| Plan Review Stops For Permit 05082009 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-02-07 |
Time |
09:01 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2006-02-07 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-19 |
Time |
13:52 |
Rev Time |
0.50 |
| Received By |
alange |
Date |
2005-09-19 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2005-09-19 00:00:00 | ****CORRECTIONS**** | | | | | | FBC FLORIDA BUILDING CODE 2001 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2001 | | | | | | 1.)PROVIDE ANCHORING INFORMATION TO | | | COMPLY WITH FBC1606.1.3; STRUCTURAL | | | MEMBERS AND SYSTEMS, AND COMPONENTS AND | | | CLADDING IN A BUILDING OR STRUCTURE | | | SHALL BE ANCHORED TO RESIST WIND-INDUCED | | | OVERTURNING, UPLIFT AND SLIDING AND TO | | | PROVIDE CONTINUOUS LOAD PATHS FOR THESE | | | FORCES TO THE FOUNDATION.WHERE A | | | PORTION OF THE RESISTANCE TO THESE | | | FORCES IS PROVIDED BY DEAD LOAD, THE | | | MINIMUM DEAD LOAD LIKELY TO BE IN PLACE | | | DURING A DESIGN WIND EVENT SHALL BE | | | USED. | | | | | | 2.)THE VALUE IS TOO LOW.PROVIDE A | | | REASONABLE VALUE OR AN ESTIMATED VALUE | | | WILL BE DONE FOR YOU USING MARSHALL & | | | SWIFT. | | | | | | 3.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 4.)SUBMIT TWO COPIES OF PLANS SIGNED | | | BY THE PERSON RESPOSIBLE FOR THE DESIGN. | | | | | | ANY QUESTIONS CALL ME. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-03-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-30 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-30 |
Time |
07:45 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-03-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-10 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-10 |
Time |
11:37 |
Sent To |
PC |
|
| Notes |
| 2006-03-10 00:00:00 | *******UNSAT 3RD REVIEW ****** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOS | | | REVIEW, AND SOME NEW COMMENTS DUE TO | | | REVISED PLASN ONCE AGAIN. | | | | | | | | | 1)NOTE:OK. | | | | | | 2)NOTE:PLEASE SEE RISER IS NOW MISSING | | | THE MEANS OF DISCONNECT AS REQUIRED PER | | | 225.31-225.39 | | | PLEASE SEE RISER SHOWS 150A OCP AT GEN | | | FEEDING A 100A MLO PANEL AND PANEL | | | SCHEDULED FOR THIS PANEL IS SHOWN AS | | | 125A ?? PLEASE CORRELATE. PLEASE SEE MAX | | | OCP ALLOWED FOR RATED PANELS. PLEASE SEE | | | MIN CONDUCTOR SIZES ETC. | | | 215.5, 240.4,310.15B6/310.16 | | | PLEASE VERIFY 150A OCP AT GEN, AS UNIT | | | IS SHOWN AS 30KW (125A UNIT). | | | | | | 3)NOTE: OK, HOWEVER SEE ABOVE | | | | | | 4)NOTE:OK, NO LOAD SHEDDING. | | | HOWEVER PLEASE SE A/C LOAD SHOWN IN LOAD | | | CALCUALTIONS, INCLUDE WHAT APPEARS TO BE | | | BOTH COOLING AND HEATING?? | | | | | | 5)NOTE: NOTE #5 NO, PLEASE SEE ONLY ONE | | | SET OF SPECS STILL SUBMITTED. | | | PLEAS KNOW, ONLY THE BASE SPECS FOR GEN | | | AND ATS ARE NEED. | | | | | | ** PLEASE SUBMIT TWO SETS OF PLANS, | | | SPEC ETC.ONLY ONE SUBMITTED. (TWO | | | SURVEYS WERE SUBMITTED . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. ONCE AGAIN, IF THERE ARE ANY | | | QUESTIONS,PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-03 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-03 |
Time |
07:03 |
Sent To |
B |
|
| Notes |
| 2006-02-03 00:00:00 | *******UNSAT ****** | | | | | | | | | 1)NOTE: PLEASE SEE OWNER BUILDER | | | DISCLOSURE STATEMENT SUBMITTED IS NOW A | | | PHOTOCOPY OF ORIGINAL, | | | PLEASE KNOW WE ARE REQUIRED TO HAVE THE | | | ORIGINAL , NOTORIZED STATEMENT. | | | FS 489. | | | | | | 2)NOTE: PLEASE SEE RISER SUBMITTED IS | | | STILL SHOWING THE CHANGING OF WHAT IS A | | | LISTED PIECE OF EQUIPMENT. PLEASE SEE | | | FEED TO TRANSFER SWITCH MAY COME FROM | | | THE LOAD SIDE OF THE METER/MAIN, HOWEVER | | | PLEASE VERIFY AS THESPACES/CIRCUITING | | | IN A METER/MAIN COMBO DO NOT SEEM TO BE | | | ENOUGH? | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE PANEL SCHEDULE | | | SUBMITTED DOES NOT CORRELATE WITH THE | | | LOAD CALCULATIONS SUBMITTED. PLEASE | | | VERIFY OF THERE IS ANOTHER PANEL. | | | 215.5 | | | | | | 4)NOTE: PLEASE INDICATE ON LOAD | | | CALCULATIONS AND SUBMIT DETAIL FOR THE | | | LOAD SHEDDING OF A/C. A/C IS SHOWN AS | | | BEING OMITTED FROM PLANS?? | | | NEC DOES PERMIT LOAD SHEDDING, HOWEVER | | | THIS NEEDS TO BE SHOWN. | | | 215.5 | | | | | | 5)NOTE: PLEASE SUBMIT TWO SETS OF PLANS, | | | SPEC ETC.ONLY ONE SUBMITTED. (TWO | | | SURVEYS WERE SUBMITTED . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-09-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-09-09 |
Time |
18:36 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2005-09-09 |
Time |
18:36 |
Sent To |
M |
|
| Notes |
