Plan Review Details - Permit 05090362
Plan Review Stops For Permit 05090362
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-28 Cont ID  
Sent By shill Date 2006-03-28 Time 16:22 Rev Time 0.00
Received By shill Date 2006-03-28 Time 16:22 Sent To FIRE
Notes
2006-03-28 00:00:00REVISED S1A,S2-S6 DATED 12/22/5
 X1.1, A1.1, A5.1, A14.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-14 Cont ID  
Sent By shill Date 2006-02-14 Time 10:44 Rev Time 0.00
Received By shill Date 2006-02-14 Time 10:16 Sent To  
Notes
2006-02-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SHEET A1.1, TWO EXTERIOR DOORS WERE
 ELIMINATED BUT THE EXIT LIGHTS WERE NOT
 RELOCATED.PLEASE REVISE.
  
 2.)SHEET S1, NO CHANGES SHOWN.PLEASE
 CLOUD ALL CHANGES OR REMOVE FROM THE
 REVISION PACKAGE; ONLY SUBMIT SHEETS
 WHICH HAVE CHANGED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-11-06 Cont ID  
Sent By shill Date 2005-11-06 Time 14:06 Rev Time 1.50
Received By shill Date 2005-11-06 Time 13:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-11-09 Cont ID  
Sent By dpalmer Date 2006-11-09 Time 08:31 Rev Time 0.00
Received By dpalmer Date 2006-11-09 Time 08:31 Sent To PC
Notes
2006-11-09 08:32:02***UNSAT *****
  
  
  
 1) NOTE: PLEASE SEE THAT THE ELECTRICAL SHEETS WERE OK
 AND EVEN STAMPED, HOWEVER THESE HAVE NOW SINCE BEEN
 VOIDED AS THE NUMERICAL IDENTIFICATION USED IS THE SAME
 AS SHEETS ALREADY ON FILE FOR COMPLETELY DIFFERENT
 SCOPE OF WORK.
 PLEASE RE-NUMBER SHEETS WITH NEW METHOD SO THAT NO
 SHEETS REPEAT ALREADY ISSED SHEETS CONTAINING THE SAME
 NUMBER.
 ******PLEASE BE SURE TO SUBMIT ALL OF THE OLD/VOIDED
 SHEETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 ** PLEASE KNOW THE ADDTIONALS FEES MUST BE PAID BEFORE
 PLANS CAN BE RESUBMITTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-10-16 Cont ID  
Sent By dpalmer Date 2006-10-16 Time 18:11 Rev Time 0.00
Received By dpalmer Date 2006-10-16 Time 18:11 Sent To  
Notes
2006-10-16 18:13:42VALUE INCREASED, CONTRACTOR WILL PAY ADDITIONAL FEE
 WHEN PICKING UP PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 17:12 Sent To  
Notes
2006-10-01 00:00:00**** TEMPORARY "F" STATUS ******
  
 1) NOTE: NOTE IS NOT FOR ELECTRICAL
 ENGINEER .
  
 PLEASE KNOW, DUE TO THE INCREASED VALUE
 AND SCOPE OF WORK UNDER THE EXSITING
 PERMIT, THE APPLIED VALUE SHALL BE
 INCREASED TO REFLECT ALL LABOUR AND
 MATERIALS WHETHER OR NOT NAY EQUIPMENT
 ETC IS OWNER SUPPLIED. PLANS ARE TO BE
 RETAINED AND ELECTRICLA PLANS ARE NOT
 SIGNED.
  
 PLEASE SEE FBC 106.3.5, (2001) 108.3
 (2004) SECTIONS OF TEH ADMIN CODE.
  
 THIS WILL BE CHANGED ONCE VALUE FOR ALL
 WORK BEING PERFORMED AT JOBSITE HAS BEEN
 ADJUSTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECRTCIAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-04 Cont ID  
Sent By dpalmer Date 2006-01-04 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2005-12-31 Time 19:03 Sent To  
Notes
2006-01-09 00:00:00REDLINED FEEDERS ON SCHEDULE #6.
  
