| 2005-10-07 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- DESIGN PRESSURES CHART:PROVIDE |
| | ENGINEERED CALCULATIONS SIGNED AND |
| | SEALED BY THE ENGINEER WHO CALCULATED |
| | THE DESIGN PRESSURES USING ASCE 7-98. |
| | CLEARLY SPECIFY THE DESIGN PRESSURES FOR |
| | EACH OPENING. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 2- PROVIDE A COMPLETE INSTALLATION |
| | SCHEDULE THAT PROVIDE ALL INFORMATION |
| | REQUIRED TO REVIEW COMPLIANCE WITH THE |
| | DESIGN PRESSURES CALCULATED IN ABOVE |
| | ITEM. SEE ATTACHED COPY OF INSTALLATION |
| | SCHEDULE SAMPLE. FILL INFORMATION THAT |
| | APPLIES TO THIS PRODUCT AND EXPAND CHART |
| | TO INCLUDE INFORMATION REQUIRED TO |
| | DESCRIBE THIS PRODUCT. SPECIFY ALL |
| | FASTENERS TO BE USED. SEC. 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | 3- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | THIS PRODUCT AS REQUIRED BY RULE 9B-72 |
| | OF DCA. SEE WWW.FLORIDABUILDING.ORG. |
| | DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATE WIDE FLORIDA |
| | PRODUCT APPROVAL. MANUFACTURER, MAY |
| | APPLY FOR LOCAL PRODUCT APPROVAL USING |
| | THE DADE COUNTY NOA AND COMPLETING THE |
| | LOCAL PRODUCT APPROVAL FORM DOWNLOADED |
| | FROM WWW.FLORIDABUILDING.ORG. |
| | |
| | 4- CLEARLY MARK ON DRAWINGS SPECIFIC |
| | SCREEN MOUNTING CONDITIONS AND ANCHORS |
| | TO BE USED INCLUDING CHART ON PAGE 2 OF |
| | 8 TO VERIFY COMPLIANCE. SEC. 104.2.1.2. |
| | |
| | 5- NEED EMERGENCY EGRESS AS REQUIRED BY |
| | SEC. 1005.4.5 FBC 2001. SPECIFY HOW IS |
| | THIS EMERGENCY EGRESS ACCOMPLISHED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |