| 2006-03-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)THIS RENOVATION INVOLVES A CHANGE |
| | OF OCCUPANCY, SEE FBC106.1.1, |
| | FBC106.4.1. |
| | |
| | 3.)PROVIDE INFORMATION IN REGARDS TO |
| | THE BUILDING; TOTAL AREA, BUILDING TYPE |
| | FBC CHAPTER 6, PROTECTED OR UNPROTECTED, |
| | SPRINKLED OR UNSPRINKLED. |
| | |
| | PROVIDE A LETTER FROM THE ENGINEER, ON |
| | ENGINEER'S LETTERHEAD, AS TO |
| | HOW YOU HAVE ARRIVED AT THE TOTAL SF |
| | AREA.SEE FBC CHAPTER 2, DEFINITIONS. |
| | PROVIDE AREA CALCULATIONS BROKEN DOWN BY |
| | FLOOR.SHOW TOTAL SF OF A/C AREA AND |
| | AREA UNDER THE BALCONY.THE LETTER IS |
| | TO DECLARE BUILDING SIZE, HEIGHT, TYPE |
| | FBC600, AND SHOW COMPLIANCE WITH FBC |
| | TABLE 500.PROVIDE A COPY OF THE |
| | SURVEY. |
| | |
| | 4. - 5.)ADDRESSED. |
| | |
| | 6.)PROVIDE A SITE PLAN SHOWING THE |
| | BUILDING'S LOCATION ON THE LOT AND THE |
| | ACCESSIBLE ROUTE, FBC11-4.1.2. |
| | |
| | NOT ADDRESSED PROPERLY.A SITE PLAN WAS |
| | PROVIDED BUT DOES NOT SHOW ACCESSIBLE |
| | ROUTE.SHOW REQUIRED INFORMATION, |
| | INCLUDING ACCESSIBLE PARKING.THE |
| | ACCESSIBLE PARKING SPACE DOES NOT COMPLY |
| | WITH FBC11-4.6.2 THROUGH 11-4.6.5.ALSO |
| | SEE ATTACHED FOR DETAIL FOR CITY OF WPB |
| | STANDARD FOR PARKING. |
| | |
| | 7.)DECLARE AN OCCUPANT LOAD FOR THIS |
| | AREA, FBC1003.1, FBC TABLE 1003.1. |
| | |
| | NOT ADDRESSED.15 PER SF IS NOT AN |
| | OCCUPANT LOAD.DECLARE OCCUPANT LOAD; |
| | SHOULD BE A TOTAL NUMBER. |
| | |
| | 8.)SHOW REQUIRED OCCUPANCY AND/OR |
| | TENANT SEPARATIONS.PROVIDE A LISTED |
| | ASSEMBLY OR CALCULATED FIRE RESISTANCE |
| | FBC709. |
| | |
| | NO RATED ASSEMBLIES SHOWN.FIRE |
| | RESISTANCE BETWEEN FIRST AND SECOND |
| | FLOORS NOT SHOWN. |
| | |
| | 9.)PROVIDE A CERTIFICATION FOR THE |
| | FLOOR LOADING FOR THIS OCCUPANCY, FBC |
| | TABLE1604.1.INCLUDE THE BALCONY. |
| | PROVIDE DETAILS. |
| | |
| | NOT ADDRESSED PROPERLY. A STATEMENT WAS |
| | ON THE PLAN BUT NO INFORMATION PROVIDED |
| | FOR THE BALCONY. |
| | |
| | 10.)PROVIDE ELEVATIONS SO THAT CODE |
| | COMPLIANCE IN REGARDS TO THE LARGE |
| | WINDOWS AND THE EXIT STAIR CAN BE |
| | DETERMINED. |
| | |
| | EXTERIOR STAIRS ARE TO COMPLY WITH |
| | FBC1006.2.2.THE STAIRS SHOWN ARE NOT |
| | ROOFED OVER. |
| | |
| | OPENINGS ARE TO COMPLY WITH FBC1006.2.4. |
| | SHOW REQUIREMENTS AND COMPLIANCE ON THE |
| | PLAN. |
| | |
| | 11.)SEE FBC2405.IS SAFETY GLASS |
| | REQUIRED? |
| | |
| | NOT ADDRESSED.TEMEPERED GLASS IS SHOWN |
