Plan Review Details - Permit 05090351
Plan Review Stops For Permit 05090351
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 12:38 Rev Time 0.00
Received By shill Date 2006-08-05 Time 12:38 Sent To FIRE
Notes
2006-08-05 00:00:00PROVISO - REVISE A1 TO SHOW BREAK ROOM
 SINK AND CABINET DETAIL BEFORE FRAMING
 INSPECTION

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 12:35 Rev Time 0.00
Received By shill Date 2006-08-05 Time 12:35 Sent To  
Notes
2006-08-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF COMMENTS
 ARE NOT ADDRESSED A THIRD TIME.
  
 ARCHITECT'S RESPONSE LETTER - "I'M
 OFFENDED BY THIS COMMENT.WITH EVERY
 PROJECT I COOPERATE IN GOOD FAITH.ALL
 PREVIOUS COMMENTS WERE ADDRESSED."
 PLEASE NOTE THAT NO OFFENSE WAS
 INTENDED; THIS IS A STATUTORY
 REQUIREMENT AND IS NOT SUBJECT TO MY
 DISCRETION.I HAVE BEEN INSTRUCTED TO
 INCLUDE THIS COMMENT IN MY COMMENT LIST
 AFTER THE SECOND PLAN REVIEW.THE FEE
 IS A MANDATORY FEE TO BE IMPOSED IF THE
 SAME COMMENT IS MADE THREE
 TIMES,REGARDLESS OF INTENTION AND GOOD
 FAITH. THIS FEE IS TO BE CHARGED
 REGARDLESS OF WHETHER OR NOT THE
 DESIGNER IS ADVISED OF THE FLORIDA
 STATUTE.THIS COMMENT IS MADE AS A
 COURTESY (ADVISORY), AND IS NOT INTENDED
 TO BE OFFENSIVE.MY APOLOGIES IF YOU
 HAVE MISUNDERSTOOD MY INTENT.
  
 ALTHOUGH COMMENT #17 HAS BEEN MADE THREE
 TIMES, THE 4X FEE IS NOT CHARGED ON THIS
 REVIEW (MISSED DETAIL) BUT WILL BE
 CHARGED ON THE NEXT SUBMITTAL IF THE
 DETAIL IS NOT PROVIDED AS REQUESTED.
  
 17.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BREAKROOM SINK, FBC11-4.24.
 THE DOR IS TO PROVIDE DESIGN CRITERIA;
 SHOPS CAN BE PROVIDED DURING THE JOB BUT
 PLANS ARE TO SHOW CODE COMPLIANCE.
  
 AS REQUESTED, PROVIDE A DETAIL.THE
 WRITTEN SPECIFICATION IS NOTED BUT DOES
 NOT CLEARLY SHOW CODE COMPLIANCE AS
 THERE HAVE BEEN PROBLEMS IN THE FIELD ON
 THE PAST REGARDING DOORS (NOT PERMITTED)
 COVERING THE ACCESSIBLE SINKS.THE
 DETAIL HAS BEEN REQUESTED BY BOTH THE
 PLUMBING REVIEWER AND MYSELF TO AVOID
 PROBLEMS WHILE THE JOB IS IN PROGRESS.
  