 ATS SWITCH TO BE VERIFIED IF INDEED TO
 BE 4POLE WITH MANUFACTURE.
  
  
 ENGINEER TO REVISE PLANS BEFORE ROUGH.
2005-12-31 00:00:00REMOVED FROM INCOMING,
 IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-09 Cont ID  
Sent By dpalmer Date 2005-10-09 Time 17:20 Rev Time 3.00
Received By dpalmer Date 2005-10-09 Time 14:23 Sent To  
Notes
2005-10-09 00:00:00IN ELEC FOR REVIEW.
 ****** UNSAT ******
  
 1)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW GENERATORS,
 FIRE PUMP CONTROLLER, NEW ATS
 SWITCHE(S), GEN SYSTEM CONTROL MODULE
 (PARALLEL OPERATION MODULE).
 PLEASE KNOW, CODE COMPLIANCE FOR SOME
 ITEMS CAN NOT VERIFIED AT THIS TIME.
 PLEASE SEE OTHER COMMENTS.
  
 2)NOTE: PLEASE SEE CODE REFERENCES ALL
 NEED TO BE UPDATED.
 NFPA-70, 2002 WHICH WAS ADOPTED ON JULY
 1ST, 2003.
 NFPA-101 2003, NFPA-20 2003, ETC.
 PLEASE SEE THAT ALL NFPA'S AS LISTED ON
 X-1 COVER SHEET SHOULD BE UPDATED TO THE
 LATEST ADOPTED CODES.
 DATE OF 3/2/04 ABOVE LISTING IS NOT
 ACCURATE TO UPDATE AS SOME OF THESE
 CHANGED BEFORE THIS DATE AND SOME HAVE
 CHANGED SINCE.
  
 3)NOTE: PLEASE SEE NOTE #8 ON E-1
 MENTIONS A "TEMPORARY ELECTRICAL
 SERVICE" FOR ANY DOWN TIMES, THIS IS
 FINE HOWEVER, NO ELECTRICAL PLANS WERE
 SUBMITTED FOR THIS?
 PLEASE KNOW, IT MAY BE EASIER TO PERMIT
 THIS TEMP SERVICE UNDER A SEPARATE
 PERMIT?
  
 4)NOTE: PLEASE PLACE ALL ROOM AND AREA
 DESIGNATIONS ON NEW BASEMENT LEVEL
 PLANS.
  
 5)NOTE: PLEASE SEE EGRESS DOORS AND
 REQUIREMENTS FROM MAIN ELECTRICAL
 ROOM/EMERGENCY ELECTRICAL ROOM.
 PLEASE SEE 110.26, FOR DOOR SWING, PANIC
 HARDWARE ETC REQUIRED. PLEASE SEE THERE
 MAY BE A CONFLICT WITH DOOR SWING FROM
 BOILER ROOM?
  
 6)NOTE: PLEASE SEE SECTION/DETAIL 2 ON
 E-5, WHICH APPEARS TO SHOW SOME SORT OF
 ?? DIRECTLY IN FRONT OF DOORS FOR EM
 SWGR RM.??
 110.26
  
 7)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 PERTAINING TO "FIRE WATCH" AS LISTED IN
 NOTE ON E-6, WHICH MENTIONS FIRE WATCH
 ETC.
 PLEASE SEE FIRE REVIEW COMMENTS AS ALL
 APPROVALS FOR SUCH MUST BE BY THE FIRE
 MARSHALS OFFICE AND AHJ.
 PLEASE KNOW, THE AGENCY TO PERFORM SUCH
 A WATCHMUST FIRST BE APPROVED BY ABOVE
 MENTIONED AND MUST SUBMIT ALL
 INFORMATION WHICH WILL BE REQUIRED AND
 SET-FORTH BY THE FIRE MARSHALS OFFICE.
  