| 2005-09-09 00:00:00 | *** UNSAT **** | | | | | | 1)NOTE: PLEASE SEE SERVICE RISER SHOWN | | | IS NOT CLEAR WHERE THE POWER IS GOING TO | | | TRANSFER?? APPEARS TO SHOW FEED FROM A | | | METER/MAIN PANEL TO A MAIN DISC AND TO | | | ATS AND BACK TO METER MAIN COMBO? | | | PLEASE SHOW WHERE FAIL SAFE OPERATION IS | | | LOCATED.700.6 | | | NO MEANS OF OCP IS SHOWN AT MAIN/METER?? | | | I | | | PLEASE SEE 230.72 FOR GROUPING OF MAINS. | | | PLEASE CLARIFY IF EXSITING MCB PANEL IS | | | LOCATED IMMEDIATELY AJACENT/CLOSE | | | PROXIMITYTO NEW ATS. | | | MAIN LOATED INSIDE ATS MAY NOT | | | CONSIDERED THE MAIN FOR SERVICE. | | | 230.70A1 | | | | | | | | | 2)NOTE: PLEASE SEE RISER MISSING ANY | | | "EQUIPMENT GROUNDING" CONDUCTORS WHERE | | | REQUIRED AFTER THE FIRST MEANS OF | | | DISCONNECT. | | | 250.24,250.110,250.122 | | | | | | 3)NOTE: PLEASE SEE NO LOAD CALCULATIONS | | | WERE SUBMITTEDFOR REVIEW OF LOADS. | | | 220,702.5 | | | PLEASE SEE GEN SHALL BE SIZED FOR ENTIRE | | | SERVICE AS SHOWN. | | | IF AN EMERGENCY SUB PANEL IS BEING | | | INSTALLED, PLEAS INDICATE. | | | | | | 4)NOTE: PLEASE SUBMIT THE MANUFACTURE | | | CUT SHEETS WHICH INDICAT ALL LISTINGS OF | | | EQUIPMENT. | | | PLEASE SEE 225.36 WHICH REQUIRES THE | | | DISCONNECTING MEANS TO BE RATED AS | | | SERVICE EQUIPMENT. | | | | | | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 6)NOTE: PLEASE SEE FBC 104.2.1 WHICH | | | REQUIRES THE PRINTED NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR PLANS. | | | | | | 7)NOTE; PLEASE SEE FBC 104.6.5 | | | ADMINISTRATIVE CODE, WHICH REQUIRES THE | | | APPLIED VALUE TO INCLUDE ALL LABOR AND | | | MATERIALS. | | | VALUE ON APPLICATION SEEM TO ONLY | | | INDICATE THE VALUE OF EQUIPMENT AND NOT | | | THE INSTALLATION. | | | PLEASE VERIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-28 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-28 |
Time |
12:20 |
Sent To |
E |
|
| Notes |
| 2006-03-28 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-03-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-09 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-09 |
Time |
09:01 |
Sent To |
E |
|
| Notes |
| 2006-03-09 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-02-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-25 |
Time |
12:30 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-25 |
Time |
12:30 |
Sent To |
Z |
|
| Notes |
| 2006-02-25 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-30 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-30 |
Time |
13:57 |
Sent To |
E |
|
| Notes |
| 2006-01-30 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-01-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-22 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-22 |
Time |
11:06 |
Sent To |
Z |
|
| Notes |
| 2006-01-22 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-09-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-09-07 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-09-07 |
Time |
11:21 |
Sent To |
E |
|
| Notes |
| 2005-09-07 00:00:00 | TO "GEN-RES" BOX "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-09-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-09-19 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-09-01 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2005-09-01 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-09-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-09-16 |
Time |
10:14 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2005-09-16 |
Time |
10:14 |
Sent To |
P |
|
| Notes |
| 2005-09-16 00:00:00 | *** PROVISO *** | | | 1) GENERATOR EXHAUST MUST BE TEN FEET | | | AWAY FROM ANY BUILDING OPENINGS | | | (WINDOWS, DOORS, ROOF & EAVE VENTS), AND | | | TEN FEET AWAY FROM ADJECENT BUILDING | | | OPENINGS. 2001 FBC/M 804.3.3 . | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-09-17 |
Time |
12:46 |
Rev Time |
0.25 |
| Received By |
jleech |
Date |
2005-09-17 |
Time |
12:45 |
Sent To |
B |
|
| Notes |
| 2005-09-17 00:00:00 | GAS APPLICATION BY FLORIDA PUBLIC | | | UTILITY CO #05060854 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2006-03-08 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-03-08 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-03-08 |
Time |
14:59 |
Sent To |
I |
|
| Notes |
| 2006-03-08 00:00:00 | ALREADY REVIEW & STAMPED 1/28/06 SURVEY | | | ENCLOSED. | | | | | | NOTE: GENERATOR MUST BE 5FT FROM SIDE | | | PROPERTY LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-28 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-28 |
Time |
11:20 |
Sent To |
I |
|
| Notes |
| 2006-01-28 00:00:00 | NEW SURVEY - RESTAMP | | | | | | PROIVSO: GENERATOR CAN ONLY ENCROACH 4FT | | | INTO SETBACK. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-09-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-09-06 |
Time |
19:17 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-09-06 |
Time |
19:16 |
Sent To |
I |
|
| Notes |
| 2005-09-06 00:00:00 | GENERATOR CAN ONLY ENCROACH 4FT INTO | | | SETBACK. |
|
|