Plan Review Details - Permit 05090521
Plan Review Stops For Permit 05090521
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By alange Date 2006-01-03 Time 15:32 Rev Time 1.25
Received By alange Date 2006-01-03 Time 14:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-01 Cont ID  
Sent By alange Date 2005-12-01 Time 11:17 Rev Time 1.00
Received By alange Date 2005-12-01 Time 11:17 Sent To  
Notes
2005-12-01 00:00:00DENIED
  
 3.PRODUCT APPROVALS STILL MISSING FOR
 LINTELS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 6.THE MINIMUM FOOTING DEPTH SHALL BE
 NO LESS THAN 12 BELOW GRADE. FBC
 1804.1.3
  
 7.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CH.13ENERGY CALS SUBMITTED NOT
 SIGNED BY THE OWNER/AGENT.ENERGY CALCS
 SPEC OUT "R" 5.0 ON WALL YET PLANS ARE
 FOR "R" 4.2.
  
 NEW:
 A.SUBMIT SPECS FOR REQUIRED HOOD
 ASSEMBLY TO GO WITH BUILT IN BBQ.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 07:38 Rev Time 2.25
Received By alange Date 2005-09-30 Time 13:48 Sent To  
Notes
2005-10-03 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS WITH QUALITY
 ASSURANCE REQUIRED FOR THE FOLLOWING:
 EXTERIOR DOORS, WINDOWS, ROOFING, IMPACT
 PROTECTION, STRAPS AND TIEDOWNS AND
 LINTELS.
  
 4.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.SUBMIT TWO ORIGONAL SIGNED AND
 SEALED SURVEYS. FS 472.025
  
 6.THE MINIMUM FOOTING DEPTH SHALL BE
 NO LESS THAN 12 BELOW GRADE. FBC
 1804.1.3
  
 7.SUBMIT TWO COPIES OF ENERGY CALCS
 PER FBC CH.13
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-30 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 07:30 Rev Time 0.00
Received By dpalmer Date 2005-12-30 Time 07:12 Sent To P
Notes
2005-12-30 00:00:00NEW SHEETS
 REDLINED 210.63, 210.70

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-22 Cont ID  
Sent By jleahy Date 2005-09-22 Time 22:34 Rev Time 0.45
Received By jleahy Date 2005-09-22 Time 22:34 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 14:22 Sent To M
Notes
2006-10-16 14:22:53TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 16:45 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 16:45 Sent To M
Notes
2006-09-13 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 10:07 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 10:07 Sent To E
Notes
2005-12-27 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 11:31 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 11:31 Sent To Z
Notes
2005-12-12 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-11-21 Cont ID  
Sent By adarroug Date 2005-11-21 Time 16:46 Rev Time 0.00
Received By adarroug Date 2005-11-21 Time 16:46 Sent To M
Notes
2005-11-21 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 08:31 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 08:31 Sent To E
Notes
2005-09-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 07:45 Rev Time 0.00
Received By alange Date 2005-09-13 Time 09:37 Sent To  
Notes
2005-09-13 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-10-18 Cont ID  
Sent By tgordon Date 2006-10-18 Time 14:18 Rev Time 0.30
Received By tgordon Date 2006-10-18 Time 14:18 Sent To  
Notes
2006-10-18 14:18:44REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-09-21 Cont ID  
Sent By hmoser Date 2006-09-21 Time 15:56 Rev Time 0.00
Received By hmoser Date 2006-09-21 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-09-15 Cont ID  
Sent By tgordon Date 2006-09-15 Time 09:12 Rev Time 0.30
Received By tgordon Date 2006-09-15 Time 09:12 Sent To  
Notes
2006-09-15 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) PLEASE SUBMIT MECHANICAL PLAN WITH
 JOB ADDRESS, A/C COMPANY INFORMATION,
 AND EQUIPMENT LISTING ON THEM.
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3) SUBMITTED REVISION DUCT WORK IS
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-01-09 Cont ID  
Sent By tgordon Date 2006-01-09 Time 08:47 Rev Time 0.20
Received By tgordon Date 2006-01-09 Time 08:46 Sent To  
Notes
2006-01-09 00:00:00ARTHITECT INFO. REMOVED FROM MECH.
 PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 08:33 Rev Time 0.30
Received By tgordon Date 2006-01-03 Time 08:33 Sent To B
Notes
2006-01-03 00:00:00*** DENIED ***
 1) RESUBMITTED SHEET A-2 A/C PLANS NEED
 TO BE STAMPED BY THE ARCHITECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2005-11-22 Cont ID  
Sent By tgordon Date 2005-11-22 Time 09:01 Rev Time 0.30
Received By tgordon Date 2005-11-22 Time 09:01 Sent To B
Notes
2005-11-22 00:00:00*** DENIED ***
 1) DUCT FROM AHU TO TRIANGLE IS NOT
 SIZED.
 2) LOCATION OF CONDENSER UNIT AND DRAIN
 LINE NOT SHOWING ON MECH. PLANS.
 3) SALES PRODUCT BOOKLET DOES NOT
 ADDRESS INSTALLATION DETAILS AND
 REQUIRMENTS FOR AN APPROVED HOOD OVER
 GRILL IN SUMMER KITCHEN. PLEASE SUPPLY A
 DETAILED MANUFACTURE'S SPECIFICATION'S
 AND INSTALLATION INSTRUCTIONS, OR AN
 APPROVED HOOD OVER GRILL.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By tgordon Date 2005-09-29 Time 10:49 Rev Time 0.30
Received By tgordon Date 2005-09-29 Time 10:49 Sent To B
Notes
2005-09-29 00:00:00*** DENIED ***
 1) NEED DUCT SIZES, GRILL SIZES, CFM'S,
 RETURN AIR DUCT AND SIZE, AND DUCT WITH
 SIZE GOING BACK TO EXISTING HOUSE,
 SHOWING ON MECHANICAL PLAN.
 2) OPEN GRILL IN NEW SUMMER KITCHEN
 UNDER COVERED PATIO NEEDS AN APPROVED
 EXHAUST HOOD. SEE 2001 FBC/M 505.3 .
 3) NEED NOTICE OF COMMENCEMENT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 08:06 Rev Time 0.25
Received By jleech Date 2006-01-03 Time 08:06 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-29 Cont ID  
Sent By dpalmer Date 2005-12-30 Time 07:35 Rev Time 0.33
Received By jleech Date 2005-09-29 Time 09:19 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-12-22 Cont ID  
Sent By mmclean Date 2005-12-22 Time 18:17 Rev Time 0.00
Received By mmclean Date 2005-12-22 Time 18:17 Sent To I
Notes
2005-12-22 00:00:00PROVISO: THE SUMMER KITCHEN REF, MUST BE
 AN U/C REF.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-20 Cont ID  
Sent By mmclean Date 2005-09-20 Time 15:06 Rev Time 0.00
Received By mmclean Date 2005-09-20 Time 15:06 Sent To I
Notes
2005-09-20 00:00:00PROVISO: REF. MUST BE AN U/C REF.