Plan Review Details - Permit 05090176
Plan Review Stops For Permit 05090176
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-13 Cont ID  
Sent By shill Date 2006-03-13 Time 13:20 Rev Time 3.00
Received By shill Date 2006-03-13 Time 11:58 Sent To  
Notes
2006-03-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THIS RENOVATION INVOLVES A CHANGE
 OF OCCUPANCY, SEE FBC106.1.1,
 FBC106.4.1.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING; TOTAL AREA, BUILDING TYPE
 FBC CHAPTER 6, PROTECTED OR UNPROTECTED,
 SPRINKLED OR UNSPRINKLED.
  
 PROVIDE A LETTER FROM THE ENGINEER, ON
 ENGINEER'S LETTERHEAD, AS TO
 HOW YOU HAVE ARRIVED AT THE TOTAL SF
 AREA.SEE FBC CHAPTER 2, DEFINITIONS.
 PROVIDE AREA CALCULATIONS BROKEN DOWN BY
 FLOOR.SHOW TOTAL SF OF A/C AREA AND
 AREA UNDER THE BALCONY.THE LETTER IS
 TO DECLARE BUILDING SIZE, HEIGHT, TYPE
 FBC600, AND SHOW COMPLIANCE WITH FBC
 TABLE 500.PROVIDE A COPY OF THE
 SURVEY.
  
 4. - 5.)ADDRESSED.
  
 6.)PROVIDE A SITE PLAN SHOWING THE
 BUILDING'S LOCATION ON THE LOT AND THE
 ACCESSIBLE ROUTE, FBC11-4.1.2.
  
 NOT ADDRESSED PROPERLY.A SITE PLAN WAS
 PROVIDED BUT DOES NOT SHOW ACCESSIBLE
 ROUTE.SHOW REQUIRED INFORMATION,
 INCLUDING ACCESSIBLE PARKING.THE
 ACCESSIBLE PARKING SPACE DOES NOT COMPLY
 WITH FBC11-4.6.2 THROUGH 11-4.6.5.ALSO
 SEE ATTACHED FOR DETAIL FOR CITY OF WPB
 STANDARD FOR PARKING.
  
 7.)DECLARE AN OCCUPANT LOAD FOR THIS
 AREA, FBC1003.1, FBC TABLE 1003.1.
  
 NOT ADDRESSED.15 PER SF IS NOT AN
 OCCUPANT LOAD.DECLARE OCCUPANT LOAD;
 SHOULD BE A TOTAL NUMBER.
  
 8.)SHOW REQUIRED OCCUPANCY AND/OR
 TENANT SEPARATIONS.PROVIDE A LISTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC709.
  
 NO RATED ASSEMBLIES SHOWN.FIRE
 RESISTANCE BETWEEN FIRST AND SECOND
 FLOORS NOT SHOWN.
  
 9.)PROVIDE A CERTIFICATION FOR THE
 FLOOR LOADING FOR THIS OCCUPANCY, FBC
 TABLE1604.1.INCLUDE THE BALCONY.
 PROVIDE DETAILS.
  
 NOT ADDRESSED PROPERLY. A STATEMENT WAS
 ON THE PLAN BUT NO INFORMATION PROVIDED
 FOR THE BALCONY.
  
 10.)PROVIDE ELEVATIONS SO THAT CODE
 COMPLIANCE IN REGARDS TO THE LARGE
 WINDOWS AND THE EXIT STAIR CAN BE
 DETERMINED.
  
 EXTERIOR STAIRS ARE TO COMPLY WITH
 FBC1006.2.2.THE STAIRS SHOWN ARE NOT
 ROOFED OVER.
  
 OPENINGS ARE TO COMPLY WITH FBC1006.2.4.
 SHOW REQUIREMENTS AND COMPLIANCE ON THE
 PLAN.
  
 11.)SEE FBC2405.IS SAFETY GLASS
 REQUIRED?
  
 NOT ADDRESSED.TEMEPERED GLASS IS SHOWN
 FOR THE FIRST FLOOR, WHAT ABOUT THE
 RENOVATION AREA WHICH IS ON THE SECOND
 FLOOR?
  
 12.)PROVIDE A LIFE SAFETY PLAN.SHOW
 ALL EXIT LIGHTS.NOT ENOUGH INFORMATION
 WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.PLEASE REACH FBC CHAPTER 10
 AND SHOW COMPLIANCE ON THE PLAN.SEE
 ALSO FBC11-4.1.3(9).
  
