Plan Review Details - Permit 05090073
Plan Review Stops For Permit 05090073
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-18 Cont ID  
Sent By shill Date 2006-04-18 Time 11:04 Rev Time 0.00
Received By shill Date 2006-04-18 Time 10:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-23 Cont ID  
Sent By shill Date 2006-01-23 Time 12:00 Rev Time 0.00
Received By shill Date 2006-01-23 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-07 Cont ID  
Sent By shill Date 2005-11-07 Time 17:26 Rev Time 1.00
Received By shill Date 2005-11-07 Time 17:26 Sent To  
Notes
2005-11-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)DECLARE THE OCCUPANCY FOR THIS
 IMPROVEMENT THE OCCUPANCY FOR THE
 ADJACENT TENANT.
  
 3.)THE BUILDING IS REQUIRED TO BE
 ACCESSIBLE.THERE ARE EXCEPTIONS IN THE
 CODE RELATED TO VERTICAL ACCESSIBILITY
 OR IN CASES WHERE IT IS STRUCTURALLY
 IMPRACTICABLE, BUT THESE EXCEPTIONS DO
 NOT APPLY.SEE FBC11-4.1.1(3), AREAS
 USED ONLY BY EMPLOYEES AS WORK AREAS.
  
 4.)SHOW ACCESSIBLE ROUTE,
 FBC11-4.1.2(1).
  
 5.)THE BATHROOM IS TO BE ACCESSIBLE.
 PROVIDE ALL DETAILS INCLUDING ALL
 DIMENSIONS.FBC11.
  
 6.)FBC11-4.1.3(9), ACCESSIBLE MEANS OF
 EGRESS SHALL BE PROVIDED IN THE SAME
 NUMBER AS REQUIRED FOR EXITS BY LOCAL
 BUILDING/LIFE SAFETY REGULATIONS.IT
 APPEARS THAT ONLY THE FRONT DOOR IS AN
 ACCESSIBLE EXIT.THE OTHER TWO APPEAR
 TO HAVE A LANDING OUTSIDE THE DOOR.
  
 7.)FOR THE EXISTING 2 HOUR WALL,
 PROVIDE AN APPROVED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE, FBC7.
  
 8.)FOR THE INFILL FOR THE 2 HOUR WALL,
 PROVIDE AN APPROVED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE, FBC7.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-04-13 Cont ID  
Sent By dpalmer Date 2006-04-13 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2006-04-12 Time 18:37 Sent To  
Notes
2006-04-13 00:00:00**********UNSAT 3RD REVIEW *********
  
 1) NOTE: PLEASE SEE VALUATION FOR
 COMPLETE SCOPE OF WORK IS STILL NOT
 BEING ADJUSTED BY THE CONTRACTOR WHEN
 RESUBMITTING PLANS AND A VALUE CAN NOT
 BE VERIFIED AT THIS TIME.
 PLEASE PROVIDE ALL SIGNED CONTRACTS FOR
 EQUIPMENT BEING INSTALLED AND LABOR.
 THIS WAS REQUESTED ON TWO PREVIOUS
 REVIEWS TO ADJUST VALUE FOR SCOPE AS
 VALUE WAS WAY TOO LOW AND DID NOT
 REFLECT WORK BEING DONE.
 PLEASE SEE FBC ADMISTRATIVE SECITON
 104.6.5,2001) 108.3 2004.
 SHALL INCLUDE ALL LABOR AND MATERIALS,
 EVEN IF EQUIPMENT IS OWNER SUPPLIED.
 PLEASE SEE THIS WOULD INCLUDE, GEN,
 TANK, ATS, ELECTRICAL SERVICE, AND ALL
 EQUIPMENT BRING INSTALLED INSIDE ROOM
 ALONG WITH ANY VALUE FOR OTHER TRADES.
 PLEASE SEE ORIGINAL VALUE WAS APPLIED
 FOR AT $17K AND THENA VALUE WAS PLACED
 ON APPLICATION FOR $67K.
 PLEASE SEE APPLICATION NOW CONTAINS
 "WHITE-OUT " WHERE BACK UP DIESEL
 GENERATOR WAS? IS THIS NO LONGER IN
 SCOPE? PLANS HOWEVER STILL INDICATE A
 GENERATOR. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUESTED ON
 APPLICATION AND CORRELATE WITH THE
 PLANS.
 IT IS NOW UNCLEAR FI GEN IS STILL PART
 OF THIS PROJECT??
  
