Plan Review Details - Permit 05090030
Plan Review Stops For Permit 05090030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 16:14 Rev Time 0.33
Received By alange Date 2005-10-17 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By jleech Date 2005-09-17 Time 13:37 Rev Time 0.33
Received By alange Date 2005-09-19 Time 13:17 Sent To M
Notes
2005-09-19 00:00:00****CORRECTIONS****
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)SUBMIT TWO COPIES OF PLANS AND HAVE
 PLANS SIGNED BY THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUIDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-10-14 Cont ID  
Sent By btrobaug Date 2005-10-14 Time 12:58 Rev Time 0.33
Received By btrobaug Date 2005-10-13 Time 07:16 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-16 Cont ID  
Sent By btrobaug Date 2005-09-16 Time 14:26 Rev Time 0.50
Received By btrobaug Date 2005-09-16 Time 13:39 Sent To M
Notes
2005-09-16 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLANS MUST CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE DESIGNER PER
 104.2.1.FBC
  
 2} TWO SETS OF PLANS ARE TO BE SUBMITTED
 FOR REVIEW PER 104.2.1.FBC
  
 3} THE TRNSFER SWITCH MUST BE SERVICE
 RATED OR MUST HAVE A RATED DISCONNECT
 AHEAD (GENERATOR SIDE) OF IT
 ELECTRICALLY.
  
 4} PLEASE SUBMIT A SITE PLAN INDICATING
 THE LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT SO THAT COMPLIANCE
 WITH 225.31 THROUGH 225.37 CAN BE
 REVIEWED.
  
 5} INDICATE THE FUEL TYPE PROPOSED AS
 PRIME MOVER.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 13:38 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 13:38 Sent To M
Notes
2005-09-17 00:00:00GAS PERMIT REQUIRED. GAS CONTRACTOR TO
 SUBMIT PLANS WITH APPLICATION. GAS
 PERMIT MUST BE ON JOB AND SIGNED OFF
 BEFORE FINAL GENERATOR INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 15:38 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 15:38 Sent To E
Notes
2005-10-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-09-30 Cont ID  
Sent By mmclean Date 2005-10-11 Time 13:49 Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 09:30 Sent To Z
Notes
2005-09-30 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-13 Cont ID  
Sent By adarroug Date 2005-09-13 Time 11:29 Rev Time 0.00
Received By adarroug Date 2005-09-13 Time 11:29 Sent To E
Notes
2005-09-13 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-02 Cont ID  
Sent By adarroug Date 2005-09-02 Time 15:34 Rev Time 0.00
Received By adarroug Date 2005-09-02 Time 15:34 Sent To Z
Notes
2005-09-02 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2005-10-14 Cont ID  
Sent By tgordon Date 2005-10-14 Time 14:16 Rev Time 0.10
Received By tgordon Date 2005-10-14 Time 14:16 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By jleech Date 2005-09-19 Time 14:35 Rev Time 0.20
Received By tgordon Date 2005-09-19 Time 14:35 Sent To  
Notes
2005-09-19 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT DUILDING
 OPENINGS. 2001 FBC/M 804.3.3 .
 IF YUO HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.
2005-09-17 00:00:00 
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2005-10-11 Cont ID  
Sent By mmclean Date 2005-10-11 Time 14:03 Rev Time 0.00
Received By mmclean Date 2005-10-11 Time 14:03 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-11 Cont ID  
Sent By mmclean Date 2005-09-12 Time 17:47 Rev Time 0.00
Received By mmclean Date 2005-09-12 Time 17:47 Sent To I
Notes
2005-09-12 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF THE
 GENERATOR
 2. MUST PROVIDE THE DIMENSON OF THE
 GENERATOR AND THE SETBACK OF THE
 GENERATOR FROM THE STRUCTURE & PROPERTY
 LINE
  
 NOTE: GENERATOR CAN ONLY BE 4FT INTO
 SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720