 8)NOTE: PLEASE PROVIDE BATTERY BACK UP
 FIXTURES IN MAIN ELECTRICAL ROOM,
 GENERATOR ROOM, FIRE PUMP ROOM, CHILLER
 ROOM FOR EGRESS TO AND FROM ALL
 ELECTRICAL EQUIPMENT WHICH MAY NEED TO
 BE TURNED OFF ETC.
 LS 101,7.8,7.9, 700.16,
  
 9)NOTE: PLEASE SEE THAT GEN ANNUNCIATOR
 PANEL/STATUS CONTROL PANEL SHALL BE
 LOCATED AT CENTRAL STATION CONTROL
 RM/AREA.
 110, 5.6.5, 101,11.8.5 ETC.
  
 10)NOTE: PLEASE PROVIDE NOTE FOR 517.17C
 FOR TESTING GFP.
  
 11)NOTE: PLEASE SEE GSB1 AND GSB2, WHICH
 INDICATES 1800A MCB'S?. PLEASE VERIFY
 THIS AS 1800 IS NOT A RECOGNIZED SIZE OF
 OCP AS SET FORTH UNDER 240.6.
  
 12)NOTE: PLEASE PROVIDE LOAD FORGSB?
 LOADS FOR OTHER MAINS ETC SHOWN, HOWEVER
 THIS COULD NOT BE LOCATED.
 215.5,220
  
 13)NOTE: PLEASE CLARIFY OF ANY MEANS OF
 OCP IS LOCATED AT GENERATOS.
 215.5 SEE PREVIOUS NOTE WHICH REQUESTED
 MORE INFORMATION FOR GEN SYSTEM MODULE
 AND PARALLEL OPERATION.
  
 14)NOTE: PLEASE KNOW, THE
 OCP/DISCONNECTING MEANS FOR FIRE PUMP
 LOCATED IN GSB, WILL BE REQUIRED TO BE
 LOCATED OUT OF THIS EQUIPMENT. THIS OCP
 AND DISCONNECTING MEANS SHALL BE LOCATED
 AHEAD OF GSB. PLEASE SEE NFPA -20
 9.3.2.2.3.2.695.4B2
 SECTIONS OF 695 AND CHAPTER 9, (9.6)
 DOES NOT SPECIFY THE DISCONNECTING MEANS
 LOCATION. THE ONLY STATEMENT AS
 MENTIONED IN NFPA-20 9.6.1.2 IS"A TAP
 AHEAD OF THE ON-SITE GENERATOR
 DISCONNECTING MEANS SHALL NOT BE
 REQUIRED".
 IT IS THE INTERPETATIONTHAT CONNECTION
 AS SHOWN MAY VERY WELL PROMOTE AN
 INADVERANT DISCONNECT OF FIRE PUMP.
  
 15)NOTE: PLEASE KNOW, AS CONVERSED WITH
 ELECTRICAL ENGINEER AND ELECTRICAL
 CONTRACTOR AND AS DETERMINED UNDER
 NFPA-20,9.1.3,9.3.1 NFPA-70 695.4, 695.6
 THE ROUTING OF THE SERVICE ENTRANCE
 CONDUCTORS AND FEEDERS SOURCES SHALL BE
 PROTECTED BY BEING CONSIDERED "OUTSIDE"
 THE BLDG. THE FIRE RATING ALONE FOR
 PROTECTION OF CONDUCTORS IS ONLY ONE
 CONSIDERATION WHICH IS GIVEN BY ABOVE
 MENTIONED 9.3.1.
 PLEASE PROVIDE A LAYOUT FOR NEW PROPOSED
 ROUTING AND DETAIL PROTECTION.
 IT IS KNOWN TO THIS OFFICE AND FIRE
 MARSHALS OFFICE; ANEW FEED FROM FPL IS
 BEING CONSIDERED WHICH IS PROPOSED TO
 EXSITING FIRE PUMP ROOM.
 THIS SEEMS TO BE SAFEST AND MOST COST
 EFFECTIVE OPTION TO MEET CODE AND LIFE
 SAFETY OF NEW INSTALLATION. THISIS
 REQUIRED AND ACCEPTABLE DUE TO THE SCOPE
 OF WORK AND PERMITTED UNDER NFPA-20 AND
 NFPA-70.IN FACT THIS IS THE
 RECOMMENDED INSTALLATION.
  