| | FOR THE FIRST FLOOR, WHAT ABOUT THE |
| | RENOVATION AREA WHICH IS ON THE SECOND |
| | FLOOR? |
| | |
| | 12.)PROVIDE A LIFE SAFETY PLAN.SHOW |
| | ALL EXIT LIGHTS.NOT ENOUGH INFORMATION |
| | WAS PROVIDED TO DETERMINE CODE |
| | COMPLIANCE.PLEASE REACH FBC CHAPTER 10 |
| | AND SHOW COMPLIANCE ON THE PLAN.SEE |
| | ALSO FBC11-4.1.3(9). |
| | |
| | NOT ADDRESSED, NO LIFE SAFETY PLAN |
| | PROVIDED.EXITING IS NOT CLEAR.THE |
| | PLAY AREA SHOWS AN EXIT AT THE DOUBLE |
| | DOOR, BUT THE TRAVEL DISTANCE TO THE |
| | STAIR EXCEEDS 150FT AND THAT STAIR |
| | CANNOT BE USED AS A MEANS OF EGRESS IF |
| | IT IS NOT COMPLIANT AS AN EXTERIOR |
| | STAIR.IT SHOULD HAVE TWO EXITS, ONLY |
| | ONE NON COMPLIANT EXIT SHOWN.PROVIDE A |
| | LIFE SAFETY AS REQUESTED. |
| | |
| | 13.)PROVIDE DETAILS AND DESIGN |
| | CRITERIA FOR BOTH STAIRS AND THE HAND |
| | RAILS AND STAIR GUARDRAILS, FBC1007 , |
| | FBC11-4.9,FBC1015, FBC1608, |
| | FBC11-4.26. |
| | |
| | THE STAIR RAIL WHICH SERVES AS A |
| | GUARDRAIL DOES NOT COMPLY WITH FBC1015.2 |
| | (HEIGHT).THE EXTENSIONS REQUIRED AT |
| | THE BOTTOM ARE NOT SHOWN.HANDRAILS |
| | REQUIRED ON BOTH SIDES, PROVIDE A |
| | DETAIL.PICKET SPACING NOT SHOWN. |
| | STRENGTH FOR HANDRAILS WAS PROVIDED BUT |
| | NOT FOR GUARDRAILS. |
| | |
| | 14.)PROVIDE A DETAIL AND DESIGN |
| | CRITERIA FOR THE BALCONY GUARDRAIL. |
| | FBC1007, FBC1608. |
| | |
| | NOT ADDRESSED. |
| | |
| | 15.)FIRE RATING IS NOT SHOWN BETWEEN |
| | THE HALL AND THE RECEPTION AREA.THIS |
| | APPEARS TO BE COMMON AREA, SEPARATION |
| | REQUIRED. |
| | |
| | 16.)IF THE WALL BETWEEN THE RECEPTION |
| | AND HALL IS TO BE RATED, A FIRE RATED |
| | DOOR REQUIRED FBC TABLE 705.1.2. |
| | |
| | NOT ADDRESSED, ONLY SHOWN AS "EXISTING". |
| | |
| | 17.)IF THIS BUILDING IS NOT FULLY |
| | SPRINKLED, AREA OF RESCUE ASSISTANCE |
| | REQUIRED, FBC11-4.1.3(9).IF THIS |
| | BUILDING IS FULLY SPRINKLED, INDICATE |
| | AND PROVIDE A SPRINKLER PLAN. |
| | |
| | THE AREA OF RESCUE ASSISTANCE IS TO |
| | COMPLY WITH FBC11-4.3.11.IT IS NOT |
| | CLEAR HOW AN AREA WITH THREE WALLS, OPEN |
| | TO THE SPACE, IS AN AREA OF RESCUE |
| | ASSISTANCE.TWO REQUIRED. |
| | |
| | 18.)THE SEATING AREA BLOCKS THE |
| | REQUIRED EGRESS WIDTH OF THE HALLWAY. |
| | SEE FBC TABLE 1004. |
| | |
| | NOT ADDRESSED.SEATING AREA STILL SHOWN |
| | IN THE HALLWAY. |
| | |
| | 19.)ADDRESSED. |
| | |
| | 20.)ADDRESSED. |
| | |
| | 21.)ADDRESSED. |
| | |
| | 22.)PROVIDE A DETAIL FOR THE |
| | ACCESSIBLE BATHROOMS.INCLUDE ALL |