 4TH REVIEW -
  
 DETAIL NOT PROVIDED.THE DETAIL SHOWN
 IS FOR A LAVATORY, THIS IS A BREAK ROOM
 SINK.THE NOTE THAT THERE ARE NO DOORS
 UNDER THE ACCESSIBLE IS NOTED, BUT NO
 DETAIL WAS PROVIDED AS PREVIOUSLY
 REQUESTED.PUT A DETAIL, NOT A WRITTEN
 SPECIFICATION, ON THE PLAN, FRONT
 ELEVATION, SHOWING BREAK ROOM SINK AND
 CABINET, WITH ALL PERTINENT DIMENSIONS
 FBC11-4.24.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-07-19 Cont ID  
Sent By shill Date 2006-07-19 Time 11:35 Rev Time 0.00
Received By shill Date 2006-07-19 Time 09:23 Sent To P
Notes
2006-07-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED. (MUST BE FILED
 PRIOR TO PERMIT PICKUP; THIS COMMENT
 DOES NOT PREVENT THE PERMIT FROM BEING
 ISSUED.)
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)ADDITIONAL FEES WILL BE DUE
 (RADON). SEE FS553.721, REQUIRED ON
 ALTERATIONS.ARCHITECT'S OBJECTION IS
 NOTED; HAS HE READ THE FLORIDA STATUTE?
 ALSO NOTE THAT THE CONTRACTOR DID NOT
 PAY THE RESUB FEE.RESUB FEES ARE DUE
 AT THE TIME OF SUBMITTAL; FAILURE TO PAY
 THIS FEE COULD RESULT IN DEALYS IN PLAN
 REVIEW.
  
 4-6.)ADDRESSED.
  
 7.)PROVIDE A FIRE SPRINKLER PLAN,
 FBC104.3.1.1. (FIRST REVIEW)
  
 THIS WAS ADDRESSED WITH AN 8 1/2 X 11
 SHEETS WITH THE RESPONSE LETTER.EITHER
 INCORPORATE INTO THE PLAN OR REMOVE FROM
 THE RESPONSE LETTER AND ATTACH TO THE
 PLAN.
  
 THESE SHEETS ARE ALSO LACKING THE
 INFORMATION REQUIRED BY FAC61G1-16.003,
 004. (2ND REVIEW)
  
 3RD REVIEW - THIS ITEM HAS BEEN
 ADDRESSED.HOWEVER, ARCHITECT HAS ASKED
 FOR CLARIFICATION, STATES IN HIS
 RESPONSE LETTER "PLEASE CLARIFY
 FAC16G1-16.003 AS IT ADDRESSES TAXES."
 NOTE THAT THE ARCHITECT IS REFERRING TO
 SECTION FAC16G1, BUT MY COMMENT REFERS
 TO 61G1.I HOPE THAT THIS ADDRESSES ANY
 CONFUSION.
  
 8-15.)ADDRESSED.
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF COMMENTS
 ARE NOT ADDRESSED A THIRD TIME.
  
 ARCHITECT'S RESPONSE LETTER - "I'M
 OFFENDED BY THIS COMMENT.WITH EVERY
 PROJECT I COOPERATE IN GOOD FAITH.ALL
 PREVIOUS COMMENTS WERE ADDRESSED."
 PLEASE NOTE THAT NO OFFENSE WAS
 INTENDED; THIS IS A STATUTORY
 REQUIREMENT AND IS NOT SUBJECT TO MY
 DISCRETION.I HAVE BEEN INSTRUCTED TO
 INCLUDE THIS COMMENT IN MY COMMENT LIST
 AFTER THE SECOND PLAN REVIEW.THE FEE
 IS A MANDATORY FEE TO BE IMPOSED IF THE
 SAME COMMENT IS MADE THREE
 TIMES,REGARDLESS OF INTENTION AND GOOD
 FAITH. THIS FEE IS TO BE CHARGED
 REGARDLESS OF WHETHER OR NOT THE
 DESIGNER IS ADVISED OF THE FLORIDA
 STATUTE.THIS COMMENT IS MADE AS A
 COURTESY (ADVISORY), AND IS NOT INTENDED
 TO BE OFFENSIVE.MY APOLOGIES IF YOU
 HAVE MISUNDERSTOOD MY INTENT.
  
 ALTHOUGH COMMENT #17 HAS BEEN MADE THREE
 TIMES, THE 4X FEE IS NOT CHARGED ON THIS
 REVIEW (MISSED DETAIL) BUT WILL BE
 CHARGED ON THE NEXT SUBMITTAL IF THE
 DETAIL IS NOT PROVIDED AS REQUESTED.
  
