Plan Review Details - Permit 05090131
Plan Review Stops For Permit 05090131
Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-08-12 Cont ID  
Sent By lmartine Date 2008-08-12 Time 15:37 Rev Time 0.00
Received By lmartine Date 2008-08-12 Time 15:37 Sent To  
Notes
2008-08-12 15:38:29DECK REVISIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-07-18 Cont ID  
Sent By lmartine Date 2008-07-18 Time 09:34 Rev Time 0.00
Received By lmartine Date 2008-07-17 Time 16:53 Sent To  
Notes
2008-07-18 09:45:30BUILDING REVISION COMMENTS
  
  
  
 PROVIDE COMPLETE ATTACHMENT DETAILS TO EXISTING
 STRUCTURES.
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-05-06 Cont ID  
Sent By lmartine Date 2008-05-06 Time 16:08 Rev Time 0.00
Received By lmartine Date 2008-05-06 Time 16:08 Sent To  
Notes
2008-05-06 16:18:54SOFFIT FRAMING REVISION
  
  
  
 PROVIDE TRUSS ENGINEERING FOR ENTIRE ROOF SYSTEM.
  
 HAVE TRUSS ENGINEER CERTIFY ADDITIONAL LOADING OF NEW
 SOFFIT.
  
 SPECIFY SPACING FOR SOFFIT TRUSSES.
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-04-16 Cont ID  
Sent By lmartine Date 2008-04-16 Time 17:11 Rev Time 0.00
Received By lmartine Date 2008-04-16 Time 17:11 Sent To  
Notes
2008-04-16 17:12:07REVISION FOR ENERGY CALCSOK R-19 VS R-30

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-03-18 Cont ID  
Sent By lmartine Date 2008-03-18 Time 13:24 Rev Time 0.00
Received By lmartine Date 2008-03-18 Time 13:21 Sent To  
Notes
2008-03-18 13:22:42FRENCH DOOR REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-04-10 Cont ID  
Sent By alange Date 2006-04-10 Time 09:15 Rev Time 0.50
Received By alange Date 2006-04-10 Time 09:15 Sent To  
Notes
2006-04-10 00:00:00DECK REVISION OK, CHANGE OF ARCHITECT
 LTR. RECEIVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-03-30 Cont ID  
Sent By alange Date 2006-03-30 Time 07:55 Rev Time 1.00
Received By alange Date 2006-03-30 Time 07:55 Sent To  
Notes
2006-03-30 00:00:00DECK REVISION
  
 1.PLANS SHALL BE APPROVED BY THE
 ORIGONALL DESIGNER OF RECORD.
  
 2.SUBMIT PRODUCT APPROVALS FOR STRAPS
 AND TIEDOWNS WITH THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3.ANCHOR DETAIL IS USING 4 3/4" BOLTS
 AT 3" LEDGER. THAT LEAVES ONLY 1 3/4"
 PENETRATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-14 Cont ID  
Sent By alange Date 2005-12-14 Time 09:10 Rev Time 1.50
Received By alange Date 2005-12-14 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-21 Cont ID  
Sent By alange Date 2005-11-21 Time 08:37 Rev Time 1.00
Received By alange Date 2005-11-21 Time 08:37 Sent To  
Notes
2005-11-21 00:00:00DENIED
  
 1.PRODUCT APPROVALS OWENS CORNING AND
 PGT MULLIONS STILL MISSING STATE PRODUCT
 APPROVAL.
 PGT PW-701 HAS THE CORRECT STATE PRODUCT
 APPROVAL.
 ALL PRODUCT APPROVALS REQUIRE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2."R" VALUE ON ENERGY CALCS FOR ROOF
 IS R-30 AND IT IT R-19 ON PLANS. PLEASE
 ADJUST "R VALUE ON PLANS TO MATCH ENERGY
 CALCS.
  
 NOTE: A STOP WORK ORDER HAS BEEN ISSED
 BY INSPECTOR RYAN NUQUIST FOR WORKING
 WITHOUT A PERMIT ON ALL TRADES.
 SEE ATTACHED INVOICE WITH ADDITIONAL
 PERMIT FEES DUE.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 07:26 Rev Time 0.00
Received By alange Date 2005-11-21 Time 08:37 Sent To  
Notes
2005-11-07 00:00:00WORKING ON PROJECT WITHOUT PERMITS , 4X
 FEE ON ALL PERMITS . UNLICENSED PEOPLE
 WORKING .
2005-10-03 00:00:00DENIED
  
 1.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVALS
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2."R" VALUE ON ENERGY CALCS FOR ROOF
 IS R-30 AND IT IS R-19 ON PLANS.PLEASE
 ADJUST R-VALUE ON PLANS.
  