 16)NOTE: PLEASE SHOW/DETAIL ON HOW NEW
 SERVICE ENTRANCE CONDUCTORS FOR SERVICE
 ARE BEING ROUTED.
 EXISTING CONDITIONS SHOW MAINS/EMERGENCY
 AND
 NORMAL LOCATED IN BASEMENT AND NEW
 INSTALLATION IS BEING SHOWN ON THE FLOOR
 ABOVE (GROUND FLR), YET IT IS UNCLEAR
 HOW THE CONDUCTORS ARE GOING TO ENTER
 NEW EQUIPMENT.
 PLEASE SEE 240.6, 230.70 ETC FOR
 CONDUCTORS TO BE CONSIDERED OUTSIDE THE
 BUILDING.
  
 17)NOTE: PLEASE BE SURE NEW FIRE PUMP
 CONTROLLER CONTAINS THE MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE OF THE
 NEW FPC, THIS DISCONNECTING MEANS SHALL
 BE RATED FOR THE FULL LOAD TO BE SERVED.
 230.76,230.79, NFPA-20 10.4.2
  
 ***************************************
 PLEASE KNOW, I AM RECOMMENDING AN
 "ON-SITE" MEETING BE HELD TO GO OVER
 PROPOSED WORK. THIS MEETING SHOULD BE
 ATTENDED BY THEELECTRICAL ENGINEER OF
 RECORD, ELECTRICAL CONTRACTOR, CHIEF
 FIRE MARSHAL, CHIEF ELECTRICAL INSPECTOR
 AND MYSELF.
 THIS WILL HELP IN THE PROCESS FOR THE
 SCOPE OF WORK PROPOSED.
 PLEASE CONTACT FOR TIME.
  
 ** PLEASE SEE POSSIBLE REVIEW NOTES FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SUBMIT "ONE" SET OF THE
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-04-06 Cont ID  
Sent By mwennerg Date 2006-04-06 Time 09:31 Rev Time 0.00
Received By mwennerg Date 2006-04-06 Time 09:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-02-17 Cont ID  
Sent By mwennerg Date 2006-02-17 Time 10:36 Rev Time 0.00
Received By mwennerg Date 2006-02-17 Time 10:36 Sent To  
Notes
2006-02-17 00:00:00******DENIED******
  
 1) STAIR #2 EXITS PERSONS INTO
 STAIRWELL, HOWEVER ONCE IN THE
 STAIRWELL, WHERE DO THEY THEN EXIT?
  
  
 MIKE WENNERGREN, CAPTAI/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-12 Cont ID  
Sent By mwennerg Date 2006-01-12 Time 12:55 Rev Time 0.00
Received By mwennerg Date 2006-01-12 Time 12:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By mwennerg Date 2005-10-11 Time 11:01 Rev Time 0.00
Received By mwennerg Date 2005-10-11 Time 11:01 Sent To  
Notes
2005-10-11 00:00:00******DENIED******
  
 1) PLEASE SEE OTHER NOTE REGARDING MORE
 CURRENT EDITIONS WHEN REFERENCING
 SPECIFIC CODES.
  
 2) PLEASE NOTE THAT AN APPROVED FIRE
 WATCH MAY BE GRANTED BY THE FIRE
 MARSHAL ONLY WHEN ALL REQUIREMENTS ARE
 MET. IF APPROVED, THE BUREAU OF FIRE
 PREVENTION WILL ASSIST YOU THROUGH THIS
 PROCESS WITH THE ESTABLISHED POLICY.
  
