Plan Review Details - Permit 05090336
Plan Review Stops For Permit 05090336
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 15:12 Rev Time 0.33
Received By alange Date 2005-10-04 Time 15:12 Sent To  
Notes
2005-10-04 00:00:00DENIED
  
 PLEASE SUBMIT A SLAB DETAIL AND INCLUDE
 METHOD OF GENERATOR ANCHORING TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-26 Cont ID  
Sent By btrobaug Date 2005-09-26 Time 08:14 Rev Time 0.50
Received By btrobaug Date 2005-09-26 Time 07:47 Sent To M
Notes
2005-09-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT 2 COPIES OF THE GENERATOR AND
 TRANSFER SWITCH MANUFACTURERS
 SPECIFICATION.
  
 2} SUBMIT A SITE PLAN SHOWING THE
 LOCATION FO ALL SERVICE AND GENERATOR
 EQUIPMENT. THIS IS REQUIRED TO INDICATE
 COMPLIANCE WITH ARTICLES 225.31 THROUGH
 225.37.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 09:58 Rev Time 0.25
Received By jleech Date 2005-10-04 Time 09:58 Sent To B
Notes
2005-10-04 00:00:00FUEL PERMIT REQUIRED. LICENSED
 CONTRACTOR TO MAKE APPLICATION AND
 SUBMIT PLANS. ALL FUEL INSPECTIONS TO BE
 COMPLETE BEFORE FINAL INSPECTION ON
 GENERATOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 08:15 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 08:15 Sent To E
Notes
2005-09-21 00:00:00TO "GEN-RES" BOX"E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-12 Cont ID  
Sent By adarroug Date 2005-09-12 Time 13:40 Rev Time 0.00
Received By adarroug Date 2005-09-12 Time 13:36 Sent To Z
Notes
2005-09-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-30 Cont ID  
Sent By tgordon Date 2005-09-30 Time 10:16 Rev Time 0.15
Received By tgordon Date 2005-09-30 Time 10:16 Sent To P
Notes
2005-09-30 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. PER 2001 FBC/M 804.3.3 .
 2) MANUFACTURE'S INSTALLATION
 INSTRUCTIONS MUST BE SUBMITTED WITH
 PERMIT APPLICATION.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-04 Cont ID  
Sent By jleech Date 2005-10-04 Time 09:58 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-20 Cont ID  
Sent By mmclean Date 2005-09-20 Time 09:36 Rev Time 0.00
Received By mmclean Date 2005-09-20 Time 09:36 Sent To I
Notes
2005-09-20 00:00:00GENERATOR CAN ONLY BE 4FT INTO A
 SETBACK.