 2) NOTE: PLEASE SEE SPECS FOR ATS IS THE
 SAME SPECS THAT WERE SUBMITTEDON THE
 PREVIOUS REVIEW.
 PLEASE SEE NO DISCONNECTING MEANS RATED
 FOR THE LOAD SERVED, GROUPED, LOCATED ON
 THE OUTSIDE OF THE EQUIPMENT COULD BE
 LOCATED.?
 230.76.230.79,230.72,225.31-225.39
  
 3) NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS.
 PLEASE SEE ONE SET HAS MULTIPLE E-SHEETS
 WHICH ARE REPEATED AND CONTAIN TWO
 DIFFERENT DATES SIGNED, DATED AND SEALED
 BY THE ENGINEER?
 PLEASE SEE ONE SET STARTS WITH E-4 AND
 E-5 DATED 2/27/06 AND THEN STARTS OVER
 AGAIN WITHE NEWER DATED SHEETS DATED
 3/3/06??
  
  
 4) NOTE: PLEASE SEE COVER SHEET MENTIONS
 2005 NEC, WE ARE CURRENTLY UNDER THE
 2002 NEC, THIS CAN BE REDLINED.
  
 ** PLEASE SEE COMMENTS FROM MECHANICAL
 REVIEWER WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-04-12 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-11 Cont ID  
Sent By dpalmer Date 2006-01-11 Time 09:45 Rev Time 0.00
Received By dpalmer Date 2006-01-11 Time 08:37 Sent To I
Notes
2006-01-11 00:00:00**** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STTILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE NEW NOTES DUE TO SOME
 CHANGES IN PLANS.
  
  
 1)NOTE: NOTE #1 NO.
 THE PERMIT APPLICATION NOW MENTIONS A
 VALUE OF $67,000, HOWEVER THIS VALUE IS
 NOT APPROPRIATE FOR SCOPE OF WORK, ALL
 LABOR AND MATERIALS.
 PLEASE KNOW, EVEN IF EQUIPMENT IS OWNER
 SUPPLIED, THE VALUE SHALL BE INLCUDED.
 WHEN RESUBMITTED , PLEASE HAVE VALUE
 INCREASED AT THAT TIME. IF VALUE IS NOT
 ADJUSTED FOR THE FOLLOWING REVIEW, ONE
 WILL BE ASSESSED. 104.6.5
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, PLEASE SEE PANEL DP1
 IS NOW BEING SHOWN AS A MCB, HOWEVER
 PLEASE SEE FEEDERS FROM ATS (FIRST MEANS
 OF DISCONNECT) TO THIS DP1. AS PER SPECS
 FOR ATS SUBMITTED, THE ATS DOES NOT
 CONTAIN A MANUAL MEANS OF DISCONNECT
 LOCATED ON THE OUTSIDE OF THE EQUIPMENT
 RATED FOR THE LOAD SERVED AS REQUIRED
 PER 230.76, 230.79.
 PLEASE SEE THE SPECS DO INDICATE A
 MANUAL SWITCH, HOWEVER NOTES AS BEING
 FOR NEMA 1 LOCATION ONLY. PLEASE SEE
 THIS ATS IS LOCATED OUTSIDE.
 THIS ATS ALSO NOT INDICATE BEING RATED
 AS SERVICE ENTRANCE AS REQUIRED.
 PLEASE SEE A DISCONNECTING MEANS MAY BE
 INSTALLED FROM METER/CT TO THE ATS AND
 ANOTHER DISCONNECT FROM GEN TO ATS,
 GROUPED AS REQUIRED BY 230.72,225.34 AND
 THE MCB WOULD NOT BE REQUIRED IN PANEL
 DP1.
 THIS IS ONLY ONE POSSIBLE METHOD.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 OK.
  
 7)NOTE: NOTE # 7 OK.
  
 8)NOTE: NOTE #8 OK, HOWEVER PLEASE SEE
 NOTES FOR REVIEW OF SPECS.
  
 9)NOTE: NOTE # 9 OK.
  