 3) PLEASE PROVIDE FURTHER INFORMATION
 REGARDING TYPES OF PROPOSED BOILERS.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 5) PROVIDE DETAILS AND MANUFACTURER SPEC
 SHEETS FOR FUEL OIL STORAGE TANK.
  
 6) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 7) EMERGENCY LIGHTING FACILITIES ARE
 REQUIRED IN AREAS WHERE NATURAL LIGHTING
 IS NOT ADEQUATE.
  
  
 MIKE WENNERGREN, CAPTAIN
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-03-07 Cont ID  
Sent By pschmitz Date 2006-03-07 Time 08:53 Rev Time 0.00
Received By pschmitz Date 2006-03-07 Time 08:53 Sent To PC
Notes
2006-03-07 00:00:00REVISION WITH SIZING CALCULATIONS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By pschmitz Date 2006-01-13 Time 11:00 Rev Time 0.00
Received By pschmitz Date 2006-01-13 Time 11:00 Sent To  
Notes
2006-01-13 00:00:00SEE ATTACHED APPROVALS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By pschmitz Date 2006-01-11 Time 11:40 Rev Time 0.00
Received By pschmitz Date 2006-01-11 Time 11:20 Sent To  
Notes
2006-01-11 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1) SUBMITAL FOR BOILER DID NOT INCLUDE
 MANFACTURE LISTING (PRODUCT APPROVAL).
 2)NOT ABLE TO DO GAS PIPING PLAN REVIEW
 WITH OUT MANMFACTURE BOILER LISTING.
 3( SEPERATE PERMIT REQUIRED FOR GAS
 PIPING.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 13:31 Sent To  
Notes
2006-10-01 00:00:00TO COMM BOARD #53
2006-09-18 00:00:00WAITING FOR "COMM" BD-REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-22 Cont ID  
Sent By dpalmer Date 2006-03-22 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2006-03-22 Time 14:48 Sent To B
Notes
2006-03-22 00:00:00TO SH'S DSK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-03 Cont ID  
Sent By adarroug Date 2006-03-03 Time 12:17 Rev Time 0.00
Received By adarroug Date 2006-03-03 Time 12:17 Sent To P
Notes
2006-03-03 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 13:57 Sent To  
Notes
2006-02-09 00:00:00TO "COMM" BD#22
2006-01-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 15:49 Sent To  
Notes
2006-01-09 00:00:00TO "COMM" BD#53
2005-12-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-07 Cont ID  
Sent By shill Date 2005-11-07 Time 12:26 Rev Time 0.00
Received By shill Date 2005-09-12 Time 16:43 Sent To  
Notes
2005-09-12 00:00:00TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-11-08 Cont ID  
Sent By tgordon Date 2006-11-08 Time 14:37 Rev Time 1.30
Received By tgordon Date 2006-11-08 Time 14:37 Sent To  
Notes
2006-11-08 14:42:01*** DENIED ***
 1) SHEET IDENTIFICATION NUMBERS T-1, M-1.1, M-1.2,
 M-1.3, E-1, E-2, E-4, E-5, AND E-6 HAVE BEEN USED IN
 THE FIRST APPROVED SET OF PLANS FOR THIS JOB, IF YOU DO
 NOT WANT TO VOID THE FIRST SET OF APPROVED PLANS THEN
 THE REVISED SET NEEDS TO BE ASSIGNED NEW SHEET I.D.
 NUMBERS THAT HAVE NOT BEEN USED IN THE FIRST SET.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-13 Cont ID  
Sent By hmoser Date 2006-02-13 Time 13:26 Rev Time 0.00
Received By hmoser Date 2006-02-13 Time 13:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-15 Cont ID  
Sent By hmoser Date 2005-10-15 Time 09:00 Rev Time 0.00
Received By hmoser Date 2005-10-15 Time 08:43 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2006-11-02 Cont ID  
Sent By kstevens Date 2006-11-02 Time 15:45 Rev Time 0.00
Received By kstevens Date 2006-10-26 Time 17:18 Sent To  
Notes
2006-11-02 17:55:22DENIED
 REFERENCE: NFPA 99C
 FBC-2004 CHAPTER 1
  