 17.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BREAKROOM SINK, FBC11-4.24.
 THE DOR IS TO PROVIDE DESIGN CRITERIA;
 SHOPS CAN BE PROVIDED DURING THE JOB BUT
 PLANS ARE TO SHOW CODE COMPLIANCE.
  
 AS REQUESTED, PROVIDE A DETAIL.THE
 WRITTEN SPECIFICATION IS NOTED BUT DOES
 NOT CLEARLY SHOW CODE COMPLIANCE AS
 THERE HAVE BEEN PROBLEMS IN THE FIELD ON
 THE PAST REGARDING DOORS (NOT PERMITTED)
 COVERING THE ACCESSIBLE SINKS.THE
 DETAIL HAS BEEN REQUESTED BY BOTH THE
 PLUMBING REVIEWER AND MYSELF TO AVOID
 PROBLEMS WHILE THE JOB IS IN PROGRESS.
  
 NEW COMMENT:
  
 18.)WHEN RESUBMITTING, REMOVE OLD
 SHEETS FROM THE PLAN.OLD SHEETS SHOULD
 BE SUBMITTED SEPARATELY AND MARKED
 "VOID".THIS IS TO PREVENT OLD SHEETS
 FROM BEING REVIEWED AND STAMPED IN
 ERROR.FOR INSTANCE, A-1 IS INCLUDED IN
 THE PACKAGE WITH BOTH REVISIONS 1 AND 2.
 WHEN RESUBMITTING, IT WILL BE ROUTED TO
 FIRE FOR FIRE PLAN REVIEW STAMP TO BE
 PLACED ON THE NEW SHEET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-07 Cont ID  
Sent By shill Date 2006-03-07 Time 07:05 Rev Time 2.00
Received By shill Date 2006-03-06 Time 14:52 Sent To  
Notes
2006-03-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 MUST BE FILED PRIOR TO PERMIT PICKUP.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 THE PLANS DID NOT INDICATE ADDITIONAL
 SQUARE FOOT AREA, STAMP STATES INTERIOR.
 AS PER WILLIE SWOPE, IMPACT FEES
 REQUIRED FOR ADDITIONAL FLOOR SPACE.
 233-5025
  
 3.)ADDITIONAL FEES WILL BE DUE
 (RADON).
  
 SEE FS553.721, REQUIRED ON ALTERATIONS.
 BILL ATTACHED.
  
 4.)PROVIDE AREA CALCULATIONS FOR THE
 PROPOSED MEZZANINE.
  
 ADD THIS NUMBER TO THE FIRST SHEET,
 BUILDING INFORMATION.IT WAS PLACED ON
 THE FLOOR PLAN FOR THE MEZZANINE ONLY,
 WHICH IS WHY THERE WAS CONFUSION IN
 REGARDS TO THE IMPACT FEES DUE.
  
 5.)ADDRESSED.
  
 6.)SHOW TRAVEL DISTANCE TO THE EXIT
 FROM THE MEZZANINE.NO DIMENSIONS SHOWN
 ON THE PLAN.FBC1005.7, 1004.1.5.
  
 THE TRAVEL DISTANCE IS TO BE LESS THAN
 75FT AT THE POINT WHERE THERE IS A
 CHOICE OF MORE THAN ONE MEANS OF EGRESS
 IF YOU ARE TO HAVE ONLY ONE MEANS OF
 EGRESS FROM THE MEZZANINE, FBC1005.7.1.
 AMEND PLANS TO SHOW COMPLIANCE.
  
 7.)PROVIDE A FIRE SPRINKLER PLAN,
 FBC104.3.1.1.
  
 THIS WAS ADDRESSED WITH AN 8 1/2 X 11
 SHEETS WITH THE RESPONSE LETTER.EITHER
 INCORPORATE INTO THE PLAN OR REMOVE FROM
 THE RESPONSE LETTER AND ATTACH TO THE
 PLAN.
  
 THESE SHEETS ARE ALSO LACKING THE
 INFORMATION REQUIRED BY FAC61G1-16.003,
 004.
  
 8.)ADDRESSED.
  
