Plan Review Details - Permit 05090201
Plan Review Stops For Permit 05090201
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-10-06 Cont ID  
Sent By shill Date 2005-10-06 Time 16:46 Rev Time 0.00
Received By shill Date 2005-10-06 Time 16:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-10-03 Cont ID  
Sent By shill Date 2005-10-03 Time 16:55 Rev Time 0.50
Received By shill Date 2005-10-03 Time 16:55 Sent To PC
Notes
2005-10-03 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.ITEM 1
 ON THE NOC IS TO INCLUDE THE LEGAL
 DESCRIPTION AS REQUIRED BY FLORIDA
 STATUTE.
  
 2.)ALL CHANGES TO THE PLAN ARE TO BE
 CLEARLY MARKED WITH CLOUDS AND A
 REVISION NUMBER.
  
 3.)SHOW MANEUVEURING CLEARANCE AT THE
 DOOR FBC11-4.13.6, FIGURE 25.THIS WAS
 ADDRESSED BY INDICATING 'MINIMUM 18"
 CLEAR' ON THE PLAN BUT WHEN SCALED IT IS
 LESS THAN 6".TO MAKE CODE COMPLIANCE
 CLEAR, PLEASE REVISE THE PLAN.
  
 4.)THE LICENSE NUMBER AA0003061 IS NOT
 FOR FLC ARCHITECTS ON THE FLORIDA DBPR
 WEBSITE.PLEASE CLARIFY OR REVISE THE
 TITLE BLOCK WITH THE CORRECT
 INFORMATION.
  
  
 SEE ATTACHED FS553.80(2)(B).A 4X PLAN
 REVIEW FEE WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED ON THE NEXT
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By shill Date 2005-09-12 Time 08:33 Rev Time 1.00
Received By shill Date 2005-09-12 Time 08:33 Sent To  
Notes
2005-09-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE INTERIOR FINISH
 CLASSIFICATION FBC803.3.
  
 3.)SHOW WIDTH OF THE NEW INTERIOR DOOR
 FBC11-4.13(2).
  
 4.)SHOW MANEUVEURING CLEARANCE AT THE
 DOOR FBC11-4.13.6, FIGURE 25.
  
 5.)PROVIDE ROOM DESIGNATION FOR THE
 AREAS AFFECTED BY THE RENOVATION.
  
2005-09-12 00:00:00PROVISO - COMPLY WITH FBC 803.3

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2005-10-08 Cont ID  
Sent By dpalmer Date 2005-10-08 Time 15:58 Rev Time 0.05
Received By dpalmer Date 2005-10-08 Time 15:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-09-21 Cont ID  
Sent By dpalmer Date 2005-09-21 Time 18:38 Rev Time 0.10
Received By dpalmer Date 2005-09-21 Time 18:38 Sent To  
Notes
2005-09-21 00:00:00** UNSAT **
  
 PLEASE SEE BLDG REVIEW COMMENTS FROM
 PREVIOUS REVIEW WHICHDO NOT APPEAR TO
 HAVE BEEN ADDRESSED. PLEASE SEE SAME
 PLANS SUBMITTED BACK.
  
  
 PLEASE KNOW, ALL PLANS WHICH ARE SIGNED,
 DATED AND SEALED BY ARCHITECT, SHALL
 ONLY HAVE CHANGES MADE BY THE ARCHITECT
 OF RECORD. PLEASE ALSO KNOW, IF ANY
 HAND-DRAWN CHANGESARE MADE TO PLANS,
 EACH CHANGED WOULD BE REQUIRED TO BE
 DATED AND SIGNED BY SAID ARCHITECT.
 PLEASE SEE PLANS SUBMITTED HAVE BEEN
 VOIDED.
 FS 481.221
  
 PLEASE KNOW, ELECTRICAL PLANS ARE OK FOR
 RE-LOCATION OF EM/EXT LT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-10 Cont ID  
Sent By dpalmer Date 2005-09-10 Time 18:04 Rev Time 0.10
Received By dpalmer Date 2005-09-10 Time 18:04 Sent To  
Notes
2005-09-10 00:00:00** UNSAT **
  
 1)NOTE:PLEASE SEE BLDG REVIEW COMMENTS,
 WHICH WILL AFFECT THE ONLY SHEET
 SUBMITTED.
  
 2)NOTE: PLEASE SEE THE ONLY ITEM
 SUBMITTED FOR ELECTRICAL SCOPE OF WORK
 WAS TO RELOCATED ONE EXIT SIGN?
 IF SO, THIS IS OK FOR ELECTRICAL,
 HOWEVER PLEASE SEE ANY POSSIBLE FIRE
 REVIEW NOTES.
  
  
 PLANS WILL BE STAMPED FOR ELECTRICAL
 ONCE BLDG REVIEW IS OK.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2005-10-07 Cont ID  
Sent By mwennerg Date 2005-10-07 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2005-10-07 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-09-13 Cont ID  
Sent By mwennerg Date 2005-09-13 Time 09:21 Rev Time 0.00
Received By mwennerg Date 2005-09-13 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 16:28 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 16:28 Sent To  
Notes
2005-10-06 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 09:13 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 09:13 Sent To  
Notes
2005-09-21 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-13 Cont ID  
Sent By shill Date 2005-09-13 Time 11:44 Rev Time 0.00
Received By shill Date 2005-09-08 Time 18:18 Sent To PC
Notes
2005-09-13 00:00:00SENT TO S HILL DESK FOR DOOR WIDTH
 (ACCESSIBILITY) AND ROOM DESIGNATION
  
2005-09-08 00:00:00TO "BOB"#2