Plan Review Details - Permit 05090156
Plan Review Stops For Permit 05090156
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-23 Cont ID  
Sent By lursu Date 2006-05-23 Time 13:50 Rev Time 0.00
Received By lursu Date 2006-05-23 Time 13:50 Sent To  
Notes
2006-05-23 00:00:00TALKED TO THE CONTRACTOR: TOWN & COUNTRY
 BUILDERS ,MELANIE
 MCDONALD@364-3302,PLANS HAVE THREE
 ADDRESSES BEACUSE THEY WERE SUBMITTED
 BEFORE RELEASING ALL NEW SITE
 ADDRESSES,PERMIT IS BEING APPLIED FRO
 THE CONDO 4545 MARAVILLA WAY ( THE NORTH
 SIDE STRUCTURE OF THE PROJECT).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-22 Cont ID  
Sent By rmcdouga Date 2006-05-22 Time 13:11 Rev Time 0.00
Received By rmcdouga Date 2006-05-22 Time 13:11 Sent To  
Notes
2006-05-22 00:00:00PERMIT NUMBER: 05090156
 ADDRESS: 3701 N MILITARY TRAIL
 CONTRACTOR: TOWN AND COUNTRY HOMES
 FOUR STORY R2 WITH PARKING GARAGE
 TYPE II SPRINKLERED (13R SYSTEM)
 CODE EDITION: 2001 FBC
 SECOND REVIEW
 ---------------------------------------
 DENIED
  
  
 1)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 2) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
 RECORDED COPY OF CONDOMINIUM DOCUMENTS
 RECEIVED.
  
 3) ALL THREE (3) COPIES OF THE
 SUBSURFACE SOIL REPORTS, OTHER REPORTS,
 CALCULATIONS AND DRAWINGS PREPARED BY A
 FLORIDA REGISTERED ARCHITECT OR ENGINEER
 ARE REQUIRED TO BE SIGNED AND SEALED.
  
 4) SUBMIT (3) SETS OF ENGINEERED LAYOUTS
 AND TRUSS DRAWINGS FOR THE METAL TRUSSES
 THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 5) REVISED DETAILS #9 THRU #13 ON SHEET
 A-8.3.1 AND #2, #4 ON A-8.3.2 SPECIFY
 WOOD TRUSSES AND DO NOT SPECIFY FIRE
 TREATED PLYWOOD. THIS STRUCTURE IS
 SPECIFIED AS TYPE II CONSTRUCTION AND
 DOES NOT ALLOW COMBUSTIBLE MATERIALS AT
 THIS LOCATION. PLEASE CORRECT.
  
 6) SPECIFY THE ATTACHMENT SPACING AND
 FASTENERS FOR THE FIRETREATED PLYWOOD
 SHEATHING TO THE METAL TRUSSES.
  
 7) SUBMIT (3) SETS OF ENGINEERED SHOP
 DRAWINGS AND LAYOUTS FOR THE PRECAST
 SYSTEM FOR THE PARKING GARAGE.(PRIOR TO
 CONSTRUCTION)
  
 8) THE CORRIDOR BETWEEN THE FITNESS
 CENTER AND THE BATH ROOMS IS A DEAD END
 HALLWAY THAT EXCEEDS TWENTY FEET IN
 LENGTH WHICH IS PROHIBITED BY FBC
 1005.2.
  
 9) 2001 FBC 903.7.6 REQUIRES GROUP R2
 OCCUPANCIES THREE OR MORE STORIES IN
 HEIGHT TO BE PROVIDED THROUGHOUT WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM.
 EXCEPTION (2) ALLOWS AN AUTOMATIC
 SPRINKLER SYSTEM COMPLYING WITH NFPA 13R
 FOR BUILDINGS NOT EXCEEDING FOUR STORIES
 IN HEIGHT PROVIDED THE AUTOMATIC
 SPRINKLER SYSTEM SHALL NOT BE CONSIDERED
 AS AN ALTERNATE TO OTHER REQUIREMENTS OF
 THE CODE. (SEE 903.2) FBC 903.2 STATES
 THAT AUTOMATIC SPRINKLER SYSTEMS
 INSTALLED IN LIEU OF OR AS AN ALTERNATE
 TO OTHER REQUIREMENTS, AS PERMITTED BY
 THIS CODE, SHALL BE CONSIDERED REQUIRED
 SYSTEMS AND SHALL COMPLY WITH NFPA 13.
 THIS MEANS THAT IN ORDER TO APPLY THE
 REDUCTION IN CORRIDOR FIRE RATING
 ALLOWED BY TABLE 704.2.4 TO 1/2 HOUR FOR
 FULLY SPRINKLERED BUILDINGS OR THE
 INCREASED TRAVEL DISTANCE OF 325' IN
 TABLE 1004 FOR SPRINKLERED BUILDINGS AN
 NFPA 13 SPRINKLER SYSTEM IS REQUIRED.
  
 10) THE BILLARD ROOM IS AN ASSEMBLY
 OCCUPANCY WHICH REQUIRES A TWO HOUR
 TENANT FIRE SEPARATION. SEE FBC 704.1.1
 HOWEVER, FBC 704.1.2.3 ALLOWS A ONE HOUR
 OCCUPANCY SEPARATION.
  
 11) ALL FIRE RATED DOORS ARE REQUIRED TO
 HAVE APPROVED CLOSERS OR BE SELF
 CLOSING. SPECIFY CLOSERS FOR ALL RATED
 DOORS PER FBC 705.1.3.2.3. SPECIFY IN
 THE DOOR SCHEDULE ON A4.0.8 THAT DOOR #4
 IS REQUIRED TO HAVE APPROVED CLOSERS.
  
 12) A VERTICAL SECTION THROUGH THE TRASH
 CHUTE IS INDICATED AS 5 ON A4.0.10 THIS
 IS INCORRECT AS IT IS LOCATED ON DETAIL
 5 ON A4.0.10. PLEASE CORRECT.
  
 13) THE TRASH CHUTE SECTION SHOWN ON
 SHEET A8.1.4 IS INCORRECTLY LABELED AS 4
 ON A4.0.7. PLEASE CORRECT.
  
 14) PLEASE REVISE NEW NOTES ON A8.2.1
 AND A8.2.2 WHICH REFER TO THE HIGH
 VELOCITY HURRICANE ZONES AS REQUIRING
 IMPACT PROTECTION. THE CITY OF WEST PALM
 BEACH IS NOT IN THE HIGH VELOCITY
 HURRICANE ZONE, HOWEVER, WE ARE LOCATED
 IN THE WIND BOURNE DEBRIS REGION AND
 BECAUSE OF THIS MISSILE IMPACT
 PROTECTION OF EXTERIOR GLAZING IS
 REQUIRED. SEE 2001 FBC 1606.1.4.
  
 15) SUBMIT THE MANUFACTURER'S
 SPECS.(LISTING) AND PRODUCT APPROVALS
 FOR THE FIRE RATED GLASS BLOCK.
  
 16) THE INTERNAL PRESSURE COEFFICENT ON
 SHEET S7 IS POSITIVE AND NEGATIVE + OR
 -0.18. PLEASE CORRECT.
  
 17) MANY OF THE FULL LOUVERED DOORS ARE
 LOCATED IN FIRE RATED WALLS AND OPEN
 ONTO THE EGRESS CORRIDORS. THESE DOORS
 ARE REQUIRED TO BE FIRE RATED. I DO NOT
 BELIEVE THAT THERE ARE ANY FIRE RATED
 FULL LOUVERED DOORS AVAILABLE. SUBMIT
 MANUFACTURER'S SPECS. AND LISTING FOR
 THE DOORS YOU WILL BE USING.
  
 18) THE PRODCUCT APPROVALS SUBMITTED FOR
 THE FULL LOUVERED DOORS REQUIRES A
 HURRICANE PROTECTION SYSTEM FOR THEM.
 SUBMIT A STATE PRODUCT APPROVAL, A KEY
 PLAN, AN INSTALLATION SCHEDULE AND A
 PRESTORM PREPARATION PLAN FOR BUILDING
 OFFICAL APPROVAL FOR THE STORM PANELS
 FOR THESE DOORS.
  
 19) SPECIFY THE LOCATIONS WHERE THE
 THERMA-TRU/ BENCHMARK DOORS WILL BE
 INSTALLED. THESE DOORS DO NOT HAVE A
 FIRE RATING.
  
 20) SUBMIT STATE PRODUCT APPROVALS FOR
 THE ROOFING MATERIAL THAT WILL BE USED
 ON THE FLAT ROOF AREAS OF THE BUILDING.
 INDICATE THE SYSTEM LISTED IN THE
 PRODUCT APPROVAL THAT WILL BE USED. MAKE
 SURE THAT THE DESIGN PRESSURES FOR THE
 SELECTED PRODUCT ARE ADEQUATE.
  
 21) THE WINDOWS (E) LOCATED IN THE ONE
 HOUR FIRE RATED PARTIONS ON SHEET A4.0.8
 ARE REQUIRED TO BE 45 MIN. FIRE
 PROTECTION RATED PER FBC 705.1.3.6.2.
 THE SCHEDULE LISTS 20 MIN. RATED. PLEASE
 CORRECT.
  
 22)A SEPARATE PERMIT WILL BE REQUIRED
 FOR SITE AMENITIES. A SITE PLAN SHOWING
 ACCESSIBLE ROUTES TO ALL BUILDINGS,
 AMENITIES, PARKING AND TO THE PUBLIC WAY
 AS REQUIRED BY FBC 11-4.1.2, THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES AND
 ANSI 4.3. SHOW CURB RAMPS, SIDE WALK
 WIDTHS, SIGNAGE, DETECTABLE WARNINGS,
 CROSSWALKS,ETC. DETAILS OF THE COMMON
 TRASH PICK-UP AREA, GAZEBOS AND TOT LOT
 MUST SHOW COMPLIANCE WITH ADA
 REQUIREMENTS.
  
 23) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 24) ADDITIONAL COMMENTS MAY RESULT FROM
 RESPONSES TO THESE ISSUES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-10 Cont ID  
Sent By rmcdouga Date 2006-01-10 Time 08:17 Rev Time 0.00
Received By rmcdouga Date 2006-01-05 Time 13:37 Sent To  
Notes
2006-01-06 00:00:00PERMIT NUMBER: 05090156
 ADDRESS: 3701 N MILITARY TRAIL
 CONTRACTOR: TOWN AND COUNTRY HOMES
 FOUR STORY R2 WITH PARKING GARAGE
 TYPE II SPRINKLERED
 CODE EDITION: 2001 FBC
 ---------------------------------------
 DENIED
  
 1) STRUCTURE IS A THRESHOLD BUILDING PER
 FLORIDA STATUES FS 553.71.
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 2)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 3)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 4) CONDOMINIUM V APARTMENTS.IF THE
 DWELLING UNITS ARE TO BE SOLD AS
 CONDOMINIUMS, A 'DECLARATION OF
 CONDOMINIUM' SHALL BE SUBMITTED TO THE
 STATE FOR APPROVAL, AND THEN RECORDED
 WITH THE CLERK OF THE COUNTY COURT.A
 RECORDED COPY SHALL BE SUBMITTED TO THE
 CITY FOR RECORDS, ADDRESSING PURPOSES,
 AND TO PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE PRIOR TO C.O.
  
 5 ) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL. REQUIRES 3,00O PSF.
  
 6) THREE (3) COMPLETE SETS OF PLANS,
 SPECIFICATIONS AND DOCUMENTS ARE
 REQUIRED FOR THRESHOLD BUILDINGS.
  
 7) SUBMIT (3) SETS OF ENGINEERED LAYOUTS
 AND TRUSS DRAWINGS FOR THE METAL TRUSSES
 THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 8) SPECIFY THE ATTACHMENT SPACING AND
 FASTENERS FOR THE FIRETREATED PLYWOOD
 SHEATHING ON THE METAL TRUSSES.
  
 9) THE ALPINE TSUC3 TRUSS CONNECTORS
 SPECIFIED FOR THE METAL TRUSSES ON S10
 AND S11 DO NOT HAVE STATE PRODUCT
 APPROVAL. SPECIFY TRUSS CONNECTORS WITH
 CURRENT STATE OF FLORIDA PRODUCT
 APPROVALS PER F.A.C. RULE 9B-72. SUBMIT
 PRODUCT APPROVALS WITH STATE COVERSHEET
 FOR THE TRUSS CONNECTORS.
  
 10) SPECIFY THE ATTACHMENT METHOD THAT
 WILL BE USED TO ATTACH THE CEMENT ROOF
 TILES AND RESIST THE REQUIRED UPLIFT
 MOMENT.
  
 11) REVISE THE ROOF RIDGE DETAIL #11 ON
 A8.3.1. WHICH DOES NOT MEET THE REQUIRED
 UPLIFT MOMENT.
  
 12) SUBMIT (3) SETS OF ENGINEERED SHOP
 DRAWINGS AND LAYOUTS FOR THE PRECAST
 SYSTEM FOR THE PARKING GARAGE.
  
 13) THE WALLS SEPARATING THE EXTERIOR
 EXIT STAIRS FROM THE INTERIOR OF THE
 BUILDING ARE REQUIRED TO HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN ONE
 HOUR PER FBC 1006.2.4.
  
 14) ELEVATORS #2 AND #4 ARE NOT LABELED
 ON SHEETS A 2.0.2 AND A 2.0.4.
  
 15) REFUSE CHUTES ARE REQUIRED HAVE A
 TWO (2) HOUR FIRE RESISTANCE RATING WITH
 ONE AND A HALF HOUR FIRE RATED OPENING
 PROTECTIVES PER FBC TABLE 705.1.2.
 DETAIL 5 ON A 4.0.10 SPECIFIES ONLY A
 ONE HOUR SHAFT WALL AND DOES NOT SPECIFY
 THAT THE DOOR HAS TO BE SELF-CLOSING AND
 1-1/2 HOUR FIRE RATED. SEE FBC 705.2.4.2
  
  
 16) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTING FOR THE SELF-CLOSING FIRE RATED
 DOORS TO THE REFUSE CHUTE SHAFT AND THE
 OPENING PROTECTIVE BETWEEN THE SHAFT AND
 THE TERMINATION ROOM.
  
 17) IN REGUARD TO FIRE RESISTANCE OF
 RESIDENTIAL CORRIDOR WALLS ON SHEET
 A1.3.1, FBC TABLE 704.2.4 ALLOWS 1/2
 HOUR RATED WALLS WHEN THE BUILDING IS
 SPRINKLERED. FBC TABLE 1004 ALLOWS THE
 TRAVEL DISTANCE TO BE INCREASED TO 325
 FT. FOR SPRINKLERED BUILDINGS. HOWEVER,
 FBC 903.2 STATES THAT SPRINKLERS
 INSTALLED IN LIEU OF OR AS AN ALTERNATE
 TO OTHER REQUIREMENTS OF THE CODE SHALL
 BE CONSIDERED REQUIRED SYSTEMS AND SHALL
 COMPLY WITH NFPA. THEREFORE, THE ENTIRE
 BUILDING SHALL COMPLY WITH NFPA 13 AND
 THE EXCEPTION TO FBC 903.7.6 WHICH
 ALLOWS AN NFPA 13R IN R2 OCCUPANCIES CAN
 NOT BE USED. SPECIFY THAT SPRINKLER
 SYSTEM IS NFPA 13.
  
 18) SHEET A1.3.1 ALSO INDICATES THAT
 OPENING PROTECTIVES ARE NOT REQUIRED AT
 THE RESIDENTIAL CORRIDOR WALLS BASED ON
 FBC 1014.1.1, 1006.2.2 AND 1006.2.4. FBC
 1014.1.1 REQUIES AT LEAST 50 PERCENT OF
 THE BALCONY, GALLERY OR SIMILAR SPACE TO
 BE OPEN ON THE LONG SIDE. THIS DOES NOT
 APPEAR TO BE APPLICABLE TO THESE PLANS.
 THEREFORE, WINDOW AND DOOR OPENING
 PROTECTIVES WILL BE REQUIRED AT THE EXIT
 ACCESS CORRIDORS. THIS ALSO WILL APPLY
 TO STORE FRONTS FOR THE REC. AREA AT THE
 COVERED EXPANSION.
  
 19) PROVIDE A LIFE SAFETY PLAN FOR THE
 POOL AND DECK AREA. SPECIFY OCCUPANT
 LOADS AND EXITS.
  
 20) NO DIMENSIONS ARE GIVEN ON THE REC.
 AREA FLOOR PLAN.
  
 21) THE OCCUPANT LOAD OF THE CARD ROOM
 AND FITNESS CENTER EXCEEDS 50 PERSONS,
 THEREFORE, THEY ARE CONSIDERED SMALL
 ASSEMBLY OCCUPANCIES REQUIRING TWO HOUR
 TENANT SEPARATIONS. SEE FBC 304.1.1,
 704.1.1
  
 22) THE DOUBLE DOORS (#6) FROM THE
 MULIPURPOSE ROOM TO THE ONE HOUR FIRE
 RATED ACCESS CORRIDOR ARE REQUIRED TO
 HAVE A 20 MINUTE FIRE RATING AND BE SELF
 CLOSING. SEE FBC 705.1.3.2.3 AND
 705.1.3.2.2
  
 23) THERE IS AN EXIT LIGHT THAT IS
 LOCATED IN THE LOCKER ROOM AT A LOCATION
 WHERE THERE IS NO EXIT. SEE SHEETS
 E1.2.2 AND E2.1.1
  
 24) DOOR #3 ON A4.0.8 IS SPECIFIED AS A
 DOUBLE 3'X 8' DOOR ON THE SCHEDULE BUT
 IS SHOWN AS A SINGLE DOOR ON THE PLANS.
  
 25) ALL FIRE RATED DOORS ARE REQUIRED TO
 HAVE APPROVED CLOSERS OR BE SELF
 CLOSING. SPECIFY CLOSERS FOR ALL RATED
 DOORS PER FBC 705.1.3.2.3.
  
 26) SPECIFY THE AMOUNT AND TYPE OF
 CHEMICALS THAT WILL BE STORED IN THE
 POOL EQUIPMENT ROOM. SPECIFY OCCUPANCY
 SEPARATION FOR STORAGE OF HAZARDOUS
 MATERIALS. SEE FBC 308 AND 704.
  
 27) NO TENANT SEPARATION IS SPECIFIED
 BETWEEN THAT POOL STORAGE ROOM AND THE
 MAIN ELECTRICAL ROOM ON SHEET A4.0.9.
 SPECIFY THE AMOUNT AND TYPE OF POOL
 CHEMICALS THAT WILL BE STORED.
  
 28) THE SECTION THROUGH THE TRASH ROOM
 IS MISSING THE ID TAG.
  
 29) FBC 707.1 DOES NOT ALLOW
 COMBUSTIBLES IN CONCEALED SPACES OF
 PARTITIONS OF TYPE II CONSTRUCTION.
 SPECIFY THAT BACKING MUST BE
 NON-COMBUSTIBLE OR FIRE RETARDANT
 TREATED WOOD.
  
 30) PLEASE REVISE NOTES ON A8.2.2 WHICH
 REFER TO THE 2001 SOUTH FLORIDA BUILDING
 CODE.
  
 31) SUBMIT THE MANUFACTURER'S SPECS. AND
 LISTINGS FOR THE FIRE RATED WINDOWS AND
 DOORS (OPENING PROTECTIVES).
  
 32) SUBMIT THE MANUFACTURER,S
 SPECIFICATIONS FOR THE CLOSERS REQUIRED
 ON THE FIRE RATED DOORS.
  
 33) DETAIL 5 ON A8.3.2 APPEARS TO SHOW A
 PRIMARY SCUPPER PIPED THROUGH A MANSARD
 ROOF. SPECIFY WHERE THIS IS LOCATED. A
 PRIMARY SCUPPER WILL BE REQUIRED TO
 EMPTY INTO A DOWNSPOUT AND BE DISCHARGED
 A MINIMUM OF 12" AWAY FROM THE
 FOUNDATION.
  
 34) WINDOWS LABELED H AND J WHICH ARE
 LOCATED IN THE MULTIPURPOSE ROOM ARE NOT
 LISTED IN THE WINDOW SCHEDULE ON SHEET
 A4.0.8.
  
 35) THE INTERNAL PRESSURE COEFFICENT ON
 SHEET S7 IS POSITIVE AND NEGATIVE + OR
 -0.18.
  
 36) MANY OF THE COLUMNS ARE MISSING THE
 ID TAGS ON THE STRUCTURAL DRAWINGS.
  
 37) SOME OF THE COLUMNS ON S2.3 APPEAR
 TO BE MISSING STUD RAIL ID TAGS.
  
 38) CLEARLY INDICATE THE LOCATIONS OF
 THE BAHAMA SHUTTERS ON THE PLANS. ARE
 THESE FOR DECORATIVE PURPOSES OR ARE
 THEY INTENDED TO PROVIDE PROTECTION FROM
 WIND BOURNE DEBRIS. IF THE LATTER
 COMPLIANCE WITH THE CITY OF WEST PALM
 BEACH'S STORM SHUTTER POLICY WILL BE
 REQUIRED.
  
 39) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. IN
 ADDITION TO THE FL# COVERSHEET THE
 EVALUATION REPORT AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED.
  
 40) THE NOA (EVALUATION REPORT)
 SUBMITTED FOR THE BAHAMA SHUTTERS IS
 EXPIRED. SUBMIT CURRENT FL COVERSHEET
 AND EVALUATION REPORT FOR THE SHUTTERS.
 SUBMIT AN INSTALLATION SCHEDULE WITH
 OPENING SIZES, SHUTTER WIDTHS AND SPANS,
 AND A KEY PLAN.
  
 41) SUBMIT PRODUCT APPROVALS FOR DOORS
 #S 1,7 AND 8 WITH THE SMALL LOUVERS
 LISTED IN THE COMMON AREA DOOR SCHEDULE
 ON A10.0.1. THE PRODUCT APPROVALS
 SUBMITTED ARE FOR FULL LOUVER DOORS.
  
 42) SUBMIT PRODUCT APPROVALS AND
 MANUFACTURER'S SPECIFICATIONS FOR ALL
 FIRE RATED DOORS AND WINDOWS.
  
 43) SUBMIT THE SBCCI REPORT # 2203 THAT
 IS LISTED ON THE STATE WEBSITE AS THE
 EVALUATION REPORT FOR THE HANSON ROOF
 TILES.
  
 44) THE INGERSOLL-RAND DOOR PRODUCT
 APPROVALS HAVE THE WRONG NOAS
 (EVALUATION REPORTS) ATTACHED TO THE
 FL# COVERSHEETS.
  
 45) SUBMIT THE FL COVERSHEET FOR THE
 L-3000 WINDOW WALL SYSTEM.
  
 46) THE PGT FL COVERSHEET FOR THE FRENCH
 DOOR IS ATTACHED TO AN ARCH ALUMNIUM
 NOA.
  
 47) THE PGT COVERSHEET AND NOA FOR
 FL#251 THE SLIDING GLASS DOORS DOES NOT
 INCLUDE TRIPLE SLIDING GLASS DOOR
 CONFIGURATION. SUBMIT PRODUCT APPROVALS
 FOR THE TRIPLE SLIDING GLASS DOORS.
  
 48) THE THERMA-TRUE/ BENCH MARK DOORS
 WILL NEED TO HAVE A FIRE RATING IF USED
 AT THE EXIT ACCESS CORRIDORS.
  
 49) SUBMIT PRODUCT APPROVALS FOR THE
 ROOFING SYSTEM THAT WILL BE USED ON THE
 FLAT ROOF AREAS OF THE BUILDING.
  
 50) SUBMIT A SITE PLAN SHOWING
 ACCESSIBLE ROUTES TO ALL BUILDINGS,
 AMENITIES, PARKING AND TO THE PUBLIC WAY
 AS REQUIRED BY FBC 11-4.1.2, THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES AND
 ANSI 4.3. SHOW CURB RAMPS, SIDE WALK
 WIDTHS, SIGNAGE, DETECTABLE WARNINGS,
 CROSSWALKS,ETC.
  
 51) THE MAILBOXES ARE REQUIRED TO BE
 ACCESSIBLE.
  
 52) SPECIFY THE LOCATION OF THE ON
 STREET ACCESSIBLE PARKING SPACES
 SPECIFIED IN THE SCHEDULE ON A0.0.5.
  
 53) SPECIFY THE NUMBER OF PARKING SPACES
 IN THE PARKING GARAGE AND THE NUMBER OF
 ACCESSIBLE SPACES IN THE SCHEDULE ON
 A0.0.5. IN PARKING STRUCTURES ONE IN
 EVERY EIGHT ACCESSIBLE SPACES, BUT NOT
 LESS THAN ONE, SHALL BE VAN ACCESSIBLE.
 SEE FBC 11-4.1.2, 11-4.6.4 AND 11-4.6.5.
  
 NOTE: GARAGE DOES NOT APPEAR TO PROVIDE
 THE REQUIRED VERTICAL CLEARANCE FOR THE
 VAN ACCESSIBLE PARKING. ALSO CONSIDER
 CLEARANCES TO SPRINKLER PIPES, DRAIN
 PIPES, ETC.
  
 54) THE UNIT E AND ER DWELLING UNITS ON
 A407 AND A407A HAVE ONE BATHROOM
 SPECIFIED AS "TYPE A" AND THE OTHER AS
 "TYPE B". THIS IS INCORRECT. IF
 "SPECIFICATION A" IS SELECTED AS THE
 BASIS FOR DESIGNING A BATHROOM IN
 DWELLING UNITS WITH MORE THAN ONE
 BATHROOM, THEN ALL OF THE BATHROOMS IN
 THE DWELLING UNIT MUST COMPLY WITH THE
 "A SPECIFICATIONS". IF "SPECIFICATION B"
 IS SELECTED ONLY ONE BATHROOM IN THE
 DWELLING UNIT MUST MEET THOSE
 REQUIREMENTS; ALL OTHER BATHROOMS IN THE
 DWELLING UNIT MUST BE ON AN ACCESSIBLE
 ROUTE, HAVE DOORS WITH A NOMINAL 32-INCH
 CLEAR OPENING, HAVE SWITCHES, OUTLETS,
 AND CONTROLS IN ACCESSIBLE LOCATIONS,
 AND HAVE REINFORCED WALLS AROUND
 TOILETS, TUBS, AND SHOWER STALLS. SEE
 CHAPTER 7 OF THE FAIR HOUSING DESIGN
 MANUAL.
  
 55) A SEPARATE PERMIT WILL BE REQUIRED
 FOR THE POOL, GAZEBOS AND TOT LOT.
 NOTE: THESE ITEMS WILL BE REVIEWED FOR
 ACCESSIBILITY. PLAY AREA WILL BE
 REQUIRED TO COMPLY WITH ADA
 ACCESSIBILITY GUIDELINES FOR PLAY AREAS.
  
 56)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 57) LIFE SAFETY NOTE #4 ON A1.3.1 STATES
 THAT THE OPEN, COVERED EGRESS CORRIDORS
 ARE SPRINKLERED, HOWEVER, THE FIRE
 SPRINKLER PLANS DO NOT INDICATE THIS.
  
 58) ON A2.1.13 THERE IS A NOTE THAT
 REFERS TO SHEET A2.1.14 FOR PARKING
 SPACES IN THIS AREA. THERE WAS NO SHEET
 A2.1.14 IN THIS PLAN SET.
  
 59) THE ROOF ACCESS DOORS FROM THE
 STAIRS SHALL HAVE KEYED LOCKSETS AND
 SIGNAGE TO PREVENT PUBLIC ACCESS.
  
 60) THE CALCULATED VALUE OF THE
 STRUCTURE BASED ON AREA BREAKDOWN ON
 PLANS IS $23,667,187.00. FEES HAVE BEEN
 ADJUSTED.
  
 61) ADDITIONAL COMMENTS MAY RESULT FROM
 RESPONSES TO THESE ISSUES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-17 Cont ID  
Sent By dpalmer Date 2006-04-17 Time 16:19 Rev Time 0.00
Received By dpalmer Date 2006-04-13 Time 15:40 Sent To  
Notes
2006-04-17 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED AND SOME NEW COMMENTS DUE TO
 INFORMATION/OR CHANGES TO PLANS.
  