 NOT ADDRESSED, NO LIFE SAFETY PLAN
 PROVIDED.EXITING IS NOT CLEAR.THE
 PLAY AREA SHOWS AN EXIT AT THE DOUBLE
 DOOR, BUT THE TRAVEL DISTANCE TO THE
 STAIR EXCEEDS 150FT AND THAT STAIR
 CANNOT BE USED AS A MEANS OF EGRESS IF
 IT IS NOT COMPLIANT AS AN EXTERIOR
 STAIR.IT SHOULD HAVE TWO EXITS, ONLY
 ONE NON COMPLIANT EXIT SHOWN.PROVIDE A
 LIFE SAFETY AS REQUESTED.
  
 13.)PROVIDE DETAILS AND DESIGN
 CRITERIA FOR BOTH STAIRS AND THE HAND
 RAILS AND STAIR GUARDRAILS, FBC1007 ,
 FBC11-4.9,FBC1015, FBC1608,
 FBC11-4.26.
  
 THE STAIR RAIL WHICH SERVES AS A
 GUARDRAIL DOES NOT COMPLY WITH FBC1015.2
 (HEIGHT).THE EXTENSIONS REQUIRED AT
 THE BOTTOM ARE NOT SHOWN.HANDRAILS
 REQUIRED ON BOTH SIDES, PROVIDE A
 DETAIL.PICKET SPACING NOT SHOWN.
 STRENGTH FOR HANDRAILS WAS PROVIDED BUT
 NOT FOR GUARDRAILS.
  
 14.)PROVIDE A DETAIL AND DESIGN
 CRITERIA FOR THE BALCONY GUARDRAIL.
 FBC1007, FBC1608.
  
 NOT ADDRESSED.
  
 15.)FIRE RATING IS NOT SHOWN BETWEEN
 THE HALL AND THE RECEPTION AREA.THIS
 APPEARS TO BE COMMON AREA, SEPARATION
 REQUIRED.
  
 16.)IF THE WALL BETWEEN THE RECEPTION
 AND HALL IS TO BE RATED, A FIRE RATED
 DOOR REQUIRED FBC TABLE 705.1.2.
  
 NOT ADDRESSED, ONLY SHOWN AS "EXISTING".
  
 17.)IF THIS BUILDING IS NOT FULLY
 SPRINKLED, AREA OF RESCUE ASSISTANCE
 REQUIRED, FBC11-4.1.3(9).IF THIS
 BUILDING IS FULLY SPRINKLED, INDICATE
 AND PROVIDE A SPRINKLER PLAN.
  
 THE AREA OF RESCUE ASSISTANCE IS TO
 COMPLY WITH FBC11-4.3.11.IT IS NOT
 CLEAR HOW AN AREA WITH THREE WALLS, OPEN
 TO THE SPACE, IS AN AREA OF RESCUE
 ASSISTANCE.TWO REQUIRED.
  
 18.)THE SEATING AREA BLOCKS THE
 REQUIRED EGRESS WIDTH OF THE HALLWAY.
 SEE FBC TABLE 1004.
  
 NOT ADDRESSED.SEATING AREA STILL SHOWN
 IN THE HALLWAY.
  
 19.)ADDRESSED.
  
 20.)ADDRESSED.
  
 21.)ADDRESSED.
  
 22.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BATHROOMS.INCLUDE ALL
 DIMENSIONS AND SHOW CLEAR FLOOR SPACE
 FOR FIXTURES.NO DETAILS WERE PROVIDED;
 CODE COMPLIANCE CANNOT BE DETERMINED.
 SEE FBC CHAPTER 11.
  
 SHOW DISTANCE FROM CL OF WATER CLOSET TO
 THE WALL, FBC11 FIGURE 30.SHOW CLEAR
 FLOOR SPACE AND TURNING RADIUS ON THE
 FLOOR PLAN.
  
 23.)SIGNAGE FOR THE ELEVATOR IS TO BE
 COMPLIANT WITH FBC11-4.10.
  
 PLANS ARE TO SHOW CODE COMPLIANT.A
 STATEMENT THAT THE ELEVATOR CONTRACTOR
 IS RESPONSIBLE FOR SIGNAGE IS NOT
 SHOWING DESIGN CRITERIA OR CODE
 COMPLIANCE.
  
 24.)SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 11-26(A).
  
