Plan Review Details - Permit 05082009
Plan Review Stops For Permit 05082009
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-07 Cont ID  
Sent By alange Date 2006-02-07 Time 09:01 Rev Time 0.50
Received By alange Date 2006-02-07 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 13:52 Rev Time 0.50
Received By alange Date 2005-09-19 Time 13:47 Sent To  
Notes
2005-09-19 00:00:00****CORRECTIONS****
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)PROVIDE ANCHORING INFORMATION TO
 COMPLY WITH FBC1606.1.3; STRUCTURAL
 MEMBERS AND SYSTEMS, AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND TO
 PROVIDE CONTINUOUS LOAD PATHS FOR THESE
 FORCES TO THE FOUNDATION.WHERE A
 PORTION OF THE RESISTANCE TO THESE
 FORCES IS PROVIDED BY DEAD LOAD, THE
 MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT SHALL BE
 USED.
  
 2.)THE VALUE IS TOO LOW.PROVIDE A
 REASONABLE VALUE OR AN ESTIMATED VALUE
 WILL BE DONE FOR YOU USING MARSHALL &
 SWIFT.
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 4.)SUBMIT TWO COPIES OF PLANS SIGNED
 BY THE PERSON RESPOSIBLE FOR THE DESIGN.
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-30 Time 08:01 Rev Time 0.00
Received By dpalmer Date 2006-03-30 Time 07:45 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-10 Cont ID  
Sent By dpalmer Date 2006-03-10 Time 11:39 Rev Time 0.00
Received By dpalmer Date 2006-03-10 Time 11:37 Sent To PC
Notes
2006-03-10 00:00:00*******UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOS
 REVIEW, AND SOME NEW COMMENTS DUE TO
 REVISED PLASN ONCE AGAIN.
  
  
 1)NOTE:OK.
  
 2)NOTE:PLEASE SEE RISER IS NOW MISSING
 THE MEANS OF DISCONNECT AS REQUIRED PER
 225.31-225.39
 PLEASE SEE RISER SHOWS 150A OCP AT GEN
 FEEDING A 100A MLO PANEL AND PANEL
 SCHEDULED FOR THIS PANEL IS SHOWN AS
 125A ?? PLEASE CORRELATE. PLEASE SEE MAX
 OCP ALLOWED FOR RATED PANELS. PLEASE SEE
 MIN CONDUCTOR SIZES ETC.
 215.5, 240.4,310.15B6/310.16
 PLEASE VERIFY 150A OCP AT GEN, AS UNIT
 IS SHOWN AS 30KW (125A UNIT).
  
 3)NOTE: OK, HOWEVER SEE ABOVE
  
 4)NOTE:OK, NO LOAD SHEDDING.
 HOWEVER PLEASE SE A/C LOAD SHOWN IN LOAD
 CALCUALTIONS, INCLUDE WHAT APPEARS TO BE
 BOTH COOLING AND HEATING??
  
 5)NOTE: NOTE #5 NO, PLEASE SEE ONLY ONE
 SET OF SPECS STILL SUBMITTED.
 PLEAS KNOW, ONLY THE BASE SPECS FOR GEN
 AND ATS ARE NEED.
  
 ** PLEASE SUBMIT TWO SETS OF PLANS,
 SPEC ETC.ONLY ONE SUBMITTED. (TWO
 SURVEYS WERE SUBMITTED .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. ONCE AGAIN, IF THERE ARE ANY
 QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 07:03 Sent To B
Notes
2006-02-03 00:00:00*******UNSAT ******
  
  
 1)NOTE: PLEASE SEE OWNER BUILDER
 DISCLOSURE STATEMENT SUBMITTED IS NOW A
 PHOTOCOPY OF ORIGINAL,
 PLEASE KNOW WE ARE REQUIRED TO HAVE THE
 ORIGINAL , NOTORIZED STATEMENT.
 FS 489.
  
 2)NOTE: PLEASE SEE RISER SUBMITTED IS
 STILL SHOWING THE CHANGING OF WHAT IS A
 LISTED PIECE OF EQUIPMENT. PLEASE SEE
 FEED TO TRANSFER SWITCH MAY COME FROM
 THE LOAD SIDE OF THE METER/MAIN, HOWEVER
 PLEASE VERIFY AS THESPACES/CIRCUITING
 IN A METER/MAIN COMBO DO NOT SEEM TO BE
 ENOUGH?
 215.5
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE
 SUBMITTED DOES NOT CORRELATE WITH THE
 LOAD CALCULATIONS SUBMITTED. PLEASE
 VERIFY OF THERE IS ANOTHER PANEL.
 215.5
  
 4)NOTE: PLEASE INDICATE ON LOAD
 CALCULATIONS AND SUBMIT DETAIL FOR THE
 LOAD SHEDDING OF A/C. A/C IS SHOWN AS
 BEING OMITTED FROM PLANS??
 NEC DOES PERMIT LOAD SHEDDING, HOWEVER
 THIS NEEDS TO BE SHOWN.
 215.5
  
 5)NOTE: PLEASE SUBMIT TWO SETS OF PLANS,
 SPEC ETC.ONLY ONE SUBMITTED. (TWO
 SURVEYS WERE SUBMITTED .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-09-09 Cont ID  
Sent By dpalmer Date 2005-09-09 Time 18:36 Rev Time 0.50
Received By dpalmer Date 2005-09-09 Time 18:36 Sent To M
Notes
2005-09-09 00:00:00*** UNSAT ****
  
