| Plan Review Stops For Permit 05090030 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-17 |
Time |
16:14 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-10-17 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-17 |
Time |
13:37 |
Rev Time |
0.33 |
| Received By |
alange |
Date |
2005-09-19 |
Time |
13:17 |
Sent To |
M |
|
| Notes |
| 2005-09-19 00:00:00 | ****CORRECTIONS**** | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | 2.)SUBMIT TWO COPIES OF PLANS AND HAVE | | | PLANS SIGNED BY THE PERSON RESPONSIBLE | | | FOR THE DESIGN. | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUIDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-10-14 |
Time |
12:58 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2005-10-13 |
Time |
07:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-09-16 |
Time |
14:26 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2005-09-16 |
Time |
13:39 |
Sent To |
M |
|
| Notes |
| 2005-09-16 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLANS MUST CONTAIN THE PRINTED NAME | | | AND SIGNATURE OF THE DESIGNER PER | | | 104.2.1.FBC | | | | | | 2} TWO SETS OF PLANS ARE TO BE SUBMITTED | | | FOR REVIEW PER 104.2.1.FBC | | | | | | 3} THE TRNSFER SWITCH MUST BE SERVICE | | | RATED OR MUST HAVE A RATED DISCONNECT | | | AHEAD (GENERATOR SIDE) OF IT | | | ELECTRICALLY. | | | | | | 4} PLEASE SUBMIT A SITE PLAN INDICATING | | | THE LOCATION OF ALL SERVICE AND | | | GENERATOR EQUIPMENT SO THAT COMPLIANCE | | | WITH 225.31 THROUGH 225.37 CAN BE | | | REVIEWED. | | | | | | 5} INDICATE THE FUEL TYPE PROPOSED AS | | | PRIME MOVER. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2005-09-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-17 |
Time |
13:38 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-09-17 |
Time |
13:38 |
Sent To |
M |
|
| Notes |
| 2005-09-17 00:00:00 | GAS PERMIT REQUIRED. GAS CONTRACTOR TO | | | SUBMIT PLANS WITH APPLICATION. GAS | | | PERMIT MUST BE ON JOB AND SIGNED OFF | | | BEFORE FINAL GENERATOR INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2005-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-12 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-12 |
Time |
15:38 |
Sent To |
E |
|
| Notes |
| 2005-10-12 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2005-09-30 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-11 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-30 |
Time |
09:30 |
Sent To |
Z |
|
| Notes |
| 2005-09-30 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-13 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-13 |
Time |
11:29 |
Sent To |
E |
|
| Notes |
| 2005-09-13 00:00:00 | TO "GEN-RES" BOX "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-02 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-02 |
Time |
15:34 |
Sent To |
Z |
|
| Notes |
| 2005-09-02 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
N |
Date |
2005-10-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-10-14 |
Time |
14:16 |
Rev Time |
0.10 |
| Received By |
tgordon |
Date |
2005-10-14 |
Time |
14:16 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-19 |
Time |
14:35 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2005-09-19 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2005-09-19 00:00:00 | *** PROVISO *** | | | 1) GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | | TEN FEET AWAY FROM ADJECENT DUILDING | | | OPENINGS. 2001 FBC/M 804.3.3 . | | | IF YUO HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. | | 2005-09-17 00:00:00 | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-11 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-11 |
Time |
14:03 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-10-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-12 |
Time |
17:47 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-12 |
Time |
17:47 |
Sent To |
I |
|
| Notes |
| 2005-09-12 00:00:00 | DENIED, | | | 1. MUST PROVIDE TWO COPY OF CURRENT | | | SURVEY SHOWING THE LOCATION OF THE | | | GENERATOR | | | 2. MUST PROVIDE THE DIMENSON OF THE | | | GENERATOR AND THE SETBACK OF THE | | | GENERATOR FROM THE STRUCTURE & PROPERTY | | | LINE | | | | | | NOTE: GENERATOR CAN ONLY BE 4FT INTO | | | SETBACK. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|