 NOT ADDRESSED.PROVIDE THE REQUIRED
 DIMENSION ON THE PLAN.
  
 25.)THE APPLICATION STATES THAT
 INTERIOR STAIRS ARE TO BE CLOSED OFF.
 PROVIDE A LOCATION AND A DETAIL.WILL
 IT BE CLOSED OFF BOTH UPSTAIRS AND
 DOWNSTAIRS?
  
 PLANS NOW SHOW THE DETAIL AND SCOPE OF
 WORK IS CLEAR, BUT NON COMPLIANT.
  
 26.)PLEASE NOTE THAT IT WOULD BE
 REASONABLE TO ANTICIPATE THAT A THIRD
 PLAN REVIEW WILL BE NECESSARY AS MANY
 ITEMS ARE NOT CODE COMPLIANT AND THERE
 IS INSUFFICIENT INFORMATION ON THE PLAN
 TO DEVELOP A COMPLETE CORRECTION LIST.
  
 27.)A COPY OF THE PLANS HAS BEEN
 RETAINED.
  
 A COPY OF THIS PLAN HAS ALSO BEEN
 RETAINED AND WILL BE FORWARDED TO FBPE.
  
 NEW COMMENTS:
  
 28.)A DETAIL HAS BEEN PROVIDED FOR A
 NEW SECTION OF FLOORING WHICH USES
 COMBUSTIBLE MATERIALS.THIS IS NOT
 PERMITTED IN A TYPE IV.
  
 29.)THE ENGINEER'S SEAL IS TO STATE
 "LICENSE" RATHER THAN "CERTIFICATE"
 EFFECTIVE 1/1/2006, FAC61G15-23.002(1).
  
 30.)PROVIDE INTERIOR FINISH
 CLASSIFICATION FBC TABLE 803.3.
  
 31.)PROVIDE A REASONABLE VALUE FOR THE
 SCOPE OF WORK, OR AN ESTIMATE WILL BE
 DONE FOR YOU USING MARSHALL & SWIFT.
  
 32.)WHEN RESUBMITTING, INCLUDE A
 RESPONSE LETTER ON THE ENGINEER'S
 LETTERHEAD INDICATING HOW EACH ITEM HAS
 BEEN ADDRESSED.
  
 33.)PROVIDE A COMPLETE DESCRIPTION OF
 THE ACTIVITY FOR EACH ROOM SO THAT
 OCCUPANCY AND OCCUPANT LOAD CAN BE
 PROPERLY DETERMINED.
  
 34.)PROVIDE A DETAIL FOR THE BAR TO
 COMPLY WITH ALL REQUIREMENTS OF
 FBC11-5.2.
  
 35.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS NOT PROPERLY ADDRSSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-06 Cont ID  
Sent By shill Date 2005-11-06 Time 12:54 Rev Time 2.00
Received By shill Date 2005-11-06 Time 12:54 Sent To  
Notes
2005-11-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THIS RENOVATION INVOLVES A CHANGE
 OF OCCUPANCY, SEE FBC106.1.1,
 FBC106.4.1.
  
 3.)PROVIDE INFORMATION IN REGARDS TO
 THE BUILDING; TOTAL AREA, BUILDING TYPE
 FBC CHAPTER 6, PROTECTED OR UNPROTECTED,
 SPRINKLED OR UNSPRINKLED.
  
 4.)PROVIDE A PLAN SHOWING ALL TENANTS,
 FIRST FLOOR AND SECOND, WITH OCCUPANCY
 FOR EACH.
  
 5.)DECLARE AN OCCUPANCY AND
 SUBCLASSIFICATION FOR THIS IMPROVEMENT,
 SEE FBC304.
  
 6.)PROVIDE A SITE PLAN SHOWING THE
 BUILDING?S LOCATION ON THE LOT AND THE
 ACCESSIBLE ROUTE, FBC11-4.1.2.
  
 7.)DECLARE AN OCCUPANT LOAD FOR THIS
 AREA, FBC1003.1, FBC TABLE 1003.1.
  
 8.)SHOW REQUIRED OCCUPANCY AND/OR
 TENANT SEPARATIONS.PROVIDE A LISTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE
 FBC709.
  
 9.)PROVIDE A CERTIFICATION FOR THE
 FLOOR LOADING FOR THIS OCCUPANCY, FBC
 TABLE1604.1.INCLUDE THE BALCONY.
 PROVIDE DETAILS.
  