 9.)ADDRESSED.
  
 10.) ADDRESSED.
  
 11.)ADDRESSED.
  
 12.)ADDRESSED
  
 13.)THE STAIR HANDRAIL IS TO COMPLY
 WITH FBC11-4.9.4.SEE ALSO FIGURE 19.
  
 EXTENSIONS REQUIRED AT THE TOP,
 FBC11-4.9.4(2).
  
 14.)ADDRESSED.
  
 NEW COMMENTS:
  
 15.)DOOR 1 IS TO COMPLY WITH
 FBC11-4.13.4, FBC11-4.13.5.SHOW
 COMPLIANCE ON THE PLAN.
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF COMMENTS
 ARE NOT ADDRESSED A THIRD TIME.
  
 17.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BREAKROOM SINK, FBC11-4.24.
 THE DOR IS TO PROVIDE DESIGN CRITERIA;
 SHOPS CAN BE PROVIDED DURING THE JOB BUT
 PLANS ARE TO SHOW CODE COMPLIANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-05 Cont ID  
Sent By shill Date 2005-11-05 Time 19:46 Rev Time 2.00
Received By shill Date 2005-11-05 Time 19:46 Sent To  
Notes
2005-11-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.561-233-5025
  
 3.)ADDITIONAL FEES WILL BE DUE
 (RADON).
  
 4.)PROVIDE AREA CALCULATIONS FOR THE
 PROPOSED MEZZANINE.
  
 5.)DECLARE AN OCCUPANT LOAD FOR THE
 MEZZANINE.
  
 6.)SHOW TRAVEL DISTANCE TO THE EXIT
 FROM THE MEZZANINE.NO DIMENSIONS SHOWN
 ON THE PLAN.FBC1005.7, 1004.1.5.
  
 7.)PROVIDE FIRE SPRINKLER PLAN,
 FBC104.3.1.1.
  
 8.)SEE FBC1005.7.3.THERE IS ENCLOSED
 SPACE UNDER THE MEZZANINE.PLEASE
 ADDRESS.
  
 9.)THE STAIRS ARE TO COMPLY WITH
 FBC1007.1.4.
  
 10.) STAIR TREADS TO COMPLY WITH
 FBC1007.3, MINIMUM OF 11 INCHES.
  
 11.)PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS, INCLUDING FIREBLOCKING.
  
 12.)SHOW THE DISTANCE BETWEEN THE TWO
 DOORS, FROM THE FRONT ENTRY TO DOOR 2.
 SEE FBC 11 FIGURE 25.
  
 13.)THE STAIR HANDRAIL IS TO COMPLY
 WITH FBC11-4.9.4.SEE ALSO FIGURE 19.
  
 14.)FIREBLOCKING REQUIRED, 8-A2,
 FBC705.3.1.1.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-24 Cont ID  
Sent By dpalmer Date 2006-06-24 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2006-06-24 Time 11:53 Sent To  
Notes
2006-06-24 00:00:00PASSED OON PREVIOUS REVIEW AND SAME
 STAMPED SHEETS ARE IN SETS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-07 Cont ID  
Sent By dpalmer Date 2006-02-07 Time 16:36 Rev Time 0.00
Received By dpalmer Date 2006-02-07 Time 15:28 Sent To  
Notes
2006-02-07 00:00:00REDLINED
 210.8B3
2006-02-06 00:00:00IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-09-24 Cont ID  
Sent By jleahy Date 2005-09-24 Time 22:42 Rev Time 1.00
Received By jleahy Date 2005-09-24 Time 22:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-28 Cont ID  
Sent By mwennerg Date 2006-06-28 Time 13:37 Rev Time 0.00
Received By mwennerg Date 2006-06-28 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-02-09 Cont ID  
Sent By mwennerg Date 2006-02-09 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2006-02-09 Time 15:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By mwennerg Date 2005-09-29 Time 11:24 Rev Time 0.00
Received By mwennerg Date 2005-09-29 Time 11:24 Sent To  
Notes
2005-09-29 00:00:00******DENIED******
  
 1) PLEASE SEE STAIR DETAIL ON SHT S-2.
 IS TREAD DEPTH IN COMPLIANCE WITH NFPA
 101, SECTION 7.2.2.2.1 (A)?
  
