Plan Review Details - Permit 05090307
Plan Review Stops For Permit 05090307
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-23 Cont ID  
Sent By shill Date 2006-01-23 Time 09:55 Rev Time 1.00
Received By shill Date 2006-01-23 Time 09:39 Sent To  
Notes
2006-01-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)TWO INDEPENDENT EXITS REQUIRED,
 FBC1004.2.1.TWO ACCESSIBLE EXITS
 REQUIRED, FBC11-4.1.3(9).
  
 2.)SHEET D1 SHOWS EXISTING OH DOORS ON
 THE EAST SIDE, SHOULD BE SWING DOORS
 (A1, LETTER).
  
 3.)A LETTER WAS INCLUDED REFERRING TO
 A RAMP.NONE SHOWN ON THE PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-06 Cont ID  
Sent By shill Date 2005-11-06 Time 10:11 Rev Time 1.50
Received By shill Date 2005-11-06 Time 08:50 Sent To  
Notes
2005-11-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING (SURVEY OR SITE PLAN),
 ADJACENT TENANTS IF APPLICABLE.THIS
 APPEARS TO BE A FREE STANDING STRUCTURE
 WITH ONE SPACE, BUT BUILDING CODE
 CLASSIFICATION (ON D1 AND A1) INDICATES
 A REQUIREMENT OF 1 HOUR SEPARATION.IS
 ANY SEPARATION NECESSARY?THIS SHOULD
 BE 2 HOUR FOR FACTORY OCCUPANCY IF IT IS
 AN OCCUPANCY SEPARATION, FBC TABLE
 704.1.
  
 3.)WHAT DOES THE SOLID SINGLE LINE
 ATTACHED TO THE BUILDING REPRESENT?IT
 HAS NOT BEEN INCLUDED ON THE WALL
 LEGEND.THIS IS ADJACENT TO THE
 EXISTING OVERHEAD ELEC SERVICE AND
 ANOTHER LINE EXTENDING FROM NEAR THE
 EXISTING FIRE SPRINKLER RISER, D1 AND
 ALSO APPEARS ON A1.THE EXIT FOR THE
 BUILDING OPENS INTO THIS SPACE.
  
 4.)D1 SHOWS AN EXISTING OVERHEAD DOOR,
 BUT GRAPHICALLY SHOWS LARGE DOUBLE DOORS
 WHICH ARE MARKED AS AN EXIT ON A1 AND
 A2.PLEASE CLARIFY.FBC1012.1, THE
 DOOR WIDTH CANNOT EXCEED 48INCHES.
  
 5.)SHOW DIMENSIONS FOR ALL DOORS IN
 THE EGRESS PATH.
  
 6.)WHAT DOES ETR STAND FOR?THIS NOTE
 IS ON SOME OF THE DOORS, A1.IF YOU ARE
 GOING TO USE NON STANDARD ABBREVIATIONS,
 PLEASE INCLUDE A SCHEDULE TO AVOID
 CONFUSION.
  
 7.)PROVIDE A MORE COMPLETE PROJECT
 DESCRIPTION.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-11 Cont ID  
Sent By dpalmer Date 2006-01-11 Time 12:19 Rev Time 0.00
Received By dpalmer Date 2006-01-11 Time 12:08 Sent To I
Notes
2006-01-11 00:00:00***** UNSAT *****
  
 1)NOTE: PLEASE CORRELATE RISER AND
 PANELS. PLEASE SEE PANEL "LA" IS SHOWN
 AS 100A S-PHASE PANEL, HOWEVER CONDUCTOR
 ON RISER ARE SHOWN FOR A 1-PHASE PANEL?
  
 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE STILL BEING SHOWN BEFORE
 THE FIRST MEANS OF DISCONNECT AS
 PROHIBITED BY 250.6, 250.24
 PLEASE CLARIFY, AS PLANS SHOW A BREAKER
 NEXT TO THESE PANELS, HOWEVER THIS IS
 NOT REFLECTED ON RISE4R? IS THIS A MAIN
 BRKR DISC AHEAD OF GUTTER OR PANELS?
 IF SO, THEN THE "EQUIPMENT GROUNDING
 CONDUCTORS WOULD REMAIN, BUT UNALBE TO
 VERIFY AT THIS TIME.
 PLEASE SEE E2.1 FOR THE "BREAKER"
 INDICATED, BUT NOT ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE KNOW, A RESPONSE LTR AS SUBMITTED
 BY ARCHITECTUAL FIRM MAY ALSO HELP IN
 ANY EXPLANATION OF COMMENTS FOR
 ENGINEERING FIRM. THIS IS NOT REQUIRED ,
 HOWEVER THIS WILL HELP IN EXPEDITING THE
 REVIEW AND PROCESS OF PLANS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-21 Cont ID  
Sent By hmoser Date 2005-10-12 Time 11:17 Rev Time 0.50
Received By dpalmer Date 2005-09-20 Time 18:35 Sent To  
Notes
2005-09-21 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE CORRELATE RISER
 ELECTRICAL NOTES WITH RISER. PLEASE SEE
 SOME NUMBERS INDICATED ON RISER, HOWEVER
 THESE COULD NOT BE LOCATED ON NOTES.
 PLEASE SEE REDLINED PLANS.
  
 2)NOTE: PLEASE SEE "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.6,250.24 ETC
  
 3)NOTE: PLEASE SEE A "WALK-IN " COOLER
 IS SHOWN ON PLANS HOWEVER THERE IS NO
 INDICATION OF THIS SHOWN ON EITHER PANEL
 SCHEDULE OR LOADS INDICATED FOR POSSIBLE
 LOADS.
 PLANS SHOW A 60A DISCONNECT ONLY. IT IS
 NOTED THAT THE OCP WILL BE PER
 MANUFACTURES SPECS/ ETC HOWEVER, SOME
 INDICATION OF SIZING/LOAD SHOULD BE
 SHOWN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-09-20 00:00:00IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-20 Cont ID  
Sent By mcarsill Date 2006-01-20 Time 14:07 Rev Time 0.00
Received By mcarsill Date 2006-01-20 Time 14:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By mwennerg Date 2005-10-06 Time 13:14 Rev Time 0.00
Received By mwennerg Date 2005-10-06 Time 13:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 19:12 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 19:12 Sent To  
Notes
2006-01-13 00:00:00TO "COMM" BD#24
2005-12-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-08 Cont ID  
Sent By shill Date 2005-11-08 Time 10:31 Rev Time 0.00
Received By shill Date 2005-09-12 Time 17:00 Sent To  
Notes
2005-09-12 00:00:00TO "COMM" BD#32

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-08 Cont ID  
Sent By hmoser Date 2005-10-12 Time 11:16 Rev Time 0.00
Received By hmoser Date 2005-11-08 Time 08:00 Sent To  
Notes
2005-11-08 00:00:00PASS PRIVISO
 1) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.FBC(M) 2001.
 2) PLEASE REFER TO MECHANICAL NOTES #7
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-25 Cont ID  
Sent By pschmitz Date 2006-01-25 Time 11:18 Rev Time 0.00
Received By pschmitz Date 2006-01-25 Time 11:18 Sent To PC
Notes
2006-01-25 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 DENIED
 PREVIOUS COMMENTS NOT ADDRESSED
 1)SEC 1003 INTERCEPTORS, (SIZED BY)
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
 3)SEC 104.2 DRAWINGS,SPECIFICATIONS
 SHOW DEMINSIONS AND SQUARE FOOTAGE.
 SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 6)LOCAL ORDINANCE#2853-95
 SHOW LOCATION OF BACK FLOW PREVENER.
  
 NEW COMMENTS
  
 1)PERMIT APPLICATION DESCRIPTION OF WORK
 IS VAGUE.
 2) CORRELATE PLANS.
 3) PLEASE SUBMIT ONE COPY OF ORIGINAL
 PLANS FOR COMPARISON.
 4)PROVIDE EQUIPMENT SCHEDULE,INCLUDE
 SMOKE EQUIPMENT.
 5) SEC 607.3.2 THERMAL EXPANSION.
 A DEVICE FOR CONTROLLING THERMAL
 EXPANSION SHALL BE INSTALLED.
 6) TAB 403.1 (NO 4) OCCUPANCY, MIXED
 USE:
 A)BUSINESS, SECTION EXISTING.
 B) FACTOTY INDUSTRIAL.
 SEPERATE HANDI CAP FACILITIES FOR MEN
 AND WOMEN.
 ONE DRINKIN FOUNTAIN.
 ONE SERVICE SINK.
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By hmoser Date 2005-10-17 Time 09:51 Rev Time 0.00
Received By pschmitz Date 2005-11-08 Time 07:58 Sent To  
Notes
2005-10-17 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODEPLAN
 REVIEW.
 1)SEC 1003 INTERCEPTORS
 CONTACT W P BEACHWATERPLANT LAB
 SUPERVISORINDUSTRIAL COORDINATOR,
 LYNN MASSON
 OFFICE 561-822-2271
 E-MAIL [email protected]
 3)SEC 104.2 DRAWINGS,SPECIFICATIONS
 SHOW DEMINSIONS AND SQUARE FOOTAGE.
 4) SECTION 11-4
 ACCESSIBLE ELEMENTS AND
 SPACES:SCOPE AND TECHNICAL REQUIREMENTS
 ?11-4.1 MINIMUM REQUIREMENTS.
 ?11-4.1.1(1) GENERAL. THIS CODE
 ESTABLISHES THE MINIMUM STANDARDS FOR
 THE ACCESSIBILITY OF BUILDINGS AND
 FACILITIES BUILT OR ALTERED WITHIN
 THE STATE.
 5)
 SHT P-2.1 A/C CONDENSATE.
 CONNECT TO DRY WELL, STORM DRAIN OR
 PLANTER AREA.
 6)LOCAL ORDINANCE#2853-95
 SHOW LOCATION OF BACK FLOW PREVENER.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  