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW ABD NOTED.
 PLEASE SEE NEW NOTES WERE ADDED TO THE
 BOTTOM OF NOTES AND ARE NOTED AS NEW.
  
 MARVILLA
  
 4-STORY CONDO BLDGS W/ PARKING GARAGES.
  
  
 1)NOTE: OK.
  
 2)NOTE: NO/YES, PLEASE SEE A DETAIL WAS
 SUBMITTED, HOWEVER PLEASE KNOW THE
 CURBING SHALL GO COMPLETELY AROUND BUS
 PENTRATING THE FLR. CAN NOT BE THREE
 SIDED UP ON WALL.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE A DETAIL FOR CURBING
 REQUIRED AROUND BUS-DUCT ON FLOOR
 PENETRATIONS WHERE A VERTICAL RISER
 PENETRATES TWO OR MORE DRY FLOORS,
 A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL
 BE INSTALLED AROUND ALL FLOOR OPENINGS
 FOR RISER BUSWAYS TO PREVENT LIQUIDS
 FROM ENTERING THE OPENING. PER 368.6
  
 3)NOTE: OK, HOWEVER SEE NOTE #7 FOR
 OTHER AREAS WHICH REQUIRE A BATTERY FIX.
  
  
 4)NOTE:NO, PLEASE SEE STAIR AREA WERE
 NOT SHOWN AND PHOTO METRICS WERE DONE
 FOR MOST FLRS AND AREAS BUT NOT ALL.
 PLEASE SEE IF FIRST FLR IS "TYPICAL"
 THEN PLEASE NOTE AS:
 PLEASE SEE WHAT APPEARS TO BE FT CANDLES
 SHOWN ON OTHER SHEETS WHICH ARE NOT
 VISABLE.
  
 ** PREVIOUS NOTE**
 PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR/CORRIDOR AREAS FOR EGRESS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE 2003
 101, 7.8 AND 7.9, WHICH REQUIRES 10FT
 CANDLES FOR STAIR AREAS AND 1FT FOR
 CORRIDOR.
 7.8.1.3,7.9.2.1
  
 5)NOTE: OK.
  
 6)NOTE:NO, PLEASE SEE RESPONSE
 MENTTIONS THIS TO BE DONE LATER, HOWEVER
 THIS IS REQUIRED AT THIS TIME AS NOTED
 PREVIOUSLY. THIS WOULD MOST LIKELY NOT
 BE DONE BY THE ELECTRICAL ENGINEER.
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE DETAIL FOR ROOF TOP LT
 POLES AND FIXTURES. PLEASE PROVIDE WIND
 LOAD CALCULATIONS FOR REVIEW. THIS IS
 REQUIRED AT THIS TIME FOR FIXTURES AND
 POLES.
 CALCULATIONS WILL BE REVIEWED BY THE
 BLDG REVIEWER FOR CODE COMPLIANCE OF FBC
 140 MPH WIND LOADS.
  
 7)NOTE: NO, PLEASE SEE SOME SHEETS
 INDICATE THE CORRECT FIXTURE
 IDENTIFICATION AND CORRELATES WITH THE
 FIXTURE SCHEDULE, HOWEVER SOME OF THE
 COMMON AREA/GARAGE AREA PLANS/SHEETS
 SHOW FIXTURES WHICH ARE NOT BATTERY BACK
 UP AND /OR ARE NOT ON FIXTURE SCHEDULE
 AND SYMBOL SEEMS TO LEND TO THE FIXTURE
 BEING A BATTERY BACK UP FIXTURE OF SOME
 SORT. "B" , B2".
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT A COMPLETED LIGHTING
 FIXTURE SCHEDULE TO CORRELATE WITH
 FIXTURES AS SHOWN ON PLANS. PLEASE ALSO
 SEE COMMON AREAS WHERE FIXTURES DO NOT
 INDICATE WHAT TYPE ETC.
 RECREATION AREA, ROOF TOP ETC.
  
 8)NOTE: OK
  
 9)NOTE: OK.
  
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 14)NOTE:OK, HOWEVER PLEASE CORRELATE
 CIRCUITING AS, UNITS SHOWN DINING ARE
 WITH 15A CIRCUIT(S). PLEASE SEE
 210.52B1, 210.11C1 AND 220.16A FOR TWO
 OR MORE CIRCUITS. PLEASE ADJUST
 CIRCUITING ANDLOAD CALCUALTIONS.
  
 ** PRWEVIOUS NOTE **
 PLEASE PROVIDE "DINING RM/AREA"
 DESIGNATIONS ON UNITS "A" AND "E".
 210.52B.
  
 15)NOTE: NO, PLEASE SEE SOME OF THESE
 RMS, ELEV EQUIPMENT ETC DO NOT SHOW ROOM
 DESIGNATIONS OR NOTE WHERE TO FIND. SEE
 GARAGE PLANS ALSO. POOL RM LABLED.OK
  
 ** PREVIOUS NOTE **
 PLEASE PROVIDE ROOM/ AREA DESIGNATIONS
 ON COMMON AREAS PLANS.
 PLEASE SEE ROOMS ETC NOT LABLED.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE "POOL EQUIPMENT " ROOM ETC.
  
 16)NOTE:NO, SAME NOTE:RESPONSE
 MENTIONS TO SEE REVISED SHEETS, HOWEVER
 THE SAME #'S ARE SHOWNA S ON PREVIOUS
 PLANS.??
  
 ** PREVIOUS NOTE **
 PLEASE SEE 424.3B WHICH REQUIRES ALL
 OVERCURRENT PROTECTION FOR AHU'S HEAT TO
 BE A MIN OF 125%.
 PLEASE SEE THESE AS REDLINED ON PLANS.
 PLEASE ALSO REVISE MIN AWG PER 310.16
 ONCE OCP HAS BEEN ADJUSTED.
 PLEASE KNOW, MOST OCP IS 150% MAX,
 HOWEVER WHEN A AMPERAGE DOES NOT
 CORRESPONED TO A COMMON OCP DEVICE AS
 LISTED IN 240.6, GOING UP TO THE NEXT
 HIGHER OCP IS PERMITTED.
  
 17)NOTE:NO, SAME NOTE,RESPONSE
 MENTIONS TO SEE REVISED, HOWEVER THE
 PANEL SCHEDULES WERE NOT CHANGED??
  
 ** PREVIOUS NOTE **
 PLEASE SEE MANY OF THE UNITS AS LISTED
 ON HOUSE PANELS ALSO NEED TO BE
 ADJUSTED.
 PLEASE SEE L2B AHU#10, SHOWS 11KW ON A
 2P-30A WITH #10 AWG.
 AHU #11 LISTED TWICE, SHOWS 11KW ON
 2P-45A WITH #8.
 AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A
 OCP THIS ONE IS OK.
 PLEASE SEE AHU#10 IS LISTED TWICE ALSO.
 PLEASE SEE AHU #6 ON LRB.
 PLEASE SEE AHU #7 ON LRB.
 BOTH WITH THE SAME COMMENTS AS LISTED
 ABOVE.
 PLEASE ADJUST.424.3B,310.16
  
 18)NOTE: NO,?? RESPONSE LTR MENTIONS TO
 SEE REVISED,HOWVER THE SAME #'S ARE
 SHOWN?
 ** PREVIOUS NOTES**
 PLEASE SEE MIN OCPFOR WATER HEATER
 UNITS, SHALL BE A MIN OF 125% AND A MAX
 OF 150%.
 PLEASE SEE 6KW SHOWN ON A 2P35.
 422.13,422.11E3
  
 19)NOTE: OK, HOWEVER PLEASE SEE THE
 CONTINUOUS LOADS NOTE WAS ADDED TO ALL
 PLANS INCLUDING UNITS??
  
 ** PREVIOUS NOTE **
 PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. PLEASE SEE THIS IS FOR LOADS
 DEDICATED TO HOUSE PANELS, POOL PUMPS,
 ANY POOL HEAT PUMPS, LIGHTING , LARGEST
 MOTOR STEC.
 215.3,230.42 ETC.
  
 20)NOTE: OK.
  
 21)NOTE: OK/NO, PLEASE SEE SPECS WERE
 SUBMITTED AND VERIFIED, HOWEVER PLEASE
 SEE PLANS DO NOT REFLECT OR NOTE
 ANYTHING FOR LOCKED ROTOR FOR THE FIRE
 PUMP AND PLANS AND SPECS FOR THE FIRE
 PUMP DO NOT CORRELATE FOR SIZING. PLEASE
 SPECIFY THE LOCAKED ROTOR SETTING PER
 MANUFACTURES SPECS AND PLEASE CORRELATE
 THE HP RATINGS. (SPECS SHOW 100HP AND
 RISER SHOWS 125HP).REVIEW FOR CONDUCTORS
 OCP ETC CANNOT BE DONE AT THIS TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT
 SHEETS FOR FIRE PUMP AND FIRE PUMP
 CONTROLLER.
 PLEASE BE SURE NOTES FOR LOCKED ROTOR
 AND MANUAL MEANS OF DISCONNECT IS
 LOCATED ON PLANS.
 PLEASE SEE 695.4B1,
 NFPA-20 10.4.2.1.1,10.4.2.2 ETC.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 AT THIS TIME EVEN IF FIRE PUMP/
 CONTROLLER IS PERMITTED UNDER FIRE
 SPRINKLER PERMIT.
  
 22)NOTE:OK.
  