 NEW NOTE;
  
 1)NOTE: PLEASE SEE PLANS WERE ORIGINALLY
 SINED , DATED AND SEALED BY AN ENGINEER
 OF RECORD AS REQUIRED, HOWEVER NOW PLANS
 ARE COMING BACK SIGNED AND SEALED BY AN
 ARCH??
 PLEASE SEE SCOPE OF WORK REQUIRES THE
 EELCTRICAL PLANS TO BE DONE BY AN
 ENGINEER AND ANOTHER DESIGNER MAY NOT
 SIGN AND SEAL ANOTHER DESIGNERS WORK.
 FS 481, 471.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-30 Cont ID  
Sent By dpalmer Date 2005-09-30 Time 07:47 Rev Time 1.25
Received By dpalmer Date 2005-09-29 Time 20:52 Sent To  
Notes
2005-09-30 00:00:00************** UNSAT ************
  
 1)NOTE: PLEASE SEE VALUATION SHALL BE
 BASED ON ALL LABOR AND MATERIALS EVEN IF
 MATERIALS ARE OWNER SUPPLIED.
 THIS WOULD ALSO INCLUDE ALL OTHER
 PERMANANTLY INSTALLED EQUIPMENT IE: DC
 SYSTEM, ETC
 PLEASE KNOW A VALUE WILL BE ACCESSED BY
 THIS OFFICE IF NOT ADJUSTED BY
 CONTRACTOR.
 THIS WOULD INCLUDE ALL ELECTRICAL
 EQUIPMENT , GENERATOR ETC.
 FBC 104.6.5, ADMINISTRATIVE AMENDMENTS.
  
 2)NOTE: PLEASE CORRELATE PLANS, ONE
 SHEET INDICATES GENERATOR TO BE A MOBILE
 UNIT WITH SOME SORT OF TAP BOX?
 PLANS AND SUBMITTALS ALSO DO NOT REFLECT
 THIS AND SHOWS A PERMANANTLY INSTALLED
 GEN ETC.??
 215.5
  
 3)NOTE: PLEASE INSTALLED A DISCONNECT
 FOR FEEDERS COMING FROM GENERATOR AT
 BLDG.
 THIS MEANS OF DISC SHALL BE GROUPED WITH
 OTHER MAINS AND RATED FOR THE LOAD
 SERVED.
 PLEASE SEE 225.31-225.39,110.27 ETC.
 A MCB MAY BE INSTALLED IN DP1 WHICH NOW
 INDICATES BEING A MLO.
 SIGNAGE WILL BE REQUIRED, 230.2E, 702.8
 ETC
  
 4)NOTE: PLEASE CLARIFY DOOR/ WINDOW
 WHICH IS SHOWN ON PLANS?
 IF A MEANS OF EXIT, SEE FIRE REVIEW
 COMMENTS FOR ANY EXT LT WHICH MAY BE
 REQUIRED.
  
 5)NOTE: PLEASE SEE "TAP BOX" AS SHOWN
 WILL NOT MEET THE DISCONNECTING MEANS
 REQUIRED.
  
 6)NOTE: PLEASE SHOW LOCATION OF ALL ASSC
 GEN EQUIPMENT.
 PLEASE SHOW LOCATION OF GEN STATUS
 PANEL.
 215.5
  
 7)NOTE: PLEASE INCLUDED COLD WATER PIPE
 IN GROUNDING DETAIL FOR SERVICE.
 250.50
  
 8)NOTE: PLEASE SUBMIT TWO COPIES OF ALL
 MANUFACTURES SPEC/CUT SHEETS FOR GEN
 ETC.
 PLEASE SEE ONLY ONE SET WAS SUBMITTED.
 PLEASE ALSO INLCUDE SPECS/CUT SHEETS FOR
 ATS.
 PLEASE ALSO SUBMIT ALL SPECS/INFORMATION
 ON DC SYSTEM PROPOSED.
 THIS EQUIPMENT
  
 9)NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS ADDRESS AS "OLD OKEECHOBEE"
 PLEASE KNOW AND SEE BLDG REVIEW
 COMMENTS, THIS SHOULD READ "OKEECHOBEE
 RD".
 PLEASE ALSO ADJUST ON PLANS/TITL BLOCK.
  