 3.PERSON RESPOSIBLE FOR THE PLANS
 SHALL HAVE A PRINTED NAME AND SIGNATURE
 ON ALL PAGES OF THE PLANS, FBC 104.2.1
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-03-03 Cont ID  
Sent By btrobaug Date 2008-03-03 Time 10:41 Rev Time 0.00
Received By btrobaug Date 2008-02-28 Time 12:06 Sent To PC
Notes
2008-03-03 10:41:52 

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-26 Cont ID  
Sent By btrobaug Date 2007-06-26 Time 16:31 Rev Time 0.00
Received By btrobaug Date 2007-06-26 Time 16:17 Sent To PC
Notes
2007-06-26 16:30:55 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE DESIGNER OF RECORD MUST MAKE ALL CHANGES/REVISIONS,
 TO HIS/HER DRAWINGS.PER STATUTES. ALSO SHEETS BEING
 REVISED MUST BE ON THE SHEET BEING REVISED, IN THIS
 CASE AN ELECTRICAL SHEET , NOT ARCHITECTURAL.THAT
 DESIGNER MUST PRINT AND SIGN THEIR NAME TO THE PLANS .
  
 THE REVISION SUBMITTED SHALL BE CLEARLY MARKED WITH
 CLOUDS, TRIANGLES OR SOME MEANS TO IDENTIFY THEM FROM
 THE ORIGINAL PLAN. 106.1.3 FBC..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-11-08 Cont ID  
Sent By btrobaug Date 2005-11-08 Time 17:53 Rev Time 0.50
Received By btrobaug Date 2005-11-08 Time 17:23 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-27 Cont ID  
Sent By btrobaug Date 2005-09-27 Time 15:20 Rev Time 0.75
Received By btrobaug Date 2005-09-27 Time 13:54 Sent To M
Notes
2005-09-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON RESPONSIBLE FOR THE PLANS
 MUST PRINT THEIR NAME AND SIGN SAME.
 104.2.1 FBC
  
 2} THE LOAD CALCULATION DOES NOT INCLUDE
 THE HOT TUB.
  
 3} THE PANEL SCHEDULE DOES NOT INDICATE
 COMPLIANCE WITH 210.11(C)(3) FOR THE
 BATH CIRCUITS. THE PLAN ALSO SHOWS THE
 CICUITS THEY ARE ON EXTENDING OUTSIDE
 THE BATHROOM.
  
 4} SHOW COMPLIANCE WITH 225.31 AND
 250.32 FOR ALL SEPERATE STRUCTURES. THIS
 CAN BE DONE ON THE RISER DIAGRAM.
  
 5} PLEASE SEE THE REVIEWED SET OF PLANS.
 SMOKE DETECTORS ARE REQUIRED OUTSIDE OF
 THE SLEEPING AREA AS WELL AS INSIDE.
 SEE 8-1.4.1.6.2 NFPA-72.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 16:52 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 16:52 Sent To B
Notes
2008-07-31 16:52:32TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-06-30 Cont ID  
Sent By adarroug Date 2008-06-30 Time 11:25 Rev Time 0.00
Received By adarroug Date 2008-06-30 Time 11:25 Sent To Z
Notes
2008-06-30 11:25:34TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 10:46 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 10:46 Sent To B
Notes
2008-04-16 10:47:06TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 09:04 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 09:04 Sent To P
Notes
2008-04-04 09:04:46TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 14:45 Sent To P
Notes
2008-03-12 14:45:26TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-03-12 Cont ID  
Sent By adarroug Date 2008-03-12 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-03-12 Time 14:37 Sent To B
Notes
2008-03-12 14:37:55TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 08:48 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 08:48 Sent To B
Notes
2008-03-06 08:48:45TO "LMARTINEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 08:38 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 08:38 Sent To P
Notes
2008-03-06 08:39:10TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 15:18 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 15:18 Sent To E
Notes
2008-02-26 15:19:37TO "BTROBAUGH" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 11:35 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 11:35 Sent To E
Notes
2007-06-20 11:36:14TO "BTROBAUG' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-11-16 Cont ID  
Sent By adarroug Date 2006-11-16 Time 11:30 Rev Time 0.00
Received By adarroug Date 2006-11-16 Time 11:30 Sent To P
Notes
2006-11-16 11:30:26TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 10:05 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 10:05 Sent To B
Notes
2006-04-05 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 14:33 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 14:32 Sent To B
Notes
2006-03-24 00:00:00TO AL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2005-12-07 Cont ID  
Sent By adarroug Date 2005-12-07 Time 10:37 Rev Time 0.00
Received By adarroug Date 2005-12-07 Time 10:37 Sent To B
Notes
2005-12-07 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-11-08 Cont ID  
Sent By adarroug Date 2005-11-08 Time 14:52 Rev Time 0.00
Received By adarroug Date 2005-11-08 Time 14:52 Sent To E
Notes
2005-11-08 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-10-11 Cont ID  
Sent By adarroug Date 2005-10-11 Time 09:30 Rev Time 0.00
Received By adarroug Date 2005-10-11 Time 09:30 Sent To Z
Notes
2005-10-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-21 Cont ID  
Sent By adarroug Date 2005-09-21 Time 19:28 Rev Time 0.00
Received By adarroug Date 2005-09-21 Time 19:28 Sent To E
Notes
2005-09-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-03 Cont ID  
Sent By alange Date 2005-10-03 Time 07:34 Rev Time 0.00
Received By alange Date 2005-09-08 Time 15:39 Sent To  
Notes
2005-09-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By tgordon Date 2005-09-29 Time 15:25 Rev Time 0.15
Received By tgordon Date 2005-09-29 Time 15:25 Sent To P
Notes
2005-09-29 00:00:00NOTE: MECH. PLANS OR CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-04-08 Cont ID  
Sent By jleech Date 2008-04-08 Time 09:23 Rev Time 0.00
Received By jleech Date 2008-04-08 Time 09:22 Sent To  
Notes
2008-04-08 09:26:01LETTER FROM ARCHITECT EXCEPTING RESPOSIBLITY FOR SHOWER
 PAN INSTALLATION. PLAN WAS NOT TESTED OR INSPECTED AS
 REQUIRED.