 23)NOTE: OK.
  
 24)NOTE: OK.
  
 25)NOTE: OK.
  
 26)NOTE: OK.
  
 27)NOTE: OK.
  
 28)NOTE: OK.
  
 29)NOTE: OK.
  
 30)NOTE:OK, HOWEVER PLEASE SEE COMMON
 AREA PLANS AND GARAGE LIGHTING PLANS
 WHICH INDICATE THE LIGHTING IN THESE RMS
 CIRCUITED TO THE GARAGE LTS.
 PLEASE ADJUST.
  
 ** PREVIOUS NOTE **
 PLEASE SEE 620.23,620.24 WHICH REQUIRES
 DEDICATED CIRCUITS FOR ELEVATOR PIT LTS
 AND RECEPTS. THIS CIRCUIT MAY NOT FEED
 ANY OTHER LTS AND RECEPTS.
 THESE SHALL ALSO BE DEDICATE TO EACH
 ELEVATOR/PIT.
 PLEASE SEE CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS SHALL ALSO BE DEDICATED
 AND MAY NOT FEED ANY OTHER ROOMS OR
 ELECTRICAL LIGHTING OR RECEPTS.
 PLEASE ALSO SEE PREVIOUS NOTE WHICH IS
 REQUIRING A BATTERY BACK-UP FIXTURE IN
 THESE ROOMS.
 PLEASE ALSO SEE 700.16D
  
 31)NOTE: OK.
  
 32)NOTE: OK.
  
 33)NOTE: OK.
  
  
 ****** NEW NOTE ****
  
 34) NOTE: PLEASE SEE ALL UNITS LOCATED
 ON THE FIRST FLR WITH GRADE LEVEL
 ACCESS/EGRESS FROM UNIT/ FROM PATIO
 SHALL CONTAIN A LT FIXTURE OF SOME SORT
 FOR EGRESS LT. THIS MAY BE ADDRESSED AS
 A CLOUDED NOTE FOR ALL FIRST FLR UNITS.
 210.70, LS 101-7.8
  
 35) NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE
 AT THIS TIME.
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEENREDLINED ON PLANS FOR AREAS
 OF COMMENTS.
  
 **PLEASE SEE ALL COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF ALL OL/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DONOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-13 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-04 Cont ID  
Sent By dpalmer Date 2005-10-04 Time 19:25 Rev Time 14.00
Received By dpalmer Date 2005-10-03 Time 15:44 Sent To  
Notes
2005-10-04 00:00:00MARVILLA
  
 4-STORY CONDO BLDGS W/ PARKING GARAGES.
  
 *********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE PLANS ARE TO
 REFERENCE THE 2002 NEC AS ADOPTED BY THE
 STATE OF FLORIDA.(JULY 1ST, 2003)
 PLEASE ALSO SEE NOTES FOR PLANS WHICH
 INDICATE LOCAL AMENDMENTS PER CITY OF
 BOYNTON BEACH. PLEASE SEE NOTE WOULD
 REFERENCE LOCAL AMENDMENTS PER CITY OF
 WEST PALM BEACH.
  
 2)NOTE: PLEASE PROVIDE A DETAIL FOR
 CURBING REQUIRED AROUND BUS-DUCT ON
 FLOOR PENETRATIONS WHERE A VERTICAL
 RISER PENETRATES TWO OR MORE DRY FLOORS,
 A MINIMUM 100 MM (4 IN.) HIGH CURB SHALL
 BE INSTALLED AROUND ALL FLOOR OPENINGS
 FOR RISER BUSWAYS TO PREVENT LIQUIDS
 FROM ENTERING THE OPENING. PER 368.6
  
 3)NOTE: PLEASE PROVIDE BATTERY BACK UP
 LIGHT FIXTURES IN ALL ELECTRICAL ROOMS,
 ELEVATOR EQUIPMENT ROOMS AND FIRE PUMP
 RM.
 THIS IS REQUIRED PER FIRE MARSHALS
 OFFICE AND AHJ FOR LIGHTING WHICH BE
 REQUIRED UNDER NFPA-101 7.8,7.9.
  
 4)NOTE: PLEASE PROVIDE PHOTOMETRICS FOR
 STAIR/CORRIDOR AREAS FOR EGRESS TO THE
 PUBLIC RIGHT OF WAY. PLEASE SEE 2003
 101, 7.8 AND 7.9, WHICH REQUIRES 10FT
 CANDLES FOR STAIR AREAS AND 1FT FOR
 CORRIDOR.
 7.8.1.3,7.9.2.1
  
 5)NOTE: PLEASE SEE MISSING CIRCUITING
 FOR FRIG IN UNIT "A".
  
 6)NOTE: PLEASE PROVIDE DETAIL FOR ROOF
 TOP LT POLES AND FIXTURES. PLEASE
 PROVIDE WIND LOAD CALCULATIONS FOR
 REVIEW. THIS IS REQUIRED AT THIS TIME
 FOR FIXTURES AND POLES.
 CALCULATIONS WILL BE REVIEWED BY THE
 BLDG REVIEWER FOR CODE COMPLIANCE OF FBC
 140 MPH WIND LOADS.
  
 7)NOTE: PLEASE SUBMIT A COMPLETED
 LIGHTING FIXTURE SCHEDULE TO CORRELATE
 WITH FIXTURES AS SHOWN ON PLANS.
 PLEASE ALSO SEE COMMON AREAS WHERE
 FIXTURES DO NOT INDICATE WHAT TYPE ETC.
 RECREATION AREA, ROOF TOP ETC.
  
 8)NOTE: PLEASE MAKE REFERENCE/ NOTES
 PERTAINING TO ALL THE ELECTRICAL
 REQUIREMENTS FOR ELECTRICAL DEVICES
 UNDER FAIR HOUSING ACT REGULATIONS, CFR
 24 100.205.
  
 9)NOTE: PLEASE SEE 2002 NFPA-72 11.8.3.5
 FOR SMOKE DETECTOR PLACEMENT. PLEASE
 KNOW ALL SD'S ARE REQUIRED TO BE WITH-IN
 12" OF A CEILINGIN FALT CEILING
 INSTALLATIONS. PLEASE SEE SD'S WHICH
 SEEM TO BE LOCATED AT AREAS OF SOFFIT
 ETC SHALL BE MOVED TO AREAS WHERE
 CEILINGS WITH HIGHEST POINT.
 IF SD'S ARE WALL MOUNTED, THEY ARE STILL
 REQUIRED TO BE WITH IN 12" OF CEILING
 BUT NO CLOSER THAN 4".
 PLEASE ALSO PLACE NOTE ON PLANS FOR SD
 PALCEMENT PER ABOVE WITH RESPECT TO SD'S
 BEING LOCATE NO CLOSER THAN 3' OF BATH
 AND KIRTCHEN DOORS AND NO CLOSER THAN
 20' OF COOKING APPLIANCES, (UNLESS
 MEETING EXCEPTIONS AS SET FORTH) AS
 LISTED IN NFPA-72
  
 10)NOTE: PLEASE SEE SOME MISSING RECEPTS
 ALONG KITCHEN COUNTERSPACES AND
 PENINSULARS.
 210.52C1,210.52C3
 PLEASE SEE REDLINED PLANS FOR LOCATIONS.
 UNIT, B
  
 11)NOTE: PLEASE SEE SOME RECEPTS MISSING
 PER 210.52, 2' OF WALL SPACE.
 ONCE AGAIN, SEE REDLINED PLANS FOR AREAS
 AS NOTED. UNIT , E, A
  
 12)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS AS REQUIRED UNDER THE
 2002 NEC 210.12. THIS REQUIRES ALL
 "OUTLETS" TO BE AF PROTECTED. THIS
 INCLUDES SD'S, LTS, RECEPTS , FANS ETC.
  
 13)NOTE: PLEASE SEE UNIT "A" WHICH SHOWS
 INDIVIDUALS WASHER AND DRYER, HOWEVER
 PANEL SCHEDULE SHOWS THIS AS A STACKABLE
 UNIT??
 PLEASE SEE "L1A WHICH SHOWS CIRCUIT #24
 AS A SPARE, YET ON PLANS THIS IS SHOWN
 FOR ABOVE.
 PLEASE CORRELATE.
  
 14)NOTE: PLEASE PROVIDE "DINING RM/AREA"
  
 DESIGNATIONS ON UNITS "A" AND "E".
 210.52B.
  
 15)NOTE: PLEASE PROVIDE ROOM/ AREA
 DESIGNATIONS ON COMMON AREAS PLANS.
 PLEASE SEE ROOMS ETC NOT LABLED.
 PLEASE SEE ELECTRICAL PLANS DO NOT
 INDICATE "POOL EQUIPMENT " ROOM ETC.
  
 16)NOTE: PLEASE SEE 424.3B WHICH
 REQUIRES ALL OVERCURRENT PROTECTION FOR
 AHU'S HEAT TO BE A MIN OF 125%.
 PLEASE SEE THESE AS REDLINED ON PLANS.
 PLEASE ALSO REVISE MIN AWG PER 310.16
 ONCE OCP HAS BEEN ADJUSTED.
 PLEASE KNOW, MOST OCP IS 150% MAX,
 HOWEVER WHEN A AMPERAGE DOES NOT
 CORRESPONED TO A COMMON OCP DEVICE AS
 LISTED IN 240.6, GOING UP TO THE NEXT
 HIGHER OCP IS PERMITTED.
  