  
 PLEASE COMPLETELY REMOVE ANY OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2005-09-29 00:00:00NOTES TO FOLLOW.
 PLANS WILL BE IN "F" STATUS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-04-19 Cont ID  
Sent By mwennerg Date 2006-04-19 Time 09:53 Rev Time 0.00
Received By mwennerg Date 2006-04-19 Time 09:53 Sent To  
Notes
2006-04-19 00:00:00******APPROVED******
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE PROTECTION AND FIRE
 ALARM SYSTEMS.
  
 2) PLEASE INCLUDE SPEC SHEETS AND
 CALCULATIONS WITH SUBMITTALS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By mcarsill Date 2006-01-20 Time 14:01 Rev Time 0.00
Received By mcarsill Date 2006-01-20 Time 14:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-09 Cont ID  
Sent By mwennerg Date 2005-11-09 Time 13:33 Rev Time 0.00
Received By mwennerg Date 2005-11-09 Time 13:33 Sent To  
Notes
2005-11-09 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIRE SUPPRESSION AND ALARM
 SYSTEMS.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 STILL REQUIRED TO BE MOUNTED SO THAT
 TRAVEL DISTANCE DOESN'T EXCEED 75'.
  
 3) PLEASE PROVIDE (2) COPIES OF
 MANUFACTURER SPEC SHEETS FOR GENERATOR.
  
 4) DOES THE STORE ROOM MEET THE
 REQUIREMENT FOR A SINGLE EXIT IN
 ACCORDANCE WITH NFPA 101, 2003 EDITION?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 14:48 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 14:48 Sent To  
Notes
2006-04-05 00:00:00TO "COMM" BD#27
2006-03-09 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-12 Cont ID  
Sent By adarroug Date 2005-12-12 Time 19:20 Rev Time 0.00
Received By adarroug Date 2005-12-12 Time 19:20 Sent To  
Notes
2006-01-13 00:00:00TO "COMM" BD#63
2005-12-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 15:47 Sent To  
Notes
2005-09-13 00:00:00TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-11-10 Time   Rev Time 0.00
Received By shill Date 2005-09-13 Time 15:56 Sent To  
Notes
2005-09-08 00:00:009/8/05PLANS REMOVED FROM BD AND PICKED
 UP BY CONTRACTOR
2005-09-07 00:00:00TO "COMM" BD#30

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-04-12 Cont ID  
Sent By hmoser Date 2006-04-12 Time 13:29 Rev Time 0.00
Received By hmoser Date 2006-04-17 Time 06:55 Sent To  
Notes
2006-04-12 00:00:00PLAN DENIED
 1) PLEASE COMPLY WITH SECTION 502.4 AND
 502.4.2 2004 FBC(M).
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-02-06 Cont ID  
Sent By hmoser Date 2006-02-06 Time 11:50 Rev Time 0.00
Received By hmoser Date 2006-02-06 Time 11:36 Sent To  
Notes
2006-02-06 00:00:00PLAN DENIED
 PLEASE REFER TO SECTION 502.5 VALAE
 REGULATED LED ACID BATTERIES.2004 FBC M
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-10 Cont ID  
Sent By pkrauss Date 2005-11-10 Time 08:05 Rev Time 1.00
Received By pkrauss Date 2005-11-10 Time 08:05 Sent To  
Notes
2005-11-10 00:00:00DENIED:
 1.PLEASE SHOW COMPLIANCE WITH 2004 FMC
 502.3 & 502.4.
  
 2.PROVIDE DETAIL FOR THE CONDENSING
 UNITS ANCHORING TO THE SLAB, REFERENCE
 2004 FMC 301.13.
  
 3.PLEASE PROVIDE ANCHORING DETAIL FOR
 THE GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL, [email protected].
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-04-15 Cont ID  
Sent By pschmitz Date 2006-04-15 Time 13:20 Rev Time 0.00
Received By pschmitz Date 2006-04-15 Time 13:20 Sent To  
Notes
2006-04-15 00:00:00RE- SUB

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-11 Cont ID  
Sent By pschmitz Date 2006-02-11 Time 12:35 Rev Time 0.00
Received By pschmitz Date 2006-02-11 Time 12:35 Sent To  
Notes
2006-02-11 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC BUILDING 2004, CH 11
 DENIED
 NEW COMMENTS
  
 1) SHT.P-1 WATER RISER.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER
 DISTRIBUTION SYSTEM SHALL BE CONTROLLED
 TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE
 INSTALLED WHERE QUICK-CLOSING VALVES ARE
 UTILIZED. WATER-HAMMER ARRESTORS SHALL
 BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS.
 WATER-HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010.
  