 10.)PROVIDE ELEVATIONS SO THAT CODE
 COMPLIANCE IN REGARDS TO THE LARGE
 WINDOWS AND THE EXIT STAIR CAN BE
 DETERMINED.
  
 11.)SEE FBC2405.IS SAFETY GLASS
 REQUIRED?
  
 12.)PROVIDE A LIFE SAFETY PLAN.SHOW
 ALL EXIT LIGHTS.NOT ENOUGH INFORMATION
 WAS PROVIDED TO DETERMINE CODE
 COMPLIANCE.PLEASE REACH FBC CHAPTER 10
 AND SHOW COMPLIANCE ON THE PLAN.SEE
 ALSO FBC11-4.1.3(9).
  
 13.)PROVIDE DETAILS AND DESIGN
 CRITERIA FOR BOTH STAIRS AND THE HAND
 RAILS AND STAIR GUARDRAILS, FBC1007 ,
 FBC11-4.9,FBC1015, FBC1608,
 FBC11-4.26.
  
 14.)PROVIDE A DETAIL AND DESIGN
 CRITERIA FOR THE BALCONY GUARDRAIL.
 FBC1007, FBC1608.
  
 15.)FIRE RATING IS NOT SHOWN BETWEEN
 THE HALL AND THE RECEPTION AREA.THIS
 APPEARS TO BE COMMON AREA, SEPARATION
 REQUIRED.
  
 16.)IF THE WALL BETWEEN THE RECEPTION
 AND HALL IS TO BE RATED, A FIRE RATED
 DOOR REQUIRED FBC TABLE 705.1.2.
  
 17.)IF THIS BUILDING IS NOT FULLY
 SPRINKLED, AREA OF RESCUE ASSISTANCE
 REQUIRED, FBC11-4.1.3(9).IF THIS
 BUILDING IS FULLY SPRINKLED, INDICATE
 AND PROVIDE A SPRINKLER PLAN.
  
 18.)THE SEATING AREA BLOCKS THE
 REQUIRED EGRESS WIDTH OF THE HALLWAY.
 SEE FBC TABLE 1004.
  
 19.)THE DOORS FROM THE RECEPTION TO
 HALLWAYS DO NOT COMPLY WITH FBC1012.1.4.
  
  
 20.)PROVIDE A DIMENSION FOR THE
 BALCONY.THE DOORS TO THE BALCONY ARE
 TO COMPLY WITH FBC1012.1.4.
  
 21.)THE DOORS MARKED DOOR 1 OR DOOR 2
 DO NOT MEET THE REQUIREMENTS OF
 FBC11-4.13.5.
  
 22.)PROVIDE A DETAIL FOR THE
 ACCESSIBLE BATHROOMS.INCLUDE ALL
 DIMENSIONS AND SHOW CLEAR FLOOR SPACE
 FOR FIXTURES.NO DETAILS WERE PROVIDED;
 CODE COMPLIANCE CANNOT BE DETERMINED.
 SEE FBC CHAPTER 11.
  
 23.)SIGNAGE FOR THE ELEVATOR IS TO BE
 COMPLIANT WITH FBC11-4.10.
  
 24.)SHOW COMPLIANCE WITH FBC11-4.13.7,
 FBC FIGURE 11-26(A).
  
 25.)THE APPLICATION STATES THAT
 INTERIOR STAIRS ARE TO BE CLOSED OFF.
 PROVIDE A LOCATION AND A DETAIL.WILL
 IT BE CLOSED OFF BOTH UPSTAIRS AND
 DOWNSTAIRS?
  
 26.)PLEASE NOTE THAT IT WOULD BE
 REASONABLE TO ANTICIPATE THAT A THIRD
 PLAN REVIEW WILL BE NECESSARY AS MANY
 ITEMS ARE NOT CODE COMPLIANT AND THERE
 IS INSUFFICIENT INFORMATION ON THE PLAN
 TO DEVELOP A COMPLETE CORRECTION LIST.
  
