Plan Review Details - Permit 05090219
Plan Review Stops For Permit 05090219
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-19 Cont ID  
Sent By jgomez Date 2005-10-19 Time 15:35 Rev Time 0.50
Received By jgomez Date 2005-10-19 Time 15:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-14 Cont ID  
Sent By jgomez Date 2005-10-14 Time 16:12 Rev Time 0.33
Received By jgomez Date 2005-10-14 Time 16:12 Sent To PC
Notes
2005-10-14 00:00:00BUILDING REVIEW SECOND CHECKLIST:
 1- FROM PREVIOUS CHECKLIST: DADE COUNTY
 NOA ALONE IS NOT AUTOMATICALLY AN STATE
 WIDE PRODUCT APPROVAL. NEED TO PROVIDE
 COMPLETE FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY RULE 9B-72 OF DCA. SEE
 WWW.FLORIDABUILDING.ORG.
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT
 APPROVAL USING THE DADE COUNTY NOA BY
 COMPLETING THE LOCAL PRODUCT APPROVAL
 FORM DOWNLOADED FROM
 WWW.FLORIDABUILDING.ORG.
 ***CALL ROBERT BROWN, LICENSE/PERMIT
 SERVICES MANAGER, AT (561)805-6652 FOR
 PROCEDURE AND TIMING FOR LOCAL PRODUCT
 APPROVALS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By jgomez Date 2005-10-04 Time 16:26 Rev Time 0.33
Received By jgomez Date 2005-10-04 Time 15:47 Sent To PC
Notes
2005-10-04 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY RULE 9B-72 FROM DCA. SEE
 WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT AN
 STATEWIDE PRODUCT APPROVAL.
 MANUFACTURER MAY APPLY FOR LOCAL PRODUCT
 APPROVAL USING THE DADE COUNTY NOA
 REPORT AND COMPLETING THE LOCAL PRODUCT
 APPROVAL FORM DOWNLOADED FROM THE WEB
 WWW.FLORIDABUILDING.ORG.
  
 2- IF USING DADE COUNTY NOA SUBMITTED,
 THEN, MAKE SURE THAT DRAWINGS ARE
 APPROVED AND STAMPED WITH THE DADE
 COUNTY APPROVAL STAMP.
  
 3- PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE.
  
 4- PROVIDE COMPLETE KEY PLAN THAT
 CLEARLY ILLUSTRATES IF OPENING IS AT THE
 END OR INTERIOR ZONE TO HELP DETERMINE
 THE CALCULATED DESIGN PRESSURES. SEC.
 1606 FBC 2001.
  
 5- KEY PLAN TO ILLUSTRATE WHICH OPENING
 IS GOING TO BE USED FOR EMERGENCY EGRESS
 AS REQUIRED BY SEC. 1005.4.5 FBC 2001.
  
 6- CLEARLY MARK ON SHUTTERS DRAWINGS
 (SHEETS 6 OF 7 OR 7 OF 7) SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED
 ACCORDING TO THE DESIGN PRESSURES, EDGE
 DISTANCE, PANEL SPAN, CONNECTION TYPE
 AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE, CONCRETE BLOCK OR WOOD). SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 18:22 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 18:22 Sent To B
Notes
2005-10-11 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-09 Cont ID  
Sent By adarroug Date 2005-09-09 Time 08:34 Rev Time 0.00
Received By adarroug Date 2005-09-09 Time 08:34 Sent To B
Notes
2005-09-09 00:00:00TO "MISC" BOX#1