 17)NOTE: PLEASE SEE MANY OF THE UNITS AS
 LISTED ON HOUSE PANELS ALSO NEED TO BE
 ADJUSTED.
 PLEASE SEE L2B
 AHU#10, SHOWS 11KW ON A 2P-30A WITH #10
 AWG.
 AHU #11 LISTED TWICE, SHOWS 11KW ON
 2P-45A WITH #8.
 AHU#11 LISTED AGAIN, 4.8KW WITHAND 30A
 OCP THIS ONE IS OK.
 PLEASE SEE AHU#10 IS LISTED TWICE ALSO.
 PLEASE SEE AHU #6 ON LRB.
 PLEASE SEE AHU #7 ON LRB.
 BOTH WITH THE SAME COMMENTS AS LISTED
 ABOVE.
 PLEASE ADJUST.424.3B,310.16
  
 18)NOTE: PLEASE SEE MIN OCPFOR WATER
 HEATER UNITS, SHALL BE A MIN OF 125% AND
 A MAX OF 150%.
 PLEASE SEE 6KW SHOWN ON A 2P35.
 422.13,422.11E3
  
 19)NOTE:PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. PLEASE SEE THIS IS FOR LOADS
 DEDICATED TO HOUSE PANELS, POOL PUMPS,
 ANY POOL HEAT PUMPS, LIGHTING , LARGEST
 MOTOR STEC.
 215.3,230.42 ETC.
  
 20)NOTE: PLEASE BE SURE MAINS 1A,2A,1B,
 2B, INDICATE THAT THE MCB CONTAINS A
 MANUAL MEANS OF DISCONNECT LOCATED ON
 THE OOUTSIDE OF THE EQUIPMENT AND RATED
 FOR THE LOAD SERVED. 230.76 AND 230.79
 PLEASE SEE PLANS ONLY INDUCATE THESE AS
 BEING SHUNT TRIP TYPE?
 PLEASE ALSO MAKE NOTES FOR MAINS DPA AND
 DPB.
  
 21)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER.
 PLEASE BE SURE NOTES FOR LOCKED ROTOR
 AND MANUAL MEANS OF DISCONNECT IS
 LOCATED ON PLANS.
 PLEASE SEE 695.4B1,
 NFPA-20 10.4.2.1.1,10.4.2.2 ETC.
 PLEASE SEE THIS INFORMATION IS REQUIRED
 AT THIS TIME EVEN IF FIRE PUMP/
 CONTROLLER IS PERMITTED UNDER FIRE
 SPRINKLER PERMIT.
  
 22)NOTE: PLEASE INDICATE THE EQUIPMENT
 GROUNDING CONDUCTORS ON RISER FEEDERS TO
 "TAP-BOXES".
 250.110,250.122
  
 23)NOTE: PLEASE SEE FEEDERS FROM MAINS
 1A,2A,1B,AND 2B TO "TAP BOXES
 COULD NOT BE LOCATED??
 PLEASE SEE, 215.5,310.16
  
 24)NOTE: PLEASE CORRELATE BUS RISER
 DETAILS AND NOTES. PLEASE SEE REDLINED
 PLANS, AS THERE ARE 2- "BUSWAY #2 SHOWN,
 AND NOTES FOR FEED TO MAIN 2B IS LISTED
 TWICE AND ONE IS CROSSED THROUGH??
 PLEASE SEE REDLINED PLANS AND CORRELATE.
 215.5
  
 25)NOTE: PLEASE SEE FEEDERS FROM "DPA"
 TO PANEL "L4A" ARE SHOWN AS 3/0'S,
 HOWEVER OCP ON DPA IS 400A'S. PLEASE
 CORRELATE AND ADJUST. 240.4,310.16
  
 26)NOTE: PLEASE SPECIFY OF PANEL "L4A"
 HAS "FEED-THRU " LUGS OR DOES THIS PANEL
 CONTAIN OCP FEEDING THRU TO PANEL
 "L4AA".?
 215.5
  
 27)NOTE: PLEASE SEE ELEVATOR CIRCUITS AS
 LISTED ON DPA #5 AND #6 SHOWS 4-POLES?
 FOR A 3-POLE BRKR?
 PLEASE ALSO SEE DPB #5 AND #6 AS THIS
 SHOWS THE SAME THING.
 215.5
  
 28)NOTE: PLEASE SEE "L1BA" WHICH IS
 SHOWN AS A 100A PANEL YET IS BEING FED
 WITH A 225A BRKR FROM DPB.
  
 29)NOTE: PLEASE SEE PANEL "LPB" WHICH IS
 SHOWN AS 200A PANEL, HOWEVER PANEL IS
 BEING FED WITH A 225A BRKR FROM "DPB".
 PLEASE CORRLEATE.
  
 30)NOTE: PLEASE SEE 620.23,620.24 WHICH
 REQUIRES DEDICATED CIRCUITS FOR ELEVATOR
 PIT LTS AND RECEPTS. THIS CIRCUIT MAY
 NOT FEED ANY OTHER LTS AND RECEPTS.
 THESE SHALL ALSO BE DEDICATE TO EACH
 ELEVATOR/PIT.
 PLEASE SEE CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS SHALL ALSO BE DEDICATED
 AND MAY NOT FEED ANY OTHER ROOMS OR
 ELECTRICAL LIGHTING OR RECEPTS.
 PLEASE ALSO SEE PREVIOUS NOTE WHICH IS
 REQUIRING A BATTERY BACK-UP FIXTURE IN
 THESE ROOMS.
 PLEASE ALSO SEE 700.16D
  
 31)NOTE: PLEASE PROVIDE A NOTE ON SHEETS
 FOR ELECTRICAL/ ELEVATOR ROOMSWHICH
 SHOULD STATE ALL REQUIRED CLEARENCES PER
 110.26 SHALL BE MET FOR ALL ELECTRICAL
 EQUIPMENT. (OR WORDS TO THAT AFFECT).
 110.26
 THIS HAS BEEN AN ISSUE IN THIS
 JURISDICTION FOR MAINS/METER CENTERS FOR
 HEIGHT AND WIDTH OF EQUIPMENT.
  
 32)NOTE: PLEASE PLACE NOTE ON "ROOF-TOP"
 PLANS WHICH WILL STATE >
 "ANY LIGHTNING PROTECTION SYSTEMS WILL
 BE REQUIRED TO BE SUBMITTED UNDER A
 SEPARATE PERMIT AND PLANS."
 "ALL SYSTEMS SHALL MEET NFPA-780."
  
 33)NOTE: PLEASE SEE RISER DIAGRAM SEEMS
 TO SHOW ELEVATOR EQUIPMENT/ DISCONNECTS,
 ETC ON 2ND FLR, HOWEVER PLANS FOR ROOMS
 ON E7.1, APPEAR TO SHOW THIS EQUIPMENT
 LOCATED ON 1ST FLR??
  
 ** PLEASE KNOW, MANY OF THE ABOVE ITEMS
 HAVE BEENREDLINED ON PLANS FOR AREAS
 OF COMMENTS.
  
 **PLEASE SEE ALL COMMENTS FROM ALL OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
 PLEASE SEE FIRE REVIEW COMMENTS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE SET OF ALL OL/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR
 REFERENCE.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DONOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-09-14 Cont ID  
Sent By mamini Date 2005-09-14 Time 09:54 Rev Time 0.50
Received By mamini Date 2005-09-14 Time 09:54 Sent To  
Notes
2005-09-14 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By mwennerg Date 2006-05-23 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2006-05-23 Time 09:26 Sent To  
Notes
2006-05-23 00:00:00***DENIED***
  
 PLEASE ADDRESS SOME PREVIOUS COMMENTS IN
 ADDITION TO NEW COMMENTS:
  
 1) PREVIOUS COMMENT #1- PLEASE INDICATE
 THE INTERIOR FINISH CLASSIFICATION THAT
 IS SPECIFIC TO THIS PROJECT. YOUR
 RESPONSE GENERALLY CITES THE TECHNICAL
 CODE REQUIREMENT.
  
 2) KEY TURN ACTIVATION KNOX BOX ENTRY
 SYSTEM IS REQUIRED ON NEW PROPERTY ENTRY
 INSTALLATIONS.
  
 3) PLEASE ILLUSTRATE ARRANGEMENT OF
 MEANS OF EGRESS, (TRAVEL DISTANCE TO
 EXITS, COMMON PATH OF TRAVEL, ETC) BASED
 ON TYPE OF OCCUPANCY ON LIFE SAFETY
 DRAWINGS.
  
 4) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES (3) STORIES OR
 (30) FEET IN HEIGHT.
  
 5) KNOX BOXES ARE REQUIRED ON THE
 BUILDINGS.
  
 6) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM WHEN ACTIVATED IN
 ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 7) NO SMOKE DETECTORS ARE SHOWN IN
 CORRIDORS. PLEASE SEE NFPA 101, SECTIONS
 9.6.2.8 AND 9.6.2.9 REGARDING
 REQUIREMENTS FOR ALL OCCUPIABLE AREAS,
 COMMON AREAS, CORRIDORS ETC.
  
 8) FDV'S TO BE 2 1/2" TO 1 1/2" REDUCER
 WITH CHAINS.
  
 9) DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 IN ADDITION TO ELECTRONIC SUPERVISION,
 BE SECURED WITH CHAIN AND LOCK.
  
 10) PLEASE PROVIDE PRESCRIPTIVE SRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By nmccray Date 2005-10-12 Time 11:48 Rev Time 0.00
Received By nmccray Date 2005-10-12 Time 11:10 Sent To  
Notes
2005-10-12 00:00:00DENIED:
  
 1) INTERIOR WALL AND CEILING FINISH
 MATERIALS COMPLYING WITH SECTION 10.2
 SHALL BE PERMITTED AS FOLLOWS:
  
 (1) EXIT ENCLOSURES - CLASS A
 (2) LOBBIES AND CORRIDORS - CLASS A OR
 CLASS B
 (3) OTHER SPACES - CLASS A, CLASS B, OR
 CLASS C.
  
 2) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE ALARMSYSTEMS.
 THE FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION
 SERVICES.
  
 3) SEPARATE PLANS AND PERMIT APPLICATION
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 4) BUILDING ADDRESS IS REQUIRED A
 MINIMUM 6" HIGH NUMBERS.
  
 5) SHALL COMPLY NFPA 101 LIFE SAFETY
 CODE, 2003 EDITION.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 10:12 Sent To  
Notes
2006-04-03 00:00:00TO "COMM" BD#2/PLANS ON RACK-3 ROLLS AND
 FOLDERS
2006-03-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 09:45 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 09:45 Sent To Z
Notes
2005-12-05 00:00:00FROM "COMM" BD#57/TO RMCDOUGAL DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-10 Cont ID  
Sent By rmcdouga Date 2006-01-10 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2005-09-07 Time 11:37 Sent To  
Notes
2005-09-07 00:00:00TO "COMM" BD#57/ PLANS ON RACK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-05-16 Cont ID  
Sent By pkrauss Date 2006-05-16 Time 12:55 Rev Time 0.00
Received By pkrauss Date 2006-05-16 Time 12:55 Sent To  
Notes
2006-05-16 00:00:00DENIED:2001 FLORIDA BUILDING CODE
 COMMENT #1 FROM REVIEW DATED 10/18/05:
 RESPONSE INDICATES NO EXHAUST DUCT
 EXTENDS OR PASS THROUGH RETURN AIR
 PLENUM.RESPONSE REFERS TO NOTE #8.
 NOTE #8 REFERS TO THE CITY OF BOYNTON
 BEACH.SEE ALSO NEW COMMENT # BELOW.
  
 COMMENT #2:OK
 COMMENT #3:RESPONSE TO COMMENT
 INDICATES RELIEF LOUVERS HAVE BEEN
 RELOCATED.SEE REV 1 ON PLAN SHEETS
 M4.4 & M4.5.PLANS STILL SHOW INTAKES
 AND EXHAUST TERMINATING AT AN EXIT
 ACCESS CORRIDOR WHICH IS PROHIBITED PER
 2001 FBC 1005.3.2.
  
 COMMENT #4:OK
 COMMENT #5:OK
 COMMENT #6:OK
  
 ****************************************
 NEW COMMENTS:
 7.PLAN SHEET M5.1 DETAIL FOR THE DRYER
 SHAFT.PLEASE ADDRESS THE FOLLOWING
 WITH REGARDS TO THE SHAFT ENCLOSURE.
 A) PER 2001 FBC 705.2.3.3, SHAFT SHALL
 CONTINUE THROUGH TO THE FIRST FLOOR. SEE
 ALSO EXCEPTION 1 TO THE AFOREMENTIONED
 CODE.
  
 8.FIRE DAMPER SHALL NOT BE INSTALLED
 ON THE DRYER EXHAUST.PLEASE PROVIDE
 MANUFACTURER'S SPECIFICATION AND
 INSTALLATION INSTRUCTIONS.
  
 9.AIR MAKE-UP IS NOT REQUIRED FOR THE
 THE SUB-DUCT SHAFT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By pkrauss Date 2005-10-18 Time 16:25 Rev Time 0.00
Received By pkrauss Date 2005-10-18 Time 16:25 Sent To  
Notes
2005-10-18 00:00:00DENIED: *********2001 FBC*********
 2 FOUR STORY CONDO'S W/ATTACHED GARAGE
  
 1.PLAN SHEET M4.1, PLAN INDICATES
 RETURN AIR PLENUM.PER 2001
 FBC(M)601.3, EXHAUST DUCTS & VENTING
 SYSTEMS SHALL NOT EXTEND INTO OR PASS
 THROUGH PLENUMS.
  
 2.PLAN SHEET M2.1.2, PLEASE CLARIFY
 WHAT THE SQUARES WITH THE ARROWS THAT
 ARE NOT IDENTIFIED ON THE LEGEND LOCATED
 ON M2.1.1.
  
 3.PLAN SHEET M2.3.2 REFERENCES M4.4
 FOR VENTILATION DETAILS.IT APPEARS THE
 EXHAUST IS TERMINATING ONTO THE WALKWAY.
 PER 2001 FBC(M)401.5.2, EXHAUST OPENINGS
 SHALL NOT BE DIRECTED ONTO WALKWAYS.
  
 4.PLAN SHEET M3.1 SHOWS DEF-7
 TERMINATING IN FRONT OF A DOOR TO THE
 STAIRWELL.TERMINATION SHALL BE IN A
 LOCATION WHERE IT WILL NOT CREATE A
 NUISANCE & PRODUCTS OF COMBUSTION WILL
 NOT INFILTRATE INTO THE STAIRWELL.2001
 FBC(M)401.5.2 & 401.5.1.
  
 5.DRYER SHAFTS SHALL HAVE SPRINKLERS
 IN ACCORDANCE WITH NFPA 13 SECTION
 8.14.2.2.1 & 8.14.2.2.2.
  
 6.PLAN SHEET M4.4 & M4.5 INDICATE AIR
 MAKE-UP WITHIN 10 FT OF THE EXHAUST.
 PLEASE PROVIDE VERTICAL SEPARATION FROM
 THE TOP OF THE AIR MAKE-UP TO THE BOTTOM
 OF THE EXHAUST.PLEASE NOTE, EXHAUST
 SHALL TERMINATE AS NOT TO BE DRAWN IN BY
 THE VENTILATION SYSTEM 2001 FBC 501.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-04 Cont ID  
Sent By kstevens Date 2006-05-04 Time 10:45 Rev Time 0.00
Received By kstevens Date 2006-05-02 Time 10:23 Sent To  
Notes
2006-05-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL REMAIN THE SAME AS FIRST REVIEW:
  
 1. SHT A2.0.5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FEET FOR EACH AREA, PLUS 1/2 AREA
 OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS, AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO EACH AREA FROM
 ABOVE ADDED IN CALCULATIONS. SECTIONS
 1106 & 1107 AND ALL SUBSECTIONS.
 ***RESPONSE NOTED, BUT CALCULATION ARE
 HARD TO READ. PLEASE SUBMIT THIS
 INFORMATION IN 1/8" MINIMUM SCALE AS
 REQUIRED IN SECTION 104.2.1.3.
  
 3. SHTS A4.0.2, A4.0.2A, A4.0.3,
 A4.0.3A, A4.0.4, & A4.0.4A, NO SHOWER
 BATH ELEVATIONS FOR W/C SHOWN. W/C TO BE
 18" OFF WALL TO CENTER OF FIXTURE. LAV
 TO BE 34" TO FLOOD RIM LEVEL. PAGES 7.43
 AND 7.52 FHA DESIGN MANUAL. SHTS A4.0.7,
 & A4.0.7A W/C TO BE 18" OFF WALL TO
 CENTER OF FIXTURE. (DETAIL E).
 ***RESPONSE NOTED, BUT SHT A4.0.4A W/C
 TO BE 1'6" OFF THE SAME WALL AS THE
 DISPENSER.
  
 4. SHT A4.0.8 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.1
 BLDG. AND 403.1 PLMG. SHOW SF OF EACH
 COMMON AREA & INDICATE THE OCCUPANCY AND
 OCCUPANCY LOAD OF EACH AREA. ALSO
 INDICATE ROOM DESIGNATION ON PLANS.
 SECTION 104.2.1.
 ***RESPONSE NOTED, BUT 1 MORE W/C
 REQUIRED IN THE WOMEN'S TOILET ROOM AS
 REQUIRED FOR POTTY PARITY PER SECTION
 403.1.1 EXCEPTION. IN ASSEMBLY
 OCCUPANCIES, THE ESTABLISHMENT SHALL
 HAVE AT LEAST THE SAME NUMBER OF WATER
 CLOSETS FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS FOR MEN.
 ALSO PER TABLE 403.1 A SERVICE SINK IS
 REQUIRED.
  
 5. SHT A4.0.8 KITCHEN SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. FORWARD
 APPROACH CLEAR FLOOR SPACE REQUIRED.
 ***RESPONSE NOTED, BUT SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL
 CODES SHALL NOT BE CITED AS A WHOLE OR
 IN PART, BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION. SECTION 104.2.1.
 SHOW THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE -
 FORWARD APPROACH IS REQUIRED AND SHALL
 EXTEND A MAXIMUM 19" UNDERNEATH THE
 SINK. CABINET DOORS ARE NOT APPROVED IN
 THE CLEAR FLOOR SPACE OF THE SINK.
 PLEASE DELETE FROM DETAIL.
 E. 11-4.24.6 EXPOSED PIPES AND SURFACES
 F. 11-4.24.7 FAUCETS
  
 6. SHT A4.0.10 DETAIL #5, BACKFLOW
 PROTECTION IS REQUIRED FOR THE TRASH
 CHUTE WASHDOWN. SECTION 608. INDICATE
 METHOD OF PROTECTION.
 ***RESPONSE NOTED, BUT THIS SHALL BE
 SHOWN ON THE WATER ISOMETRIC RISER
 DIAGRAM TO REFLECT THE FLOOR TIME.
  