 27.)A COPY OF THE PLANS HAS BEEN
 RETAINED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-22 Cont ID  
Sent By dpalmer Date 2006-02-22 Time 20:13 Rev Time 0.00
Received By dpalmer Date 2006-02-22 Time 19:43 Sent To  
Notes
2006-02-22 00:00:00********* UNSAT 2ND REVIEW ********
  
 *** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS DUE TO
 INFORMATION ON PLANS.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE RISER
 STILL SHOWS THE SAME.
 PLEASE KNOW, AN INSPECTION BY THE CHEIF
 ELECTRICAL INSPECTOR WAS DONE AND NO
 ADDTIONAL ELECTRICAL METER/MAINS WILL BE
 PERMITTED WITHOUT A SERVICE CHNAGE TO
 INCREASE SERVICE. " ONE SERVICE AND A
 MAX OF 6 MAINS, OR ONE MAIN AND THEN
 TENANT METERS AND MAINS IN EXCESS OF 6
 WOULD BE PERMITTED AS LONG AS MAIN
 SERVICE INSTALLED IS ADEQUATE.
 230.70,230.2, ETC
  
 ** PLEASE SEE SERVICE RISERS SHOWN
 INDICATE MORE THAN 6 MAINS FOR BLDG.
 PLEASE SEE THE TWO NEW METERS AND MAINS,
 SHOWN ARE NOT PERMITTED.230.2
  
 2)NOTE: OK. NO CHNAGE NEED , ONLY NOTED
 FOR INFORMATION.
  
 **PLEASE SEE REVIEW COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT
 ELECTRICAL PLANS.
 PLEASE SEE POSSIBLE CHANGE IN
 USE/OCCUPANCY INSTENED.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NEW
 COMMENT WITH RESPECT TO ALL CIRCUITING,
 PLEASE ALSO SEE THIS COMMENT BELOW.
 PLEASE SEE THESE WERE NOT ADDED AS
 REQUIRED.
 PLEASE INCLUDE EM LTS, NONE COULD BE
 LCOATED ON PLANS?? NEW WALLS ETC ARE
 BEING SHOW, HALLWAY, HALL ETC, HOWEVER
 NO LTS FOR MIN FT CANDLE ARE SHOWN.
 PLEASE SEE 7.8.1.3 WHICH REQUIRES A MIN
 OF 10 FT CANDLES UNDER NORMAL CONDITIONS
 ON ALL STAIR AREAS AND 1FT CANDLE UNDER
 EM CONDITIONS.
  
 ** PLEASE SHOW ALL NEW AND EXISTING
 EMERGENCY LT/ EXT LTS AND CIRCUITING PER
 700.12E. THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE NFPA-101 7.8 AND 7.9
 WHICH WILL REQUIRE EM LT FOR EXIT
 DISCHARGE FROM 2ND FLR TO PUBLIC RIGHT
 OF WAY.
  
 4)NOTE: NOTE #4 OK/ NO, PLEASE SEE ONLY
 HALF OF THIS NOTE WAS DONE.
 PLEASE SEE BATH RMS WILL REQUIRE AN EM
 LT BATTERY BACK UP FIXTURE.
 LS 101 7.8,7.9
  
 ** PLEASE SEE A SWITCHED RECEPT IN
 A COMMERICAL OCCUPANCY ISNOT PERMITTED
 AS MEANS OF PROVIDING ILLUMINATION.
 PLEASE PROVIDE A LIGHTING LAYOUT OF
 EITHER EXISTING OR NEW FOR ALL AREAS.
 PLEASE ALSO SEE NEW BATH ROOMS WILL
 REQUIRE EM LTS.
  
 5)NOTE: NOTE #5 OK, LOAD CALCUALTIONS
 ADDED, HOWEVER PLEASE SEE ALL CONTINUOUS
 LOADS ARE REQUIRED TO BE SHOWN AT 125%.
 PLEASE ALSO SEE A/C LOADS WHICH DO NOT
 CORRELATE WITH LOAD CALCS.
 PLEASE KNOW, SERVICE AS SHOWN LOOKS TO
 BE VERY CLOSE IF NOT OVER THE RATING OF
 THE SEC'S OF 350 MCM IN RISER.
 PLEASE ALSO SEE OPTIONS GIVEN UNDER
 220.35.
  
 ** PLEASE PROVIDE LOAD CALCUALTIONS
 FOR NEW LOADS ADDED TO EXSITING PANEL
 AND SERVICE.
 215.5,220.3,220.10,.220.11,220.13 ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125%. 215.3,230.42
  
 6)NOTE: PLEASE PROVIDE SIGNCIRCUIT PER
 600.5
  
 7)NOTE: NOTE #7 OK?NO, NEW OR EXISTING
 RT GFI?
 PLEASE SEE COMMENT FOR LOADS FOR A/C
 UNITS ABOVE.
  