 2)SHT.P-1 WATER RISER.
 606.1 LOCATION OF FULL-OPEN VALVES.
 FULL-OPEN VALVES SHALL BE INSTALLED IN
 THE FOLLOWING LOCATIONS:
 4.ON THE TOP OF EVERY WATER DOWN-FEED
 PIPE IN OCCUPANCIES OTHER THAN ONE- AND
 TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
 3)SHT.P-1 WATER RISER, DEHUM 1,2
 608.3 DEVICES, APPURTENANCES, APPLIANCES
 AND APPARATUS.
 ALL DEVICES, APPURTENANCES, APPLIANCES
 AND APPARATUS INTENDED TO SERVE SOME
 SPECIAL FUNCTION, SUCH AS STERILIZATION,
 DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT
 CONNECT TO THE WATER SUPPLY SYSTEM,
 SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF
 THE WATER SUPPLY SYSTEM. WATER PUMPS,
 FILTERS, SOFTENERS, TANKS, COMMERCIAL
 DRINKING WATER DISPENSERS AND ALL OTHER
 APPLIANCES AND DEVICES THAT HANDLE OR
 TREAT POTABLE WATER SHALL BE PROTECTED
 AGAINST CONTAMINATION.
  
 4)SHT A-3 MINIMUM NUMBER OF REQUIRED
 PLUMBING FIXTURES. TAB.403.1
 4 FACTORY AND INDUSTRIAL STRUCTURES IN
 WHICH OCCUPANTS ARE ENGAGED IN WORK
 FABRICATING, ASSEMBLY OR PROCESSING OF
 PRODUCTS OR MATERIALS.
 1 SERVICE SINK REQUIRED.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-12 Cont ID  
Sent By kstevens Date 2005-11-12 Time 15:21 Rev Time 1.25
Received By kstevens Date 2005-11-12 Time 15:21 Sent To  
Notes
2005-11-12 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 1. ALL SHEETS, ADDRESS IS OKEECHOBEE RD,
 NO "OLD" IN ADDRESS. PLEASE CORRECT
 TITLE BLOCK INFORMATION. FAC
 61G1-16.004(3).
 2. SHT A-3 SPECIAL NOTE: REFERENCE
 11-4.1.2 IS FOR NEW CONSTRUCTION.
 REFERENCE TO USE FOR ALTERNATIONS IS
 11-4.1.6(K)(III). PLEASE CHANGE
 REFERENCE.
 3. SHT P-0 CODES AND STANDARDS, CODES
 AD0PTED ARE FBC-2004 NOT THE STANDARD
 CODES. PLEASE CHANGE CODE REFERENCE.
 - PLUMBING & DRAINAGE PIPING. REFERENCE
 TO STANDARD CODE TO BE CHANGED TO
 FBC-2004.
 - SOLDER SHALL CONFORM TO ASTM B 32.
 4. SHT P-1 MINIMUM 1 VENT THRU ROOF PER
 BUILDING PER SECTION 903.1. INDICATE THE
 LOCATION OF THE VTR FOR THIS BUILDING.
 5. SHT P-1 SANT. RISER (DETAIL D) DOES
 NOT REFLECT THE FLOOR LAYOUT (DETAIL B).
 THE FLOOR DRAIN IS SHOWN CONNECTING AT
 THE LAV ARM ON THE FLOOR PLAN. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 106.1.1.
 6. SHT P-1 DETAIL E AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM RISER DIAGRAM.
 SECTION 604.9
 7. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR THE INSTA HOT WATER HEATER. MUST BE
 LISTED. SECTION303.4 & TABLE 303.4.
 8. SHT P-2 DETAIL DOES NOT REFLECT THE
 WATER RISER DIAGRAM. PLEASE CORRELEATE.
 SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]