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-03-17 Cont ID  
Sent By jleech Date 2008-03-17 Time 09:12 Rev Time 0.00
Received By jleech Date 2008-03-17 Time 08:54 Sent To  
Notes
2008-03-17 09:13:37REVISED RISER DIAGRAM.

Review Stop P PLUMBING
Rev No 4 Status F Date 2008-03-07 Cont ID  
Sent By jleech Date 2008-03-07 Time 09:24 Rev Time 0.00
Received By jleech Date 2008-03-07 Time 09:06 Sent To  
Notes
2008-03-07 09:38:57REVISION DENIED;
 1. RISER DIAGRAM NOT TO CODE, BIDET IS NOT VENTED.
 2. RISER DIAGRAM NOT TO FLOOR PLAN;
 A) 2 W/M'S AND 2 L/T'S SHOWN ON RISER
 DIAGRAM ONLY ONE SHOWN ON PLANS.
 B) LAVATORY FOR BATH #1 MISSING FROM
 RISER DIAGRAM.
 C) TUB SHOWN IN BATHROOM # 1 ON RISER
 DIAGRAM NOT SHOWN ON FLOOR PLAN.
 D) REVISED RISER DIAGRAM REVIEWED DEC. 9
 TH 2006 SHOWS A SEWAGE PUMP ADDED TO RISER DIAGRAM, NOT
 SHOWN ON THIS DIAGRAM
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-12-09 Cont ID  
Sent By jleech Date 2006-12-09 Time 12:41 Rev Time 0.00
Received By jleech Date 2006-12-09 Time 12:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-11-18 Cont ID  
Sent By jleech Date 2005-11-18 Time 08:27 Rev Time 0.50
Received By jleech Date 2005-11-18 Time 08:27 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-09-29 Cont ID  
Sent By jleech Date 2005-09-29 Time 17:39 Rev Time 0.75
Received By jleech Date 2005-09-29 Time 17:39 Sent To B
Notes
2005-09-29 00:00:00DENIED;
 1.FBC-2001 FUEL GAS SEC303.3 WATER
 HEATER IS NOT PERMITED IN A BATHROOM. IF
 A DOOR IS INSTALLED IT MUST HAVE WEATHER
 STRIPING AROUND GAM AND A THESHOLD MUST
 BE INSTALLED, ALSO SHOW MEANS OF
 COMBUSTION AIR FOR WATER HEATER SEE
 FBC-2001 FUEL GAS SEC. 304.4.2.
 2.SUBMIT INSTALLATION INSTRUCTION FOR
 GAS HOT TUB, MAY NOT BE PROMITED ON WOOD
 PORCH.
 3.SANITARY RISER DIAGRAM IS NOT TO CODE.
 NOT PROPERLY VENTED.
 DONOT SHOW A TRAP FOR W/C TRAP IS
 BUILT INTO THE TOILET.
 ONE SET OF PLANS ARE MARKED IN RED
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-07-03 Cont ID  
Sent By jroach Date 2008-07-03 Time 08:24 Rev Time 0.00
Received By jroach Date 2008-07-03 Time 08:24 Sent To B
Notes
2008-07-03 15:05:09***APPROVED - REVISION***

Review Stop Z ZONING
Rev No 2 Status P Date 2005-11-07 Cont ID  
Sent By jroach Date 2005-11-07 Time 12:23 Rev Time 0.00
Received By jroach Date 2005-11-07 Time 12:23 Sent To  
Notes
2005-11-07 00:00:00GIVEN TO INCOMING MM

Review Stop Z ZONING
Rev No 1 Status F Date 2005-09-13 Cont ID  
Sent By jroach Date 2005-09-13 Time 14:01 Rev Time 0.00
Received By jroach Date 2005-09-13 Time 14:01 Sent To  
Notes
2005-09-13 00:00:009/13/05 ***FAILED***
  
 1) SITE PLAN, SURVEY, ETC. SHALL BE
 ADJUSTED TO SHOW THAT THE NEW BUILDINGS
 ARE CONNECTED TO THE EXISTING RESIDENCE
 AND THAT THEY ARE ONE (1) STRUCTURE,
 WITH THE EXCEPTION OF THE SHED.
  
 2) ADJUST SITE PLAN, FOUNDATION PLAN,
 ETC. TO SHOW THAT ONLY A SLAB IS TO BE
 PROVIDED BETWEEN THE SHED AND THE NEW
 STRUCTURE.NO FOOTERS, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH
 AT (561) 822-1435.