  
 **PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU/RTU'S.125% MIN.
 PLEASE ALSO INDICATE IF NEW OR EXISTING
 GFI'S ARE AT ROOF TOP LOCATION FOR
 EQUIPMENT.
 210.63
  
  
 ** NEW NOTES:
  
 8)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
  
 9)NOTE: PLEASE SEE ATTACHED COPY OF
 FLORIDA STATUES, 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR CODE COMPLIANCE AND
 PLAN REVIEWS.
 PLEASE KNOW, THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
  
  
 PLEASE BE SURE TO SEE ALL COMMENTS FROM
 OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE TO GO OVER
 COMMENS OR QUESTIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-12 Cont ID  
Sent By dpalmer Date 2005-09-12 Time 07:52 Rev Time 1.50
Received By dpalmer Date 2005-09-12 Time 07:52 Sent To  
Notes
2005-09-12 00:00:00*********** UNSAT ************
  
 1)NOTE: PLEASE SEE SERVICE RISERS SHOWN
 INDICATE MORE THAN 6 MAINS FOR BLDG.
 PLEASE SEE THE TWO NEW METERS AND MAINS,
 SHOWN ARE NOT PERMITTED.230.2
  
 2)NOTE: PLEASE SEE REVIEW COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT
 ELECTRICAL PLANS.
 PLEASE SEE POSSIBLE CHANGE IN
 USE/OCCUPANCY INSTENED.
  
 3)NOTE: PLEASE SHOW ALL NEW AND EXISTING
 EMERGENCY LT/ EXT LTS AND CIRCUITING PER
 700.12E. THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE SEE NFPA-101 7.8 AND 7.9
 WHICH WILL REQUIRE EM LT FOR EXIT
 DISCHARGE FROM 2ND FLR TO PUBLIC RIGHT
 OF WAY.
  
 4)NOTE: PLEASE SEE A SWITCHED RECEPT IN
 A COMMERICAL OCCUPANCY ISNOT PERMITTED
 AS MEANS OF PROVIDING ILLUMINATION.
 PLEASE PROVIDE A LIGHTING LAYOUT OF
 EITHER EXISTING OR NEW FOR ALL AREAS.
 PLEASE ALSO SEE NEW BATH ROOMS WILL
 REQUIRE EM LTS.
  
 5)NOTE: PLEASE PROVIDE LOAD CALCUALTIONS
 FOR NEW LOADS ADDED TO EXSITING PANEL
 AND SERVICE.
 215.5,220.3,220.10,.220.11,220.13 ETC
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE
 SHOWN AT 125%. 215.3,230.42
  
 6)NOTE: PLEASE PROVIDE SIGNCIRCUIT PER
 600.5
  
 7)NOTE: PLEASE SEE 424.3B FOR MIN OCP
 FOR AHU/RTU'S.125% MIN.
 PLEASE ALSO INDICATE IF NEW OR EXISTING
 GFI'S ARE AT ROOF TOP LOCATION FOR
 EQUIPMENT.
 210.63
  
 PLEASE BE SURE TO SEE ALL COMMENTS FROM
 OTHER TRADES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-02-16 Cont ID  
Sent By mcarsill Date 2006-02-16 Time 10:06 Rev Time 0.00
Received By mcarsill Date 2006-02-16 Time 09:55 Sent To  
Notes
2006-02-16 00:00:001. EXISTING EMERGENCY LIGHTING EQUIPMENT
 SHALL BE TESTED TO ENSURE PROPER
 FUNCTION.
  
 2. PLANS DO NOT ILLUSTRATE OCCUPANT
 LOADS FOR THE PROPOSED SPACE. CERTAIN
 OCCUPANT LOADS REQUIRE FIRE ALARM OR
 FIRE SPRINKLER SYSTEMS. PLEASE DOCUMENT
 PROPOSED OCCUPANT LOAD FOR THE SPACE.
  
 3. PLANS DO NOT DISPLAY PORTABLE FIRE
 EXTINGUISHER LOCATIONS AS REQUESTED
 PREVIOUSLY BY THIS OFFICE.
  
 4. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 5. DOORS SUBJECT TO OCCUPANT LOADS OF
 100 OR MORE PERSONS SHALL BE EQUIPPED
 WITH PANIC HARDWARE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-05 Cont ID  
Sent By mwennerg Date 2005-10-05 Time 14:44 Rev Time 0.00
Received By mwennerg Date 2005-10-05 Time 14:44 Sent To  
Notes
2005-10-05 00:00:00******DENIED******
  
 1) PLEASE SHOW THE LOCATIONS OF NEW OR
 EXISTING 2A-10B,C RATED FIRE
 EXTINGUISHERS THAT ARE REQUIRED.
  