 2) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS WHERE
 PROVIDED SHALL BE WIRED TO THE FIRE
 ALARM PANEL TO CAUSE A GENERAL FIRE
 ALARM CONDITION WHEN ACTIVATED.
  
 3) PLEASE SHOW LOCATIONS OF NEW OR
 EXISTING 2A-10B,C RATED FIRE
 EXTINGUISHERS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 12:53 Rev Time 0.00
Received By shill Date 2006-08-05 Time 12:53 Sent To  
Notes
2006-08-05 00:00:00TO SMH DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 10:47 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 10:47 Sent To  
Notes
2006-06-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-17 Cont ID  
Sent By adarroug Date 2006-01-17 Time 14:15 Rev Time 0.00
Received By adarroug Date 2006-01-17 Time 14:15 Sent To  
Notes
2006-02-01 00:00:00TO "COMM" BD#26
2006-01-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-05 Cont ID  
Sent By shill Date 2005-11-05 Time 19:47 Rev Time 0.00
Received By shill Date 2005-09-12 Time 13:52 Sent To  
Notes
2005-09-12 00:00:00TO "COMM" BD#26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-23 Cont ID  
Sent By hmoser Date 2006-02-23 Time 18:52 Rev Time 0.00
Received By hmoser Date 2006-02-23 Time 18:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By pkrauss Date 2005-10-18 Time 08:41 Rev Time 0.55
Received By pkrauss Date 2005-10-18 Time 08:41 Sent To  
Notes
2005-10-18 00:00:00DENIED:
 1.PLAN SHEET M-1, OUTSIDE AIR SCHEDULE
 INDICATES 2 AHU-2 ON AHU-3 IS NOT LISTED
 PLEASE CLARIFY & CORRECT.
  
 2.PLAN SHEET P-1 INDICATES THE
 AUXILIARY DRAIN LINE FROM THE PAN
 TERMINATING OVER THE ENTRANCE DOOR.
 PLEASE NOTE, PER 2001 FBC 307.2.1,
 CONDENSATE SHALL NOT DISCHARGE INTO A
 STREET ALLEY OR OTHER AREAS SO AS NOT TO
 CREATE A NUISANCE.THIS MAY CAUSE A
 SLIP AND FALL TERMINATING INTO THE
 ENTRANCE WAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 11:21 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 11:21 Sent To  
Notes
2006-08-05 00:00:00PROVISO:
 REVISE SHT A-1 FOR BREAK ROOM SINK.

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 10:45 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 10:45 Sent To  
Notes
2006-08-05 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 UNSAT
  
 BREAK RM SINK CLEARANCES ARE SHOWN AS A
 LAVATORY.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-07-20 Cont ID  
Sent By pschmitz Date 2006-07-20 Time 06:08 Rev Time 0.00
Received By pschmitz Date 2006-07-20 Time 06:06 Sent To B
Notes
2006-07-20 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW FBC
 2001 FL ACESSIBILITY CODE PLANREVIEW
 DENIED "THIRD TIME"
  
 PREVIOUS NOTE #2 NOT ADDRESSED.
  
 104.2 DRAWINGS AND SPECIFICATIONS.
 104.2.1 REQUIREMENTS. AS REQUIRED BY
 104.3.1.1 OF THE CODE, TWO OR MORE
 COPIES OF
 SPECIFICATIONS, AND OF DRAWINGS DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE
 NATURE AND CHARACTER OF THE WORK, SHALL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 SUCH
 DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY
 IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC, AND
 THE TECHNICAL CODES SHALL NOT BE CITED
 AS A WHOLE OR IN
 PART, NOR SHALL THE TERM ?LEGAL? OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 2)SHT A-1 BREAK ROOM SINKS:
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM) DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE 11-32)
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-28 Cont ID  
Sent By pschmitz Date 2006-02-28 Time 13:00 Rev Time 0.00
Received By pschmitz Date 2006-02-28 Time 12:59 Sent To  
Notes
2006-02-28 00:00:00PAUL SCHMITZ
 [email protected]
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW FBC
 2001 FL ACESSIBILITY CODE PLANREVIEW
 DENIED
  
 PREVIOUS NOTE #2 NOT ADDRESSED.
  
