Plan Review Details - Permit 05090097
Plan Review Stops For Permit 05090097
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 13:30 Rev Time 0.00
Received By alange Date 2005-10-04 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2005-10-04 Cont ID  
Sent By alange Date 2005-09-29 Time 13:51 Rev Time 0.50
Received By alange Date 2005-09-29 Time 13:51 Sent To  
Notes
2005-09-29 00:00:00DENIED
  
 1.CLEARLY SHOW EXISTING WALLS AND NEW
 WALLS ADDED.
  
 2.SUBMIT A INTERIOR FRAMING DETAIL.
  
 3.PERSON RESPOSIBLE FOR THE DESIGN
 SHALL SIGN ALL PAGES.FBC 104.2.1
  
 ANY QUESTIONS CALL ME
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By jleahy Date 2005-09-13 Time 23:39 Rev Time 0.30
Received By alange Date 2005-09-13 Time 23:37 Sent To M
Notes
2005-10-04 00:00:00PLANS STAMPED OK BY JAKE BUT NOT ENTERED
 OKALANGE
2005-09-13 00:00:00LAYOUT IS NOT CLEAR PLEASE SHOW KITCHEN
 LAYOUT WITH ALL EXISTING AND NEW
 ELECTRIC.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-30 Cont ID  
Sent By adarroug Date 2005-09-30 Time 14:34 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 14:34 Sent To E
Notes
2005-09-30 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-29 Cont ID  
Sent By alange Date 2005-09-29 Time 13:55 Rev Time 0.00
Received By alange Date 2005-09-06 Time 16:45 Sent To  
Notes
2005-09-06 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-10-04 Cont ID  
Sent By alange Date 2005-10-04 Time 13:32 Rev Time 0.15
Received By tgordon Date 2005-10-04 Time 09:57 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-09-15 Cont ID  
Sent By tgordon Date 2005-09-15 Time 09:41 Rev Time 0.15
Received By tgordon Date 2005-09-15 Time 09:41 Sent To P
Notes
2005-09-15 00:00:00*** DENIED ***
 1) NEED MORE INFORMATION ON GAS RANGE
 AND PLACEMENT.
 2) NEED DETAILED INFORMATION ON HOOD
 SIZE AND EXHAUST DUCTS.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-09-20 Cont ID  
Sent By jleech Date 2005-09-20 Time 15:04 Rev Time 0.25
Received By jleech Date 2005-09-20 Time 15:04 Sent To B
Notes
2005-09-20 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW.