Time |
10:07 |
Sent To |
E |
|
| Notes |
| 2005-12-27 00:00:00 | TO "JLEAHY" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-12-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-12 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-12 |
Time |
11:31 |
Sent To |
Z |
|
| Notes |
| 2005-12-12 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-11-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-21 |
Time |
16:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-21 |
Time |
16:46 |
Sent To |
M |
|
| Notes |
| 2005-11-21 00:00:00 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-21 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-21 |
Time |
08:31 |
Sent To |
E |
|
| Notes |
| 2005-09-21 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-10-03 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-03 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-09-13 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2005-09-13 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2006-10-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-18 |
Time |
14:18 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-18 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2006-10-18 14:18:44 | REVISION TO MECHANICAL PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2006-09-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-09-21 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-09-21 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
F |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-15 |
Time |
09:12 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-09-15 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2006-09-15 00:00:00 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) PLEASE SUBMIT MECHANICAL PLAN WITH | | | JOB ADDRESS, A/C COMPANY INFORMATION, | | | AND EQUIPMENT LISTING ON THEM. | | | | | | 2) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . | | | | | | 3) SUBMITTED REVISION DUCT WORK IS | | | DIFFICULT TO READ. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY. PER 2004 FBC 106.1.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-01-09 |
Time |
08:47 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-01-09 |
Time |
08:46 |
Sent To |
|
|
| Notes |
| 2006-01-09 00:00:00 | ARTHITECT INFO. REMOVED FROM MECH. | | | PLANS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2006-01-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-01-03 |
Time |
08:33 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-01-03 |
Time |
08:33 |
Sent To |
B |
|
| Notes |
| 2006-01-03 00:00:00 | *** DENIED *** | | | 1) RESUBMITTED SHEET A-2 A/C PLANS NEED | | | TO BE STAMPED BY THE ARCHITECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2005-11-22 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-11-22 |
Time |
09:01 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-11-22 |
Time |
09:01 |
Sent To |
B |
|
| Notes |
| 2005-11-22 00:00:00 | *** DENIED *** | | | 1) DUCT FROM AHU TO TRIANGLE IS NOT | | | SIZED. | | | 2) LOCATION OF CONDENSER UNIT AND DRAIN | | | LINE NOT SHOWING ON MECH. PLANS. | | | 3) SALES PRODUCT BOOKLET DOES NOT | | | ADDRESS INSTALLATION DETAILS AND | | | REQUIRMENTS FOR AN APPROVED HOOD OVER | | | GRILL IN SUMMER KITCHEN. PLEASE SUPPLY A | | | DETAILED MANUFACTURE'S SPECIFICATION'S | | | AND INSTALLATION INSTRUCTIONS, OR AN | | | APPROVED HOOD OVER GRILL. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-09-29 |
Time |
10:49 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-09-29 |
Time |
10:49 |
Sent To |
B |
|
| Notes |
| 2005-09-29 00:00:00 | *** DENIED *** | | | 1) NEED DUCT SIZES, GRILL SIZES, CFM'S, | | | RETURN AIR DUCT AND SIZE, AND DUCT WITH | | | SIZE GOING BACK TO EXISTING HOUSE, | | | SHOWING ON MECHANICAL PLAN. | | | 2) OPEN GRILL IN NEW SUMMER KITCHEN | | | UNDER COVERED PATIO NEEDS AN APPROVED | | | EXHAUST HOOD. SEE 2001 FBC/M 505.3 . | | | 3) NEED NOTICE OF COMMENCEMENT. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-01-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-01-03 |
Time |
08:06 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2006-01-03 |
Time |
08:06 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-30 |
Time |
07:35 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2005-09-29 |
Time |
09:19 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-12-22 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-12-22 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-12-22 |
Time |
18:17 |
Sent To |
I |
|
| Notes |
| 2005-12-22 00:00:00 | PROVISO: THE SUMMER KITCHEN REF, MUST BE | | | AN U/C REF. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-20 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-20 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-20 |
Time |
15:06 |
Sent To |
I |
|
| Notes |
| 2005-09-20 00:00:00 | PROVISO: REF. MUST BE AN U/C REF. |
|
|