 104.2 DRAWINGS AND SPECIFICATIONS.
 104.2.1 REQUIREMENTS. AS REQUIRED BY
 104.3.1.1 OF THE CODE, TWO OR MORE
 COPIES OF
 SPECIFICATIONS, AND OF DRAWINGS DRAWN TO
 SCALE WITH SUFFICIENT CLARITY AND DETAIL
 TO INDICATE THE
 NATURE AND CHARACTER OF THE WORK, SHALL
 ACCOMPANY THE APPLICATION FOR A PERMIT.
 SUCH
 DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY
 IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC, AND
 THE TECHNICAL CODES SHALL NOT BE CITED
 AS A WHOLE OR IN
 PART, NOR SHALL THE TERM ?LEGAL? OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN.
  
 2)SHT A-1 BREAK ROOM SINKS:
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM) DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE 11-32)
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-08 Cont ID  
Sent By pschmitz Date 2005-10-08 Time 07:01 Rev Time 0.00
Received By pschmitz Date 2005-10-08 Time 07:01 Sent To  
Notes
2005-10-08 00:00:00PAUL SCHMITZ
 FBC 2001 PLUMBING CODE PLAN REVIEW
 FBC 2001 CH 11, FL ACESSIBILITY CODE
 DENIED
 SHT A-1 PROPOSED PLAN
 1)TAB 403.1 DRINKING FOUNTAIN OR A WATER
 COOLER REQUIRED.COMPLYING WITH.
 SECTION P410, SHOW LOCATION.
 DRINKING FOUNTAINS
 ?P410.1 APPROVAL. DRINKING FOUNTAINS
 SHALL CONFORM TO ASME A112.19.1,
 A112.19.2 OR A112.19.9, AND WATER
 COOLERS SHALL CONFORM TO ARI 1010.
  
 2)SHT A-1 BREAK ROOM SINKS:
 11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM) DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE 11-32)
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 END OF COMMENTS, QUESTIONS.
 561-805-6692
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2006-07-17 Cont ID  
Sent By eschneid Date 2006-07-17 Time 17:09 Rev Time 0.00
Received By eschneid Date 2006-07-17 Time 17:08 Sent To  
Notes
2006-07-17 00:00:00MEZZANINE FOR STORAGE ONLY.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-13 Time 11:55 Rev Time 0.00
Received By mmclean Date 2006-04-13 Time 11:54 Sent To  
Notes
2006-04-13 00:00:00PASSED PER ERIC SCHNEIDER.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-04-11 Cont ID  
Sent By eschneid Date 2006-04-11 Time 09:11 Rev Time 0.00
Received By eschneid Date 2006-04-11 Time 09:10 Sent To  
Notes
2006-04-11 00:00:00THE BUILDING HAS NO ADDITIONAL MEZZANINE
 SPACE AVAILABLE.
  
 ADDITIONAL SQUARE FOOTAGE WILL NOT MEET
 PARKING REQUIREMENTS.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-20 Cont ID  
Sent By mmclean Date 2005-09-20 Time 10:22 Rev Time 0.00
Received By mmclean Date 2005-09-20 Time 10:22 Sent To  
Notes
2005-09-20 00:00:00DENIED,
 1. NEED TO PROVIDE THE APPROVED LIST FOR
 MEZZANINE FOR ALL UNITS AT ADDRESS (1335
 OLD OKEECHOBEE)
  
  


Account Summary | Usage Policy | Privacy Policy