 1. THE FOLLOWING SHEETS WERE SUBMITTED WITH NEW
 INFORMATION AND NEW SCOPE OF WORK. THE ORIGINAL SHEETS
 SCOPE OF WORK HAS NOT BEEN DELETED. THESE SHEETS SHALL
 EITHER BE RESUBMITTED WITH NEW NUMBERS AS A REVISION,
 OR BE SUBMITTED UNDER A NEW PERMIT NUMBER. SHEETS T-2,
 M-1.1, M-1.2, AND M-1.3.
  
 2. SUBMIT ALL INFORMATION FOR THE MED-GAS WITH THE
 REQUIRED MED-GAS PERMIT. THE CONTRACTOR SHALL SUBMIT
 ALL CERTIFICATION FOR THE CERTIFIED OR REGISTERED
 PLUMBING CONTRACTOR, THE ACTUAL INSTALLER(S), AND THOSE
 PERSONS WHO ONLY BRAZE, (IF APPLICABLE), WITH THE
 APPLICATION AND PLANS FOR THE MED-GAS.
  
 3. SHEETS M-8.1 THRU M-8.5 WILL BE RETURNED WITH THE
 REVISION SUBMITTAL FORM. ALL OTHER SHEETS THAT
 REFERENCE MED-GAS SHALL BE RESUBMITTED WITH THE MED-GAS
 APPLICATION AS WELL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-12-13 Cont ID  
Sent By kstevens Date 2006-12-13 Time 17:05 Rev Time 0.00
Received By kstevens Date 2006-12-13 Time 17:05 Sent To  
Notes
2006-12-13 17:25:29NEW PLUMBING WORK SUBMITTED AS A REVISION. SHTS M-8.6 &
 M-9.8 APPROVED. M-8.6 NEW DOMESTIC WATER BOOSTER PUMP
 HOUSE PUMPS. - M-9.8 NEW WATER HEATER & WATER PIPING. -
 ORIGINALLY SUBMITTED 9-15-06

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-11-02 Cont ID  
Sent By kstevens Date 2006-11-02 Time 17:55 Rev Time 0.00
Received By kstevens Date 2006-10-26 Time 17:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-13 Cont ID  
Sent By pschmitz Date 2006-01-13 Time 11:02 Rev Time 0.00
Received By pschmitz Date 2006-01-13 Time 11:02 Sent To  
Notes
2006-01-13 00:00:00SEE GAS NOTES

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-11 Cont ID  
Sent By pschmitz Date 2006-01-11 Time 11:08 Rev Time 0.00
Received By pschmitz Date 2006-01-09 Time 15:29 Sent To  
Notes
2006-01-11 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 1) SUBMITAL FOR BOILER DID NOT INCLUDE
 MANFACTURE LISTING (PRODUCT APPROVAL).
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-07 Cont ID  
Sent By pschmitz Date 2005-11-07 Time 09:54 Rev Time 0.00
Received By pschmitz Date 2005-11-07 Time 09:54 Sent To  
Notes
2005-11-07 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW.
 DENIED
 1)PRE CONSTRUCTION MEETING IS RECOMENDED
 PRIOR TO RE SUB OF PLANS.
 2) PROVIDE MANFACTURES EQUIPMENT
 SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS.
 3) SHT P-4.1 SHOW GAS PSI, IN LBS OF PSI
 OR INCHES OF WATER COLUMN.
 END OF COMMENTS QUESTIONS 561-808-6692