 19. SHTS P5.3 & P5.4 SANT. ISOMETRIC
 SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1 & TABLE
 710.1(1).
 ***RESP0NSE NOTED, BUT THE DFU'S ARE NOT
 SHOWN AS THE ACCUMULATE IN THE BLDG.
 SANT. (SEE RED LINE CORRECTIONS ON
 SHEET)
  
 22. SUBMIT A STORM RISER DIAGRAM
 ISOMETRIC FOR THE BLDG. STORM DRAIN
 SYSTEM. SHOW ALL PIPE SIZES, RISER
 CONNECTION LOCATION, AND SF AS THEY
 ACCUMULATE IN THE SYSTEM. SECTIONS
 104.2.1 AND 104.3.1.1.
 ***RESPONSE NOTED, BUT SQUARE FOOTAGE IS
 NOT SHOWN AS IT ACCUMULATES IN THE
 SYSTEM. SQUARE FOOTAGE FROM ROOF DRAINS
 IS NOT REFLECTED ON THE BUILDING STORM
 DRAIN ISOMETRIC RISER DIAGRAM. PLEASE
 CLARIFY. SECTION 104.2.1.
  
 23. SUBMIT STORM RISER DIAGRAMS FOR EACH
 RWL. SHOW ALL PIPE SIZES AND SF FOR EACH
 RISER. SECTIONS 104.2.1 & 104.3.1.1.
 ***RESPONSE NOTED, BUT THIS IS ANOTHER
 BUILDING STORM DRAIN ISOMETRIC AND NOT
 STORM RISER DIAGRAMS, (FOR RWL'S) SUBMIT
 VERTICAL RISER DIAGRAMS FOR EACH RWL.
 INDICATE RWL NUMBER FOR EACH. (EXAMPLE
 RWL-1, RWL-2 ETC).
  
 **************NEW COMMENTS**************
 1B. CLEANOUTS ARE REQUIRED IN THE STORM
 SYSTEM AS REQUIRED IN THE SANITARY
 SYSTEM. SECTION 1101.8. SHOW CLEANOUTS
 ON THE FLOOR PLAN, AS WELL AS ON THE
 BUILDING STORM DRAIN ISOMETIC.
 2B. SHT P5.2 RISER S/E4 IS 32 FU'S NOT
 24 FU'S AS SHOWN. TABLE 709.1.
 3B. SHT P5.3 RISER S/D3 IS NOT SHOWN ON
 THE BUILDING DRAIN SANT. ISOMETRIC.
 4B. SHT P5.3 CAN NOT SEE PART OF THE
 BLDG DRAIN ISOMETRIC, (RISER S/D2),
 BECAUSE OF THE WAY IT IS STAPLED
 TOGETHER. PLEASE SHOW THAT PART OF THE
 ISOMETRIC AS INDICATED IN RED OR ADJUST
 THE WAY THE PLAN IS STAPLED TOGETHER.
 SECTION 104.2.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 11:14 Rev Time 5.00
Received By kstevens Date 2005-11-12 Time 11:14 Sent To  
Notes
2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 1. SHT A2.0.5 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FEET FOR EACH AREA, PLUS 1/2 AREA
 OF ALL VERTICAL WALLS, INCLUDING
 PARAPETS, AS WELL AS THE AREA OF ALL
 ROOFS THAT DRAIN ONTO EACH AREA FROM
 ABOVE ADDED IN CALCULATIONS. SECTIONS
 1106 & 1107 AND ALL SUBSECTIONS.
 2. A2.1.13 SUBMIT CALCULATIONS FOR THE
 PRIMARY AND SECONDARY ROOF DRAINS FOR
 THE GARAGE. (SEE COMMENT #1 FOR ALL
 INFORMATION REQUIRED IN CALCULATIONS).
 SECTIONS 1106 & 1107.
 3. SHTS A4.0.2, A4.0.2A, A4.0.3,
 A4.0.3A, A4.0.4, & A4.0.4A, NO SHOWER
 BATH ELEVATIONS FOR W/C SHOWN. W/C TO BE
 18" OFF WALL TO CENTER OF FIXTURE. LAV
 TO BE 34" TO FLOOD RIM LEVEL. PAGES 7.43
 AND 7.52 FHA DESIGN MANUAL. SHTS A4.0.7,
 & A4.0.7A W/C TO BE 18" OFF WALL TO
 CENTER OF FIXTURE. (DETAIL E).
 4. SHT A4.0.8 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.1
 BLDG. AND 403.1 PLMG. SHOW SF OF EACH
 COMMON AREA & INDICATE THE OCCUPANCY AND
 OCCUPANCY LOAD OF EACH AREA. ALSO
 INDICATE ROOM DESIGNATION ON PLANS.
 SECTION 104.2.1.
 5. SHT A4.0.8 KITCHEN SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. SUBMIT A DETAIL. FORWARD
 APPROACH CLEAR FLOOR SPACE REQUIRED.
 6. SHT A4.0.10 DETAIL #5, BACKFLOW
 PROTECTION IS REQUIRED FOR THE TRASH
 CHUTE WASHDOWN. SECTION 608. INDICATE
 METHOD OF PROTECTION.
 7. SHT A8.3.1 DETAIL #2 OVERFLOW SCUPPER
 DETAIL, INDICATE HEIGHT & WIDTH OF
 SCUPPER OPENING AND INDICATE THE
 MEASUREMENT ABOVE THE ROOF TO THE FLOW
 LINE AS REQUIRED IN SECTION 1503.4.2.
 8. SHT A8.3.2 DETAIL #5 PRIMARY ROOF
 SCUPPER THRU MANSARD ROOF. SHOW THIS
 SCUPPER AS AN OVERFLOW SCUPPER AND SHOW
 AS REQUIRED PER SECTION 1503.4.2.
 SCUPPER SHALL BE 2" TO 4" ABOVE ROOF TO
 FLOW LINE. PLEASE CLARIFY.
 9. SHT A8.3.2 DETAIL #4 SHT A2.0.5 DOES
 NOT INDICATE WHERE THIS OVERFLOW SCUPPER
 WILL BE LOCATED/USED. PLEASE CLARIFY
 SECTION 104.2.1.
 10. SHT P0.1 WATER HEATER SCHED/DETAIL,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE METHOD.
 11. SHT P2.1.1 4" RWL (800SF) UNIT "A" &
 4" RWL (900SF) UNIT "C" ARE NOT
 CONNECTED TO THE BLDG STORM DRAIN.
 SECTION 104.2.1.
 12. SHT P2.1.1 CLEANOUTS ARE REQUIRED IN
 THE BUILDING SANITARY DRAIN MAX. 100'
 AND IN ALL CHANGE OF DIRECTION GREATER
 THAN 45 DEGREES. SECTIONS 708.3.1 AND
 708.3.3.
 13. SHT P2.1.2 4" RWL (815SF) UNIT C NOT
 CONNECTED TO BLDG STORM DRAIN. SANT.
 RISERS S/C4 & S/C2 NOT CONNECTED TO BLDG
 SANT. DRAIN. PLEASE CLARIFY. SECTION
 104.2.1.
 14. SHT P2.1.4 3/4" COLD WATER SUPPLY TO
 FOUNTAIN SHALL HAVE BACKFLOW PROTECTION.
 SECTION 608. PLEASE INDICATE METHOD.
 15. SHT P2.4.1 ROOF DRAIN, 4 ROOF DRAINS
 SHOW NO DRAIN SIZE OF SF. 2 ROOF DRAINS
 ARE SHOWN IN WRONG LOCATIONS. PLEASE
 CLARIFY. SECTION 104.2.1.
 16. SHT P2.4.2 ROOF DRAINS, 1 ROOF DRAIN
 SHOWS NO DRAIN SIZE OF SF. 1 ROOF DRAIN
 SHOWN IN THE WRONG LOCATION. PLEASE
 CLARIFY. SECTION 104.2.1.
 17. SHT PR.3.3 INSTA HOT WATER HEATER.
 SUBMIT MANUF. SPECIFICATION FOR
 APPROVAL. SHALL BE LISTED. SECTION 303.4
 18. SHT P5.2 RISER S/E4 MAX. 4FU ON 2"
 WET VENT. TABLE 909.3.
 19. SHTS P5.3 & P5.4 SANT. ISOMETRIC
 SHOW DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM. SECTION 104.2.1 & TABLE 710.1(1)
 20. SHT P6.1 DOMESTIC WATER ISOMETRIC
 RISER DIAGRAM, WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 21. SHT P6.2 COMMON AREA DOMESTIC WATER
 ISOMETRIC RISER DIAGRAM, SEE PREVIOUS
 COMMENT.
 22. SUBMIT A STORM RISER DIAGRAM
 ISOMETRIC FOR THE BLDG. STORM DRAIN
 SYSTEM. SHOW ALL PIPE SIZES, RISER
 CONNECTION LOCATION, AND SF AS THEY
 ACCUMULATE IN THE SYSTEM. SECTIONS
 104.2.1 AND 104.3.1.1.
 23. SUBMIT STORM RISER DIAGRAMS FOR EACH
 RWL. SHOW ALL PIPE SIZES AND SF FOR EACH
 RISER. SECTIONS 104.2.1 & 104.3.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-19 Cont ID  
Sent By pkrauss Date 2006-01-19 Time 08:51 Rev Time 0.00
Received By pkrauss Date 2006-01-19 Time 08:51 Sent To  
Notes
2006-01-19 00:00:00PLANS APPROVED BY GRACE JOYCE/SIGNED BY
 MICHELLE MCLEAN.