 2) PLEASE EXPLAIN THE SEATING AREA THAT
 LEADS TO AN EXIT OUTSIDE THE BIRTHDAY
 SITTING ROOM. REQUIRED MEANS OF EGRESS
 SHALL REMAIN CLEAR AT ALL TIMES.
  
 3) THE DOOR TO THE RECEPTION ROOM
 APPEARS TO OBSTRUCT THE MEANS OF EGRESS
 BY GREATER THAN 1/2 THE WIDTH.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-23 Cont ID  
Sent By adarroug Date 2006-01-23 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-01-23 Time 16:12 Sent To  
Notes
2006-02-16 00:00:00TO "COMM" BD#20
2006-01-23 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By lmartine Date 2005-11-21 Time 13:00 Rev Time 0.00
Received By lmartine Date 2005-09-08 Time 07:47 Sent To  
Notes
2005-09-08 00:00:00TO COMM BOARD #61
  
  
2005-09-07 00:00:00TO "BOB" #9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-10-15 Cont ID  
Sent By hmoser Date 2005-10-15 Time 10:55 Rev Time 0.00
Received By hmoser Date 2005-10-15 Time 10:39 Sent To  
Notes
2005-10-15 00:00:00PLEASE HAVE MECHANICAL CONTRACTOR PULL
 PERMIT FOR BATHROOM EXHAUST.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-15 Cont ID  
Sent By kstevens Date 2006-03-15 Time 10:28 Rev Time 0.00
Received By kstevens Date 2006-03-15 Time 10:28 Sent To  
Notes
2006-03-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 1. SHT 1 MINIMUM PLUMBING FACILITIES
 SHALL BE PER TABLES 1003.1 AND TABLE
 403.1. THIS IS ADDRESSED BY SQUARE
 FOOTAGE OF SPACE. PLEASE INDICATE THE
 SQUARE FOOTAGE OF THE SPACE BEING
 ALTERED.- OCCUPANCY IS SHOWN AS GROUP
 A ASSEMBLY.
 2. SHT 1 TOILET ROOMS SHALL COMPLY WITH
 SECTION 11-4.22 AND ALL SUBSECTIONS.
 DOORS SHALL COMPLY WITH 11-4.13,
 CLEAR FLOOR SPACE FOR ALL ACCESSIBLE
 FIXTURES REQUIRED. 11-4.22.3 - (SHOW ON
 FLOOR PLAN)
 TURNING AREA REQUIRED IN EACH TOILET
 ROOM. 11-4.22.3 - (SHOW ON FLOOR PLAN)
 IF TOILET STALLS ARE PROVIDED, AT LEAST
 ONE STALL SHALL COMPLY WITH FIGURE 30E.
 A LAV IS REQUIRED IN THE STALL
 IF URINALS ARE PROVIDED, THEN ONE SHALL
 BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 COMLIANCE WITH SECTION 11-4.18 AND ALL
 SUBSECTIONS.
 LAVS SHALL COMPLY WITH 11-4.19 AND ALL
 SUBSECTIONS.
  