| | DIMENSIONS AND SHOW CLEAR FLOOR SPACE |
| | FOR FIXTURES.NO DETAILS WERE PROVIDED; |
| | CODE COMPLIANCE CANNOT BE DETERMINED. |
| | SEE FBC CHAPTER 11. |
| | |
| | SHOW DISTANCE FROM CL OF WATER CLOSET TO |
| | THE WALL, FBC11 FIGURE 30.SHOW CLEAR |
| | FLOOR SPACE AND TURNING RADIUS ON THE |
| | FLOOR PLAN. |
| | |
| | 23.)SIGNAGE FOR THE ELEVATOR IS TO BE |
| | COMPLIANT WITH FBC11-4.10. |
| | |
| | PLANS ARE TO SHOW CODE COMPLIANT.A |
| | STATEMENT THAT THE ELEVATOR CONTRACTOR |
| | IS RESPONSIBLE FOR SIGNAGE IS NOT |
| | SHOWING DESIGN CRITERIA OR CODE |
| | COMPLIANCE. |
| | |
| | 24.)SHOW COMPLIANCE WITH FBC11-4.13.7, |
| | FBC FIGURE 11-26(A). |
| | |
| | NOT ADDRESSED.PROVIDE THE REQUIRED |
| | DIMENSION ON THE PLAN. |
| | |
| | 25.)THE APPLICATION STATES THAT |
| | INTERIOR STAIRS ARE TO BE CLOSED OFF. |
| | PROVIDE A LOCATION AND A DETAIL.WILL |
| | IT BE CLOSED OFF BOTH UPSTAIRS AND |
| | DOWNSTAIRS? |
| | |
| | PLANS NOW SHOW THE DETAIL AND SCOPE OF |
| | WORK IS CLEAR, BUT NON COMPLIANT. |
| | |
| | 26.)PLEASE NOTE THAT IT WOULD BE |
| | REASONABLE TO ANTICIPATE THAT A THIRD |
| | PLAN REVIEW WILL BE NECESSARY AS MANY |
| | ITEMS ARE NOT CODE COMPLIANT AND THERE |
| | IS INSUFFICIENT INFORMATION ON THE PLAN |
| | TO DEVELOP A COMPLETE CORRECTION LIST. |
| | |
| | 27.)A COPY OF THE PLANS HAS BEEN |
| | RETAINED. |
| | |
| | A COPY OF THIS PLAN HAS ALSO BEEN |
| | RETAINED AND WILL BE FORWARDED TO FBPE. |
| | |
| | NEW COMMENTS: |
| | |
| | 28.)A DETAIL HAS BEEN PROVIDED FOR A |
| | NEW SECTION OF FLOORING WHICH USES |
| | COMBUSTIBLE MATERIALS.THIS IS NOT |
| | PERMITTED IN A TYPE IV. |
| | |
| | 29.)THE ENGINEER'S SEAL IS TO STATE |
| | "LICENSE" RATHER THAN "CERTIFICATE" |
| | EFFECTIVE 1/1/2006, FAC61G15-23.002(1). |
| | |
| | 30.)PROVIDE INTERIOR FINISH |
| | CLASSIFICATION FBC TABLE 803.3. |
| | |
| | 31.)PROVIDE A REASONABLE VALUE FOR THE |
| | SCOPE OF WORK, OR AN ESTIMATE WILL BE |
| | DONE FOR YOU USING MARSHALL & SWIFT. |
| | |
| | 32.)WHEN RESUBMITTING, INCLUDE A |
| | RESPONSE LETTER ON THE ENGINEER'S |
| | LETTERHEAD INDICATING HOW EACH ITEM HAS |
| | BEEN ADDRESSED. |
| | |
| | 33.)PROVIDE A COMPLETE DESCRIPTION OF |
| | THE ACTIVITY FOR EACH ROOM SO THAT |
| | OCCUPANCY AND OCCUPANT LOAD CAN BE |
| | PROPERLY DETERMINED. |
| | |
| | 34.)PROVIDE A DETAIL FOR THE BAR TO |
| | COMPLY WITH ALL REQUIREMENTS OF |
| | FBC11-5.2. |
| | |
| | 35.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF |
| | COMMENTS NOT PROPERLY ADDRSSED. |