 1)NOTE: PLEASE SEE SERVICE RISER SHOWN
 IS NOT CLEAR WHERE THE POWER IS GOING TO
 TRANSFER?? APPEARS TO SHOW FEED FROM A
 METER/MAIN PANEL TO A MAIN DISC AND TO
 ATS AND BACK TO METER MAIN COMBO?
 PLEASE SHOW WHERE FAIL SAFE OPERATION IS
 LOCATED.700.6
 NO MEANS OF OCP IS SHOWN AT MAIN/METER??
 I
 PLEASE SEE 230.72 FOR GROUPING OF MAINS.
 PLEASE CLARIFY IF EXSITING MCB PANEL IS
 LOCATED IMMEDIATELY AJACENT/CLOSE
 PROXIMITYTO NEW ATS.
 MAIN LOATED INSIDE ATS MAY NOT
 CONSIDERED THE MAIN FOR SERVICE.
 230.70A1
  
  
 2)NOTE: PLEASE SEE RISER MISSING ANY
 "EQUIPMENT GROUNDING" CONDUCTORS WHERE
 REQUIRED AFTER THE FIRST MEANS OF
 DISCONNECT.
 250.24,250.110,250.122
  
 3)NOTE: PLEASE SEE NO LOAD CALCULATIONS
 WERE SUBMITTEDFOR REVIEW OF LOADS.
 220,702.5
 PLEASE SEE GEN SHALL BE SIZED FOR ENTIRE
 SERVICE AS SHOWN.
 IF AN EMERGENCY SUB PANEL IS BEING
 INSTALLED, PLEAS INDICATE.
  
 4)NOTE: PLEASE SUBMIT THE MANUFACTURE
 CUT SHEETS WHICH INDICAT ALL LISTINGS OF
 EQUIPMENT.
 PLEASE SEE 225.36 WHICH REQUIRES THE
 DISCONNECTING MEANS TO BE RATED AS
 SERVICE EQUIPMENT.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE SEE FBC 104.2.1 WHICH
 REQUIRES THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS.
  
 7)NOTE; PLEASE SEE FBC 104.6.5
 ADMINISTRATIVE CODE, WHICH REQUIRES THE
 APPLIED VALUE TO INCLUDE ALL LABOR AND
 MATERIALS.
 VALUE ON APPLICATION SEEM TO ONLY
 INDICATE THE VALUE OF EQUIPMENT AND NOT
 THE INSTALLATION.
 PLEASE VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 12:20 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 12:20 Sent To E
Notes
2006-03-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-09 Cont ID  
Sent By adarroug Date 2006-03-09 Time 09:01 Rev Time 0.00
Received By adarroug Date 2006-03-09 Time 09:01 Sent To E
Notes
2006-03-09 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 12:30 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 12:30 Sent To Z
Notes
2006-02-25 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 13:57 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 13:57 Sent To E
Notes
2006-01-30 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-22 Cont ID  
Sent By adarroug Date 2006-01-22 Time 11:06 Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 11:06 Sent To Z
Notes
2006-01-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-09-07 Cont ID  
Sent By adarroug Date 2005-09-07 Time 11:21 Rev Time 0.00
Received By adarroug Date 2005-09-07 Time 11:21 Sent To E
Notes
2005-09-07 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-09-19 Cont ID  
Sent By alange Date 2005-09-19 Time 13:53 Rev Time 0.00
Received By alange Date 2005-09-01 Time 11:04 Sent To  
Notes
2005-09-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-09-16 Cont ID  
Sent By tgordon Date 2005-09-16 Time 10:14 Rev Time 0.15
Received By tgordon Date 2005-09-16 Time 10:14 Sent To P
Notes
2005-09-16 00:00:00*** PROVISO ***
 1) GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENINGS. 2001 FBC/M 804.3.3 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-09-17 Cont ID  
Sent By jleech Date 2005-09-17 Time 12:46 Rev Time 0.25
Received By jleech Date 2005-09-17 Time 12:45 Sent To B
Notes
2005-09-17 00:00:00GAS APPLICATION BY FLORIDA PUBLIC
 UTILITY CO #05060854

Review Stop Z ZONING
Rev No 3 Status N Date 2006-03-08 Cont ID  
Sent By mmclean Date 2006-03-08 Time 14:59 Rev Time 0.00
Received By mmclean Date 2006-03-08 Time 14:59 Sent To I
Notes
2006-03-08 00:00:00ALREADY REVIEW & STAMPED 1/28/06 SURVEY
 ENCLOSED.
  
 NOTE: GENERATOR MUST BE 5FT FROM SIDE
 PROPERTY LINE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-28 Cont ID  
Sent By mmclean Date 2006-01-28 Time 11:20 Rev Time 0.00
Received By mmclean Date 2006-01-28 Time 11:20 Sent To I
Notes
2006-01-28 00:00:00NEW SURVEY - RESTAMP
  
 PROIVSO: GENERATOR CAN ONLY ENCROACH 4FT
 INTO SETBACK.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-09-06 Cont ID  
Sent By mmclean Date 2005-09-06 Time 19:17 Rev Time 0.00
Received By mmclean Date 2005-09-06 Time 19:16 Sent To I
Notes
2005-09-06 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO
 SETBACK.