 ****************NEW COMMENTS************
  
 1B. A DRINKING FOUNTAIN IS REQUIRED PER
 TABLE 403.1. PLEASE INDICATE LOCATION
 AND SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH 11-4.15 AND ALL SUBSECTIONS. IF NOT
 A HI/LOW, ALSO SHOW COMPLIANCE WITH
 SECTION 11-4..1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 2B. AS OF JANUARY 01, 2006 ENGINEERS
 SHALL US THE NEW TYPE SEAL REQUIRED BY
 FLORIDA DEPT OF PROFESSIONAL ENGINEERS.
 (SEE ATTACHED SHEET). ALL SHEETS SEALED
 AFTER ABOVE DATE WILL BE REQUIRED TO BE
 SEALED WITH NEW TYPE SEAL.
 3B.A SERVICE SINK IS REQUIRED PER TABLE
 403.1. SHOW THE LOCATION ON THE FLOOR
 PLAN.
 4B. SHOW THE LOCATION OF THE WATER
 HEATER. SECTION 104.2.1.
 5B. SHT 2 WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. NO WATER IS
 SHOWN FOR THE UNINALS. SECTION 104.2.1.
 6B. SHT 2 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. ONLY ONE URINAL
 IS SHOWN ON THE RISER DIAGRAM.- INDICATE
 WHAT THE SANT. LINE BETWEEN THE WATER
 CLOSETS CONNECTS TO IN MENS TOILET ROOM
 AND WHAT THE SANT. LINE UPSTREAM OF THE
 WATER CLOSETS IN THE WOMENS TOILET ROOM
 CONNECTS TO. SECTION 104.2.1.
 7B. WATER HEATER REQUIRES THERMAL
 EXPANSION CONTROL. SECTION 607.3.2.
 8B. SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) AND THE DESIGN
 PROFESSIONAL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-22 Cont ID  
Sent By pschmitz Date 2005-10-22 Time 10:12 Rev Time 0.00
Received By pschmitz Date 2005-10-22 Time 10:12 Sent To  
Notes
2005-10-22 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW.
 DENIED
 1) SHT-1
 SECTION P403
 MINIMUM PLUMBING FACILITIES
 ?P403.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED
 FOR THE TYPE OF OCCUPANCY AND IN THE
 MINIMUM NUMBER SHOWN IN TABLE P403.1.
 TYPES OF OCCUPANCIES NOT SHOWN IN TABLE
 P403.1 SHALL BE CONSIDERED
 INDIVIDUALLY BY THE CODE OFFICIAL.THE
 NUMBER OF OCCUPANTS SHALL BE
 DETERMINED BY THE BUILDING CODE.
 OCCUPANCY CLASSIFICATION SHALL BE
 DETERMINED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2)?11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH
 ?11-4.13.DOORS SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE REQUIRED FOR ANY
 FIXTURE.
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH 11-4.2.3
 SHALL BE PROVIDED WITHIN AN ACCESSIBLE
 TOILET ROOM.THE CLEAR FLOOR SPACE AT
 FIXTURES AND CONTROLS, THE ACCESSIBLE
 ROUTE, AND THE TURNINGSPACE MAY
 OVERLAP.
 ?11-4.22.4 WATER CLOSETS. IF TOILET
 STALLS ARE PROVIDED, THEN AT LEAST
 ONE SHALL BE A STANDARD TOILET STALL
 COMPLYING WITH ?11-4.17; WHERE 6 OR
 MORE STALLS ARE PROVIDED, IN ADDITION
 TO THE STALL COMPLYING WITH
 ?11-4.17.3, AT LEAST ONE STALL 36 IN
 (915 MM) WIDE WITH AN OUTWARD
 SWINGING, SELF-CLOSING DOOR AND
 PARALLEL GRAB BARS COMPLYING WITH
 FIGURE 11-30(D) AND ?11-4.26 SHALL BE
 PROVIDED.WATER CLOSETS IN
 SUCH STALLS SHALL COMPLY WITH
 ?11-4.16.IF WATER CLOSETS ARE NOT IN
 STALLS, THEN AT LEAST ONE SHALL COMPLY
 WITH ?11-4.16.
 ?11-4.22.5 URINALS. IF URINALS ARE
 PROVIDED, THEN AT LEAST ONE SHALL
 COMPLY WITH ?11-4.18.
 ?11-4.22.6 LAVATORIES AND MIRRORS. IF
 LAVATORIES AND MIRRORS ARE
 PROVIDED, THEN AT LEAST ONE OF EACH
 SHALL COMPLY WITH ?11-4.19.
 ?11-4.22.7 CONTROLS AND DISPENSERS. IF
 CONTROLS, DISPENSERS, RECEPTACLES, OR
 OTHER EQUIPMENT ARE PROVIDED, THEN AT
 LEAST ONE OF EACH SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL COMPLY WITH
 ?11-4.27.
 3) PROVIDE A DETAIL SHT SHOWING
 ELEVATIONS,DIMENSIONS AND CLEAR FLOOR
 SPACE FOR ALL FIXTURES.
 END OF COMMENTS QUESTIONS 561-805-6692
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By lmartine Date 2005-11-21 Time 12:48 Rev Time 0.00
Received By lmartine Date 2005-11-21 Time 12:48 Sent To  
Notes
2005-11-21 00:00:00REVIEW IS NOT REQUIRED PER SHIRLY GRAHM


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved